Configuration Information, EA India

No: 001 S
Procedure to Change Device ID of Secure
0 SIMATIC 26-01-2017 PSP NSB
make meter using Modscan Tool
REV PRODUCT DATE DESCRIPTION AUTHOR Approved By
DRAWING/DOCUMENT DESCRIPTION SCALE SIZE
N.A A4

TOTAL NO OF PAGES
SIEMENS Configuration Info EA India: 001
06

Template.doc
Page 1 of 7
Date saved:26.01.17
Unrestricted
Configuration Information, EA India
No: 001 S
Table of Contents
1 Brief
2. Configuration in Modscan Tool
…………………………………………………………………………………..3

Template.doc
Page 2 of 7
Date saved:26.01.17
Unrestricted
Configuration Information, EA India
No: 001 S
1 Brief
This document describes the configuration that has to be done in Modscan Tool to
change Device ID of Secure make meter.

2 Configuration in Modscan Tool.


Open Modscan32 Software and connect with the device and follow the below steps.

1. Change following configuration settings and check the data on modbus with default device id.
a. Address – 2013 or 2014(42013 to 42014 is Modbus device id)
b. Device Id- 1(default meter device id is one)
c. Modbus Point Type- Holding Register

2. Steps to Change Device Id:


Setup Extended Preset Regs

Template.doc
Page 3 of 7
Date saved:26.01.17
Unrestricted
Configuration Information, EA India
No: 001 S

Just click OK after the above

Change the device id

Template.doc
Page 4 of 7
Date saved:26.01.17
Unrestricted
Configuration Information, EA India
No: 001 S
3. Now device id has changed, Meter is not responding with old MODBUS ID(1) & Time out message is
displaying (marked in circle) .

4. Now device new ID is 10.

Template.doc
Page 5 of 7
Date saved:26.01.17
Unrestricted
Configuration Information, EA India
No: 001 S

5. Procedure To change Baud rate:-


To change the baud rate use same procedure mentioned above.
Address =2015 or 2016 (address to change the baud rate)
Write 04=1200(Baud Rate),06=2400,08=4800 and 0A=9600 (Baud Rate).

Template.doc
Page 6 of 7
Date saved:26.01.17
Unrestricted
Configuration Information, EA India
No: 001 S

By default meter Baud Rate is 9600.

Note: This procedure is tested for “PREMIER 300 SECURE METER”.

Template.doc
Page 7 of 7
Date saved:26.01.17
Unrestricted