3-C CU 5kV 115 NLEPR 133 Percent ARMOR-X PVC MV-105 VFD - Spec
3-C CU 5kV 115 NLEPR 133 Percent ARMOR-X PVC MV-105 VFD - Spec
3-C CU 5kV 115 NLEPR 133 Percent ARMOR-X PVC MV-105 VFD - Spec
B) Conductor
semi-con
B) Conductor
semi-con
1 3 9 10
10 9 8 7 6 5 4 3 2 1
CONSTRUCTION:
1. Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
2. Conductor Shield: Semi-conducting cross-linked copolymer
3. Insulation: 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level,
4. Insulation Shield: Stripable semi-conducting cross-linked copolymer
5. Copper Tape Shield: Helically wrapped 5 mil copper tape with 25% overlap
6. Grounding Conductor: 3 Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
7. Filler: Wax paper filler
8. Binder: Polypropylene tape
9. Armor: Continuous Corrugated Welded Armor (Armor-X)
10. Overall Jacket: Polyvinyl Chloride (PVC)
SPECIFICATIONS:
• ASTM B3 Soft or annealed copper
• ASTM B8 Concentric-lay-standard copper
• UL 1072 - Medium Voltage Power Cables
• ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable & ICEA S-97-682 5-46 KV Utility
• UL 1685/FT4 Vertical-Tray Fire Propagation and Smoke Release Test
• IEEE 1202 -Flame Test (70,000) BTU/hr Vertical Tray Test
• AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV