SIPROTEC 7SE20 DeviceManual enUS
SIPROTEC 7SE20 DeviceManual enUS
Table of Contents
Safety Notes 1
SIPROTEC Device Structure 2
Travelling Wave Recorder
Travelling Wave Explorer 3
7SE20
Assembly and Commissioning 4
V01.00 Maintenance and Repair 5
Packing, Storage, and Transport 6
Device Manual
Technical Data 7
Appendix A
Glossary
E50417-X0040-C000-A1
NOTE
i For your own safety, observe the warnings and safety instructions contained in this document, if available.
Target Audience
This manual is primarily aimed at protection system engineers, system configurers, commissioning engineers,
persons entrusted with the setting, testing and maintenance of fault recorder equipment, automation, selec-
tive protection and control equipment, and operational crew in electrical installations and power plants.
Scope
This manual applies to the Travelling Wave Recorder 7SE20.
Indication of Conformity
The product complies with the directive of the Council of the European Communities
on harmonization of the laws of the Member States concerning protection and safety
(Directive 2014/35/EU), electromagnetic compatibility (EMC Directive 2014/30/EU), and
the efficient use of the radio spectrum (Directive 2014/53/EU Art. 3, paras. 1-2) as well
as the the restriction of the use of hazardous substances in electrical and electronic
equipment (RoHS Directive 2011/65/EU).
This conformity has been proved by tests performed according to by Siemens AG in
accordance with the guidelines in accordance with the EN 61326-1 standard for the
EMC Directive, standard EN 61010-1 for the Directive 2014/35/EU, the standard EN 303
413 V1.1.1 for the efficient use of the radio spectrum, and the EN IEC 63000 for the
RoHS Directive.
The device is designed and manufactured for application in an industrial environment.
Additional Support
For questions about the system, contact your Siemens sales partner.
Notes on Safety
This document is not a complete index of all safety measures required for operation of the equipment (module
or device). However, it comprises important information that must be followed for personal safety, as well
as to avoid material damage. Information is highlighted and illustrated as follows according to the degree of
danger:
! DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.
! WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
² Comply with all instructions, in order to avoid death or severe injuries.
! CAUTION
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
² Comply with all instructions, in order to avoid moderate or minor injuries.
NOTICE
NOTICE means that property damage can result if the measures specified are not taken.
² Comply with all instructions, in order to avoid property damage.
NOTE
i Important information about the product, product handling or a certain section of the documentation
which must be given attention.
Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the
technical description, and only in combination with third-party equipment recommended and approved by
Siemens.
Problem-free and safe operation of the product depends on the following:
• Proper transport
• The equipment must be grounded at the grounding terminal before any connections are made.
• All circuit components connected to the power supply may be subject to dangerous voltage.
• Hazardous voltages may be present in equipment even after the supply voltage has been disconnected
(capacitors can still be charged).
• Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the
equipment, ensure that the current-transformer circuits are short-circuited.
• The limiting values stated in the document must not be exceeded. This must also be considered during
testing and commissioning.
Preface.......................................................................................................................................................... 3
1 Safety Notes................................................................................................................................................. 8
2 Device Structure......................................................................................................................................... 10
2.1 Scope and Key Features of the Device................................................................................11
2.2 Traveling Waves................................................................................................................ 11
2.3 Recording Traveling Waves................................................................................................12
2.4 Positioning of the Antenna................................................................................................14
2.5 LED Assignment and Device Status.................................................................................... 16
2.6 Application and Setting Notes........................................................................................... 17
2.6.1 Overview.....................................................................................................................17
2.6.2 Station and Device Name.............................................................................................17
2.6.3 Transformer Data........................................................................................................ 18
2.6.4 Connection between the Transformer and the Device.................................................. 19
2.6.5 Resolution and Trigger Thresholds............................................................................... 20
2.6.6 Recording Events......................................................................................................... 26
2.6.7 Setting the GNSS Module.............................................................................................27
2.6.8 Configuration of the Ethernet Interface........................................................................28
2.6.9 Setting Notes for Fault Location................................................................................... 29
2.7 Evaluating a Traveling Wave Record with SIGRA................................................................. 29
2.8 Monitoring Functions........................................................................................................33
2.9 Dimensions.......................................................................................................................34
2.10 Device Connections...........................................................................................................35
7 Technical Data............................................................................................................................................ 65
A Appendix.................................................................................................................................................... 68
A.1 Figures............................................................................................................................. 69
A.2 Meaning of the LEDs......................................................................................................... 70
A.3 Ordering Information and Accessories............................................................................... 70
A.4 Connection Diagrams........................................................................................................71
Glossary...................................................................................................................................................... 72
NOTE
i The Travelling Wave Explorer tool uses .NET Framework version 4.7.2. The framework is part of the
Microsoft Windows 10 and 11 operating systems. Siemens recommends activating and installing automatic
updates for the operating system. This will ensure that any potential vulnerabilities in the .NET Framework
are closed promptly.
Network Security
The device and the Travelling Wave Explorer program do not guarantee secure communication. No user
authentication takes place. This means there is a risk that unauthorized users in the network will be able to
read data or make unauthorized changes to settings on the devices.
Therefore, Siemens recommends setting up a secure communication channel for data transmission. To avoid
vulnerabilities, set up a virtual private network (VPN) and use a securely configured firewall. Siemens recom-
mends using industrial VPN devices, such as SCALANCE S615. Install the Travelling Wave Explorer program
on the computer in the control center and ensure that only authorized users have access to this computer.
Note the instructions in the Secure Substation Manual.
[dw_TWR-network-security, 1, en_US]
• 8 channels for recording signals, split into 4 current channels and 4 voltage channels
The channels have a fixed assignment to the analog inputs. The signals are recorded with a sampling
rate of 10 MHz. The assignment of the channels to the input terminals of the device can be found in the
connection diagrams in the Annex A.4 Connection Diagrams.
• The integrated GNSS module sets an absolute time stamp at the start of recording. The GNSS module
receives signals from GPS and GLONASS satellites.
• Parameterization, evaluation of traveling wave records, and fault location are only possible with the help
of external tools.
– With the Travelling Wave Explorer tool, you can set the parameters of the device, download
records, and determine the fault location.
– Alternatively, you can use the SIGRA tool to evaluate records and determine the fault location.
• Via an Ethernet interface, you can operate the device with the Travelling Wave Explorer tool and
download the records.
• Switching operations
• Short circuits
• Ground faults
• Lightning strikes
[dw_principle_propagation_traveling-waves, 2, en_US]
Traveling waves are measured in the current signals and voltage signals at both ends of the line. In each case,
the arrival of the traveling waves is marked with a precise time stamp. Based on the time stamps at both ends
of the line, the following formula can be used to calculate the origin of the traveling wave:
[fo_TW_FaultLocation_2side_formula, 1, en_US]
where:
x Distance from station A to the fault location
l Line length
Δt Difference tA - tB between the time stamps of both ends of the line
v Propagation velocity of the wave
With the Travelling Wave Explorer tool, you can evaluate the recorded data and determine the fault location.
The Travelling Wave Explorer tool shows the associated traveling wave records for the line. To do this, it
compares the time stamps of the records.
Two records belong together if the time difference Δt meets the following condition:
[fo_TW_max_delta_t, 1, --_--]
The fault location is then either on the monitored line or near the line.
Trigger Thresholds
Trigger thresholds specify the voltage or current value from which a traveling wave record is triggered. The
trigger thresholds can be adjusted separately for the current channels and the voltage channels. Follow the
setting notes in 2.6.5 Resolution and Trigger Thresholds.
Record Duration
The maximum length of a traveling wave record is 50 ms. The length is defined by parameters Pre trigger
length and Post trigger length. These parameters define the length of the fault record before and
after the trigger event. Follow the setting notes in 2.6.6 Recording Events.
Time stamp
When the trigger threshold is exceeded for the first time, the time is saved. The time determined in this way is
entered in the traveling wave record as a time stamp. If there are records from both ends of the line, the time
stamp can be used for fault location.
NOTE
Example:
The following figure shows a section of a traveling wave record for a 1-phase short circuit B-G. The trigger
threshold was exceeded for all 3 phase currents and phase-ground voltages. The time stamp 21.11.2022,
05:42:10.550 specifies the time when a trigger threshold was exceeded for the first time. This time specifies
the start of the edge of the 1st wave.
[sc_faultrecording_trigger, 1, --_--]
The exact time stamp can be seen in the CFG file of the record:
21/11/2022,05:42:10.548366 ← 1st time stamp: Start of the record
21/11/2022,05:42:10.550366 ← 2nd time stamp: Trigger threshold exceeded for the 1st time, start of
the edge of the 1st wave
The 2nd time stamp is used for double-end fault location.
• The antenna for receiving the GNSS signal is installed and connected to the device. To do this, follow the
instructions in 4.3 Antenna Assembly.
• In the Travelling Wave Explorer, a system with one or more stations and at least one device is created.
• The parameters for the connection between the device and the antenna are saved in the device (see
2.6.7 Setting the GNSS Module). For how to set the parameters, see 3.7.3.3 Editing Online Parameters.
Always start positioning after the following events:
Completing Positioning
If the threshold value of parameter Required GNSS antenna position accuracy has been reached
or exceeded and the minimum observation time for parameter Minimum synchronization time for
GNSS locking is reached, the process is complete. Ongoing positioning can be interrupted by restarting it
with changed threshold vaues. To end the process prematurely, set the following:
• Minimum observation time Minimum synchronization time for GNSS locking = 5 minutes
Restarting Positioning
Positioning can be restarted. For this, the threshold values for parameter Required GNSS antenna
position accuracy and parameter Minimum synchronization time for GNSS locking can be
changed and set again.
The information from the canceled positioning run is saved in the device so that the new positioning can be
completed more quickly.
LED 1 – Run
LED 1 Run lights up as soon as the device is connected to a supply voltage.
LED 2 – Error
LED 2 Error indicates that the device is in a fault condition. This LED must not be lit up during operation.
During system startup, LED 2 Error lights up until initialization of the device is completed. When LED 2 Error
goes out, the device is ready for use. In this case, the device can also be operated via the Ethernet Interface. If
LED 2 Error does not go out during system startup, this can indicate problems with the SD card or the device.
In this case, follow the instructions in 2.8 Monitoring Functions. Check whether an SD card is inserted and
whether write protection has been deactivated for the card. If LED 2 Error is flashing, no SD card has been
inserted.
• If this LED is not lit up, at least 50 % of the storage capacity of the SD card is still available.
• If the LED is flashing, this indicates that more than 80 % of the card is filled with records.
NOTICE
An interruption during write access can make the records saved on the SD card unreadable.
² Do not switch off the device during write access to the SD card.
• LED off: Saved position data is not available. Time synchronization is not possible.
• LED flashes: Determination of the positioning has not yet been completed. Time synchronization is
possible, even if determination of the position has not yet been completed.
NOTE
i For additional information on the possible fault statuses, refer to 2.8 Monitoring Functions.
2.6.1 Overview
To display the channels correctly in the fault records, the device requires information about the system and
the respective channels. This information is made available to the device via the parameters. Set the device
parameters using the Travelling Wave Explorer program. A description of these parameters and their effect
on the fault records follows.
To assign a traveling wave record to a device, use the station name and the device name. Both
names are entered in the record in accordance with the COMTRADE standard IEC 60255-24:2013 and
IEEE C 37.111:2013. The names are displayed in SIGRA or another COMTRADE viewer.
The start of the file name for a record is also composed of the station name and the device name. The
names are followed by the date, the time, and the trigger time in ns. The runtime on the cable between the
transformer and the device is not taken into account in the trigger time in the file name.
Example:
There is a record from the following device with the following time stamp:
• Time: 08:58:54
Berlin_7SE20_20230614_085854_304900120.cfg
To detect traveling waves, connect the device directly to the current and voltage transformers in a system. The
following parameters can be used to configure the current and voltage channels in the device:
[dw_polstromwdl_7SE20, 1, en_US]
For fault location, the time of arrival of the wave at the end of the line is required. This is where the current
and voltage transformers are installed. But the time stamps are only assigned in the device. The trigger event
is delayed by the propagation of the traveling wave in the secondary cabling. Therefore the trigger signal is
recorded by the device with a time delay. To record the correct runtime, the time delay is subtracted from the
time of the trigger event. To do this, enter the length of the cable and the propagation velocity on this cable.
These values are set separately for the current transformer and the voltage transformer. Only the setting value
of the signal in which the trigger event was first recorded is effective.
This time delay is calculated based on the following formula:
where:
tc Calculated time delay of the trigger signal through the wiring
lT Length of the cable between the current or voltage transformer and the device.
Depending on the transformer, the parameter is Cable length CT or Cable
length VT.
c Speed of light
velocity factor Relative propagation velocity of the wave on the cable in relation to the speed of light
c.
Current transformer: Parameter Velocity factor cable CT
Voltage transformer: Parameter Velocity factor cable VT
NOTE
i All of the following setting values relate to the secondary parameters at the respective transformer.
Adjust the resolution of the current and voltage channels to the size of the high-frequency signal shares.
The recommended setting values can be calculated from the line and transformer data using the following
formulas. Larger values do not result in any improvement, as the resolution of the signal in the evaluated
frequency range is smaller.
NOTE
i The fundamental component of the current and voltage signals is filtered out and is therefore not visible in
the record. Therefore, the fundamental component does not have to be taken into account when setting
the resolution and the trigger thresholds.
The trigger thresholds specify the current or voltage level from which recording of a record starts. If the
trigger threshold in one of the channels is exceeded, a record is recorded. If the setting values are too small,
unnecessary records will be generated even when there is no event in the power system.
On the other hand, if the setting values are too high, no record will be generated when there is an event.
Siemens recommends the following settings:
When calculating the setting value, take parameter Full scale current into account as well as the
current transformation ratio and the attenuation factor Fatt. The setting value for parameter Full scale
current can be determined as follows:
where:
Fatt Attenuation factor of the primary current of the current transformer
Vrated, prim Rated primary voltage (Parameter Rated primary voltage)
ZW Characteristic impedance of the line
Irated, prim Rated primary current (Parameter Rated primary current)
Irated, sec Rated secondary current (Parameter Rated secondary current)
The current transformer attenuates the high-frequency signal shares in the range from 10 kHz to 2 MHz more
than the fundamental component of 50 Hz or 60 Hz. The attenuation factor Fatt specifies the transmission ratio
for high-frequency signal shares in comparison to the fundamental component share.
NOTE
i The attenuation factor is not specified by the transformer manufacturer. If the attenuation factor of the
primary current is not known, Siemens recommends using an attenuation factor of 1.0 for the calculation.
The characteristic impedance ZW is independent of the length of the line. It is determined by the design,
materials, and insulation of the line. For overhead lines, the characteristic impedance ZW is 200 Ω to 400 Ω,
for underground cables, it is 10 Ω to 40 Ω.
If the characteristic impedance of the line ZW is not known, it can be calculated approximately using the
following formula:
where:
L' Inductance per unit length of the line. Calculate this value using the positive-sequence
impedance Z1 of the line.
C' Capacitance per unit length of the line. This value is also called the capacitance per unit
length of the line CB, is identical to the capacitance of the positive-sequence system C1,
and can be found in the technical data of the line.
Example:
For the following system, calculate the setting value for parameter Full scale current as follows:
Size Value
Rated primary voltage Vrated, prim 380 kV
Rated secondary voltage Vrated, sec 100 V
Rated primary current Irated, prim 800 A
Rated secondary current Irated, sec 1A
Rated frequency frated 50 Hz
Positive-sequence impedance R'1 + j X'1 (0.027 + j0.307) Ω
Positive-sequence impedance capacity C'1 11.8 nF/km
Attenuation factor Fatt of the current transformer Unknown
In the 1st step, the characteristic impedance of the line is calculated. The inductance per unit length is
calculated from the positive-sequence impedance of the line:
[fo_TW_Example_Induct_L1, 1, en_US]
The attenuation factor Fatt is unknown, therefore the calculation is carried out with the value 1.0:
Table 2-1 shows the characteristic impedance ZW for some overhead lines, and the possible setting value for
parameter Full scale current. The secondary setting value was calculated for a rated primary current of
600 A.
Table 2-1 Characteristic impedance ZW and possible setting value for parameter Full scale current
for some selected overhead lines
The following table shows how different settings of parameter Full scale current affect the measuring
results:
Setting value for Possible impacts on the measuring results
parameter Full
scale current
Too low • Current curves that are too large are clipped.
• If the current curves are clipped, the edges appear very steep. The tip of the edge
is no longer included in the signal.
According to the • No clipping of the current curves
formula
• Resolution is used optimally
• Edges are clearly identifiable.
Too high • No clipping of the current curves
• Resolution is not fully used
• If the resolution is not adequate, the edges cannot be clearly identified.
Example:
The setting value for parameter Full scale current was calculated as 1.8 A. This results in the following
limiting values for parameter Trigger level current:
The voltage transformer attenuates the high-frequency signal shares in the range from 10 kHz to 2 MHz more
than the fundamental component of 50 Hz or 60 Hz. The attenuation factor Fatt,V specifies the transmission
ratio for high-frequency signal transmission in comparison to the fundamental component share.
NOTE
i If the attenuation factor of the primary voltage of the voltage transformer is not known, Siemens recom-
mends using an attenuation factor of 1.0 for the calculation.
The correct value for parameter Full scale voltage can be determined as follows:
where:
Fatt,V Attenuation factor of the primary voltage of the voltage transformer
Vrated, sec Rated secondary voltage
The following table shows possible impacts of the setting value on the measuring results:
Setting value for Possible impacts on the measuring results
parameter Full
scale voltage
Too low • Voltage curves that are too large are clipped.
• If voltage curves are clipped, the edges can no longer be determined with the
necessary accuracy.
According to the • No restriction of the voltage curves
formula
• Resolution is used optimally
• Edges are clearly identifiable.
Too high • No restriction of the voltage curves
• Resolution is not fully used
• If the resolution is not adequate, the edges cannot be clearly identified.
The following figures show examples of a voltage curve after a traveling wave test signal with different
settings of parameter Full scale voltage:
[sc_faultrecording_full_scale_voltage_too_small, 1, --_--]
Figure 2-4 Maximum voltage value set too low: The voltage curve is clipped.
[sc_faultrecording_full_scale_voltage_OK, 1, --_--]
Figure 2-5 Maximum voltage value set correctly: The voltage curve is displayed properly.
[sc_faultrecording_full_scale_voltage_too_large, 1, --_--]
Figure 2-6 Maximum voltage value set too high: The voltage curve is superimposed with noise.
Example:
The setting value for parameter Full scale voltage was calculated as 25.0 V. This results in the following
limiting values result for parameter Trigger level voltage:
The device continuously saves the current and voltage signals, so data is available even before the start of
the record if there is a trigger event. The maximum length of a traveling wave record is 50 ms. Adjust the
pre-trigger time and post-trigger time for a trigger event using the following parameters.
where:
l Line length
c Speed of light
Example:
The following image shows a traveling wave record. The Pre-trigger length was set to 2 ms, and the
Post-trigger length was set to 3 ms.
[sc_faultrecording_pre_post_trigger_time, 1, --_--]
Figure 2-7 Traveling waves record with Pre-trigger length and Post-trigger length
For time synchronization, the device has a GNSS module (Global Navigation Satellite System). This can receive
signals from GPS and GLONASS satellites. Before commissioning, exact positioning of the installed antenna is
required. For how to start positioning with the Travelling Wave Explorer program, refer to 3.7.4.1 Initiating
Positioning.
The antenna is connected to the device with a cable. Due to the cable, the GNSS signals arrive at the device
with a delay. This time delay is compensated for during calculation of the time stamp. To do this, enter the
length of the cable and the propagation velocity on this cable:
default value corresponds to the supplied antenna cable. Only change the setting value if you are using a
different cable.
If you do not know the relative propagation velocity of a signal on your cable, use the default value of 80 %.
The Ethernet interface is used to operate the device with the Travelling Wave Explorer program:
• Setting parameters
• Downloading records
Parameter: IP address
NOTE
i In the delivery status, the IP address 172.16.60.60 is saved in the device. The device can initially only be
accessed and configured via this address.
Using the Travelling Wave Explorer program, you can perform double-end fault location. To do this, the
matching records from both ends of the line and some line data that you enter in the Travelling Wave
Explorer program are required. For how to enter the line data, see Editing the Line Properties, Page 44.
[fo_TW_Propagation_Speed, 1, --_--]
where:
L' Inductance per unit length of the line. Calculate this value using the positive-sequence
impedance Z1 of the line.
C' Capacitance per unit length of the line. This value is also called the capacitance per unit
length of the line CB, is identical to the capacitance of the positive-sequence system C1,
and can be found in the technical data of the line.
The following table shows the propagation velocity for some overhead lines.
Table 2-2 Propagation velocity of the wave for some selected overhead lines
² Open the record for the first side of the line via menu option File / Open.
- or -
² Open the first record by double-clicking the CFG file.
The record is displayed. For fault location, perform the following steps:
² Switch to the instantaneous values view. To do this, click the Instantaneous values button.
² To select all diagrams in the illustration, use the keyboard shortcut Ctrl + A.
² Right-click in one of the displayed diagrams and select Optimize in the menu.
The diagrams are then scaled so that the full current and voltage curves are shown. The first record can be
seen in SIGRA.
[sc_SIGRA_Record_1, 1, en_US]
Figure 2-8 Illustration of a traveling wave record in SIGRA. You can see the record for a 1-pole fault on a
400 kV line.
You can now load the 2nd record from the other end of the line:
² In SIGRA, select Paste / Fault record in the menu.
² In the file selection dialog, select the 2nd record.
You can see both records one on top of the other in SIGRA. The records are automatically synchronized. You
can see the time difference between the two trigger events. All evaluation options of SIGRA are available to
you.
For double-end fault location, it is helpful to display the current or voltage curves of both sides of the line in
one diagram:
² In SIGRA, right-click in the last diagram of the record.
² Select New.
² Right-click in the newly created diagram and select Assign signals.
² Select the signals that are to be displayed together in the new diagram. For fault BG, this could be fault
signals N1:IB B and N2:IB B.
The signals for both ends of the lines are shown in one diagram. Use the two cursors to determine the fault
location.
² Slide cursor 2 (blue) to the first edge of the signal from the first device (node N1). Select either the start
or the top of the edge.
² Slide cursor 1 (orange) to the first edge of the signal from the 2nd device (node N2).
In SIGRA, the time difference between the two marks is displayed in ms in the top left in field C2-C1.
[sc_delta_t_2side_flt_loc, 1, en_US]
Figure 2-9 Determining the time difference between the edges on both ends of the line
² Determine the fault location with the measured time difference according to the following formula:
[fo_TW_FaultLocation_2side_formula, 1, en_US]
where:
x Distance from the fault location in km
l Length of the line in km
v Propagation velocity of the wave in km/s
Δt Time difference between the edges in s
Example:
There is a line with the following data:
Size Value
Length of line l 117 km
Voltage level: 400 kV
Propagation velocity v 294 486 km/s
With SIGRA, a time difference of -0.24796 ms was measured. The distance from the fault location is:
[fo_TW_Example_2-Side, 1, --_--]
[dw_TWFL_Reflections, 1, --_--]
The traveling wave propagates from the fault location. At time tA1, the wave reaches measuring point A for
the first time. The wave is reflected at the line ends and at the fault location. At time tA2, the 2nd reflection
reaches measuring point A. The distance between the fault location and measuring point A can be determined
from the time difference Δt = tA2-tA1.
If you know which edge is a reflection of the fault location, then reliable single-end fault location is possible. If
the record contains other reflections of the fault location, then the time difference between the edges of the
reflections is the same. Reflections can also occur at other places on the line. Possible reflections are:
The record is displayed. For fault location, perform the following steps:
² Switch to the instantaneous values view. To do this, click the Instantaneous values button.
² To select all diagrams in the illustration, use the keyboard shortcut Ctrl + A.
² Right-click in one of the displayed diagrams and select Optimize in the menu.
The record can be viewed in SIGRA.
² Search for a current or voltage signal in which the 1st and 2nd edge of the traveling wave can be seen.
Other edges enable you to check the result.
² Zoom in on the record so that the edges are clearly visible.
² Slide the 1st cursor (orange) to the start of the 1st edge.
² Slide the 2nd cursor (blue) to the start of the 2nd edge.
In SIGRA, the time difference between the two marks is displayed in the top left in the C2-C1 field.
[dw_delta_t_1-side, 1, --_--]
Figure 2-11 Measuring the time difference between 2 edges for single-end fault location
² Calculate the distance from the fault location using the following formula:
[fo_TW_FaultLocation_1side, 1, --_--]
Example:
In the record, a time difference of 0.06793 ms was measured between the two edges on current signal IC. The
distance from the fault location is:
[fo_Example_1-Side, 1, --_--]
• If LED 2 Error lights up and LED 3 SD card status flashes, the SD card is full. The SD card must be
replaced.
LED 3 SD card status shows the fill level of the SD card:
LED 3 SD card status Occupied storage capacity
off < 50 % of the storage capacity of the SD card
on 50 % to 80 % of the storage capacity of the SD card
flashes > 80 % of the storage capacity of the SD card. Delete records that are no
longer required or replace the SD card.
Self Monitoring
During operation, the following monitoring functions are permanently active:
• Monitoring of the consistency of parameters (only after the parameters have been changed)
If LED 2 Error lights up and checking the SD card as well as restarting the device does not remedy the fault,
contact the Customer Support Center.
2.9 Dimensions
Stripped length (for use without bootlace ferrule) 10 mm or 11 mm; Use solid copper
conductors only
Permissible tightening torque at clamping screw Max. 2.7 Nm
Position on the device See Rear View, Page 69
[sc_current_terminal_7SE20, 1, --_--]
Terminal point 1 2 3 4 5 6 7 8
Signal designation I1_N I1_P I2_N I2_P I3_N I3_P I4_N I4_P
Voltage Terminal V
Note the following when connecting to the voltage terminal of the device:
Cable cross-section AWG 20–14 (0.5 mm2 to 2.5 mm2)
When using terminal lugs AWG 16–14 (1.0 mm2 to 2.5 mm2)
Stripped length (for use without bootlace ferrule) 9 mm or 10 mm; Use solid copper conduc-
tors only
Permissible tightening torque at clamping screw Max. 1.8 Nm
Position on the device See Rear View, Page 69
[sc_voltage_terminal_7SE20, 1, --_--]
Terminal point 1 2 3 4 5 6 7 8
Signal designation V1_P V1_N V2_P V2_N V3_P V3_N V4_P V4_N
Note the following when connecting to the voltage terminal of the device:
Cable cross-section AWG 18–12 (0.75 mm2 to 2.5 mm2)
With bootlace ferrule AWG 18–12 (0.75 mm2 to 2.5 mm2)
Stripped length of bootlace ferrules 7 mm (only use shielded lines and connect the shield to the
grounding point of the device.)
Permissible tightening torque at clamping 0.6 Nm
screw
Connection Cables
The following applies to all voltage, current, and power supply connections:
Min. rated voltage 300 V
Minimum temperature of the lines 105 °C
PE Port
The equipment must be grounded at the protective grounding terminal before any connections are made. The
line cross-section must be at least 4 mm2. The permissible tightening torque is 1.2 Nm.
USB port
The Type B USB port on the back of the device is used only for service purposes by Siemens AG.
BNC Port
The socket-type BNC ports (CH1 to CH8) on the back of the device are used only for service purposes by
Siemens AG.
SD Card Slot
The SD card slot is on the front of the device. To ensure safe operation of the device, only use the supplied and
approved industrial SD card. The SD card must not be removed from the device during operation.
Antenna Connection
The device requires an external antenna.
The socket-type SMA connection is on the back of the device next to the supply voltage connection (see Rear
View, Page 69).
! DANGER
Risk of fire due to ungrounded antenna.
Disregarding this may result in fire, serious injuries, or death.
² Ground the antenna properly in accordance with the manufacturer’s instructions and ensure lightning
protection.
Project
A project comprises several systems, stations, lines between the stations, and the associated devices. For a
project, Travelling Wave Explorer creates a file in .twe format on the PC. This file is used to store all data
about the systems, stations, lines, and devices. When using Travelling Wave Explorer for the first time, create
a new project.
A new project always consists of a system with 2 stations, each with a device 7SE20 and a line.
System
A system comprises all associated stations and lines of a voltage level. It comprises at least 2 stations, one line,
and 2 devices. In the System settings tab, enter the name of the line system and the voltage level.
Station
The station specifies the place where the devices are installed. A station consists of at least one device. In the
Station settings tab, enter the name of the station.
Line
A line connects 2 stations. In the Line tab, enter the technical data of the line. For fault location, enter the
line length in km and the propagation velocity of the wave cw in km/s. Assign one device to each of the two
line ends.
Device
The Device is a 7SE20 device. An outgoing line is assigned to each device. In the Device tab, enter all
parameters for the specified device.
• The installation package with the .msi format has been loaded from SIOS.
• The UDP and TCP protocols are permitted in the Firewall of the operating system for communication for
the Travelling Wave Explorer.
² Start the installation package.
² Follow the instructions displayed regarding the license agreement.
² Select a suitable storage location for Travelling Wave Explorer. The default installation path is
C:\Program Files\Siemens\Travelling Wave Explorer.
NOTE
i When installation is started, a dialog field with the security function of the operating system will be
displayed in the background. To continue installation, authorize the function.
The entry Travelling Wave Explorer is located in the Siemens folder in the start menu. This folder also
contains the entry Uninstall Travelling Wave Explorer.
Uninstalling
To uninstall the Travelling Wave Explorers, the following prerequisites apply:
NOTE
i During uninstallation, the Travelling Wave Explorer is removed. The project files and settings are retained.
² If the Travelling Wave Explorer is active during uninstallation, a dialog field will be displayed. Select
whether to close the processes automatically, continue uninstalling, or cancel uninstalling. Unsaved
project settings of running processes may be lost.
- or -
² In the list box, navigate to the file directory of the project file.
² Select the project file in .twe format and confirm the selection.
[Sc_Save_Project, 1, --_--]
Adding a System
² Select the Add system icon.
A new system is added to the project. The System Settings tab is shown on the right-hand side.
[Sc_Add_System, 1, --_--]
Deleting a System
² Select a system.
² Select the Delete selected item icon.
² Confirm the selection.
[Sc_Delete_System, 1, --_--]
Adding a Station
To edit a station, the following prerequisites must be met:
[Sc_Add_Station, 1, --_--]
² Assign a meaningful name for the station. Follow the instructions in 2.6.2 Station and Device Name.
Renaming a Station
² Select the system and the station to be named.
The Station Settings are displayed on the right-hand side.
² Assign a new name for the station.
Deleting a Station
² Select a station.
² Select the Delete selected item icon.
² Confirm the selection.
Creating a Line
To create a line between 2 devices, the following prerequisites must be met:
Renaming a Line
² Select a line.
The Line Settings are displayed on the right-hand side.
² Assign a new name for the line.
The name is displayed in the Lines tab. The changed project is marked as modified.
Deleting a Line
² Select a line.
² Select the Delete selected item button.
² Confirm the selection.
Adding a Device
² Select a system and the station to which you wish to add the device.
² Select Add device.
[Sc_Add_Device, 1, --_--]
A new device is created. The Device Settings tab is displayed on the right-hand side. Initially, only parameters
Name and IP address are displayed.
[sc_Device_Settings_IP_only, 1, --_--]
² Name the device. Follow the instructions in 2.6.2 Station and Device Name.
² Specify the IP address of the device for which you wish to set parameters. In the delivery status, the IP
address of the device is 172.16.60.60.
The Travelling Wave Explorer now automatically connects to the device and displays all parameters of the
device.
NOTE
i For an overview of the device parameters, see 2.6 Application and Setting Notes.
Deleting a Device
² Select a device.
² Select the Delete selected item button.
² Confirm the selection.
² Open a project.
² On the left-hand edge, select the Devices tab.
² Select a device from the system navigation.
² Select the Device Settings tab.
² Ensure that the device connection status is online.
² Select the Restart button.
Ongoing write processes to the device are ended. During this time, no further inputs can be made.
The device is restarted.
If the device is online, the online parameters and also the following information are displayed:
• Firmware Version
Automatic Request
² Open a project.
² On the left-hand edge, select the Devices tab.
² Select a device from the system navigation.
² Select the Device Settings tab.
² Ensure that the device connection status is online.
The device parameters are automatically requested and displayed.
Initiating Requests
You can overwrite offline parameters by requesting the current online parameters.
² Open a project.
² On the left-hand edge, select the Devices tab.
² Select a device from the system navigation.
² Select the Device Settings tab.
² Ensure that the device connection status is online and that there are changed online parameters.
Changed online parameters are marked as modified with an asterisk next to the parameter name.
² Select Fetch Settings.
The current device parameters are requested and displayed. Previously changed values of the online parame-
ters are overwritten and are no longer marked as modified with an asterisk in the parameter name.
NOTE
i A connection to the device is only possible with the new IP address. Make a note of the new IP Address
and store it in a safe place. Ensure that the project is saved with the Save button after the IP address is
changed.
² From the SIOS portal (https://support.industry.siemens.com/), download the current firmware for the
device.
² Save the file with the ending .cms on your personal computer.
² Open a project.
² Select the device from the system navigation as described in 3.7.1 Editing a Device.
On the right-hand side, next to the device parameters, the device status is displayed.
² Ensure that the device connection status is online.
² Select the FW Update button.
NOTE
i During the firmware update, no further actions are possible until completion of the restart.
3.8 Records
For fault location, the data from the record overview is used. Refresh the overview of available records as
follows:
² Open a project.
² On the left-hand edge, select the Device tab.
² Select a device from the system navigation.
² Select the Record overview tab.
The overview of all records of the device is displayed.
² Select Refresh record overview.
The current device records are requested and displayed. Download the records as a COMTRADE file. The
records are saved in the project folder.
[sc_Refresh_Record_Overview, 1, --_--]
² Open a project.
² On the left-hand edge, select the Devices tab.
² Select a device from the system navigation.
² Select the Record Overview tab.
A list of available records for the device is displayed. If the list is empty, refresh the list, see3.8.1 Refreshing
the Record Overview.
² Select at least one fault record.
² Select Download selected record(s).
[sc_Download_Selected_Records, 1, --_--]
Optionally, you can download a record via the menu at the end of the row:
[sc_Menu_Download_Record, 1, --_--]
The records are saved in the project folder as a COMTRADE file and are available offline. During the download
process, no further inputs can be made.
NOTE
i If the download was unsuccessful, the records will be marked with no in the Downloaded column.
² Open a project.
² On the left-hand edge, select the Devices tab.
² Select a device from the system navigation.
² Select the Record overview tab.
The overview of all records of the device is displayed.
² Select Initiate test record.
The test record is initiated.
[sc_Initiate_Test_Record, 1, --_--]
² Wait at least 10 seconds until LED 5 SD card write and LED 6 Trigger active go out on the device.
² Click the Refresh record overview button.
The new record is displayed in the overview. The record can be downloaded and displayed in SIGRA (see
3.8.5 Opening a Record in SIGRA).
² Open a project.
² On the left-hand edge, select the Devices tab.
² Select a device from the system navigation.
² Select the Record Overview tab.
The overview of all records of the device is displayed.
² Open the right-hand menu next to the desired downloaded record.
² Select Reveal in file explorer. The menu option only appears if the record has already been downloaded.
Microsoft Windows Explorer opens and the storage location of the record is displayed.
[sc_Open_File_Location, 1, --_--]
Figure 3-11 Displaying the file storage location of a record or opening the record in SIGRA
² Open a project.
² On the left-hand edge, select the Lines tab.
² Select a line from the system navigation.
² Select the Fault Location tab.
The overview of all records of the device assigned to the line is displayed. The records themselves do not have
to be stored on the computer.
² If not all records are displayed in the list yet, select Refresh record overview.
An overview of the records from the assigned devices is requested. Only records with associated time stamps
are displayed. Based on the time stamps, the fault location is calculated for all associated records, as described
in 2.2 Traveling Waves, and displayed. The fault location is specified as the distance from the device in the first
column.
Example:
On December 4, 2023 at 10:03 a.m., a fault was identified on the line. This is located at a distance of
79.299 km, starting from Device 1 in Station 1.
[sc_TWE_FaultLocation, 1, --_--]
Figure 3-12 Assigning the records from both ends of the line and the position of the fault on the line
Unpacking a Device
² Check the packaging for external transport damage. Damaged packaging may indicate that the devices
inside have also sustained damage.
² Unpack devices carefully; do not use force.
² Visually check the devices to ensure they are in perfect mechanical condition.
² Check the enclosed accessories against the delivery note to make sure everything is complete.
² Keep the packaging in case the devices need to be stored or transported elsewhere.
² Return damaged devices to Siemens, stating the defect. Use the original packaging or transport pack-
aging that meets the requirements of ISO standard 2248.
Repacking a Device
If you need to repack the device, proceed as follows:
² If the device is to be transported, pack it in transport packaging.
² Enclose the supplied accessories and the test certificate in the package.
Grounding a Device
Protection class I devices must be connected to the system ground prior to commissioning.
² Ground the device with a low-impedance operating ground. Use a cross-section of ≥ 4.0 mm2, an M4
ground screw and a tightening torque of 1.2 Nm.
! DANGER
Risk of electric shock due to live connecting cables.
Disregarding this may lead to death or severe injuries.
² Disconnect the cables and determine voltage-free status.
² Guide all connection lines to the current terminal I through the supplied ferrite core.
² Position the ferrite core close to the current terminal I.
² Connect the device to the current and voltage transformer of the system, as shown in A.4 Connection
Diagrams.
² Lay the communication lines separately from the operating voltage, measurement, and control lines.
² Connect the supply voltage to the device.
! DANGER
Danger during electrical inspection
Failure to observe this can result in death, serious injury, or significant material damage.
² If visual inspection or measurements on the protective conductors and insulation resistances reveal
defects, disconnect the line and determine voltage-free status.
! DANGER
Risk of fire due to ungrounded antenna.
Disregarding this may result in fire, serious injuries, or death.
² Ground the antenna properly in accordance with the manufacturer’s instructions and ensure lightning
protection.
NOTE
i To avoid interference signals, the antenna must be positioned at a distance from other devices and radio
systems.
4.4 Commissioning
For commissioning, the following conditions apply:
• The device is installed for stationary use, see 4.2 Device Assembly.
! DANGER
Risk of electric shock due to live connecting cables.
Disregarding this may lead to death or severe injuries.
² Disconnect the cables and determine voltage-free status.
² Ensure that the supply voltage corresponds to the technical data (Supply Voltage, Page 65).
Connect the supply voltage to the device.
NOTE
NOTE
i Make a note of the new password and store it in a safe place. Without the password, it is not possible to
update the device firmware.
5.1 Maintenance 62
5.2 Repair 62
5.3 Environmental Protection Hints 62
5.1 Maintenance
Cleaning the Device
! DANGER
Risk of electric shock due to live connecting cables.
Disregarding this may lead to death or severe injuries.
² Disconnect the cables and determine voltage-free status.
Update firmware
² On the SIOS portal (https://support.industry.siemens.com/), check whether new firmware for the device is
available.
² Carry out the firmware update as described in 3.7.5 Update firmware.
5.2 Repair
You are not permitted to perform troubleshooting or repairs on a defective device.
² If you suspect a defect in the device, send the device to the manufacturing facility.
² Use the original transport packaging or equivalent.
By disposing of these products correctly you will help to save valuable resources and prevent any potential
negative effects on human health and the environment.
NOTE
i Our products and batteries must not be disposed of as household waste. For disposing batteries it is
necessary to observe the local national/international directives.
Disposal of Mobile Storage Devices (e.g. USB Sticks and Memory Cards)
When disposing of/transferring mobile storage devices, using the format or delete functions only changes the
file management information and does not completely delete the data from your mobile storage device. When
disposing of or transferring a mobile storage device, Siemens strongly recommends physically destroying it
or completely deleting data from the mobile storage device by using a commercially available computer data
erasing software.
REACH/RoHS Declaration
You can find our current REACH/RoHS declarations at:
https://www.siemens.com/global/en/home/products/energy/ecotransparency/ecotransparency-down-
loads.html
NOTE
i You can find more information about activities and programs to protect the climate at the EcoTransparency
website:
https://www.siemens.com/global/en/home/products/energy/ecotransparency.html
Packing a Device
• If you store the device after the incoming goods inspection, it must be packed in appropriate storage
packaging.
NOTICE
Improper storage can cause damage to the device.
² Comply with all instructions regarding the storage area and storage temperature in order to avoid
material damage.
• Only store devices on which you have carried out an incoming inspection, thus ensuring that the
warranty remains valid.
• The storage area must be clean and dry to prevent the formation of condensation or ice.
• If the device has been in storage for more than 2 years, connect it to the supply voltage for 1 to 2 days.
This will cause the electrolytic capacitors to form on the printed circuit board assemblies again. Also do
this before planned operation of the device.
• If the device is to be shipped again, reuse the transport packaging. If other packaging is used, you must
ensure that the stresses during transport do not exceed those specified in ISO 2248. The storage packing
of the individual devices is not adequate for transport purposes.
Supply Voltage
Direct voltage
Rated input voltage 110 V to 250 V
Admissible input voltage tolerance -10 % of the rated value
+20 % of the rated value
Alternating voltage
Rated input voltage 100 V to 230 V
Power frequency 50 Hz to 60 Hz
Admissible input voltage tolerance ± 10 %
Power
Max. power consumption 30 W
Environmental Conditions
NOTE
Temperature specifications
Temperature during operation 0 °C to +40 °C
Temperature during transport and storage -25 °C to +85 °C
Humidity specifications
Average relative humidity ≤ 75 %
Maximum relative humidity 95 % on 30 days per year
Condensation during operation Not permitted
Condensation during transport and storage Permitted
Other environmental information
Maximum altitude above sea level 2000 m
Degree of pollution 2
Fuses
Degrees of Protection
Device IP20
Structural Variant
Electrical Connections
Current inputs, I1 to I4
Overvoltage category III
Insulation Double
ISO test voltage AC 2700 V, 1 min
Current-carrying capacity For Irated = 5 A continuous, 100 ⋅ Irated for 1 s
Voltage inputs, V1 to V4
Overvoltage category III
Rated Voltage AC 125 V
Insulation Protective impedance
ISO test voltage 4 kV, surge voltage
GNSS (time sync)
Rated Voltage 3.3 V
Insulation PELV
Ethernet, USB
Rated Voltage 5.0 V
Insulation PELV
Supply Voltage
Overvoltage category II
Insulation Double
ISO test voltage DC 2 kV, 1 min
Radiated
30 MHz to 1000 MHz Class A
Line-conducted
0.15 MHz to 30 MHz Class A
NOTE
i Class A devices are devices that are suitable for use in all other areas except the residential area and such
areas as are directly connected to a low voltage supply network that (also) supplies residential buildings.
HF fields
EN 61000-4-3 3 V/m (80 MHz to 1 GHz)
3 V/m (1.4 GHz to 2 GHz)
1 V/m (2.0 GHz to 6 GHz)
Standards Description
Vibration Test (sinusoidal) Sinusoidal 2 Hz to 9 Hz: ± 1.5 mm amplitude
IEC 60068-2-6 9 Hz to 200 Hz; 5 m/s2 acceleration
Frequency sweep 1 octave/min
20 cycles in 3 axes perpendicular to one another
Shock Test Semi-sinusoidal
IEC 60068-2-27 Acceleration 40 m/s2
Duration 22 ms
3 shocks each in both directions of the 3 axes
Seismic Tests Sinusoidal 2 Hz to 35 Hz:
IEC 60068-3-3 2 Hz to 8 Hz: ± 1 mm amplitude (horizontal axes)
2 Hz to 8 Hz: ± 2 mm amplitude (vertical axes)
8 Hz to 35 Hz: 5 m/s2 acceleration (horizontal axes)
8 Hz to 35 Hz: 2.5 m/s2 acceleration (vertical axis)
Frequency sweep 1 octave/min
1 cycle in 3 axes perpendicular to one another
Standards Description
Vibration Test (sinusoidal) Sinusoidal 2 Hz to 9 Hz: ± 3.5 mm amplitude
IEC 60068-2-6 9 Hz to 200 Hz: 10 m/s2 acceleration
200 Hz to 500 Hz: 15 m/s2 acceleration
Frequency sweep 1 octave/min
20 cycles in 3 axes perpendicular to one another
Shock Test Semi-sinusoidal
IEC 60068-2-27 Acceleration 100 m/s2
Duration 11 ms
3 shocks each in both directions of the 3 axes
A.1 Figures 69
A.2 Meaning of the LEDs 70
A.3 Ordering Information and Accessories 70
A.4 Connection Diagrams 71
A.1 Figures
Front View
[sc_Front_view_7SE20, 1, en_US]
Rear View
[sc_Rückansicht, 1, en_US]
Top View
Accessories
[dw_type-of-connection-current_7SE20, 1, en_US]
[dw_type-of-connection-voltage_7SE20, 1, en_US]
COMTRADE
COMTRADE is a file format for storing oscillography and status data associated with transient faults in the
electricity-supply system.
GLONASS
Global Navigation Satellite System
GNSS
Global Navigation Satellite System
GPS
Global Positioning System
PPS
Pulse Per Second
SIGRA
SIGRA is licensed software for the evaluation of fault records.
SIOS
Siemens Industry Online Support
TCP
Transmission Control Protocol
UDP
User Datagram Protocol
VPN
Virtual Private Network