Manual de Usuario
Manual de Usuario
Manual de Usuario
SPECIFICATIONS
Input voltage................................................... 115/277V, 120/347V, 50/60 Hz
For 0-10V models:
Sinks up to 100 mA per 0-10V input (50 fixtures at 2mA each)
0-10V signal will open on loss of power to panel
Class 2 connection to two independent DLM local networks
24VDC output................up to 250mA across 2 RJ45 ports per local network
...................................................................(A and B networks, 250 mA each)
Free-topology DLM local network may include Digital Lighting Management
(DLM) switches, occupancy sensors, daylight sensors, load controllers, and
input modules.
Category 5e cable, 150’ per device, up to 1,000 ft. total per local network
Terminals for connection to DLM segment network (BACnet MS/TP)
Segment network parameters
Wattstopper LM-MSTP wire
Linear topology, 4000 ft. maximum per segment
Accessory power (jumper selectable)
LMCP8/LMCP8-10V.............................................................................N/A
LMCP24/LMCP24-10V................. 650 mA @ 15VDC, 400 mA @ 24VDC
LMCP48/LMCP48-10V................. 650 mA @ 15VDC, 400 mA @ 24VDC
................................15VDC to power optional internal Network Controller
....................................................... 24VDC for Class 2 accessory devices
HDR relays (used in both On/Off and 0–10V panels):
Coil voltage, 24VDC, pulse ON and pulse OFF
Mechanically latched contacts
½” K.O. mounting, LV plug-connection, individually replaceable
HDR Heavy Duty Relay contact ratings:
30 A ballast................................................................................... @ 277V
20 A ballast................................................................................... @ 347V
16 A, E-Ballast.............................................................................. @ 120V
10 A, E-Ballast.............................................................................. @ 277V
20 A tungsten................................................................................ @ 120V
30 A resistive................................................................................ @ 347V
20 A receptacle load..................................................................... @ 120V
1.5 HP........................................................................................... @ 120V
SCCR (short circuit current rating) ...........................14,000 A @ 347VAC
Operating conditions:
for indoor use only.................................................... 32–140° F (0–60° C)
....................................................................... 5-95% RH, non-condensing
Upon loss of power, date and time info is maintained for 14+ days.
Programming info (including schedules) is maintained for the life of the
product.
UL and cUL listed (E207852). Listed for receptacle rated circuit control
Complementary Listed to Emergency Lighting Equipment, UL924
OSHPD (OSP) Approved (Certification No: OSP-0257)
Specifications.......................................................................................................................................................................1
Introduction..........................................................................................................................................................................4
Features and Basic Terminology.......................................................................................................................................................... 4
Panel Circuit Board Layout and Connection.....................................................................................................................5
Dip Switches ....................................................................................................................................................................................... 7
Connecting Panels to Other DLM Devices, and Panels to Panels...................................................................................................... 8
Connecting Override Switches Directly to a Panel.............................................................................................................................. 8
Load Numbering................................................................................................................................................................................... 8
Groups, Scenes, Schedules, and Macros..........................................................................................................................9
Group Settings vs. Individual Relay Settings..................................................................................................................................... 10
Group Functionality............................................................................................................................................................................ 10
Scenes............................................................................................................................................................................................... 11
Schedules.......................................................................................................................................................................................... 11
Macros............................................................................................................................................................................................... 12
Dark/Light Events...............................................................................................................................................................12
Astronomical Dark/Light Switching.................................................................................................................................................... 13
Switching Based on Input From an LMIO-301 or LMIN-104 and Photocell....................................................................................... 13
Connecting Switches, Sensors, Photocells, and Other DLM Accessory Devices.......................................................14
Accessory Device Support................................................................................................................................................................. 14
Switches............................................................................................................................................................................................. 14
Occupancy Sensors........................................................................................................................................................................... 14
Daylight Sensors................................................................................................................................................................................ 14
Analog Photocells.............................................................................................................................................................................. 14
Using the LMIN-104 to Interface with Third Party Devices................................................................................................................ 14
Using an LMCP with Room Controllers and Plug Load Controllers.............................................................................15
Load Control Arbitration..................................................................................................................................................................... 15
Programming the LMCP....................................................................................................................................................15
Load Binding to Groups 1–8 (Smartwire)........................................................................................................................................... 16
Push n’ Learn..................................................................................................................................................................................... 16
Programming Using the LMCT-100..................................................................................................................................17
LMCT-100-2 Basics............................................................................................................................................................................ 17
Configuring the Network Settings...................................................................................................................................................... 17
Viewing the Network Status............................................................................................................................................................... 19
Accessing Panel Setup...................................................................................................................................................................... 19
Setting the Panel Location................................................................................................................................................................. 19
Setting the Date and Time.................................................................................................................................................................. 20
Panel Programming........................................................................................................................................................................... 21
Schedules.......................................................................................................................................................................................... 21
Holidays............................................................................................................................................................................................. 22
Panel Status....................................................................................................................................................................................... 22
Accessing Group Setup Options........................................................................................................................................................ 23
Group Loads...................................................................................................................................................................................... 24
Group Occupancy Sensors................................................................................................................................................................ 25
Group Dark/Light................................................................................................................................................................................ 26
Utilities................................................................................................................................................................................................ 28
Load Status........................................................................................................................................................................................ 29
Group Status...................................................................................................................................................................................... 30
Light Level.......................................................................................................................................................................................... 31
2
Occupancy Sensor Status.................................................................................................................................................................. 31
Connecting Multiple LMCP Panels in a Network.............................................................................................................32
BACnet Settings................................................................................................................................................................................. 32
Examples of Using the LMCP in a BACnet Network.......................................................................................................................... 33
Appendix A..........................................................................................................................................................................35
BACnet Objects.................................................................................................................................................................................. 35
3
INTRODUCTION
The LMCP series panels are available for Dimming (LMCPx-10V) or INTERIOR ENCLOSURES
Switching (LMCPx) control of lighting and plug loads. The panels can be
networked together to enable automation through out an entire facility.
With LMCP panels, you can maintain code-compliant control of building exterior
lighting as well as larger interior areas. Recommended applications include office
building lobbies, corridors, loading docks, school gymnasiums, commons areas
and hallways. LMCP panels are also ideal for retrofit scenarios where mounting
control equipment near existing branch circuit breakers is beneficial, and digital
switches, sensor devices, and load parameter configuration are required to meet
complex operational sequences.
The HDR panel relays respond to inputs from Digital Lighting Management
(DLM) switches, occupancy sensors, daylight sensors, input modules and
0-10V outputs on dimming panel models.
Multiple panels may be networked together for global control operation
without the use of a Network Controller or BAS. The LMCP panel also
provides a native-BACnet integration solution via BACnet MS/TP, or with
optional NB-ROUTER, BACnet/IP. Relay, group, and control device status,
including occupancy sensor status, are available as BACnet objects. When a Figure 1: Panel interior and enclosures
Wattstopper Network Controller is used, it will automatically recognize LMCP
panels and map them to the browser-based user interface so that they can be configured with minimal additional setup.
Relay Connection Header Relay Status LEDs – The LED will be ON when the relay
turns on, and OFF when the relay turns off. It will blink during
the transition between Normal Hours and After Hours, for the
amount of time specified with the Blink parameter. (If blink time
is set to 0, it will not blink.)
In Smartwire mode, the LED will BLINK on and off when relay
is included in Group, and OFF when relay is excluded from
Group.
In PnL mode, the LED will be ON when relay is selected for
binding with buttons, and OFF when not selected.
5
Figure 2b: LMCPx-10V – Dimming Panel
LMRD Board
0-10V Connections
Override Buttons and Status LEDs Connect purple wire on “+” terminal,
Relay Connection Header
and pink wire on “-” terminal on the
removable connector
+
–
6
The photo below shows the current version of the LMPI board.
An older version of the board is shown on the following page.
Transformer
Power
Connector
Aux Power
Jumper
Selection
Aux Power
Connector
SW2 – 511 ohm
Group LEDs – Indicates the Group Buttons – Toggles Group 1 to 8
Bias Up
status for Group 1 to 8 for when pressed and released. Also used to
SW3 – 511 ohm
loads in this panel only, where enter and exit Smartwire mode.
Pull down
any member load ON indicates
(behind MS/TP Connector) SW4 – 120 ohm ON, and all member loads
Termination Resistor OFF indicates OFF. Blinks
LMRD Communication (behind MS/TP Connector)
Activity LEDs – Light when during Smartwire mode.
communication occurs MS/TP Connector –
between one of the four For connection to other
LMRD cards. panels - 3 connections Panel Config Button and LED
available
Dip Switches
The default for all dip switches is OFF.
P: Pilot Signal
Pilot Light
24VDC (max 5mA)
C: Pilot common
S: Override Signal
Momentary
PC SC C: Override common
Push Button
NOTE: These connectors are only found on LMCPX switching panels, and not on the LMCPx-10V dimming panels.
Load Numbering
Load IDs are assigned on the panel based on the LMRD cards. Loads are numbered on a single card from top to bottom. With multiple
cards, numbering continues from left to right, top, then bottom. So on an LMCP-48, loads are numbered as follows:
• Top Left Card – Loads 1–12 • Top Right Card – Loads 13–24
• Bottom Left Card – Loads 25–36 • Bottom Right Card – Loads 37–48
8
GROUPS, SCENES, SCHEDULES, AND MACROS
A group allows you to control one or more relays in one or more panels. Each group has seven parameters that will determine the
normal hours/after hours behavior of the relay(s):
Parameter Definition
Blink Amount of minutes load stays ON, when a scheduled event occurs that switches the load OFF when
transitioning from Normal Hours to After Hours. The relay will turn off and on once, then the Override LED for
that relay will blink continuously for the time period. The LEDs for all switches bound to that group will also
blink continuously. Pressing the button will keep the load ON and the time delay countdown will start. When
the countdown reaches 0, the blink function re-occurs.
NOTE: Blink does not apply when transitioning from After Hours to Normal Hours.
Possible values are:
• None
• 1–240 minutes
• Use Load – If set to this value , each individual load will use the value of the same parameter found
under the Load Settings menu.
• Reset to Load – This value is identical to “Use Load”.
Time Delay NH If a load is commanded to turn ON when the schedule switches to Normal Hours, the load will automatically
turn OFF after the time delay expires. If the load is turned on manually by a switch after the schedule
switches to Normal Hours, the load will again automatically turn OFF after the time delay expires.
Possible values are the same as Blink. Default is “None”
Time Delay AH Identical to Time Delay NH, but the behavior occurs when the schedule switches to After Hours. Works in
conjunction with Blink.
Possible values are the same as Blink. Default is “120 minutes”.
Transition AH > NH Behavior of the relay when Normal Hours begins.
Possible values:
• 0–100%
• LNZ – Returns to load to the last value that was not 0 (completely off)
• Do Nothing – No change occur
• LNZ Occupied – Returns to load to the last value that was not 0 (completely off) if the room has an
occupancy sensor and the sensor indicates the room is occupied. If the room is unoccupied or if there
no sensor in the room, there is no change to the load.
• Use Load – This uses the value for each individual load instead of a group value. Setting this value for
individual loads is only possible if using LMCS-100 software.
• Turn Off – Turns the load Off
Transition NH > AH Behavior of the relay when After Hours begins.
Possible values are the same as AH–>NH.
Sensor NH Determines how the relay responds to sensor input during Normal Hours. Possible values are:
• Nothing – Load does not respond to occupancy sensor
• Off Only – Responds to sensor input when vacancy is detected but not when occupancy is detected
• On Only – Responds to sensor input when occupancy is detected but not when vacancy is detected
• On/Off – Responds to sensor input for both occupancy and vacancy detection
• Off Only Internal – Responds to vacancy commands only. Instead of using the default value of one
minute for the blink warn feature, the sensor will use the amount of time entered in the Blink parameter.
• On Only Internal – The load responds only to Occupancy commands and once the load is on, it will
not shut off for the length of time entered in the Time Delay NH parameter. Instead of using the default
value of one minute for the blink warn feature, the sensor will use the amount of time entered in the
Blink parameter.
• On/Off Internal – Responds to both occupancy and vacancy commands. Instead of using the default
value of one minute for the blink warn feature, the sensor will use the amount of time entered in the
Blink parameter.
• Use Load – This uses the value for each individual load instead of a group value. Setting this value for
individual loads is only possible if using LMCS-100 software.
NOTE: Keep in mind that this parameter determines whether the loads assigned to the group will respond
to sensor input. It does not determine whether the loads will turn on or off. That is set within the
sensor programming (either on the sensor itself, or by using the LMCT-100-2 remote or LMCS-100
software).
Sensor AH Determines how the relay responds to sensor input during After Hours. Possible values same as above
NOTE: The start times for normal hours and after hours are determined by a Schedule. For details on Schedules, see “Schedules” on
page 11.
9
A group can be set to one of six macros, which contain pre-defined values for each of the seven parameters. Or, you can customize the
setting for your own specific needs. For details, see “Macros” on page 12.
10
Occupancy Sensor Events for Groups
An occupancy sensor event determines how loads assigned to a group will respond, based on input from an occupancy sensor. You can
program up to 99 events. A single event will be assigned to a group.
NOTE: If using multiple occupancy sensors, when programming with the LMCT-100, you should only assign ONE sensor input to a
group. Assigning more than one sensor to a group will lead to inconsistent response (but you can assign different sensors to
different groups). If you need to assign multiple sensors to a group, use the LMCS-100 software to program the actions. The
LMCS software has additional capabilities for programming input from multiple sensors.
NOTE: Occupancy sensor events can be assigned to either a group or a scene. For details on scenes, see below.
For each group, there is an Occupancy parameter (triggered when the sensor detects occupancy) and a Vacant parameter (triggered
when it detects vacancy). For group events, the available values for both occupancy and vacancy are:
• 0–100% – Load goes to the specific value selected
• LNZ – Set the load to the last non-zero level.
• Turn Off – This relinquishes the load—it doesn’t actually “turn off” the load. The loads will still wait for the sensor delay timers to
expire before turning off. If the Partial Off parameter on the Load Settings menu is a value other than 0, the load will go to that
level.
• Do Nothing – No change to the load.
• NH Ovrride – Set the load to Normal Hours. The value of the AH–>NH parameter for the group will be applied.
• AH Ovrride – Set the load to After Hours. The value of the NH–>AH parameter for the group will be applied.
• Normal Hrs – Set the load to Normal Hours. All settings found on the Normal Hours tab within LMCS-100 for loads and sensors will
be applied. (These settings are only available if you are using LMCS-100 software.)
• After Hrs – Set the load to After Hours. All settings found on the After Hours tab within LMCS-100 for loads and sensors will be
applied. (These settings are only available if you are using LMCS-100 software.)
Scenes
The LMCP also has the ability to control Scenes (but only on the panel’s Cat 5e local network). Scenes are similar to Groups in that they
control group of loads but also provide the ability to fade between one value and another when the scene is changed. For a switching
LMCP, if assigning relays within the LMCP to a scene, it will switch relays on or off, since no dimming is possible.
There are sixteen possible scenes per “room” (or in this case a panel). When a scene is activated (typically by assigning it to a switch),
all loads assigned to that scene will respond. You can select which loads are included in the scene.
Scenes are normally assigned to a button switch (the LMSW-105 5-Button Switch is commonly used for this but any button can be set
as a scene button).
Scenes can also be triggered by Occupancy Sensors and Dark/Light events. The load control is similar to that of Occupancy Sensors
and Dark/Light events for groups, but for scene events, you determine whether to turn the scene On or Off.
NOTE: Even though Scene events are separate from Group events, in the LMCT-100-2, you access these events from the Group Occ
Sensors and Group Dark/Light screens within the Group Setup menu
Schedules
You can schedule up to 254 date and time based events per panel. Each event is assigned to a group, and determines one action for
the group. For each event, you specify the time the event occurs. You also specify the days of the week in which the event will occur.
Additionally, you specify whether the event will occur on any day designated as a holiday.
The possible actions sent to the group include:
If panels are networked and multiple panels use the same group number to control relays in those panels, then any events scheduled
in one panel will affect the other panels (since events are always assigned to a group number). By using different group numbers in
different panels, you can limit which panels will respond to those scheduled events.
Assigning a Panel to be the Master Clock
Every LMCP has a clock in it, which allows you to set time and date for controlling schedule events and calculating sunrise and sunset for
Dark/Light events. To set the clock, use the LMCT-100-2 hand held remote, LMCS-100 software, or BACnet Time Synchronization via a BAS.
Additionally, if you have more than one panel networked together, any panel can be set to be the master clock. It will periodically send
out clock information to the other panels so that they remain synchronized. You can set how often the master sends the clock message.
The advantage of having any panel act as a master is that if the master panel is taken off-line for any reason, any other panel can be
easily set to be master and all panels will still remain in sync. (Note that if the original panel is put back on-line you will want to revert the
replacement master or the original panel to back to being a slave, so that you don’t have two master clocks on the network.)
To assign a panel as the master, you need LMCS-100 software. For more information on LMCS-100, see “Programming the LMCP” on
page 15.
11
Macros
A macro is a set of pre-defined values for the seven parameters that are part of a group. Each group can be set to a specific macro,
or to use no macro and instead use a customized set of values. There are six macros in the LMCP. Following is a description of the
intended use for each macro, followed by a list of all parameter values:
NOTE: If you want to set up custom parameters that are similar to one of the macros, select that macro first, then go into Custom mode
and change only the value that different from the macro default.
• Manual – This macro should be used when there are no occupancy sensors or switches associated with the Group and only on/off
actions from schedules or dark/light are intended. Since On/Off changes are based only on schedules and dark/light sensors, the
only parameter in the macro that has any effect is Blink, which will provide a warning to occupants by momentarily shutting the load
off and then back on.
• Override Time AH – This macro is designed for situations where only switches are used (no occupancy sensors). An override time
delay is set so that if a switch is used to keep the light on during after hours, the load turns off after two hours. The load is set to
turn ON when entering Normal Hours. If you instead want to require that the load be manually turned on, start with this macro when
creating the group, select CUSTOM, and modify the Transition AH > NH action to a value of “Do Nothing.” Additionally, adjust Time
Delay AH if you want a different amount of time before the load turns off.
NOTE: The settings in this macro are used for Groups 1–8, when you use Smartwire to assign relays to a group.
• Sensor Day Disable – For use with occupancy sensors, this macro turns all loads ON during Normal Hours; they can be turned off
or back on manually, with no override time delay. When After Hours begins, loads are turned OFF and sensor functionality is set to
Auto On/Off. A two hour time delay is set for cases in which some loads in the group are not bound to sensors, but only to switches.
• Sensor Man-On NH – In this macro, relays are left OFF when Normal Hours begins. Occupancy sensors trigger loads on occupant
arrival, but do not time out until after hours. When After Hours begins, loads turn OFF and sensors switch to Auto On/Off. As with
the Sensor Day Disable macro, a two hour time delay is set for cases in which some loads in the group are not bound to sensors,
but only to switches.
• Sensor Auto – This macro sets sensors to Auto On/Off for both Normal Hours and After Hours operation, so loads turn ON only
based on sensor or switch input. A 120 minute override time delay is used during the After Hours period. This allows for consistent
functionality in response to sensors at all times, while accommodating the inclusion of relays not bound to sensors that share the
same operational time window.
• Auto Switch-1xx – This macro is designed to work with the AS-100 Automatic Control Switch. The AS-100 is a switch that controls
the line voltage (instead of sending a low voltage control message to the panel or other room controller). Instead, the AS-100
responds to timed power interrupt signals coming from a relay in the panel, providing automatic shutoff with a blink warning when
transitioning between normal hours and after hours. Other timed interrupt signals can turn the power on or off. You assign a relay
to “AS-100” mode using LMCS-100 software or on the Load Config (PnL) menu in the LMCT-100-2. All relays in “AS-100 mode”
remain closed except for the timed interrupts. If this macro is assigned to a group, you should only assign relays in “AS-100” mode
to that group. When using this Macro, none of the seven group parameters apply. (Although Blink is set to 5 minutes, the blink time
is actually controlled by the AS-100, not the LMCP.)
NOTE: Since selecting this mode puts all relay in the associated group into “AS-100” mode, you should not assign those relays to
another group set to a different macro.
NOTE: Keep in mind that Macros only affect the behavior during the transitions to Normal Hours and After Hours, plus the response to
occupancy sensors. Any scheduled events and input from photocell sensors will still affect the loads.
NOTE: The values for the seven parameters are only applied to the Group when the Macro (or custom) information is sent to the LMCP
from the LMCT-100-2 remote or LMCS-100 software. If a subsequent message is sent to the LMCP with a different value for
a parameter, the original value is overwritten, and will only change back to the original value if the Macro is sent again to the
group. So for example, if a relay is assigned to two different groups, and each group has been assigned a different Macro, the
last macro sent to the LMCP will determine the behavior of that relay.
Macro Values
General Settings Transition Settings Sensor Behavior
Macro Blink Time Delay NH Time Delay AH NH>AH AH>NH NH AH
Manual 5 min None None Do nothing Do nothing Off Only Off Only
Override Time AH 5 min None 120 min Turn off Turn on Off Only Off Only
Sensor Disable Day 5 min None 120 min Turn off Turn on Follow On Auto
Only
Sensor Man-On NH None None 120 min Turn off Do nothing Off Only Auto
Sensor Auto 5 min None 120 min Do nothing Do nothing Auto Auto
Auto Switch-1xx 5 min None None Do nothing Do nothing Do nothing Do nothing
DARK/LIGHT EVENTS
The LMCP can be programmed to turn relays on or off based on when it becomes dark outside (night) or light (day). You can program
up to 32 separate dark/light events, and each event is assigned to a group or a scene. For each event, you can select whether to base
the change from dark to light and light to dark on either an astronomical calculation of sunrise and sunset, or from a photocell connected
to an LMIN-104 or LMIO-301. You can have multiple LMIN-104s/LMIO-301s connected to the network and assign different groups to
different LMIN-104 or LMIO-301s, or you can have a single LMIN-104 or LMIO-301 but assign different light thresholds to different
groups.
NOTE: You can only select a single LMIN-104 or LMIO-301 if programming with the LMCT-100-2. To use multiple LMIN-104s/LMIO-
301s, you must program with the LMCS-100 software.
12
Each Dark/Light event has a Dark parameter and Light parameter.
If the event is assigned to a group, then for each parameter you can choose the following:
• 0-100% – Load goes to the specific value selected
• LNZ – Set the load to the last non-zero level.
• Turn Off – This relinquishes the load—it doesn’t actually “turn off” the load. The loads will still wait for the sensor delay timers to
expire before turning off. If the Partial Off parameter on the Load Settings menu is a value other than 0, the load will go to that
level.
• Do Nothing – No change to the load.
• NH Override – Set the load to Normal Hours. The value of the AH–>NH parameter for the group will be applied.
• AH Override – Set the load to After Hours. The value of the NH–>AH parameter for the group will be applied.
• Normal Hrs – Set the load to Normal Hours. All settings found on the Normal Hours tab within LMCS-100 for loads and sensors will
be applied. (These settings are only available if you are using LMCS-100 software.)
• After Hrs – Set the load to After Hours. All settings found on the After Hours tab within LMCS-100 for loads and sensors will be
applied. (These settings are only available if you are using LMCS-100 software.)
If the event is assigned to a Scene, then for each parameter you choose whether to turn the Scene On or Off.
Dark Light
aka Sunset aka Sunrise
aka Dusk aka Dawn
13
CONNECTING SWITCHES, SENSORS, PHOTOCELLS, AND OTHER DLM ACCESSORY DEVICES
Switches
The panel’s local DLM network supports all models of DLM switches. Switch buttons may be bound to an individual relay (load), scene,
or network group in the panel. If a switch is bound to a group and any load assigned to that group is ON, the LED on that switch will
indicate ON.
There are several advantages to binding a switch to a group:
• If you add a load to a group, that switch will immediately control that load without having to re-program the switch.
• You can assign a switch to the same set of loads controlled by a schedule or dark/light event
• If you have multiple panels connected, and the same group number assigned to loads in those panels, the switch will control the
loads from those other panels in addition to the panel in its local network. This allows you to program a single switch that can be
used as a master, to turn all lights on or off in the case of an emergency or other special circumstance.
Occupancy Sensors
The panel’s local network supports all models of DLM occupancy sensors. Using Push n’ Learn, any number of occupancy sensors can
control the same relay(s) in the local panel. In this case, all sensors must be in the unoccupied state before the relay(s) turn off.
A maximum of 32 sensors can control an individual load. (The total number of sensors controlling various loads is limited only by the
network limitations described above.)
Daylight Sensors
The LMLS-400 and LMLS-500 daylight sensors are capable of controlling relays in the panel as switching loads, or dimming loads if a
dimming capable room controller is connected to the local DLM network.
Analog Photocells
As described in the previous section on Dark/Light Events, the panel’s local network supports the LMIO-301 Analog Photocell Module or
LMIN-104. This module supplies the “light” and “dark” trigger. The panel has user settings for foot candle levels and time delay. The time
delay is used before triggering “light” and “dark” events to establish a dead band and prevent nuisance switching. Only one LMIO-301
per panel can be programmed via the LMCT-100; more can be connected if using LMCS-100 software.
Two types of photocell sensor heads can be used. The LMPO-200 is intended for outdoor use, while the LMPS-6000 is intended
for indoor use where there is direct exposure to high light levels, as would be present adjacent to the glass in an atrium, skylight, or
clearstory.
14
USING AN LMCP WITH ROOM CONTROLLERS AND PLUG LOAD CONTROLLERS
By connecting room controllers and plug load controllers to the DLM local network, you can increase the number of loads in the network.
The maximum number of loads, including all the loads within the panel, is 64. Since the maximum number of devices on a single
network is 48, the total number of additional controllers possible will also be dependent on the number of other DLM devices on that
network. The same cable length requirements apply as with other DLM devices.
Connecting additional controllers to the panel provides several advantages:
• The loads connected to those controllers can be assigned to groups, the same as the relays in the panel. This allows for scheduling
of those loads and all other group features.
• Dimming loads can be added to the network, provided you have a room controller with dimming capability.
• Current monitoring of plug loads and dimming loads is possible as part of the network control. (Note that current monitoring of
dimming loads within the panel is not available.)
NOTE: There is a maximum of 4 LMRC-10x room controllers, LMPL-101 plug load controllers, and/or LMPB-100 power boosters
allowed per network (A or B), for a maximum total of 8. This applies only to the 10x series and not the 2xx series.
Connecting Room and Plug Load Controllers
Network A LMPL-
213 102 211 213 221 101
16
3. To exit PnL, hold the Config button for 3 seconds, until the LED stops blinking. Or if using the LMCT-100-2, select EXIT.
If you have one or more DLM Room controllers connected to the LMCP, then as when you cycle through the loads by pressing the
Config button, once the last relay is reached on the LMCP, the sequence advances to the Room Controller with the highest serial
number and cycles through the loads on that controller in order.
A primary difference in operation of the LMCP compared to a DLM Room Controller is that by default, while in load configuration mode,
the panel relays do not turn on and off in sequence as the Config button is pressed. Only the LED associated with the relay turns on On
a DLM Room Controller, the load itself will turn on and off.
NOTE: It is possible to change the LMCP so that the relays turn on and off in PnL, just like a room controller. This is done by setting Dip
switch #7 on the LMPI board to the ON position.
LMCT-100-2 Basics
The LMCT-100-2 provides an easy to read display and a simple user interface that makes it easy to navigate through programmable
features It both send information to and receives information from the LMCP and other DLM devices.
It is important to understand that all information is stored in the LMCP or accessory devices, and not the
LMCT-100-2. Therefore, if you change any values on the LMCT-100-2, you must select the Send option in order to save your changes.
If you press the Home button, Back button, or select Done without first sending the data to the LMCP, that data is not saved.
User Interface Navigation
You navigate from one field to another using (up) or (down) arrow keys. The active field flashes between yellow text on black
background and black text on yellow background. Navigation “wraps” around, so if the active field is the top field and you need to get to
the field at the bottom of the screen, pressing will bring you to the bottom in a single key press.
NOTE: The up and down arrow keys are always used to move between fields. So even when fields are placed on the same horizontal
line, which is often found with the Action options at the bottom of the screen, you still use the Up/Down arrows to move left/right
between fields.
Once a menu field is active, press the Select button to open that menu.
Value fields are used to adjust parameter settings. They are shown within “less than/greater than” symbols: <value>. Change the value
using and arrow keys. In general the key increments and the key decrements a value. Selections wrap-around if you
continue to press the key beyond maximum or minimum values. Move between value fields using or arrow keys.
The button takes you to the main menu.
The (Back) button can be thought of as an undo function. It takes you back one screen. Changes that were in process prior to
pressing the key are lost.
At the bottom of any screen that includes programmable fields, you will see Send and Done (and sometimes additional choices). As
mentioned previously, you must press Send to save your data to the LMCP before pressing Done, if you want to save the values you
set on that screen.
On some screens, one of the options at the bottom of the screen will take you to a secondary, related screen. For example, at the
bottom of the Program Schedules screen is an Active Days option, where you choose which days the schedule will be active. In the
case, the Schedule Active On screen has only a Done option at the bottom—you must return to the Program Schedules screen
before you can send the schedule information to the LMCP.
Up or Down Select
Button Button
17
Display Description Press
B AT =
Adjust Light Level
Global Network then
Utilities Scroll to Global Network. Press Select. Select
Panel Setup
Group Setup
More
Network - Panel
18
Viewing the Network Status
The Network Status shows the communication “health” of the network and the number of devices currently found on the network.
Display Description Press
Network - Panel
B AT =
Adjust Light Level
Global Network Scroll Down or Up to Highlight Panel Select, then
press Select. or then
Utilities Select
Panel Setup
Group Setup
More
Panel Setup
Location Settings This screen is the starting point for all following
Date and Time instructions.
Panel Programming
Panel Status
19
Display Description Press
Panel Setup
Location Settings When you first enter the Panel Setup screen,
Date and Time Location Settings is already highlighted. Select
Panel Programming Press Select.
Panel Status
Panel Setup
Location Settings From Panel Setup, scroll to Date and Time. Press then
Date and Time Select. Select
Panel Programming
Panel Status
Date and Time Set Scroll to each field and set the value. An illegal to move to each
or
Ye a r : <2014> date (for example, February 30) cannot be entered. parameter
Month: <August> After selecting all values, scroll to DSTSTD and to change the value
Date: <14> press Select. or
of the parameter
Hour (24 Hour): <16>
Minute: <37> NOTE: There is no clock in the LMCT-100-2, then choose
so the time values will not change if you DSTSTD and
SEND DSTSTD DONE remain on this screen longer than a minute. press Select
This screen determines if the panel will follow to move to each
D S T C o n fi g u r a t i o n Daylight Savings Time. If you set Follows DST or
parameter
to “Yes”, you can choose a value of “Auto” or
F o l l o w s D S T: < Ye s > “Manual” for Method. Select BEGINS. to change the value
Method: <Auto> or
NOTE: If you set Follows DST to “No”, the of the parameter
Method field disappears. Highlight DONE then choose
and press Select, or press to return to BEGINS and
BEGINS ENDS DONE press Select
the Date and Time Set screen
20
Display Description Press
Panel Programming
Panel Programming functions include:
• Schedules – Allows you to specify an event and assign it to a group
• Holidays – Allows you to specify a specific date as a holiday. Used in conjunction with schedules.
Display Description Press
Panel Setup
Panel Programming
603981210
To avoid repeating the same steps for every function described in the following pages, the Panel Programming Sections assume you
have already navigated to the Panel Programming screen.
Schedules
On this set of screens, you assign and event to a group, and set one action for that event. For each event, you specify the time the
event occurs. You also specify whether the event will occur on a per day basis. Additionally, you specify whether the event will occur on
any day designated as a holiday.
Display Description Press
Panel Programming
603981210
From the Panel Programming screen, highlight Select
Schedules
Holidays Schedules and press Select
21
Display Description Press
Schedule Active On For each day of the week, select whether the to move to each
or
event will be active (Yes or No). Additionally, select parameter
Mon: <Y> Tu e : <Y> whether the event will be active on holidays. (You
We d : <Y> Thu: <Y> to change the value
determine which days are holidays in the Holidays or
Fri: <Y> Sat: <N> of the parameter
Sun: <N> Holiday: <N> screen.)
then choose
Highlight DONE and press Select to return to the DONE and
DONE Program Schedule screen. press Select
Holidays
On this screen, you determine which days are designated as holidays.
Display Description Press
Panel Programming
603981210
From the Panel Programming screen, highlight then
Schedules
Holidays Holidays and press Select Select
Point to the desired Point the LMCT-100-2 at the infrared sensor on the
Panel IR Sensor and
press ‘Select’ LMRD board and press Select to open the Holiday Select
Setup screen.
Panel Status
This screen displays the date and time,based on the panel settings, sunrise/sunset times based on date and location settings, whether
the current date is a holiday, and the current settings of the dip switches. Additionally, it will display an error message for certain
problems.
22
Display Description Press
Panel Setup
Point to the desired Point the LMCT-100-2 at the infrared sensor on the
Panel IR Sensor and LMRD board and press Select.
press ‘Select’
Select
One of the following screens will display,
depending on the Status option you selected.
B AT =
Adjust Light Level
Global Network Navigate to the Group Setup option on the second then
Utilities main menu screen and press Select. Select
Panel Setup
Group Setup
More
WARNING:
LMBC or Panel must
be connected A warning appears, explaining that a bridge or
To a c c e s s panel is needed for this functionality. Press Select, Select
Group Setup then point the LMCT-100-2 at any IR enabled
device and press Select again..
Press ‘Select’
to proceed
23
Display Description Press
DONE
Group Loads
On this set of screens, you assign loads to groups and customize the behavior of those groups.
Display Description Press
DONE
Group Setup
to choose the
Group: <1+> or
Ty p e : <Custom+> Choose the Group number. Press Select to open Group number
the Group x Loads screen. then press
Select
DONE DELETE SEND
to move to each
or
Group 1 Loads To assign various loads to the group, scroll through parameter
each Load number and select whether that load to change the value
is a Member of that group. When complete, select or
Load: <1> of the parameter
DONE to return to the Group Setup screen. then choose
Member: < Ye s > DONE and
You also select have the option of using the
Smartwire function instead of manually scrolling press Select
DONE SMARTWIRE through the loads. To do this, select SMARTWIRE. OR
Select SMARTWIRE
P oint to any IR
enabled devic e and
press Selec t to Point the LMCT-100-2 at the infrared sensor on the Select
begin Smartwiring LMRD board and press Select
loads within the
P anel
24
Display Description Press
DONE
25
Display Description Press
Group Dark/Light
On this set of screens, you assign individual dark/light events.
Display Description Press
DONE
Point to the desired Point the LMCT-100-2 at the infrared sensor on the
Panel IR Sensor and
press ‘Select’ LMRD board and press Select to open the Dark/ Select
Light Events screen.
26
Display Description Press
Dark/Light Events
Event: <1> to change the value
or
Select the Event number in which to store the of the parameter
dark/light event. Then highlight NEXT and press then choose
Select to open the Dark/Light Event x screen. NEXT and
press Select
NEXT DONE DELETE SEND
27
Display Description Press
Utilities
The LMCT-100-2 contain a number of different Utilities. This section covers the Status utilities provide status information on loads and
groups, photosensors, and sensors connected to the panel.
An additional screen containing status information specific to panels is also available from the Panel Setup screen. See “Panel Status”
on page 22.
Display Description Press
B AT =
Adjust Light Level
Global Network Navigate to the Utilities option on the second main then
Utilities menu screen and press Select. Select
Panel Setup
Group Setup
More
Utilities Menu
SmartWire
Identify Devices
Force System into PnG
Navigate to the Status option and press Select.
then
Room Mode Select
Load Shed
Status
Done
Status – Panel
Load Status
Group Status
Light Level Press Select to choose the Load Status option. Select
Occupancy Sensors
Done
28
Load Status
This set of screens displays details about each load in the panel, as well as any loads in connected room controllers.
Display Description Press
Load 1 Online
This screen displays the BACnet priority of the load
1 2 3 4 5 6
. . . . . . DLM devices will typically have a priority of 8. Select
7 8 9 10 11 12 Highlight PROPERTIES and press Select.
. 1 . . . .
13 14 15 16
. . . .
PROPERTIES DONE
Load 2 Properties 3
This screen displays the sensor behavior for this
Sensor Behavior
AH: Man On/Auto Off load.
Select DONE
NH: Auto On/Off Highlight DONE and press Select to return to the
Status screen.
PRIOR DONE
29
Group Status
This set of screens displays the loads that are assigned to the group, along with their current on/off state. Additionally, you can view the
settings for the group. Finally, in cases where the setting of an individual load are different from the group settings, you can view the
differences. This can be extremely helpful when trying to diagnose a situation in which a load is not responding as expected. Keep in
mind that individual loads can be programmed with different values from the group but still be a member of the group.
Display Description Press
Status – Panel
Load Status
Group Status From the Status Menu, highlight the Group Status then
Light Level option and press Select. Select
Occupancy Sensors
Done
Group Status
to change the value
Group: <1> or
Select the Group number that you want to display, of the parameter
highlight NEXT, and press Select. then choose
NEXT and
press Select
NEXT DONE
Press
Select Point the LMCT-100-2 at the infrared sensor on the
Point to the desired
Panel IR Sensor and LMRD board and press Select.
press ‘Select’
Select
One of the following screens will display,
depending on the Status option you selected.
30
Display Description Press
Light Level
This screen displays the current light level, in foot candles, registered by an LMIO-301 with an attached photosensor.
Status – Panel
Load Status
Group Status From the Status Menu, highlight the Light Level then
Light Level option and press Select. Select
Occupancy Sensors
Done
Status – Panel
Load Status
Group Status From the Status Menu, highlight the Occupancy then
Light Level Sensors option and press Select. Select
Occupancy Sensors
Done
31
Display Description Press
BACnet Settings
The following parameter settings and concepts are important to understand when configuring the LMCP for BACnet communication:
• Device ID – The device ID is a unique number, between 0 and 4194302, that identifies a device in a BACnet network. Every device
in the network must have a different number. By default, the LMCP uses the last 6 digits of the serial number (plus a leading 0 to
complete the seven digit number). This number can be changed if needed, for example, when required by an integrator, as part of a
BAS. Once set, the LMCP will remember the ID number even if other parameters are reset to their default values.
• Device Name – This is a label for the panel, useful when working with LMCS in a situation where multiple panels are used, to help
more easily distinguish between the panels. Any numerals or letters can be used in naming the panel. By default, the name is the
same as the serial number. The name can be programmed using either LMCS, the LMCT-100-2, or a BAS application.
• MS/TP MAC Address – The MS/TP MAC address is an additional identifier, used by the devices on the network to communicate
with each other. It is a number between 0 and 127. It is important to understand the difference between the device ID and the MS/
TP MAC Address. The Device ID is, in essence, a number that identifies “who” the devices is, while the MS/TP MAC address
identifies its “location”.
In a BACnet network, all the devices pass a token to each other to determine which device has control of communication over
the network. The MS/TP MAC address is used to “locate” other devices. When a device receives the token, it will take control of
the communication and send messages to other devices as needed. It then passes the token to the device with the next highest
MS/TP MAC address. In order to do this, it sends an “Are you there?” message on the MAC address one higher than its own. If it
receives a response, it passes the token. If it does not receive a response, it tries again on the next highest number, continuing in
this manner until it receives a response. This “Are you there?” message is referred to as a Poll For Master.
NOTE: In order to send and respond to this Poll For Master message, a device must be designated as a master device. Other
devices (slave devices) on the network will not respond, and cannot take control of the communication.
While the Device ID is fixed and should not change, the MS/TP MAC address can change as devices come on or drop off the
network. By default, the LMCP will automatically assign an MS/TP MAC address. When the LMCP is powered up, it will check
the network for other devices to determine if its current MAC address is being used by another device. If, not it will keep the same
address, but if it is, and will assign an unused number between 32 and 127.
You can manually assign an MS/TP MAC address instead of having the LMCP automatically assign the number. This can be
useful, especially in larger networks where response time is important. Since the Poll For Master message checks the next highest
address number and then increments that number until it finds a device, having devices with gaps between numbers can increase
latency. If you have 10 devices, numbered 0–9, you will have optimal performance since no time is wasted sending the Poll For
Master message to an unused number.
32
• Max Master – The Max Master parameter is another parameter that will cut down on latency. The value you set for this parameter
is the highest number the LMCP will check when sending a Poll For Master message, before returning to 0. So, in the previous
example, where there are 10 devices numbered 0–9, if you set the Max Master to 9, it will never check addresses 10–127.
NOTE: If using the LMCP with a global controller such as a router, BAS or Segment Manager, the global controller will always
default to a MAC address of 0.
NOTE: You should be aware that devices connected over the DLM Local Network also have MAC addresses for communication
purposes, but that MAC address is entirely separate from the MS/TP MAC address.
Further details on Device IDs and MAC addresses can be found in WattStopper’s Technical Bulletin #180 at http://www.wattstopper.com/
resources/download-center/tech-bulletins-whitepapers.aspx.
33
BACnet Connectivity Scenarios
LMCP Panels
ID: 86004 ID: 86005 ID: 86006 ID: 86007 ID: 86008
MAC: 04 MAC: 01 MAC: 06 MAC: 07 MAC: 08
The Device ID’s of this BACnet Segment Network are unique so that it could be combined
with the top network if desired. Combining Segment Networks is done using NB-ROUTERs
that must then assign a network number to each Segment Network.
34
APPENDIX A
BACnet Objects
NOTE: While there are 96 object instances available for many of the objects listed below, keep in mind that the LMCP panel supports
only 48 devices per network (A & B), and the panel itself is one of the devices in each network. Therefore, there is never a case
where you would use all 48 instances of an object in a single network.
35
Object Instance Object Alias Object Function
BI101–BI9608 Button state Read button state for 1 to 8 buttons per switch for 1 to 96 switches.
BI1–BI96 Detection state Occupancy sensor detection state. Active = occupied.
BV101–196 Switch lock status Read switch status (locked or unlocked).
Active = locked.
BV201-299 Group Normal Hours/After Hours Normal Hours/After Hours selection for a group.
Active = after hours.
MV4001–MV4096 Daylight sensor 1–96, operating mode For LMLS-400 daylight sensor 1–96, operation mode:
1 = ON/OFF, 2 = bi-level, 3 = tri-level, 4 = dimming.
MV4101–MV4196 Daylight sensor 1–96, setpoint multiplier For LMLS-400, off setpoint multiplier: 1=1.25x, 2=1.50x, 3=1.75x, 4=2x.
Room Level Control Objects
BV1 Schedule state Normal hours/after hours selection. Active = after hours.
NOTE: This changes the status for the entire panel, and therefore can
conflict with BV201-299, if not used carefully.
BV2 Switch lock control Lock or unlock enabled switches. Active = lock.
NOTE: This changes the switch lock status for every switch connected
to the panel, and therefore can conflict with BV101-196, if not
used carefully.
BV3 Room occupancy status Read occupancy status (occupied or unoccupied).
Active = occupied.
NOTE: This is the logical OR of the states of ALL sensors connected
to the panel regardless of their local control scheme. In other
words, if any sensor has a status of occupied, this value will
read occupied.
BV4 Force all loads ON Active = all loads ON at priority 1. Inactive = relinquish at 1 and ON at
priority 8.
NOTE: This will force all loads connected to the panel ON.
BV5 Force all loads OFF Active = all loads OFF at priority 2. Inactive = relinquish.
NOTE: This will force all loads connected to the panel OFF.
MV1 Scene control Write scene selection. Range = 1 to 16.
MV2 Demand response (shed) control Activate room level DR mode: 1 = no shed, 2 = shed mode, permit
switch override, 3 = shed mode, prohibit switch override.
NOTE: This will affect all loads connected to the panel.
AV901 MS/TP MAC address Default is 255 for automatic, writable in the range of 0 to 127.
AV902 MS/TP network speed Baud rate: 9600, 19200, 38400, 57600, 78600, 115200.
AV903 Input room size Allows user to write area in square feet from 0 to 65,534, default is 0.
AV904 Room lighting watts Read total lighting wattage for room.
Total of baseline watts for active relays, or if no baseline wattage for
the relays are used, then this is calculated as AV401 * AV501 + any
usage from LMRC/LMFC connected via CAT5 to the panel.
NOTE: This does not include used from LMPLs. Use AV906 for plug
load controllers.
AV905 Room watts/sq.ft. Read total room lighting W/ft2.
If the input room size for the entire application area is used and the
baseline watts method or AV401 * AV501 method is used, then this
object will calculate the aggregate watts per square foot of the whole
panel’s application area.
Use of this object is not recommended for use in applications where
panels cover mixed areas.
AV906 Room plug load watts Read total plug load wattage for LMPLs connected to the panel.
36
WARRANTY INFORMATION INFORMATIONS RELATIVES À LA GARANTIE INFORMACIÓN DE LA GARANTÍA
Wattstopper warranties its products to be free Wattstopper garantit que ses produits sont Wattstopper garantiza que sus productos
of defects in materials and workmanship for a exempts de défauts de matériaux et de fabrication están libres de defectos en materiales y mano
period of five (5) years. There are no obligations pour une période de cinq (5) ans. Wattstopper de obra por un período de cinco (5) años. No
or liabilities on the part of Wattstopper for ne peut être tenu responsable de tout dommage existen obligaciones ni responsabilidades por
consequential damages arising out of, or in consécutif causé par ou lié à l’utilisation ou parte de Wattstopper por daños consecuentes
connection with, the use or performance of this à la performance de ce produit ou tout autre que se deriven o estén relacionados con el
product or other indirect damages with respect dommage indirect lié à la perte de propriété, de uso o el rendimiento de este producto u otros
to loss of property, revenue or profit, or cost of revenus, ou de profits, ou aux coûts d’enlèvement, daños indirectos con respecto a la pérdida
removal, installation or reinstallation. d’installation ou de réinstallation. de propiedad, renta o ganancias, o al costo
de extracción, instalación o reinstalación.