Speed controllers for DC motors
Module adaptation référence vitesse
Speed reference adaptation module

VW3-RZE101

GS
Sommaire / Contents

Français Fonctionnement - Caractéristiques 1

Synoptique - Raccordements 2

English Operation - Characteristics 3

Block diagram - Cabling 4


Operation This module generates the ± 10 V speed reference for the speed controller from an
operating direction and from :
- either a 0 +10 V reference,
- or a 0 - 20 mA or 4 - 20 mA current reference.

The voltage reference input and the 0 - 20 mA current reference input may be used
simultaneously. If so, the following correspondence must always be checked :

500 ± I(EC1) + V(E1) ≤ 10 V with I(EC1) in mA .

The 4 - 20 mA current reference input must be used alone.


The power is supplied from the speed controller.

Electrical Name function


characteristics
E1 0 + 10 V reference input (Z = 29 kΩ)
0E 0 V from 0 + 10 V reference input
EC1 0 -20 mA reference input
EC2 4 - 20 mA reference input
0EC 0 V from 0 - 20 mA and 4 - 20 mA reference inputs
RV reverse
FW forward }direction
SW ± 10 V reference output for the speed controller, max I 11 mA
0SW 0 V from the reference output
P15 +15 V, max I : 7 mA
0V
N15
PL
-15 V, max I : 7 mA } module power supply

24 V from speed controller, max I : 11 mA


PL 24 V available for selection of FW - RV

Mechanical Mounting of module on omega rail, width 35 mm


characteristics
=

Weight : 0,220 kg.


96
=

42 48
50

3
Block diagram
E1
-1


0E1
0V
-1


SW
EC1 I/U
#
0-20 mA

I/U 0SW
EC2
4-20 mA 0V

0EC P15
0V #

FW 0V

RV N15

PL PL

Cabling
N15

P15
PL

0V

0V

E1

Speed
controller
0SW
N15

RV and FW are validated by + 24 V


P15

SW
PL

PL

0V

from :

VW3-RZE101 - either terminal PL on the speed


controller,
- or an external power supply with its 0 V
connected to the speed controller 0 V.

NOTE :
EC1

EC2

0EC
0E1

FW
RV
E1

If RV and FW are activated at the same


time, they send a zero voltage to SW.

Voltage Current
reference reference

Operating
direction

4
VD0C29B302 Septembre/September 1991