0% found this document useful (0 votes)
69 views

Addc

Uploaded by

Eyob Bogale
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
69 views

Addc

Uploaded by

Eyob Bogale
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 229

The

Electricity Wiring
Regulations

Issued by:
the Regulation and Supervision Bureau
for the Water, Wastewater and Electricity Sector
in the Emirate of Abu Dhabi
www.rsb.gov.ae

December 2007
Regulation and Supervision Bureau
for
the Water, Wastewater and Electricity
Sector in the Emirate of Abu Dhabi

Tel: +971 2 642 6777 Fax: +971 2 642 4217


P.O. Box: 32800 Abu Dhabi,
U.A.E e-mail:
[email protected]
www.rsb.gov.ae
Foreword
The Regulation and Supervision Bureau (the Bureau) was established
in law to oversee the economic and technical activities of electricity
and water companies that are licensed to operate in the Emirate of
Abu Dhabi. These companies were formed following restructuring of
the government-owned water and electricity sector, previously
managed by the Water and Electricity Department (WED).

In addition to its duties over licensed companies, the Bureau has


certain responsibilities towards the general public, including the
assurance of safe and efficient electricity and water supplies to
customers.

The Bureau has drafted these Regulations to promote the installation and
operation of safe electricity wiring systems in all customers’ premises.
These Regulations are based on the general principles defined in
British Standard BS 7671 (otherwise known as the IEE Wiring
Regulations, UK) which are also similar to the International Standard
IEC 60364. Such principles have been common practice in Abu Dhabi
and were adopted in previous documents, including the first Wiring
Regulations issued by WED in 1972.

The new Regulations are less prescriptive than previous documents,


but provide closer definition of technical parameters compared with
BS 7671. The Regulations also take account of the physical
environment in Abu Dhabi and the typical skills and language
diversity of the region.

This publication contains a section of guidance notes which, although


not part of the Regulations, provides useful data and advice to assist in
the correct application of the Regulations.

Copies of this document may be purchased from the Bureau.


Updates and amendments will be posted on the Bureau’s website,
www.rsb.gov.ae.

N Carter Zaal M. Zaal Al Hameeri


Director General Chairman

The Electricity Wiring Regulations 2007 3


Acknowledgements
The Bureau gratefully acknowledges the contributions and comments
provided by the following organisations:

Government organisations:
Abu Dhabi Water and Electricity Authority
Al Ain Distribution Company
Abu Dhabi Distribution Company
Abu Dhabi Municipality
Al Mirfa Power Company
Dubai Electricity and Water Authority (DEWA)
Dubai Municipality (Central Laboratory)
Sharjah Electricity and Water Authority
(SEWA) Federal Electricity and Water
Authority (FEWA)
Emirates Standardisation and Metrology Authority (ESMA)

Private organisations:
Benchmark Electrical Safety Technology
Ltd Parsons International Ltd
Schneider Electric FZE
Voltas Limited, UAE
Ian Banham Associates
Pell Frischmann Consultants
Gibb Ltd
Power Economy Middle East
WSP Middle East Ltd
GHD Ltd (Aust/UAE)
ABB Industries LLC
(Dubai) Power Connections
Ltd Reed Smith Richards
Butler British Standards
Institute Electrium Ltd

In particular, the Bureau wishes to acknowledge permission granted


by the Institute of Engineering Technology and the British Standards
Institute for the use in this document of data and information taken
from BS 7671 (The Electricity Wiring Regulations, UK).

4 The Electricity Wiring Regulations 2007


Document numbering
These Regulations use the following numbering system:

Chapters: are referenced by integers (e.g. 1, 2, 3, etc)


Regulations: are referenced by one full stop between numbers
(e.g. 1.1, 1.2, etc)
Clauses: are referenced by two full stops between numbers
(e.g. 3.1.2, etc)
Notes: are indicated below the clause in square brackets and
italic text. For Example, [Note: this clause does not
apply to Installations that have been …]

Chapter

Regulation

Note

Clause

The Electricity Wiring Regulations 2007 5


List of revisions

Revision Date Prepared Checked Issued to:


Number by: by:

ED/R01/010
Dec 2007 TK LH Publication
Issue 1

6 The Electricity Wiring Regulations 2007


Table of contents
Foreword 3
Acknowledgements 4
Document numbering 5
List of revisions 6

1 Introduction 11
1.1 Citation and commencement 11
1.2 Purpose and document structure 11
1.3 Scope and enforcement 12

2 Definitions 15
2.1 Interpretation 15

3 General principles and safety


requirements 27
3.1 Technical standards, materials and
workmanship 27
3.2 Approval of installations 28
3.3 Extensions, alterations and repairs 29
3.4 Licensed contractors 29
3.5 Requirements for safety 30
3.6 Labelling and identification 31
3.7 Environmental conditions 33

4 Electricity supply intake and supply


parameters 35
4.1 Electricity supply parameters 35
4.2 Electricity supply intake 36
4.3 The customer connection point 38
4.4 Multiple occupancy premises 39
4.5 Metering requirements 39

5 Protection 41

The Electricity Wiring Regulations 2007 7


5.1 General principles 41
5.2 Overload and short-circuit protection 41
5.3 Electric shock protection 43
5.4 Earth leakage protected systems 44
5.5 Earthed equipotential bonded systems 47
5.6 Isolation and switching 50
5.7 Insulation 51

6 Earthing 53
6.1 General principles 53
6.2 Systems of earthing 53
6.3 Main earth terminal 54
6.4 Earth electrodes 55
6.5 Earth conductors 56
6.6 Exposed-metallic-parts 58
6.7 Earth fault loop impedance 59
6.8 Lightning protection 60
6.9 Functional earthing and high
leakage currents 60

7 Selection of components and installation


requirements
63
7.1 Plugs and socket-outlets 63
7.2 Switches and isolators 65
7.3 Lighting 66
7.4 Conduit, trunking and cable trays 68
7.5 Cables 71
7.6 Final circuits 75
7.7 Busways, bus ducts and busbar risers 76
7.8 Distribution boards 77
7.9 LV switchboards 79

8 Inspection, testing and certification 81


8.1 Electrical installation certificates 81
8.2 Routine inspection and testing 83

9 Special locations and systems 85

8 The Electricity Wiring Regulations 2007


9.1 Separated extra-low voltage (SELV) 85
9.2 Protective extra-low voltage (PELV) 86
9.3 Bathrooms and similar locations 86
9.4 Swimming pools 88
9.5 Water fountains 89
9.6 Construction sites and outdoor supplies 91
9.7 Street lighting 92

10 Capacitors and motors 93


10.1 General requirements 93
10.2 Specifications for capacitors 94
10.3 Electric motors and starters 96
10.4 Standby generators 97

Appendices 101

Guidance Notes 191

The Electricity Wiring Regulations 2007 9


10 The Electricity Wiring Regulations 2007
Introduction
1
1.1 Citation and commencement

1.1.1 These Regulations shall be cited as the Electricity Wiring


Regulations 2007.

1.1.2 These Regulations shall take effect from 1 January 2008.

1.1.3 These Regulations are issued by the Regulation and


Supervision Bureau through the powers vested in it under
Article 62 of Law No (2) of 1998 (including amendments
and re-enactments thereof).

1.1.4 These Regulations supersede the following regulations:


(a) ADWEA Wiring Rules and Regulations (3rd
Edition 2003);
(b) WED Regulations for Electrical Installation
Works (1980); and
(c) Earth Leakage Protection Regulations (2001).

1.2 Purpose and document structure

1.2.1 The purpose of these Regulations is to establish standards


and principles that promote the design, construction and
operation of safe and efficient systems of wiring in buildings
and other Premises.

1.2.2 The main part of this document is structured into


chapters, regulations and clauses, see illustration on
page 5. Regulations and clauses are mandatory. Notes
which are included below clauses, in italic text, are not
mandatory and are for guidance or to provide supporting
technical information.

1.2.3 The second part of this document consists of Appendices,


which contain mandatory information, and Guidance
Notes which contain supporting information.

The Electricity Wiring Regulations 2007 11


1 1.3 Scope and enforcement

1.3.1 These Regulations apply to all Distribution Companies,


Customers, property Owners, Licensed Contractors, or
any other persons involved in the design, construction,
installation, maintenance or operation of Electrical
Installations in any Premises or other place where there is
an electricity supply provided by a Distribution Company.
Such locations include, but are not limited to, domestic,
commercial and industrial premises, public buildings,
parks, farms, temporary supplies, construction sites, wedding
tents, outbuildings, caravans, street lighting and traffic
signs.

1.3.2 The scope of these Regulations does not include the


electricity distribution networks belonging to Distribution
Companies, except such equipment that is required at the
interface with Customers, as detailed in these Regulations.
[Note: requirements governing Distribution Companies’networks
are covered under the Electricity Supply Regulations 2007, as
well as other relevant Licences, codes and standards.]

1.3.3 These Regulations shall apply to all new Electrical


Installations constructed following the commencement
date (clause 1.1.2). Requirements for extensions,
alterations and repairs to existing Installations are covered
under Regulation 3.3.
[Note: where the design of an Installation has been completed
before the date of commencement of these Regulations advice must
be sought from the Distribution Company before construction is
commenced.]

1.3.4 For Electrical Installations constructed before the date of


commencement, the clauses listed in Appendix A4(a)
shall either not apply, or shall apply after 1 January 2010
or, if earlier, at the time of any extension work or re-
certification of a Premises, as indicated in Appendix
A4(a).

12 The Electricity Wiring Regulations 2007


1ntroductio
1.3.5 These Regulations shall be enforced by the relevant
Distribution Companies in the Emirate of Abu Dhabi, in
1
accordance with procedures which shall be published by
the Distribution Company and approved by the Bureau.
See Regulation 3.2.

1.3.6 Compliance with these Regulations requires compliance


with other relevant technical standards, see Regulation
3.1. References to British Standards or other standards
means the current edition of the standard cited or its
replacement. For existing Installations clause 1.3.4
applies.

1.3.7 Failure to comply with these Regulations, or any part


thereof, shall be deemed as contrary to the Law and
subject to punishment by the imposition of a fine. Any
such failures will be addressed in accordance with the
Law under Article 65(5) (notices served by the Bureau)
and Article 66 (failure to comply and imposition of fines).
Action may be taken against any Distribution Company,
Customer, Owner, Licensed Contractor or other person to
which these Regulations apply.
[Note: see Appendix A4(b) for a list of relevant Articles of Law
No (2) of 1998.]

1.3.8 Relaxation of any of the requirements of the Regulations


shall be approved by the Bureau upon written request
from any Distribution Company, Customer, property
Owner, Licensed Contractor or other person.

1.3.9 In the event of a dispute between any parties mentioned in


clause 1.3.1, the matter may be referred to the Bureau to
advise a solution or recommended action. This does not
preclude any party referring a matter to the relevant Court
of Abu Dhabi.

1.3.10 These Regulations and the rights and duties of any parties
thereunder shall be governed by, construed and applied
in accordance with the Laws of Abu Dhabi Emirate and
the Federal Laws of the UAE as applied by the Courts of
Abu Dhabi.

The Electricity Wiring Regulations 2007 13


1

14 The Electricity Wiring Regulations 2007


Definitions
2
2.1 Interpretation

Words which are defined under this section are used in the
Regulations beginning with capital letters. For example, “all Earth
Conductors within a Premises shall be ...”.

Terms in common use are not defined here and normal dictionary
definitions apply (e.g. circuit-breaker, plug, conduit).

Words and expressions other than those described in this section,


which are defined in the Law, shall have the meanings ascribed to
them in the Law.

Words using the singular or plural number also include the plural or
singular number, respectively.

2.1.1 Accessory: a device, other than current-using equipment,


associated with an Electrical Installation.

2.1.2 Appliance: an item of current-using equipment.

2.1.3 Arm’s Reach: a zone of accessibility to touch, extending


from any point on a surface where a person may stand or
move about, to the limits which such person may reach
without assistance (i.e. without any tool or ladder, etc).
Such a distance may be taken as 2.5 m height from the
standing surface, and 1.25 m horizontally from the
standing position.

2.1.4 Bonding Conductor: see Equipotential Bonding


Conductor.

2.1.5 Bureau: the Regulation and Supervision Bureau for the


Water, Wastewater and Electricity Sector in the Emirate
of Abu Dhabi, as established under the Law.

2.1.6 Cable Tray: a cable support consisting of a continuous


base with raised edges and no covering. A cable tray is
considered to be perforated where more than 30% of the
material is removed from the base.

The Electricity Wiring Regulations 2007 15


2.1.7 Cable Trunking: a manufactured enclosure for the
protection of cables, normally of rectangular cross-
section, of which one side is removable or hinged.

2.1.8 Category 1 Circuit: a Circuit (other than a fire alarm or


2 emergency lighting Circuit) operating at LV and supplied
from the Distribution Company.

2.1.9 Category 2 Circuit: a Circuit (other than a fire


alarm or emergency lighting Circuit) which supplies
telecommunications equipment (such as telephones,
intruder alarms, data transmission, call bells, etc).

2.1.10 Category 3 Circuit: a fire alarm or emergency lighting


Circuit.

2.1.11 Circuit: a set of phase and neutral conductors installed as


a group to supply power to a location, and which originate
from one Protective Device. The following are related
definitions:
(a) Ring Circuit: a Circuit which is wired from a
single Protective Device, being run through an
area to be supplied (via appropriate socket-
outlets, connectors, etc) and returning back to the
same Protective Device, thus forming an
electrically continuous loop;
(b) Radial Circuit: a Circuit which is wired in a
‘radial’ or ‘branch’ configuration, emanating from
a Protective Device, to the area to be supplied;
(c) Spur Circuit: a Circuit which is wired in a
‘radial’ or ‘branch’ configuration from any point
on a Ring Circuit;
(d) Final Circuit: a Circuit which supplies
Appliances (normally via socket-outlets or other
types of connectors); and

16 The Electricity Wiring Regulations 2007


Definitio
(e) Distribution Circuit: a Circuit connecting
between Distribution Boards (may also be
referred to as a ‘sub-Circuit’).

2.1.12 Circuit Protective Conductor: see Earth Conductor.


2
2.1.13 Class I Equipment: equipment which includes a means
for connection of Exposed-Metallic-Parts of the
equipment to the Earth Conductor, thus providing
protection against electric shock in case of failure of the
basic insulation of the equipment or other fault condition.

2.1.14 Class II Equipment: equipment which does not include a


means for connection to an Earth Conductor, and which
provides supplementary insulation in addition to the basic
insulation of the equipment such that a breakdown of the
basic insulation will not present a dangerous voltage on
Exposed-Metallic-Parts (also known as Double Insulated
equipment). Class II Equipment is required to comply
with BS 2754. See Appendix A18(b).

2.1.15 Class III Equipment: equipment in which protection


against electric shock relies on supply at SELV and in
which voltages higher than SELV are not generated in the
equipment, see BS 2754.

2.1.16 Competency Licence: a licence issued by a Distribution


Company to a Licenced Contractor assessed as competent
for work on Electrical Installations.

2.1.17 Connected Load: the aggregate load of Appliances and


other electrical equipment at a Premises, summated using
the method described under clause 3.2.5. See Guidance
Note G2.

2.1.18 Consumer Unit: an integrated unit which accepts the


incoming supply to a domestic Premises, or other similar
installation, and contains the main isolating device.

The Electricity Wiring Regulations 2007 17


2.1.19 Customer: any person, corporate body, or company who
has an agreement with a Distribution Company for the
supply of electricity.

2.1.20 Customer Connection Point (CCP): the point which defines


2 the boundary between the Customer’s Installation and that
of the Distribution Company (also known as the Point of
Supply). This point will normally be at the incoming
cable of the Main Distribution Board and before the main
circuit- breaker, see Appendix A13. In special cases, an
alternative definition of the Connection Point may be
agreed between the Customer and the Distribution
Company.

2.1.21 Direct Contact: the contact with electricity by a person


(accidental or otherwise) through the phase or neutral
conductors of an Installation or Appliance, leading to an
electric shock, see Guidance Note G4(a).

2.1.22 Distribution Company: a company or body holding a


Licence from the Bureau, pursuant to the Law.

2.1.23 Danger: risk of injury to people or animals from fire, electric


shock, burns, explosion or from mechanical movement of
electrically controlled equipment, or the risk of damage to
property.

2.1.24 Distribution Board: an assembly designed for housing


isolation switches and Protective Devices and for connecting
multiple Circuits, including their associated neutral and
Earth Conductors. The following are related definitions:
(a) Main Distribution Board (MDB): the Distribution
Board which accepts the main incoming LV supply
from the Distribution Company or Customer’s
transformer;
(b) Sub Distribution Board (SDB): any Distribution
Board which is neither a Main Distribution Board
nor a Final Distribution Board; and

18 The Electricity Wiring Regulations 2007


Definitio
(c) Final Distribution Board (FDB): a Distribution
Board which supplies Final Circuits only.

2.1.25 Double Insulated Equipment: see Class II Equipment.


2
2.1.26 Earth: the conductive mass of Earth, whose electrical
potential (voltage) at any point is conventionally taken as
zero. The following are related definitions:
(a) Customer Earthed System (TT): a system of
supply where the Customer provides a Main Earth
Terminal for the Installation, which is connected
to a sufficient number of local Earth Electrodes to
provide a maximum Earth Resistance measured at
the Customer’s Main Earth Terminal of not more
than 10 Ohms.
(b) Distribution Company Earthed System (TN-S): a
system of supply where the Distribution Company
provides a connection to the Customer’s Main Earth
Terminal, using the distribution network Earthing
system, normally via the armouring or metallic
sheath of the main incoming supply cable.
(c) Distribution Company Earthed System with
additional Customer Earth (TN–S–TT): a system of
supply where the Distribution Company provides an
Earth connection to the Customer’s Main Earth
Terminal and a local Earth provided by the
Customer is also connected to the same MET,
having an Earth Resistance value of not more than
10 Ohms.

2.1.27 Earthing or Earthed: a general term used to describe the


connection of metallic parts of an Electrical Installation or
an Appliance to Earth.
[Note: the terms ‘Grounding’ or ‘Grounded’ are sometimes
used outside these Regulations to mean the same as the above.]

The Electricity Wiring Regulations 2007 19


2.1.28 Earth Conductor: a conductor used to connect Exposed-
Metallic-Parts of an Electrical Installation and associated
Appliances to Earth, and providing a means for the safe
passage of earth fault current. This includes the following
defined terms:
2
(a) Main Earth Conductor (MEC): conductors connected
between Distribution Boards, Earth Electrodes and
Main Earth Terminals; and
(b) Circuit Earth Conductor (CEC): conductors
connected from Final Distribution Boards and
associated with Final Circuits, including Appliance
Earth Conductors such as within a flexible cord.
Outside these Regulations these may also be known
as the Circuit Protective Conductor (CPC) or Earth
Continuity Conductor (ECC).

2.1.29 Earth Electrode: a conductor or group of conductors


in intimate contact with Earth, providing an electrical
connection to Earth, and normally having a known and
measurable value of Earth Resistance (may also be known
outside these Regulations as ‘Earth Rod’, or ‘Grounding
Rod’).

2.1.30 Earthed Equipotential Bonding (EEB): the connection


of Extraneous-Metallic-Parts within a Premises using
designated conductors such that potential Touch Voltages
are kept to a safe value during the passage of earth fault
current (also known outside these Regulations as ‘PME
Bonding’). This definition includes the following:

(a) Main Equipotential Bonding: the connection


of major Extraneous-Metallic-Parts, such as pipe
services and metallic structures, at their point of
entry into a Premises to the Main Earth Terminal in
an Installation, using designated conductors; and

20 The Electricity Wiring Regulations 2007


Definitio
(b) Supplementary Equipotential Bonding: the
connection of Extraneous-Metallic-Parts with each
other or with Exposed-Metallic-Parts within an area
where such parts are simultaneously accessible to
persons, such that the potential Touch Voltage
during an earth fault is kept to safe limts. 2
[Note: for disconnection times greater than 0.4 seconds
a safe Touch Voltage limit may be taken as 50 V for dry
conditions and 25 V for wet conditions.]

2.1.31 Earthed Equipotential Bonded System (EEBS): a system


where protection against electric shock due to Indirect
Contact is achieved bytheprovision of Earthed Equipotential
Bonding conductors, in association with Protective
Devices for the automatic disconnection of supply.

2.1.32 Earth Leakage Protection (ELP): theprovision of protection


against electric shock due to Indirect Contact by the use of
RCDs or other sensitive earth fault protective devices
which automatically disconnect the supply sufficiently
quickly so as to prevent danger to persons.

2.1.33 Earth Leakage Protected System (ELPS): a system of


supply where Earth Leakage Protection is provided on
Final Circuits and back-up ELP is provided at the Supply
Intake.

2.1.34 Earth Resistance: the resistance (in Ohms) from any


point on an Installation to Earth, being measured using an
approved testing device and approved procedure.

2.1.35 Earth Fault Loop Impedance (Zs): the total impedance


presented to an earth fault current, comprising the
impedance of the following parts of a system, illustrated
in Appendix A5(g):

(a) the Circuit Earth Conductor;


(b) the Main Earth Terminal;

The Electricity Wiring Regulations 2007 21


(c) the main Earth Conductors connecting to Earth
Electrodes or the Distribution Company Earth;
(d) the path of earth fault current through the general
mass of Earth, or through the earth sheath or
2 armouring of the Distribution Company cable;
(e) the neutral earth connection at the Distribution
Company transformer;
(f) the distribution transformer winding; and
(g) the phase conductor of the Circuit back to the point
of fault.

2.1.36 Earth Leakage Circuit-Breaker (ELCB): see Residual


Current Device.
[Note: the term ELCB is commonly used interchangeably with
the term RCD.]

2.1.37 Electrical Installation (abbrv: Installation): an Electrical


Installation comprises any fixed or temporary cable,
switchgear, transformer or other electrical equipment or
apparatus within a Premises or other place where there is
an electricity supply (including outdoor locations). Fixed
or portable electrical Appliances are not considered part
of the Electrical Installation, although these Regulations
do include requirements for the connection of Appliances
(e.g. plugs and socket-outlets).

2.1.38 Electrical Installation Certificate: a certificate in the format


indicated in these Regulations which is issued by a
Licensed Contractor after completion of work on an
Installation and provided to the Customer or Owner of the
Premises.

2.1.39 Exposed-Metallic-Part: a metallic part of an Installation


or Appliance which can be touched by persons and which
is not normally live but may become live due to a fault
condition. Exposed-Metallic-Parts are required to be
connected to Earth, see Regulation 6.6.

22 The Electricity Wiring Regulations 2007


Definitio
2.1.40 Extraneous-Metallic-Part: a metallic part, structure or
any metalwork within a Premises which is not part of, and
is unrelated to, the electrical Installation and which is not
designed to carry current, but which may become live
due to a fault condition. Extraneous-Metallic-Parts are
required to be connected to Earth for Installations or parts
2
of Installations classified as Earthed Equipotential Bonded
Systems, see Regulation 5.5.

2.1.41 Extra-Low Voltage (ELV): see Voltage.

2.1.42 Final Circuit: see Circuit.

2.1.43 Functional Earth: an Earth or Earthing system which is


provided for special functions (such as reduction of radio
frequency interference, noise filtering for computers, etc)
and which is separate from other Earth Conductors in an
Installation but is connected to the Main Earth Terminal.

2.1.44 High Voltage: see Voltage.

2.1.45 Indirect Contact: contact of a person with electricity


through Exposed-Metallic-Parts of an Installation or
Appliance, or through Extraneous-Metallic-Parts in a
Premises which have become live during fault conditions,
see Guidance Note G4(b).

2.1.46 Installation: see Electrical Installation.

2.1.47 Law: means Law No (2) of 1998 Concerning the


Regulation of the Water, Wastewater and Electricity
Sector in the Emirate of Abu Dhabi (as amended by Law
No (19) of 2007).

2.1.48 Licensed Contractor: a company which has been assessed


by the Distribution Company as competent to work on
Electrical Installations and issued a Competency Licence.

The Electricity Wiring Regulations 2007 23


2.1.49 Low Voltage: see Voltage.

2.1.50 Luminaire: equipment which is designed to house one


or more electric lamps and which may include diffusers,
fixtures, transformers and auxiliary Circuits but is taken to
2 exclude the lamps themselves. Outside of these
Regulations a Luminaire may commonly be referred to as
a ‘light fitting’.

2.1.51 Main Distribution Board: see Distribution Board.

2.1.52 Main Earth Terminal (MET): the main connection point


at which the nominal value of Earth Resistance for an
installation is taken, and to which Earth Conductors from
Earth Electrodes or the Distribution Company Earth are
connected. This will normally be at or close to the
Customer Connection Point. The Main Earth Terminal
may also be known as the ‘main earth bar’.

2.1.53 Owner: the legal owner of a building or property in which


an Electrical Installation is installed and connected to a
supply of electricity.
[Note: in some cases an Owner may also be a Customer.]

2.1.54 Premises: any occupied or unoccupied building or enclosure


or other place where there is an electricity supply. Such
locations would include, but are not limited to, domestic
premises, commercial premises, industrial premises,
public buildings, parks, farms, temporary supplies,
construction sites, wedding tents, outbuildings, caravans,
street lighting and traffic signs.

2.1.55 Prospective Fault Current: the value of current that


would flow due to a short-circuit fault of negligible
impedance between live phase conductors, or between phase
conductors and Earth, also known as ‘fault level’. The
maximum Prospective Fault Current for an installation is
normally taken at the Customer Connection Point.

24 The Electricity Wiring Regulations 2007


Definitio
2.1.56 Protective Conductor: see Earth Conductor.

2.1.57 Protective Device: a device installed at the start of a


Circuit which will automatically disconnect the input of
electricity in the event of a fault or overload occurring on
that Circuit. Such devices include, but are not limited to, 2
fuses, fuse links, miniature circuit-breakers (MCB),
moulded case circuit- breakers (MCCB), earth leakage
circuit-breakers (ELCB), and residual current devices
(RCD).

2.1.58 Radial Circuit: see Circuit.

2.1.59 Residual Current Device (RCD): a Protective Device which


is installed to automatically isolate the supply to a Circuit
or Distribution Board when the vector sum of currents in
the phase and neutral conductors reaches a preset value
(referrerd to as the residual operating current or residual
current rating).

2.1.60 Ring Circuit: see Circuit.

2.1.61 Sub Distribution Board: see Distribution Board.

2.1.62 Supply Intake: a term used to describe the location or


room housing the main cable and equipment provided by
a Distribution Company to provision a supply of
electricity to a Premises (includes the Customer
Connection Point).

2.1.63 Spur Circuit: see Circuit.

2.1.64 Touch Voltage: the Voltage that would appear during an


earth fault condition between Exposed-Metallic-Parts
and Extraneous-Metallic-Parts which are simultaneously
accessible to persons.
[Note: this term is used only in connection with protection
against Indirect Contact and is not used to refer to Direct
Contact with electricity. The seriousness of impact of Touch
Voltage on a person will depend on the body resistance
and the immediate surroundings, in particular the

The Electricity Wiring Regulations 2007 25


presence of water. See Guidance Note G4(h) and G5(b).]

26 The Electricity Wiring Regulations 2007


2.1.65 Voltage:
(a) High Voltage (HV): an a.c. voltage greater
than Low Voltage and less than 36 kV between
phases or 21 kV between any phase and Earth
2 (internationally referred to as Medium Voltage);
(b) Low Voltage (LV): an a.c. voltage below
1000 V between phases, or below 600 V between
any phase and Earth or, a d.c. voltage below
1500 V between conductors, or below 900 V
between any conductor and Earth;
(c) Extra-Low Voltage (ELV): a voltage not
exceeding 50 V a.c. or 120 V d.c. whether
between live conductors or between live
conductors and Earth;
(d) Separated Extra-Low Voltage (SELV): an Extra-
low Voltage system which is electrically
separated from Earth in such a way that a single
fault cannot give rise to the risk of electric shock.
(e) Protective Extra-Low Voltage (PELV): a system
which has the same features as SELV except that
connection of Exposed-Metallic-Parts to Earth is
allowed; and
(f) Reduced Low Voltage (RLV): a voltage which does
not exceed 55 V a.c. between phase and Earth or
110 V a.c. between phases.

The Electricity Wiring Regulations 2007 27


General principles and safety
requirements 3
3.1 Technical standards, materials and
workmanship

3.1.1 These Regulations provide guidelines and technical


standards which are consistent with the principles
contained in BS 7671:2001 (also known as the IEE Wiring
Regulations 16th Edition). Where any provision in these
Regulations contradicts any provision in BS 7671, the
requirements, standards or specifications under these
Regulations shall apply.
[Note: these Regulations are in some aspects more prescriptive
than BS 7671, and take account of the physical environment of
Abu Dhabi Emirate, as well as the typical skills and language
diversity in the region.]

3.1.2 Where a provision or technical requirement is not covered


by these Regulations, BS 7671 may be used as a guideline
or specification, with prior approval from the Distribution
Company and the Bureau.

3.1.3 All materials used in Electrical Installations shall be of


good quality and installed in a neat and orderly manner.

3.1.4 All materials and equipment shall comply with relevant


international standards which shall be mainly BS (British
Standards) or IEC (International Electrotechnical
Commission) standards, as referenced in these
Regulations. Other international standards may be used, in
particular where none are specified in these Regulations,
with the prior approval of the Distribution Company and
the Bureau. A list of BS and IEC standards applying to
the main types of equipment is given in Appendix A3.

3.1.5 The Distribution Company may issue specifications and


requirements in addition to these Regulations, which will
be endorsed or approved by the Bureau, and provided to
interested parties on request.

The Electricity Wiring Regulations 2007 27


3.1.6 Reference must be made, where relevant, to UAE or
Gulf standards which may be issued from time to time by
the Emirates Standardisation and Metrology Authority
(ESMA).

3.2 Approval of installations

3.2.1 Any Customer requiring a new supply or alteration to an


3 existing supply must make an application to the
Distribution Company using the appropriate forms and
procedure published by the Company.

3.2.2 The proposed design of an Installation must be approved


by the Distribution Company before commencement
of construction. Details of the proposed design must be
submitted, together with appropriate calculations and
wiring diagrams, using the standard symbols shown in
Appendix A11.

3.2.3 New Installations must be inspected and tested by the


Distribution Company in accordance with the
requirements of Chapter 8 of these Regulations, prior to
providing an electricity supply.

3.2.4 The Distribution Company may, where appropriate, seek


evidence of compliance against relevant standards of
equipment and components used in the Installation.

3.2.5 The Customer must provide an estimate of the expected


maximum electricity demand or Connected Load at the
Premises. This must be calculated by the Customer’s
appointed Licensed Contractor, design engineer or
other qualified person using the guidelines given in
Guidance Note G2.

28 The Electricity Wiring Regulations 2007


3.3 Extensions, alterations and repairs

3.3.1 No extension or alteration to an Electrical Installation


may be made without prior notification to the Distribution
Company or without approval, testing and certification in

Principl
accordance with Regulation 3.2.

3.3.2 All extensions or alterations to an existing Installation


must comply with the requirements of these Regulations.
3
3.3.3 Not withstanding clause 3.3.1 and 3.3.2, repairs to
existing installations may be made using standards of
equipment compliant with the old installation, but limited
to work of an essential nature on a like-for-like basis.
Work on any part of the Installation other than Final
Circuits, including any Distribution Board and any items
at the Supply Intake, must be notified to the Distribution
Company.

3.3.4 Any proposed increase greater than 10% of the total


Connected Load at a Premises, or greater than 10% of
the Connected Load at any Distribution Board, must be
approved by the Distribution Company.

3.4 Licensed contractors

3.4.1 Work on Electrical Installations may only be carried out


by Licensed Contractors who have been assessed and
approved by the Distribution Company and issued a
Competency Licence.

3.4.2 The process for approval of Licensed Contractors shall be


published by the Distribution Company and approved by
the Bureau.

3.4.3 A register of Licensed Contractors shall be kept up-to-


date by the Distribution Company and provided on request
to any person.

The Electricity Wiring Regulations 2007 29


3.5 Requirements for safety

3.5.1 The provisions of these Regulations require that all Electrical


Installations are designed and constructed so as to ensure
the safety of all persons who may operate, maintain or
otherwise use or be affected by any part of an Installation.
In addition to the requirements detailed under the relevant
sections of these Regulations, the following general safety
principles shall apply.
3
[Note: these Regulations do not include detailed requirements
for the maintenance of Installations. However, the
maintainability of Installations must be adequately catered for
in their design and construction. In addition the requirements
for periodic inspection and testing, as detailed in Chapter 8,
may give rise to the need for maintenance and repair work.]

3.5.2 All parts of an Electrical Installation shall be designed and


constructed so as to prevent Danger.

3.5.3 All parts of an Electrical Installation shall be sufficiently


sized and rated to safely carry out the function for which
they are required.

3.5.4 All parts of an Electrical Installation shall be insulated


appropriate to the function they serve, in consideration
of the expected operating environment, so as to prevent
Danger, see Regulation 5.7.

3.5.5 All Exposed-Metallic-Parts of an Installation and of


Appliances must be connected to Earth via appropriate
Earth Conductors, so as to protect against electric shock,
see Regulation 6.6.

3.5.6 Except in specified circumstances, all Electrical Installations


shall be provided with Earth Leakage Protection at
the source of supply, at all Final Circuits and at other
appropriate points, see Regulation 5.3.4. Where Earth
Leakage Protection is not provided the requirements
for Earthed Equipotential Bonding shall apply, see
Regulation 5.5).

30 The Electricity Wiring Regulations 2007


3.5.7 All Electrical Installations must be protected against
damage caused by excess current due to a fault or
overload by suitable Protective Devices, see Regulation
5.2.

3.5.8 All Electrical Installations must be provided with a means

Principl
of isolating the electricity supply at suitable sections,
subsections and Circuits, and at points where Appliances
are used, see Regulation 5.6.

3.5.9 All parts of an Electrical Installation must be suitably located 3


so as to provide safe access for operation, maintenance
and repair and must be protected against accidental or
deliberate interference or damage.

3.5.10 Electrical Installations must be designed and constructed


with particular consideration given to the risk of fire due
to electrical faults and the propagation of fire through
parts of the Installation. See clauses 6.1.1(c), 7.2.4, 7.4.5,
7.4.15, 7.5.3, 7.5.4, 8.1.4(g) and 10.3.2.

3.5.11 All Electrical Installations must be inspected and tested


at the time of first commissioning and at regular intervals
thereafter to ensure ongoing safety, as detailed under
Chapter 8 of these Regulations.

3.5.12 Additional requirements for safety in special locations are


covered in Chapter 9.

3.6 Labelling and identification

3.6.1 All Electrical Installations must be suitably labelled so as


to give information on the electricity supply parameters,
the source of supply, location in relation to other
Installations, and any special precautions to be taken.
[Note: such information would normally be provided at
the Supply Intake room; special precautions would include
information on other sources of supply such as local generation
or interconnection with other Premises.]

The Electricity Wiring Regulations 2007 31


3.6.2 The means of isolation of the main source of supply
must be clearly labelled and accessible to authorised
persons, see Regulation 5.6.

3.6.3 The provision of Earth Leakage Protection (as required


under Regulation 5.3.4) must be clearly indicated at
appropriate isolation points, including a notice informing
Customers of the need for regular testing of RCD
devices, see Appendix A12(c).
3
3.6.4 Individual Circuits (including neutral and Earth
Conductors) must be identified by numbering at the
source end and, where appropriate, at intervals along the
route, see Guidance Note G7(f).

3.6.5 For non-domestic Installations, all accessories and


fittings must be marked with Circuit identification
numbers.
[Note: Circuit identification numbers must indicate the
Distribution Board from which an Accessory or fitting is supplied,
and may be fixed externally or internally, i.e. either outside or
inside cover plates.]

3.6.6 Load distribution schedules, as shown in Appendix


A20(e), must be provided at each Distribution Board. An
overall wiring diagram showing the location and
interconnection of Distribution Boards must be provided
at the Supply Intake.

3.6.7 Where parts of an Installation are accessible or visible to


the general public they must be labelled with a warning:
“LIVE – 230/400 VOLTS – DANGER OF DEATH” or
similar wording. This warning must be written in English
and Arabic, see example in Appendix A12(a). However,
parts of final Circuits and other points of normal use may
be excluded from this requirement.

32 The Electricity Wiring Regulations 2007


3.7 Environmental conditions

3.7.1 All parts of an Electrical Installation must be suitably


designed, constructed and maintained so as to operate
safely and carry out their designed function in the

Principl
expected operating environment. The following
environmental conditions may be used as a guide if no
other special factors apply:
3
(a) maximum ground temperature (at 1 m depth): 35˚C;
(b) soil resistivity: according to local conditions;
(c) weather: mainly sunny, occasional fog (causing
condensation on outdoor equipment), and occasional
sandstorms;
(d) air quality: frequently dusty;
(e) maximum humidity: 100%;
(f) maximum ambient (air) temperatures:
• outdoor (shaded): 50˚C
• outdoor (unshaded): temperature rise due to solar
gain must be calculated for the relevant equipment
or the maximum ‘black bulb’ temperature may be
used (typically 10 ˚C above ambient temperature)
• indoor (not air conditioned): 40˚C
• indoor (air conditioned): 30˚C
[Note: in some situations the ambient temperature for indoor
non-air-conditioned situations may reach the outdoor shaded
temperature e.g. a small prefabricated building with little
ventilation, or a garage which is open to the atmosphere.]

The Electricity Wiring Regulations 2007 33


3

34 The Electricity Wiring Regulations 2007


Electricity supply intake and
supply parameters 4
4.1 Electricity supply parameters

4.1.1 The parameters for electricity supplies provided to


Customers in the Emirate of Abu Dhabi are defined in the
Electricity Supply Regulations 2007, issued by the
Bureau. These are repeated below.

Declared voltage and frequency

4.1.2 The declared supply voltage provided to Customers


connected at LV shall be 230 V single-phase or 400 V
three-phase.
[Note: this is a change to the previous supply voltage declared
by Distribution Companies of 240/415 V. See Guidance
Note G1.]

4.1.3 The permissible variation of the supply voltage shall be


kept within + 10% and - 6% of the declared supply
voltage.

4.1.4 The declared supply frequency provided to Customers


shall be 50 Hz.

4.1.5 The permissible variation of supply frequency shall be


+/- 0.1% (i.e. +/- 0.05 Hz).

4.1.6 For Customers supplied at voltages above LV the


permitted variation of supply voltage shall be +/- 10% and
the permitted variation of frequency shall be +/- 0.1%.

Harmonics, voltage disturbances and power factor

4.1.7 Customers’ Installations, and the use of electrical equipment


therein, must be designed to avoid the generation of
disturbances in the electricity supply. These may include
voltage fluctuations, voltage dips, voltage unbalance and
harmonics, which are of a magnitude that adversely affect
other Customers.

The Electricity Wiring Regulations 2007 35


4.1.8 The permitted limits of such disturbances are given in the
Electricity Distribution Code, Annex 1. Customers will
be required to install filters or other equipment to mitigate
against such disturbances that are outside the permitted
limits (as explained in the Electricity Distribution Code).

4.1.9 The power factor at the Connection Point between the


Distribution Company and the Customer’s Installation
must be maintained at 0.9 lagging or higher. Power factor
correction equipment must be used where required to
achieve this value, see Chapter 10.

4 Prospective fault current

4.1.10 The maximum three-phase Prospective Fault Current


(fault level) for LV supplies shall be 46 kA (1 second) at
the LV busbar of the Distribution Company’s HV or LV
substation, or 30 kA (1 second) at an LV feeder pillar,
or 25 kA (1 second) at an LV service turret.

4.1.11 The maximum 3-phase Prospective Fault Current for HV


supplies shall be 31.5 kA (for 3 seconds) or such lower value
as otherwise agreed between the Distribution Company
and the Customer.

4.2 Electricity supply intake

4.2.1 The electricity Supply Intake must be positioned in a


dedicated room or housing.

4.2.2 Other than in exceptional circumstances, and with prior


approval from the Distribution Company, there shall be
only one electricity Supply Intake for any Premises.

4.2.3 The Supply Intake must be positioned in an area which is


readily accessible to Distribution Company staff and other
authorised persons, particularly in an emergency, and
must be at or close to the outside perimeter of a Premises.

36 The Electricity Wiring Regulations 2007


4.2.4 The Supply Intake must not be positioned in an area
controlled by one of the tenants in a multi-occupancy
building.

4.2.5 Equipment at the electricity Supply Intake must be located


in a safe and accessible position, and kept clear of
hindrance at all times.

4.2.6 The use of Supply Intake rooms as storage rooms for any

Supply
tools, equipment or other materials is prohibited.

4.2.7 The Supply Intake must not be located on the reverse side
of a bathroom or kitchen wall, or below a bathroom or
kitchen. The Supply Intake must not be located below any 4
water services or pipes, such as mains water supply,
storage tanks, air conditioning chillers, or other liquids or
hazardous materials.

4.2.8 The Supply Intake room must be well ventilated,


preferably without the need for forced air circulation.
Where air conditioning is required in the Supply Intake
room the requirement for fresh air circulation must also be
provided to avoid condensation.

4.2.9 At least one emergency lighting unit must be fitted in all


Supply Intake rooms, which must be provided with a
battery rated for minimum 2 hours illumination, and
subject to adequate routine maintenance.

4.2.10 Doors to Supply Intake rooms must be arranged to open


outwards, be kept free from obstructions, and be capable
of being opened from the inside without the use of a key.

4.2.11 The need for delivery of heavy equipment to the Supply


Intake room during construction and for future repair or
alterations must be taken into account in the location of
the Supply Intake room.

The Electricity Wiring Regulations 2007 37


4.2.12 For Supply Intake rooms of greater than 6 m in length
more than one door shall be provided as a means of
emergency access.

4.2.13 Installation layouts and minimum sizes of the electricity


Supply Intake are given in Appendix A12(b) and A12(d).

4.2.14 For large Installations the Supply Intake may consist of


one or more LV switchboards, the requirements for which
are given in Regulation 7.9.

4.2.15 Where an HV or LV substation is required for the supply of


Premises, the design and construction requirements for the
4 substation will be specified by the Distribution Company.

4.3 The customer connection point

4.3.1 Except where an alternative definition of the Customer


Connection Point (CCP) has been agreed between the
Customer and the Distribution Company, the CCP is
deemed to be at the incoming cable connection from the
Distribution Company. This is most commonly at the
Main Distribution Board and before the main circuit-
breaker. Metering equipment may be connected through a
current transformer at a position remote from the
Customer Connection Point.

4.3.2 Equipment at the Customer Connection Point must be


locked or sealed by the Distribution Company to prevent
deliberate or accidental interference. Such locks or seals
will include those for metering equipment, etc.

4.3.3 The Customer Connection Point must always include


a means of emergency isolation in the case of a fault or
breakdown (e.g. main circuit-breaker) which is readily
accessible and clearly labelled so as to be easily operated
by the Customer. Such means of emergency isolation
must be left unlocked at all times, except when locked in

38 The Electricity Wiring Regulations 2007


the open position to allow access to the Installation (e.g. for
maintenance).
4.4 Multiple occupancy premises

4.4.1 Multiple occupancy Premises may be supplied by rising


and lateral mains (cabling or busbars) which are connected
directly to the Supply Intake from the Distribution
Company. Rising and lateral mains will normally be
owned and operated by the building Owner on behalf of

Supply
all Customers in a Premises.

4.4.2 The electricity metering for individual Customers for a


rising or lateral mains system will normally be at the point 4
nearest to each Customer, remote from the main Supply
Intake.

4.5 Metering requirements

4.5.1 The requirements for Customer metering are contained


in the Customer Metering Regulations 2005, issued by the
Bureau. Additional detailed requirements and procedures
will be provided by the Distribution Company where
required.

The Electricity Wiring Regulations 2007 39


4

40 The Electricity Wiring Regulations 2007


Protection
5
5.1 General principles

5.1.1 All Electrical Installations must be designed, constructed and


maintained to provide protection against the following:

(a) overload;
(b) short-circuits (phase to phase or phase to Earth); and
(c) electric shock (due to Direct or Indirect Contact with
electricity).

5.1.2 Protection against conditions of overload and short-circuit


will normally be provided by MCBs, MCCBs or similar
devices, see Regulation 5.2 below.

5.1.3 Protection of persons against electric shock due to Direct


Contact or Indirect Contact must be provided by one of
the methods detailed in Regulation 5.3 below.
[Note: see Guidance Note G4(a) and G4(b) for explanation of
Direct and Indirect Contact.]

5.2 Overload and short-circuit protection

5.2.1 All Electrical Installations must be provided with devices


that protect against thermal, electromagnetic and other
detrimental effects caused by overload and short-circuits.
Such devices must be located at suitable sections and
Circuits so as to give effective automatic disconnection in
such conditions.

5.2.2 The main circuit-breaker at the Customer Connection


Point must be of MCB or MCCB type and adequately
rated for the maximum Prospective Fault Current. Fused
cutouts must not be used except in special circumstances
approved by the Distribution Company (e.g. street lighting
supplies).

The Electricity Wiring Regulations 2007 41


5.2.3 All Circuits must be individually protected against overloads
and short-circuits by suitable devices. Replaceable or
re-wireable fuse links are not permitted for this purpose
(except in the case of capacitor banks – see Regulation
10.2).

5.2.4 The time-current performance characteristics of Protective


Devices must conform to the relevant reference standards
listed in Appendix A3.
[Note: the time-current performance curves for MCBs are
shown in Appendix A6(a) – (d).]

5.2.5 To ensure protection against overload, Circuit conductors


must be sized taking into account the time-current
characteristic of the Protective Device.
[Note: in order to provide adequate protection against overload
5 the Protective Device nominal rating must be not more than the
maximum rating of the Circuit for which overload protection is
required – see Appendix A6(f).]

5.2.6 Protective Devices at the Main Distribution Board must


have a maximum Prospective Fault Current rating above
that declared by the Distribution Company for the relevant
Customer Connection Point.

5.2.7 Protective Devices downstream of the Main Distribution


Board may have a reduced Prospective Fault Current
rating, taking into account the ‘energy let-through’
characteristic (I2t) of the upstream Protective Device, see
Appendix A6(e). Where appropriate, an allowance may
also be made for the attenuation of Prospective Fault
Current due to the Circuit impedance.

42 The Electricity Wiring Regulations 2007


5.3 Electric shock protection

Direct contact

5.3.1 Protection of persons against the risk of Direct Contact


with electricity must be provided by either physically
preventing contact or by an inherently safe systems of
supply, using one or more of the following measures:

(a) insulated conductors, see Regulation 5.7;


(b) secure enclosures, barriers or covers on live parts;
(c) Separate Extra-Low voltage (SELV) system; or

Protectio
(d) Protective Extra-Low Voltage (PELV) system.
[Note: SELV conductors at voltages of 12 V a.c. or 30 V d.c.
may be un-insulated but must be provided with overload and
short circuit protection.]
5
5.3.2 Residual Current Devices with a residual current rating of
30 mA and complying with IEC 60898 or BS 3871 may
be used as a means of supplementary protection against
Direct Contact. However, RCDs may not be used as the
sole means of protection against Direct Contact i.e. one
of items (a) to (d) above must be used in addition to RCD
protection.
[Note: RCD devices with a residual current rating above 30 mA
are not considered to provide adequate protection against
Direct Contact but may be used to provide protection against
Indirect Contact – see Regulation 5.4. It should also be noted
that earth leakage devices do not protect against electric shock
between phase conductors or between phase and neutral.]

The Electricity Wiring Regulations 2007 43


Indirect Contact

5.3.3 Indirect Contact with electricity can occur when a voltage


appears on Earthed parts of an Installation or Appliance
due to the passage of earth fault current and whilst a
person is in contact with either:
(a) an Exposed-Metallic-Part and an Extraneous-
Metallic-Part; or
(b) an Exposed-Metallic-Part and Earth; or
(c) an Extraneous-Metallic-Part and Earth.

5.3.4 Protection against the risk of electric shock in the above


cases must be provided by either:
(a) an Earth Leakage Protected System, where RCDs
or similar devices are provided at Final Circuits and
5 back-up RCDs or other sensitive earth fault
protection is provided at the Supply Intake, see
Regulation 5.4; or
(b) in parts of Premises where Earth Leakage Protection
is not provided, or other specified circumstances,
an Earthed Equipotential Bonded System, see
Regulation 5.5.

5.3.5 Not withstanding clause 5.3.4(b) the requirement for Earth


Leakage Protection on all Final Circuits where Appliances
may be used by any person is made compulsory by these
Regulations.

5.4 Earth leakage protected systems

5.4.1 An Earth Leakage Protected System (ELPS) is defined as


one where protection against Indirect Contact is provided
by the use of RCDs or other sensitive earth fault devices
on all Final Circuits and back-up ELP is provided at the
Supply Intake. Such a system is required to automatically
disconnect the supply at a Final Circuit or at the Supply
Intake sufficiently quickly so as to prevent Danger.

44 The Electricity Wiring Regulations 2007


5.4.2 For Final Circuits ELP devices must be of the RCD type
whereby the device will trip if the vector sum of currents
carried by the phase and neutral conductors is above a
preset value, see Guidance Note G5(c). Voltage-operated
earth leakage devices (ELCB) are not permitted.
[Note: modern RCDs are magnetically actuated whilst the
older type of ELCB devices operate by detecting fault voltage
and require a connection between a Main Earth Conductor and
an Earth Electrode; these devices are therefore vulnerable to
maloperation due to parallel earth paths.]

5.4.3 RCD devices for Final Circuits must have a time-current

Protectio
performance characteristic complying with IEC 60898 or
BS 3871. This requires that the device must operate
within 200 milliseconds at its residual current rating and
within 40 milliseconds at 5 times its residual current
rating. It must not operate below 50% of its residual
current rating, see Guidance Note G5(a). 5

5.4.4 For Final Circuits which are liable to carry pulsating or


d.c. currents RCD devices must be of type A (pulsating
d.c. sensitivity) and for RCD devices requiring time-
delayed operation type S devices must be used, see
Guidance Note G5(d).

5.4.5 Earth Leakage Protection provided at the Supply Intake


must be set to discriminate with ELP devices at Final
Circuits (i.e. earth faults on Final Circuits must be
automatically disconnected by the closest ELP device,
except in the case of back-up operation of devices at the
Supply Intake). See Guidance Note G4(e).
[Note: such discrimination may be provided by time delayed
devices at the Supply Intake.]

The Electricity Wiring Regulations 2007 45


5.4.6 The operating current setting for ELP devices at the
Supply Intake must take into account the nature of the
Installation (e.g. commercial, industrial, etc), the
likelihood and magnitude of earth fault currents, and the
requirement for protection against Indirect Contact, see
Appendix A5(m) and Guidance Note G4(f).

5.4.7 Earthed Equipotential Bonding is not required in an ELP


system, although it may be provided as supplementary
protection against Indirect Contact, see Guidance
Note G4(d).
[Note: Earth Leakage Protection devices provide protection
against electric shock by limiting the time that current may
pass through the body of a person to Earth; they do not limit
the magnitude of current, except by the feature of early cut-off
for a rising current. In addition, ELP devices provide
protection against ‘high resistance’ earth faults that may persist
5 in an installation if the fault current is too low to operate
overcurrent devices such as MCBs. Such faults may cause
overheating of Circuits or connections and lead to a fire.]

5.4.8 At each Distribution Board or other point where an RCD


is provided a suitable label must be affixed to inform the
Customer of the characteristics and mode of operation
of the device and the need for routine testing, see
Appendix A12(c).

5.4.9 For domestic Premises the residual current rating for


ELP devices must be 100 mA for Final Circuits supplying
fixed equipment (e.g. lighting and air conditioning) and
30 mA for Final Circuits where Appliances may be used
by persons (e.g. all socket-outlets, all kitchen Appliances,
other Appliances accessible to persons), and 30 mA for
all Circuits in a bathroom, see Regulation 9.3. A full list
of applications and residual current ratings is provided in
Appendix A5(m).

5.4.10 Special Circuits within a Premises, where there would be


significant detriment or danger from the tripping of the

46 The Electricity Wiring Regulations 2007


Earth Leakage Protection, may be excluded from the zone
of Earth Leakage Protection. Such instances may include
Circuits supplying fire protection equipment or safety
alarms (not security alarms) or unoccupied sites (such as
telecommunications stations, water pumping stations, etc).
All such cases must be declared in the Electrical
Installation Certificate for the site and approved by the
Distribution Company. In these cases the requirements for
an Earthed Equipotential Bonded System must be met for
the relevant Circuits, see Regulation 5.5.

5.4.11 Circuits with high earth leakage currents (e.g. electronic

Protectio
equipment or industrial machinery) may be provided with
ELP devices with higher residual current ratings, up to
500 mA. These must be clearly stated on the Electrical
Installation Certificate.

5.4.12 Notwithstanding clauses 5.4.10 and 5.4.11, all Circuits from 5


which portable Appliances may be used, or any outdoor
equipment accessible to persons, must be provided with
Earth Leakage Protection devices with a residual current
rating no greater than 30 mA.

5.4.13 An earth leakage alarm may be provided for Circuits


which are excluded from the zone of Earth Leakage
Protection (e.g. an alarm that does not cause tripping of
the Circuit but gives an audible and visible warning to
appropriate persons in the Premises).

5.5 Earthed equipotential bonded systems

5.5.1 An Earthed Equipotential Bonded System (EEBS) is


defined as one where protection against Indirect contact
is provided by the installation of Earthed Equipotential
Bonding such that voltage rises between Exposed-
Metallic- Parts and Extraneous-Metallic-Parts are kept to a
safe value for the duration of an earth fault (i.e. the time it
takes for the relevant Protective Device to trip).

The Electricity Wiring Regulations 2007 47


[Note: an EEB system relies on the principle that all Exposed-
Metallic-Parts and Extraneous-Metallic-Parts which are
accessible to persons are connected to the Main Earth Terminal
and therefore the prospective Touch Voltage between them is
limited to a value which is safe when taking into account the
operating time of the relevant Protective Device. In addition, it
is assumed that a person cannot be in contact with Earth whilst
touching any Metallic Part in a Premises – see Guidance Note
G4(b) and G4(h).]

5.5.2 For an EEB system the operating characteristics of


Protective Devices must limit the duration of any earth
fault to less than 0.4 seconds for Circuits supplying
Appliances which are accessible to people, and less than 5
seconds for all other parts of the Installation.

5.5.3 The most commonly used method for checking the


5 prospective fault duration is by reference to data on
the limiting values of earth loop impedance for the
Protective Device concerned. For MCBs this is provided
in Appendix A5(h), taken from BS 7671.

5.5.4 Main Equipotential Bonding Conductors must be installed


from the Main Earth Terminal to connect metallic service
pipes and other Extraneous-Metallic-Parts at points closest
to the entry of such parts to a Premises.

5.5.5 In high risk areas Supplementary Equipotential Bonding


must be provided so that the Touch Voltage between
Exposed-Metallic-Parts and Extraneous-Metallic-Parts is
kept to safe limits for the duration of an earth fault.
[Note: high risk areas may include bathrooms, kitchens,
laboratories, garages, confined spaces or other locations where
the normal resistance of the body is reduced or the consequence
of an electric shock may lead to another accident, such as fall
from a height. For disconnection times greater than 0.4 seconds
safe Touch Voltage limits may be taken as 50 V for dry
conditions and 25 V for wet conditions.]

48 The Electricity Wiring Regulations 2007


5.5.6 The method for calculation of Touch Voltage between
Exposed-Conductive-Parts and Extraneous-Metallic-Parts
is illustrated in Guidance Note G4(h).

5.5.7 Items requiring Equipotential Bonding may include metallic


pipes (particularly those connected to underground
services such as water supply), steel beams, water tanks,
baths, sinks and washbasins, etc. An illustration of typical
Equipotential Bonding arrangements is given in Guidance
Note G4(c).

5.5.8 It is not necessary to provide Equipotential Bonding for


standalone metallic items which:

Protectio
(a) do not pose any risk of providing a conductive path
to Earth (are isolated from Earth); or
(b) do not pose any risk of providing a conductive path
to any other Earthed part of the Installation; or
(c) do not pose any risk of becoming live as a result of
5
an electrical fault in the Installation (i.e. are
sufficiently remote from any Circuit or Appliance);
or
(d) are out of reach of any person.
[Note: such items may include metal doors, window frames,
inaccessible structural beams, small metallic fixings such as
screws and brackets, etc.]

5.5.9 Where Circuit conductors are installed close to or within


items of metalwork (such as mentioned in clause 5.5.8)
consideration must be given to provide additional
protection or double insulation of such conductors.
[Note: examples include situations where cables pass through
walls containing steel frames, metal door frames, metallic floor
grids, suspended ceilings, etc.]

5.5.10 The sizing of Equipotential Bonding Conductors is given


in Appendix A5(j).

The Electricity Wiring Regulations 2007 49


5.5.11 The point of connection of an Equipotential Bonding
Conductor to any item must be labelled: SAFETY EARTH
BONDING – DO NOT REMOVE, as illustrated in
Appendix A5(d).

5.6 Isolation and switching

5.6.1 All Electrical Installations must be provided with a means of


safe isolation at the Supply Intake, which must be lockable or
otherwise provided with a means of preventing
interference (e.g. by the removal of operating handles into
the safe custody of a responsible person). Isolation for
maintenance or other work may be provided by the
Protective Device if it is lockable (except for HV
equipment).
[Note: mechanical equipment should be provided with a means
of isolation close to the equipment which can be locked and kept
5 under the control of the person performing maintenance.]

5.6.2 An Installation must be further sectionalised by means of


isolation at the origin of each Circuit, in order to provide
ease of access for safe working.

5.6.3 Each socket-outlet or other connection point to an


Appliance or other electrical equipment must be provided
with a switch as a means of isolation. Such switches must
be provided with a neon indicator where it is desirable to
have a visual indication of the presence or absence of
power (e.g. fridge, fire alarm, gas or smoke alarm, and
water heater).

5.6.4 Emergency switching (e.g. push-button switch) must


be provided for moving machinery which may require
immediate manual disconnection from the supply in the
case of an accident or other situation to avoid Danger.
Such equipment may include large motors, ventilation
equipment, industrial machinery, etc. Emergency push
switches must operate on all phases and neutral of the
supply, must be clearly marked and must be located in an
easily accessible position.

50 The Electricity Wiring Regulations 2007


5.6.5 Emergency switches must be designed so that their operation
retains the switch in the off position until it is
intentionally unlocked or reset. The release of the
emergency switch must not automatically restart the
related Appliance or machinery.

5.6.6 Functional switching devices required for control or


operation of equipment and not for safety reasons need
not comply with the requirements of clauses 5.6.1 to
5.6.5.

5.6.7 Semiconductor devices cannot be used as a means of


isolation for safety.

Protectio
5.7 Insulation

5.7.1 All Electrical Installations must be sufficiently insulated


to protect against electric shock from Direct Contact by 5
any person (clause 5.3.1). Such insulation must be capable
of withstanding wear and tear during normal use of the
equipment. Supplementary insulation or ‘double insulation’
may be used where additional robustness is required.

5.7.2 The application of paints, resins, varnishes and similar


materials is not considered to satisfy the requirements of
clause 5.7.1 and additional insulation, barriers or obstacles
are required to prevent Direct Contact by any person.
[Note: an example may be a motor winding which is enamelled
or resin coated and therefore must be guarded against Direct
Contact by persons.]

5.7.3 Live conductors are required to be inaccessible without


the use of a special key or tool, available only to
authorised persons and only for the purpose of testing,
using special equipment and procedures.

The Electricity Wiring Regulations 2007 51


5.7.4 Uninsulated equipment may be used at voltages not
exceeding 12 V a.c. or 30 V d.c. and only where supplied
by a SELV source, see Regulation 9.1.

5.7.5 The insulation resistance of Circuit conductors must


be measured as part of the test procedures given in
Chapter 8 and must be greater than the values given in
Appendix A19(f).

5.7.6 Where an Installation is supplied by underground cables


no special provisions are required for protection against
over-voltages arising from atmospheric origin or from
switching. Where an Installation is supplied by overhead
lines advice should be sought from the Distribution
Company or the requirements of BS 7671 – Chapter 44
may be used.

52 The Electricity Wiring Regulations 2007


Earthing
6
6.1 General principles

6.1.1 Earthing of Exposed-Metallic-Parts of an Installation and


of Appliances in a Premises is required to serve the
following functions of safety:

(a) allow the passage of fault current in the event of a


live conductor touching an Exposed-Metallic-Part;
(b) ensure that the magnitude of fault current is
sufficient to operate Protective Devices, including
Earth Leakage Protection devices, within 0.4
seconds for Final Circuits supplying Appliances
which are accessible to any person and within 5
seconds for all other parts of an Installation; and
(c) ensure that, in association with Protective Devices, a
‘high resistance’ fault to Earth does not persist so as
to cause overheating or fire.

6.1.2 The necessary requirements to achieve the above


functions of safety are detailed in the following sections.

6.2 Systems of earthing

6.2.1 Customers must be provided with a supply operating


under either of the following earthing systems:
(a) Customer Earthed System (TT): the Customer
provides a Main Earth Terminal for the Installation,
which is connected to a sufficient number of local
Earth Electrodes to provide a maximum Earth
Resistance measured at the Customer’s Main Earth
Terminal of no greater than 10 Ohms (referred to in
BS 7671 as a ‘TT’ system);
(b) Distribution Company Earthed System (TN-S): the
Distribution Company provides a connection to
the Customer’s Main Earth Terminal, using the
distribution network Earthing system, normally via
the armouring or metallic sheath of the incoming

The Electricity Wiring Regulations 2007 53


supply cable (referred to in BS 7671 as a TN-S
system). The Distribution Company system is
earthed at the distribution transformer (11 kV or
400 V) and separate earth and neutral conductors are
used throughout the distribution network; or
(c) Distribution Company Earthed System with
additional Customer Earth (TN-S-TT): the
Distribution Company provides an earth connection
to the Customer’s Main Earth Terminal and a local
Earth provided by the Customer is also connected to
the same MET, having an Earth Resistance value of
no greater than 10 Ohms.
[Note: These types of earthing systems are illustrated in
Appendix A5(a) – A5(c).]

6.2.2 The preferred earthing system to be used in Abu Dhabi


Emirate is TN-S-TT. However, either TN-S or TT
systems may be used where agreed between the
Distribution Company and the Customer. The type of
earthing system must be stated on the Electrical
6 Installation Certificate and clearly labelled at the Main
Distribution Board.

6.2.3 In all cases the neutral and Earth Conductors must be kept
separate and not connected together at the MET or at any
other point in the Customer’s Installation.

6.3 Main earth terminal

6.3.1 The Main Earth Terminal must be provided close to or


within the Main Distribution Board or other switchgear at
the Supply Intake.

6.3.2 A means of removing the connection to Earth (such as


by a detachable metal link) must be provided at the Main
Earth Terminal to facilitate testing of the earthing of the
installation and the source of supply, see Appendix A5(e).

54 The Electricity Wiring Regulations 2007


6.3.3 The Earth Resistance measured at the MET must be
recorded on the Installation Certificate in accordance
with the procedures described in Chapter 8. Methods
of measuring Earth Resistance are shown in
Appendix A19(a).

6.4 Earth electrodes

6.4.1 Earth Electrodes must be provided at Premises which


are supplied by a Customer Earthed System (TT) or a
Distribution Company Earthed System with additional
Customer Earths (TN-S-TT).

6.4.2 For Premises consisting of more than one building, where


either a TT or TN-S-TT system is used, Earth Electrodes
must be provided at each building that is more than 30 m
distance from the Supply Intake.

Earthi
6.4.3 Earth Electrodes will normally comprise of 15 mm
diameter steel-cored copper rods driven to a minimum
depth of 3 m. The top of each Earth Electrode must be 6
housed inside a 300 mm x 300 mm x 300 mm inspection
pit which is clearly labelled and accessible for routine
testing, see Appendix A5(d). Alternative types of Earth
Electrodes may be used with prior approval of the
Distribution Company (e.g. plate or wire mesh type, or
structural steelwork in a building).

6.4.4 Where more than one Earth Electrode is required to


achieve the required Earth Resistance value these must be
separated at a distance greater than their mutual resistance
zone.
[Note: a minimum separation of twice the earth electrode
depth is considered to give adequate separation of the mutual
resistance zones. See BS 7430 for further advice on spacing of
Earth Electrodes.]

The Electricity Wiring Regulations 2007 55


6.4.5 The condition of the ground in which an Earth Electrode
is placed must be taken into account to ensure its long-
term performance. In particular, potential corrosion effects
and ground moisture content is of critical importance.
Proprietary chemical or salt materials may be used around
the Earth Electrode to maintain moisture content but these
must be stable and sustain their chemical properties over
time.

6.4.6 For supplies of 500 A rating and above, at least two


independent Earth Electrodes must be provided, regardless
of the Resistance Value achieved for each Earth
Electrode, and connected to the same Main Earth
Terminal, see Appendix A5(k).

6.4.7 Metallic service pipes (such as water, gas, etc) must not be
used as Earth Electrodes.

6.5 Earth conductors

6 6.5.1 In these Regulations the following terminology is used to


refer to Earth Conductors in an installation, see illustration
in Appendix A5(f):

(a) Main Earth Conductors (MEC): conductors


connected between Distribution Boards, Earth
Electrodes and Main Earth Terminals; and
(b) Circuit Earth Conductors (CEC): conductors
connected from Final Distribution Boards and
associated with Final Circuits, including Appliance
Earth Conductors such as within a flexible cord.
Outside these Regulations these may also be
known as the Circuit Protective Conductor (CPC)
or Earth Continuity Conductor (ECC).

56 The Electricity Wiring Regulations 2007


6.5.2 All Earth Conductors must be covered with green/yellow
PVC insulation and terminated with purpose made lugs or
fixings.

6.5.3 Where associated with Circuits, all Earth Conductors


must be labelled at their termination points with Circuit
identification numbers, see Guidance Note G7(f).

6.5.4 The connection of Earth Conductors to Earth Electrodes


must be made using corrosion resistant clamps.

6.5.5 Where Earth Conductors are buried below ground they


must be mechanically protected (e.g. in plastic or metal
duct or pipe and, where necessary, with additional tiles or
plates laid above the duct or pipe, see Appendix A5(d) and
Guidance Note G6.

6.5.6 The connection of Earth Conductors to the Main Earthing

Earthi
Terminal must be made using purpose made lugs or other
fixings and the connection must be clearly labelled as shown
in Appendix A5(d).
6
6.5.7 All Circuits must have a Circuit Earth Conductor sized in
accordance with Appendix A5(j).

6.5.8 Circuit Earth Conductors must, where practicable, run


alongside the associated phase and neutral conductors.
[Note: this minimises the risk of a Circuit Earth Conductor
being damaged or disconnected without any damage or fault
indication being detected via the phase conductors.]

6.5.9 For metal sheathed or armoured cables, the sheath or


armouring may be used as the Earth Conductor where
it is rated to the equivalent of the conductor sizes shown
in Appendix A5(j). The metal sheath or armouring must
be terminated by suitable cable glands with appropriate
connection to an Earth Condutor, see Guidance
Note G7(i). However, where such cables are installed
underground a separate Earth Conductor must be laid
alongside the power cable.

The Electricity Wiring Regulations 2007 57


6.5.10 The use of metal conduit, trunking, busbar trunking or
switchgear metal enclosures as Earth Conductors is not
permitted without the prior approval of the Distribution
Company. In such cases, the provision of additional
measures such as resistance measurements or supplementary
Earth Conductors will normally be required.
[Note: metal conduit, although not to be used as an Earth
Conductor, must nevertheless be effectively connected to Earth
since it comprises an Exposed-Metallic-Part. See Guidance
Note G7(j).]

6.5.11 No switches, isolators or circuit-breakers may be installed


in the electrical path of any Earth Conductor. Removable
links may be installed to allow testing at the Main Earth
Terminal.

6.6 Exposed-metallic-parts

6.6.1 All Exposed-Metallic-Parts of an Installation, including


Appliances, must be connected to Earth via Earth
6 Conductors which in accordance with the requirements of
Regulation 6.5.

6.6.2 Exceptions to clause 6.6.1 may include internal parts of


equipment or Appliances which cannot be accessed
without first disconnecting the electricity supply.

6.6.3 Class I Appliances having Exposed-Metallic-Parts must


be provided with a suitable connection point or plug &
socket arrangement which includes connection to the
Circuit Earth Conductor. Class II Appliances do not
require an Earth connection, see illustrations in Appendix
A18(a) and A18(b).

6.6.4 All connection points in an Installation must include an


Earth Conductor for future use.
[Note: an example would be a plastic light switch which does
not require a Circuit Earth Conductor but one must be provided
in any case for future use – see Guidance Note G7(d).]

58 The Electricity Wiring Regulations 2007


6.6.5 Items within an Installation where it is mandatory for a
connection to be made to an Earth Conductor are listed in
Appendix A5(l).

6.6.6 The requirement for connection of Extraneous-Metalic-


Parts to Earth Conductors depends on the type of
protection system used in an Installation, as explained
under Regulation 5.5.

6.7 Earth fault loop impedance

6.7.1 The Earth Fault Loop Impedance (Zs) is defined as the


total impedance presented to an earth fault current,
comprising the impedance of the following parts of a
system, illustrated in Appendix A5(g):

(a) the Circuit Earth Conductor (including the

Earthi
Appliance Earth Conductor);
(b) the Main Earth Terminal;
(c) the main Earth Conductors connecting to local Earth
Electrodes (TT system) or the Distribution Company
6
Earth (TN-S system);
(d) the path of earth fault current through the general
mass of Earth, or through the earth sheath or
armouring of the Distribution Company cable;
(e) in the case of a Customer Earthed System (TT system)
the neutral earth connection at the Distribution
Company transformer;
(f) the distribution transformer winding; and
(g) the phase conductors of the Circuit back to the point
of fault.

6.7.2 All Installations must be designed and tested such that the
Earth Fault Loop Impedance at any point in the
Installation is of a sufficient value to operate Protective
Devices within
0.4 seconds for Final Circuits supplying Appliances which

The Electricity Wiring Regulations 2007 59


are accessible to any person and within 5 seconds for all
other parts of an Installation.
[Note: this requirement is important for parts of Installations
where protection against Indirect Contact is provided by
Earthed Equipotential Bonding rather than by Earth Leakage
Protection, see Regulations 5.4 and 5.5.]

6.7.3 The maximum Earth Fault Loop Impedance values


required to meet the disconnection times in clause 6.7.2
for MCB devices are given in Appendix A5(h).

6.7.4 The method for testing Earth Fault Loop Impedance


(including the external earth fault loop impedance) is
given in Appendix A19(b) and A19(c).

6.8 Lightning protection

6.8.1 Lightning protection systems and associated earth electrodes


must be separate from the electrical Installation earthing
system.
6
6.8.2 A minimum distance of 7 m must be provided between
lightning protection earth electrodes and the Installation
Earth Electrodes.

6.8.3 Lightning protection systems must be designed,


constructed and maintained in accordance with BS
6651, except that the lightning protection system is not
to be bonded to the Installation Main Earth Terminal.
[See clause 5.7.6 for requirements for protection against over-
voltages.]

6.9 Functional earthing and high


leakage currents

6.9.1 Functional Earth conductors may be required for purposes


such as, but not limited to, radio frequency noise
reduction,

60 The Electricity Wiring Regulations 2007


filters for computers and other equipment with high earth
leakage currents.

6.9.2 Functional Earth conductors must be separate from other


parts of the Installation Earthing system, except at their
connection to the Main Earth Terminal where a suitable
label must be provided, see Appenix A5(f).

6.9.3 Equipment which produces high earth leakage currents


(above 10 mA) may be provided with a Functional Earth
and in any case must be provided with duplicate Circuit
Earth Conductors to the Main Earth Terminal. Such
equipment must remain connected to Earth at all times to
avoid the risk of electric shock from Exposed-Metallic-Parts
of the equipment.
[Note: metallic conduit may be considered as one of the
duplicate Earth Conductors required for high leakage

Earthi
equipment. Alternatively, Circuit Earth Conductors in a Ring
Circuit are also accepted as providing a duplicate earth path.
This requirement safeguards against electric shock due to
Indirect Contact if only one Circuit Earth was provided and was
damaged or broken.] 6

The Electricity Wiring Regulations 2007 61


6

62 The Electricity Wiring Regulations 2007


Selection of components
and installation requirements 7
7.1 Plugs and socket-outlets

7.1.1 For domestic Installations all single-phase plugs and


socket- outlets must comply with BS 1363 and be fitted
with a switch. The use of any other type of single-phase
plugs and sockets-outlets, such as BS 546 (3 round pins) is
not permitted.
[Note: BS 1363 requires plugs to have partly insulated live and
neutral pins and include a fuse complying with BS 1362. Socket-
outlets are required to have tamper-proof shutters on the live,
neutral and Earth connections.]

7.1.2 For single-phase applications in non-domestic


Installations either BS 1363 or BS 546 type plugs and
socket-outlets are permitted. However, BS 546 plugs and
socket-outlets must be restricted to specialist applications
such as high load Appliances (BS 546 15 A plug) or
where it is desirable not to intermix certain Appliances,
see Appendix A17(a).
[Note: examples of the use of BS 546 plugs include table lamps
in hotel rooms which are switched from a dedicated lighting
Circuit (3 A or 5 A) or self contained air conditioning units
(15 A). In the latter case 15 A BS 546 socket-outlets must be
supplied from a dedicated Radial Circuit.]

7.1.3 The use of 2-pin plugs such as the ‘Euro’ CEE7/16 plug
and the ‘Shuko’ CEE7/7 plug is strictly prohibited, unless
provided with an approved adaptor converting such plugs
for use on BS 1363 type sockets, see Appendix A17(a).
[Note: adapters must be approved by a recognised international
approvals authority such as KEMA, NSAI, ASTA, etc.]

7.1.4 An allowable exception to clause 7.1.1 is the use of shaver


supply units in bathrooms, complying with BS 3535.
For these types of socket-outlet, which are supplied by
a SELV safety isolating transformer, a 2-pin plug may
be used but which must also comply with BS 3535. See
Appendix A17(c).

The Electricity Wiring Regulations 2007 63


7.1.5 No socket-outlets shall be installed in a bathroom except
for a socket-outlet complying with BS 3535 (shaver
socket- outlet including a safety isolating transformer).

7.1.6 Three-phase and industrial plugs and socket-outlets must


comply with BS 4343 and BS EN 60309, see Appendix
A17(b). The rating of three-phase socket-outlets must
be selected according to the load of the Appliance or
equipment to be connected.
[Note: BS 4343 plugs and socket-outlets are not fused and are
not shuttered and therefore must not be used in any domestic
application.]

7.1.7 Socket-outlets for normal use must be positioned at a


height of 450 mm above floor level or 100 mm above
work surfaces, see Appendix A16. Where required, low
level or skirting height may be used (e.g. in offices) at a
minimum of 100 mm above the floor level, and where
adequate precautions are taken against damage. Access
for limited ability persons must be given due
consideration in such cases (e.g. alternative socket-outlets
provided).

7.1.8 Floor socket-outlets may be used where there is no undue


risk of water ingress or flooding and which are designed
to relevant international standards.
7
7.1.9 Socket-outlets in kitchens or other areas where water is
used must be positioned at least 1.0 m away from sources of
water (e.g. sinks, basins, filter units, supply taps).
Consideration must be given to the use of splash proof
socket- outlets (IP 56).

7.1.10 The recommended minimum number of socket-outlets for


domestic Installations is given in Appendix A15.

7.1.11 All socket-outlets in one room or service area shall be


connected to the same phase.

64 The Electricity Wiring Regulations 2007


7.1.12 The maximum number of single-phase socket-outlets on
each Ring or Radial Circuit shall be determined according
to the anticipated load and usage of Appliances. The
assumed loads given in Guidance Note G2 may be used in
the absence of other loading information.

7.1.13 Three-phase socket-outlets must be connected on


individual Radial Circuits.

7.1.14 Outdoor socket-outlets must be of the weather protected


type (IP55) and incorporate a 30 mA RCD, see Guidance
Note G7(c).

7.2 Switches and isolators

7.2.1 All switches provided for local isolation of Appliances


and equipment (including lighting) must comply with
BS 3676. The rating of switches must be selected based
on the expected load, taking into account any capacitive or

Componen
inductive effects.

7.2.2 For outdoor locations, damp or wet areas, weather-


protected switches must be used (BS 3676).

7.2.3 Wall-mounted switches must not be installed in 7


bathrooms, shower rooms or other locations where normal
body resistance is reduced due to the presence of water.
In such locations, ceiling mounted cord-pull switches may
be used or wall-mounted switches may be used outside the
room. Wall-mounted switches may be used in kitchens but
at least 2 m from a sink or other source of water.

7.2.4 For areas with higher than normal risk of fire or explosion
gas-sealed switches must be used (BS 5345). For example, in
gas storage areas, battery rooms, etc.

7.2.5 The normal mounting height for switches shall be 1.3 m


from floor level. Other mounting heights may be used
where there is a specific need, such as, but not limited to,

The Electricity Wiring Regulations 2007 65


the prevention of access by children or the requirement
for access by disabled persons.

7.2.6 Switches with neon indicators must be provided for


Appliances such as water heaters, air conditioning units,
fridges and freezers, where a visual indication of the
presence of power is desirable.

7.2.7 Double-pole switches must be provided for water heaters,


air conditioning units and other fixed Appliances
operating with or near water supplies.

7.2.8 Cooker control units (isolators) for domestic Installations


must comply with BS 4177. The use of cooker control
units with an integral 3-pin socket-outlet is prohibited
except where the Final Circuit supplying the cooker
control unit is protected by an RCD with a residual current
rating of 30 mA, in accordance with clause 5.4.9.
[Note: in addition to the above restriction it is considered
undesirable to use cooker control units with integral socket-
outlets where there is a risk of Appliances or flexible cables
supplied by the socket-outlet being damaged by heat from the
cooker.]

7.2.9 Flexible cables from switches or isolators to fixed Appliances


7 (such as water heaters, cookers, etc) must be adequately
rated and securely fixed with a purpose-made flex outlet
plate (which may be integral with or separate from the
switch or isolator unit).

7.3 Lighting

7.3.1 Lighting Circuits will normally be fed from 6 A, 10 A or


16 A MCBs from a Final Distribution Board.

7.3.2 The rating of lighting Circuits shall be selected in


accordance with the number of connection points to be
supplied, the type and rating of luminaires to be used, and

66 The Electricity Wiring Regulations 2007


the expected loading. The standard rating and diversity
factors given in Appendix A6(f) and Guidance Note G2
may be used in the absence of other specific information.

7.3.3 Lighting Circuits supplying small Edison screw (SES) or


small bayonet cap (SBC) fittings must be supplied from
Protective Devices of nominal current rating no greater
than 6 A.

7.3.4 Switching of Circuits containing discharge lighting or


other lighting with high inductance may require special
consideration due to high switching voltages that may
occur. In order to accommodate the switching voltage in
discharge lighting Circuits, the rating of the switch shall
be suited to the conditions expected and shall not be less
than twice the load current.

7.3.5 High voltage discharge lighting (such as neon signs) must


comply with BS 559 and be provided with an emergency
isolation switch which must be clearly marked and located

Componen
in an easily accessible position.
[Note: such switches may be marked “Fireman’s Switch for
Neon Sign” or similar wording.]

7.3.6 The connection of mains-operated clocks to lighting


Circuits other than through a clock connector unit is 7
prohibited.

7.3.7 All Luminaires must be connected to Final Circuits using


a ceiling rose or other purpose made connection point
and not directly to such Circuits. Where cables are run
within Luminaires they shall be of the heat resistant type,
or protected by heat resistant sleeving. See Guidance
Note G7(b).

7.3.8 Lighting Circuits in false ceilings or voids must be


installed in conduit or trunking in compliance with clauses
7.5.12 and
7.5.13. However, short lengths (less than 3 m) of flexible
or sheathed cables may be provided between a lighting

The Electricity Wiring Regulations 2007 67


connection point or ceiling rose and a Luminaire, provided
that provision is made for future access and maintenance.
In addition, the use of purpose made plug and socket
connection systems for Luminaires is not precluded,
provided that approval is sought from the Distribution
Company. See Guidance Note G7(h).

7.3.9 Luminaires and other light fittings must be installed with due
consideration to the weight taken by fixings and supports,
and the need for adequate ventilation and heat dissipation.

7.3.10 Heat resistant cables and flexible cords should be used


for the connection of high temperature luminaires. See
Guidance Note G7(b).

7.3.11 Where light switch boxes contain more than one phase
(for large groups of lighting) they must be labelled to
indicate the presence of a 400 V supply, and suitable
phase barriers should be provided inside the box.

7.3.12 Outdoor lighting should be of suitable weatherproof


construction with appropriate connection points and
fittings.

7.3.13 Underwater lighting must be supplied by a Separated


Extra-Low Voltage System (SELV) not exceeding 12 V
7 a.c. or 30 V d.c.

7.3.14 Emergency light fittings must comply with BS 5266 and


shall be provided with a battery of minimum 2 hours
rating.

7.4 Conduit, trunking and cable trays

7.4.1 All plastic conduit and trunking must comply with BS


4607 and be suitable for the ambient conditions expected.

7.4.2 All metal conduit and trunking must comply with either
BS 4568, BS EN 60423 or BS EN 50086. Cable tray must
comply with BS EN 61537.

68 The Electricity Wiring Regulations 2007


7.4.3 Flexible conduit must be of metal construction, PVC covered
and comply with BS 731 part 1. Flexible conduit may be
of plastic construction only in indoor locations, where
damage is unlikely and where it contains only sheathed
conductors or Earth Conductors.

7.4.4 Metal conduit, trunking or cable tray may not, on their


own, be used as Circuit Earth Conductors; separate
Circuit Earth Conductors must be run inside the conduit,
trunking or cable tray, see also clause 6.5.10). This does
not obviate the requirement to comply with clause 6.6.1
(i.e. metal conduits are required to be Earthed), see Guidance
Note G7(j).

7.4.5 Plastic conduit or trunking must not be used in situations


subject to higher than normal temperatures or fire risk
(e.g. near industrial machinery, generator rooms,
workshops, petrol stations, etc). Where plastic conduit is
installed outdoors it should be suitable for exposure to
solar radiation.

Componen
7.4.6 Where conduit is buried in a wall, floor or ceiling it must
be installed at a minimum depth of 50 mm from the
surface. If installed at a shallower depth, then metal
conduit must be used. See Guidance Note G7(e).
7
7.4.7 Conduit, trunking and cable tray must be installed so as
to provide ease of access to cable Circuits throughout the
route. Sufficient inspection plates and pulling points must
be provided to enable inspection, repair and drawing out
of cables throughout the life of the Installation.

7.4.8 The ends of conduit, trunking and cable tray shall


be provided with bushes or other finished ends such
that cables do not sustain damage during installation
or throughout the life of the Installation, and must be
suitably sealed against the ingress of water. Where such
bushes or ends are not provided any sharp angles, burrs
or projections must be removed, see Guidance Note

The Electricity Wiring Regulations 2007 69


G7(g). Care must be taken not to leave sections of cable
exposed at ends of conduit or trunking. See Guidance
Note G7(a).

7.4.9 Plastic conduit boxes for accessories shall be provided


with copper or brass earth terminals. See Guidance Note
G7(d).

7.4.10 Single-insulated cables may not be installed in slotted


(perforated) trunking or cable trays.

7.4.11 The minimum internal radius of any bend or elbow fitting


in a conduit shall be 2.5 times the diameter of the conduit.

7.4.12 Elbow fittings of trunking may be 90º formation only


where the cover is removable so that cables may be
installed without the need for pulling through.

7.4.13 Conduit shall be installed with a maximum of two 90º


bends or three 120º bends between inspection or pulling
points.

7.4.14 Cable trunking and cable tray shall be run exposed or


otherwise accessible after installation, throughout its
length, for the purpose of removing or installing cables.
7
7.4.15 Where cable trunking or cable tray passes through walls,
floors or other barriers it shall be provided with a
continuous cover and an internal fire barrier where fire
separation is specified for the Premises. See Guidance
Note G3(a).

7.4.16 Where trunking or cable tray is used for the combined


provision of power, telecommunications and other
Circuits adequate segregation must be provided, together
with suitably sealed service boxes and connection boxes.

7.4.17 Category 3 Circuits (fire and emergency lighting) may


not be installed in the same conduit or trunking as
Category 1 (mains supplied) Circuits or Category 2
(telecommunications) Circuits.

70 The Electricity Wiring Regulations 2007


7.4.18 Category 1 and Category 2 Circuits may only be installed
in the same conduit or trunking if the latter are insulated
to the level of Category 1 Circuits.
[Note: trunking or conduit referred to in clauses 7.4.17 and
7.4.18 may be metallic or non-metallic.]

7.4.19 Under floor cable trunking shall be used only in areas


which are not susceptible to water ingress or flooding.
Suitable junction boxes, flush service boxes and
inspection compartments shall be provided according to
the design of the under floor trunking system.

7.4.20 The maximum number of cables for typical sizes of


conduit and trunking are given in Appendix A9.

7.4.21 Where conduit or trunking is installed on the Distribution


Company’s side of the Customer Connection Point, these
must be provided with a means of locking or sealing
against unauthorised interference.

Componen
7.5 Cables

7.5.1 For fixed wiring within Premises PVC (thermoplastic),


rubber (thermosetting) or XLPE insulated cables with
stranded copper conductors must be used, complying with 7
the reference standards given in Appendix A3. Solid-core
or Aluminium conductor cables are not permitted.

7.5.2 For locations subject to a higher than normal risk


of interference or damage armoured cables are
recommended.

7.5.3 For locations with higher than normal fire risk either
cables must be installed in metal conduit or mineral-
insulated- copper-clad (MICC) cables must be used
(complying with BS 6207). In addition, safety Circuits
such as fire alarms, emergency lighting and control
Circuits, which are required to remain operational in the
event of a fire, must be installed in metal conduit or
supplied by MICC cables.

The Electricity Wiring Regulations 2007 71


7.5.4 The location and selection of cables must take into
consideration any special requirements for the prevention
of spread of fire. Fire barriers, low smoke insulation or
other measures may be required (relevant building
regulations should be referenced).

7.5.5 General-purpose flexible cables and cords for Appliances


must be PVC insulated, with a PVC oversheath, stranded
copper conductors, and comply with BS 6500.

7.5.6 Cables for high temperature Appliances (e.g. electric heaters,


irons, pendant lighting, connections within luminaries)
must be heat resistant rubber insulated, with oversheath,
stranded copper conductors, and comply with BS 6141.

7.5.7 Cables under repetitive mechanical strain (e.g. lifts, heavy


outdoor machinery, etc) must comply with BS 6977.

7.5.8 Where cables are installed underground they must be


installed in ducts to protect against mechanical damage
and enable future removal, see Guidance Note G6.

7.5.9 Cables for meter tails (at 230 V) shall be single-core, PVC
insulated, with oversheath, and comply with BS 6004.

7 7.5.10 The cross-section of cables must be selected according


to the expected load, voltage drop, ambient temperature
and installation conditions using Appendix A7(a) - A7(h)
including appropriate grouping factors. The maximum
voltage drop from the Customer Connection Point to the
remote end of any Final Circuit must not exceed 4%,
except in special cases where equipment has been
designed to operate under a greater voltage drop (such
cases must be clearly stated in the Installation design and
approved by the Distribution Company).

7.5.11 The use of single-core armoured cables should be avoided


due to the possibility of induced heating effects.
However, such cables may be used where there is an
exceptional need, with the written consent of the
Distribution Company

72 The Electricity Wiring Regulations 2007


and where adequate precautions are taken to avoid
induced heating effects. Such precautions may include the
appropriate spacing of phases to balance induced currents,
Earthing at one end only and the use of non-ferromagnetic
armouring, cable glands, and switchgear gland plates, see
Guidance Note G7(l).

7.5.12 Other than as allowed under clause 7.5.15, all cables


which are not armoured must be installed in plastic or
metal conduit or trunking throughout their entire length.

7.5.13 Cables running through inaccessible areas such as walls,


floors and solid ceilings shall be installed, without exception,
in conduit or trunking so as to be withdrawable in the
future. In such cases, suitable inspection plates and
pulling out points must be provided.

7.5.14 Non-sheathed cables must not be installed in concrete


ducts.

Componen
7.5.15 Exceptions to clause 7.5.12 may be allowed only for
sheathed or flexible cables which will remain accessible
but in locations free from undue risk of damage or
interference (e.g. above head height, or in unoccupied
areas). Such cables must be securely supported by cable
clips, cable tray or other fixings at suitable intervals. 7
[Note: although flexible cords must not be used as fixed wiring
this clause covers Appliance connection cables which should be
limited to 3 m in length where practicable. In addition, proprietary
plug and fit connection systems may be installed from a suitable
connection point in the fixed wiring system, provided they are
suitably supported, mechanically protected, or otherwise
located in areas where there is minimal risk of damage or
interference. See Guidance Note G7(h).]

7.5.16 All cables must be installed between purpose-made


termination points (switches, junction boxes, Distribution
Boards) and be terminated with purpose-made lugs,
crimps, screw connectors or other connectors. Joints
between

The Electricity Wiring Regulations 2007 73


such points are strictly prohibited. Termination points
and junction boxes must remain accessible to facilitate
future inspection, repair and alteration. See Guidance
Note G7(k).
[Note: terminations for MICC cables must be suitably sealed
against the ingress of moisture.]

7.5.17 Where cables are terminated at high temperature Appliances


their insulation must be suitable for the expected operating
temperature or, where necessary, shall be protected by
heat resistant material. See Guidance Note G7(b).

7.5.18 Armoured cables must be terminated using suitable cable


glands which incorporate a suitably rated Earth tag or
other purpose-made connection to the armouring of the
cable and to the metallic sheath if present. See Guidance
Note G7(i).

7.5.19 Cables must not be installed in lift shafts other than those
serving lift functions.
[Note: although a lift shaft may be a convenient means of
providing a cable route through a building this creates
unwarranted risk when accessing such Circuits for
maintenance and also provides a vulnerable route for the
propagation of fire.]
7
7.5.20 The colour identification for cables is given in
Appendix A8.
[Note: although the identification colours for cables has
recently been changed in European countries a similar change
is not currently proposed for Abu Dhabi Emirate. For fixed
wiring in an Installation the phase colours remain as red,
yellow and blue whilst neutral remains as black. However, for
flexible sheathed cables supplying single-phase Appliances
brown is used for live and blue is used for neutral – see
Appendix A8.]

74 The Electricity Wiring Regulations 2007


7.6 Final circuits

7.6.1 The sizing of Final Circuits must take into account the
diversity of use of Appliances and equipment as well as
possible increases in load requirements. See Guidance
Note G2 for advice on load diversity factors.

7.6.2 Radial Circuits should be provided to large Appliances,


particularly those in continuous or near continuous
operation, or those of importance for safety or other
priority functions within a Premises. Examples include
main water pumps, air conditioning units, water heaters,
room heating, fire or intruder alarms, cookers and ovens,
etc.

7.6.3 Ring Circuits should be provided to areas within a


property which can be most economically served by
several Appliances sharing the same cable feed, arranged
in a loop, from one circuit-breaker on the Final
Distribution Board. This is particularly suitable where
Appliances are expected to operate at diverse times of the

Componen
day. Ring Circuits would typically be installed in
bedrooms, living rooms, kitchens (except major
Appliances such as cookers), partitioned office areas, etc.

7.6.4 Circuits supplying a kitchen must not be used to supply


any other area. However, ceiling lighting Circuits from a 7
kitchen may be common to other areas.

7.6.5 For domestic Premises all Circuits supplying one room


must be on the same phase, other than for kitchens, and
for ceiling lighting.

7.6.6 Typical Radial and Ring Circuit arrangements for


domestic Premises are shown in Appendix A14.

The Electricity Wiring Regulations 2007 75


7.7 Busways, bus ducts and busbar risers

7.7.1 Busways, bus ducts, busbar risers or other similar systems


may be used in Premises for the supply of large loads
where they provide a more economic or practical option
than cables.

7.7.2 Busways, bus ducts and busbar risers shall comply with
the relevant reference standards given in Appendix A3.

7.7.3 Busways, bus ducts and busbar risers shall be totally enclosed
(non-perforated) for protection against mechanical
damage, moisture, dust and other environmental effects.

7.7.4 Busways, bus ducts and busbar risers shall not be located
in areas prone to mechanical damage or where they may
be exposed to hazardous materials, liquids or gases, unless
special precautions are taken.

7.7.5 Busways, bus ducts and busbar risers shall be located so


that they are accessible for future maintenance and repair
throughout their length. They shall not be installed in
habitable areas such as flats, offices, shops, etc (a separate
riser shaft or room must be provided).

7 7.7.6 Busways, bus ducts and busbar risers shall have neutral
conductors of equal size to the phase conductors and shall
have a dedicated Earth Conductor. The use of the metal
casing as an Earth Conductor shall not be permitted.

7.7.7 The current rating of busways, bus ducts and busbar risers
shall be based on the Connected Load of the relevant part
of the Installation being supplied. However, additional
diversity factors may be applied for high-rise buildings
or other large installations rather than taking the sum of
Connected Loads. Any applied diversity factors must be
justified and submitted with the design for approval by the
Distribution Company, see Regulation 3.2.

76 The Electricity Wiring Regulations 2007


7.7.8 Purpose made plug-in circuit-breaker units may be used
with busbar risers systems where they are mechanically
interlocked to prevent removal whilst energised. See
Guidance Note G3(a).

7.7.9 The number of busways, bus ducts or busbar risers


required for a high-rise building and the number of floors
served by each must be selected by taking due account of
the future accessibility, maintainability and safety of the
system, whilst limiting the extent of power outage to
serviced areas.
[Note: a typical arrangement may be to serve each 10 floors
of a 30 storey building by a separate bus riser; however, other
arrangements are not precluded.]

7.8 Distribution boards

7.8.1 All Distribution Boards must be factory assembled,


type-tested and comply with BS EN 60439.

Componen
7.8.2 Distribution Boards must be of robust construction,
capable of withstanding expected electrical, thermal, and
environmental stresses in normal service and during
faults.

7.8.3 Apparatus forming part of the assembly of Distribution


Boards shall have electrical isolation clearances sufficient to 7
withstand normal voltages, surge voltages and creepages
as defined in BS EN 60439-1.

7.8.4 Each Distribution Board must have a neutral bar which is


mounted on insulators and which has a sufficient number
of terminal points of adequate size for the largest cable
expected to be used.

7.8.5 Each Distribution Board must have an Earth bar which has
a means of connection to the incoming Earth Conductor
and cable gland of the incoming cable, see Appendix
A5(e) and A12(c).

The Electricity Wiring Regulations 2007 77


7.8.6 All Final Distribution Boards must have at least two
busbar sections (split busbars) so as to provide for different
levels of Earth Leakage Protection (e.g. 100 mA RCD and
30 mA RCD). See Appendix A12(c).
[Note: for additional levels of Earth Leakage Protection
individual RCBO devices may be provided for the relevant Final
Circuits.]

7.8.7 Other than for small 2-storey buildings each floor of


a Premises shall be provided with at least one Final
Distribution Board installed in an easily accessible
location.

7.8.8 The number of Final Distribution Boards and Sub


Distribution Boards provided in a Premises shall take into
account the future accessibility, maintainability and safety
of the system, whilst limiting the extent of possible power
outages to serviced areas.
[Note: to meet the above requirement Final Distribution Boards
should be limited to a maximum capacity of 14 ways 3-phase
i.e. 42 Circuit positions.]

7.8.9 Single-phase Distribution Boards may be permitted in a


Premises where adequate provision is made for balancing
the total load at the Supply Intake between the three
7 phases.
[Note: single-phase Distribution Boards would normally be
used for small load applications such as hotel rooms, garages,
small out buildings.]

7.8.10 The phase and neutral busbars in all Distribution Boards


shall be identified by the colours given in Appendix A8.

7.8.11 The phase and neutral conductors in all Distribution


Boards shall be of the same cross sectional area.

7.8.12 Neon indicators, voltmeters and ammeters must be


provided for Distribution Boards rated at 400 A and
above, and where

78 The Electricity Wiring Regulations 2007


reasonably practicable for other Distribution Boards.
[Note: where practicable, maximum demand meters and power
factor meters should also be provided]

7.8.13 All Distribution Boards must be provided with only


circuit- breakers (such as CBs, MCBs, MCCBs, RCDs,
etc) and shall not contain fuses of any kind, except for
capacitor banks. See Regulation 10.2.

7.8.14 All Distribution Boards must be installed in locations


easily accessible for inspection, operation and
maintenance, preferably at the entrance to the area they
serve. Such locations must be secured from unauthorised
interference.

7.8.15 Distribution Boards of rating 200 A and above shall be


installed in a dedicated room. See Appendix A12(b).

7.8.16 Distribution Boards shall not be installed in locations


where water is used (e.g. kitchens, bathrooms, pump

Componen
rooms), within 2 metres of any pipe or other source of
water, or in difficult-to-access positions (such as
stairways).

7.8.17 Distribution Boards must be provided with sufficient


numbers of Protective Devices so as to enable every
outgoing Circuit to be connected to an individual
Protective Device and shall include not less than 10% 7
spare Protective Devices or blank positions.

7.9 LV switchboards

7.9.1 Where prefabricated Distribution Boards of sufficient


rating are not available, LV switchboards, consisting of
cubicle panel switchgear, may be provided. LV switchboards
must consist of type-tested assemblies which satisfy the
requirements of BS 5486 or BS EN 60439.

The Electricity Wiring Regulations 2007 79


7.9.2 Switchboards must be located in a dedicated room to
provide for safe access and egress at all times, including
during maintenance, repair and replacement work.

7.9.3 LV switchrooms must meet the requirements of Supply


Intake rooms listed in Regulation 4.2. Typical layouts and
minimum space requirements for LV switchrooms are
given in Appendix A12(d).

7.9.4 Switchboards rated above 400 A must be provided with


instruments for voltage, current, maximum demand and
power factor measurement, as well as phase indicating
lamps.

7.9.5 Where more than one incoming supply cable is provided


at the Supply Intake these must be connected to separate
switchboards (or separate sections of the same
switchboard) which have the facility for interconnection
through a bus coupler circuit-breaker or switch. In order to
prevent parallel connection of the incoming supply cables
the bus coupler circuit-breaker or switch must be
interlocked to prevent its closure when both incoming
supply cables are live. Bus switches and circuit-breakers
must be capable of closure onto a fault unless interlocked
so as to only be operated whilst dead.
7
7.9.6 All busbars in switchboards must be tinned copper and
rigidly supported throughout their length. The neutral
and earth busbars must run throughout the length of the
switchboard. The neutral busbar must be of the same
cross- sectional area as the phase busbars.

7.9.7 The main incomer circuit-breaker(s) must be clearly


marked and left unlocked to allow immediate operation in
an emergency, see clause 4.3.3.

80 The Electricity Wiring Regulations 2007


Inspection, testing and
certification 8
8.1 Electrical installation certificates

8.1.1 Every new Installation shall, on completion and before


being energised, be inspected and tested by a Licensed
Contractor who shall duly complete the relevant test
reports and submit these to the Distribution Company
(with the exception of tests that can only be done after
energising).
[Note: see Regulation 3.4 for details of contractor licencing.]

8.1.2 In order to verify compliance with these Regulations


the Licensed Contractor shall complete and sign an
Electrical Installation Certificate in the format shown in
Appendix A20(a), as shall the designer and installer of the
Installation (may be the same person or company).

8.1.3 Two original copies of the Electrical Installation


Certificate and associated test results shall be provided,
one to the Customer or Owner of the Premises, and one to
the Distribution Company. An additional copy must be
affixed at the Main Distribution Board or Supply Intake
position, see Appendix A12(b).

8.1.4 The Distribution Company shall verify on site the test


results for Earth Resistance at the Main Earth Terminal
and inspect or test other items as deemed appropriate,
including as a minimum:

(a) connection of conductors;


(b) identification of conductors and labelling of
equipment;
(c) routing of cables and their protection against
mechanical damage;
(d) cross-sectional area of conductors for current-
carrying capacity and voltage drop;
(e) connection of single-pole devices for protection or
switching in phase conductors only;

The Electricity Wiring Regulations 2007 81


(f) correct positioning and connection of accessories
and equipment;
(g) presence of fire barriers and protection against
thermal effects;
(h) methods of protection against electric shock, both
Direct and Indirect Contact;
(i) inspection of integrity of Main Earth Conductors
and Earth Electrodes;
(j) presence and correct location of devices for
isolation; and
(k) measurement of Earth Fault Loop Impedance.

8.1.5 The Distribution Company may carry out intermediate


inspection(s) prior to the final inspection mentioned in
clause 8.1.4. This is to verify compliance of concealed
parts of the Installation (e.g. conduit, buried cables and
Earth Conductors).

8.1.6 Internal checks and inspection shall be carried out on a


10% sample of the Installation, relevant to the items listed
under clause 8.1.4.

8.1.7 After any extension or alteration to an electrical


Installation a Licensed Contractor is required to issue an
amended Electrical Installation Certificate, together with a
copy of the original certificate, and stating the details of
the work carried out, see Regulation 3.2 and 3.3.
8

82 The Electricity Wiring Regulations 2007


8.2 Routine inspection and testing

8.2.1 The responsibility for routine inspection and testing of


Electrical Installations lies with the Owner of the
Premises who shall request the services of a Licensed
Contractor at the intervals shown in the table below. The
Owner must also ensure that any necessary rectification
work is carried out.

Internal External
Installation Installation

Domestic 5 years 5 years

Non-domestic
3 years 3 years
(commercial, industrial, farms, etc)

Premises used by the public


(schools, hospitals, hotels, malls, 3 years 2 years
parks, wedding tents, mosques)

Special locations
1 year 1 year
(construction sites, swimming
pools and fountains, street lighting)

Inspectio
8.2.2 Electrical Installations which were constructed before the
date of commencement of these Regulations (clause 1.1.2)
shall be inspected and tested within the time indicated
above from the date of commencement.
8
8.2.3 Routine inspection and testing shall be recorded on the
standard forms shown in Appendices A20(b) – A20(d)
and shall include:

(a) continuity of Ring and Final Circuit conductors;


(b) continuity of Earth Conductors including
Equipotential Bonding Conductors;
(c) insulation resistance;

The Electricity Wiring Regulations 2007 83


(d) protection against Direct Contact;
(e) protection against Indirect Contact;
(f) polarity of Circuits;
(g) Earth Fault Loop Impedance;
(h) Earth Electrode Resistance; and
(i) operation of Earth Leakage Protection devices.
[Note: see Appendix A19(a) to A19(g) for relevant test
procedures.]

8.2.4 The continuity test shall be carried out with an instrument


having a no-load voltage between 4 V and 24 V d.c or
a.c. and a short-circuit current not less than 200 mA, in
accordance with the procedure in Appendix A19(d).

8.2.5 The insulation resistance tests between live conductors


and between each live conductor and Earth shall be
measured with a test voltage of 500 V d.c, in accordance
with the procedure in Appendix A19(f).

84 The Electricity Wiring Regulations 2007


Special locations and systems
9
9.1 Separated extra-low voltage (SELV)

9.1.1 SELV systems are used where an inherently safe system


of supply is required such that a breakdown of primary
insulation will not lead to the risk of electric shock. This
is achieved by electrical separation of the Final Circuit
from the source of energy, typically using a safety
isolating transformer, see illustration in Appendix A18(c).

9.1.2 For a Separated Extra-Low Voltage system the Final


Circuit voltage shall not exceed “extra-low voltage” i.e. 50
V a.c. or 120 V d.c. between conductors or to Earth.

9.1.3 The source of SELV power shall be provided by either:

(a) a safety isolating transformer complying with


BS 3535, in which there is no connection between
the output winding and the body or with the Circuit
Earth Conductor, if any; or
(b) a battery source.

9.1.4 All components of a SELV system (including conductors,


switches, relays, etc) shall be physically separated from those
of any other live system.

9.1.5 No Exposed-Metallic-Part of a SELV system shall be


connected to any of the following:

(a) Earth;
(b) any Earthed Metallic Part of another system or
Extraneous-Metallic-Part; or
(c) an Earth Conductor of any system.

9.1.6 Insulation against Direct Contact of the conductive parts


of a SELV system is required if the operating voltage
exceeds 12 V a.c. or 30 V d.c. Insulation is not required if
the operating voltage is at or below these values.

The Electricity Wiring Regulations 2007 85


9.2 Protective extra-low voltage (PELV)

9.2.1 A PELV system is one where the same provision for


electrical separation is provided as for SELV, i.e. between
the source of energy and the Final Circuit. However, in a
PELV system the connection to Earth of Exposed-
Metallic- Parts is permitted. See Appendix A18(d).

9.3 Bathrooms and similar locations

9.3.1 Special provisions are required for the protection against


electric shock of persons in locations containing a bath or
shower. Such provisions, as listed in the following
clauses, must also be applied in other similar situations
where persons are likely to be partly clothed and in
contact with water, with or without footwear.
[Note: similar locations would include washrooms, toilets,
wudu areas in mosques, etc. The requirements for swimming
pools are listed in Regulation 9.4.]

9.3.2 The following principal requirements must be met for


bathrooms and similar locations:

(a) all Final Circuits must be protected by an RCD


of residual current rating 30 mA and complying
with IEC 60898 or BS 3871. Such protection may
be grouped across several Circuits at the Final
Distribution Board;
(b) no socket-outlets are permitted except those
supplied by an isolating transformer and
complying with BS 3535 (e.g. ‘shaver’ socket-
outlet);
(c) all Appliances, Luminares and other Accessories must
9 have a minimum level of moisture ingress
protection of IPX4;
(d) Appliances, Luminares or other Accessories may
not be installed within Arm’s Reach from a bath,
shower or similar facility. However, such items are
permitted

86 The Electricity Wiring Regulations 2007


within the room containing a bath or shower at a
distance greater than Arm’s Reach from the bath,
provided that the requirements of clauses 9.3.2(a)
to 9.3.2(c) above are complied with. In addition, all
switches associated with such equipment must be
installed outside the bathroom or provided with a
cord-pull switch; and
(e) Appliances, Luminares or Accessories which are
within Arm’s Reach from a bath, shower or similar
facility must be supplied by SELV or PELV and
have a minimum level of ingress protection of
IPX7. Underwater lighting must be supplied by
SELV at a maximum voltage of 12 V a.c. or 30 V
d.c.
[Note: items which are within a distance of Arm’s Reach but are
inaccessible to persons need not comply with clause 9.3.2(e).
For example, water pumps installed under a bath which are not
accessible without removal of covers requiring a tool.]

9.3.3 The provision of Earthed Equipotential Bonding is not


required in a bathroom or similar location where the
Installation is classified as an Earth Leakage Protected
System, as described under Regulation 5.4. In particular,
the requirement for Earth Leakage Protection on Final
Circuits, along with back-up earth fault protection at the
Supply Intake must be met. Earthed Equipotential
Bonding and Supplementary Equipotential Bonding are
required where back-up earth fault protection is not
provided, even where RCD protection has been provided
at the Final Distribution board supplying the bathroom or
Special

similar location.

The Electricity Wiring Regulations 2007 87


9.4 Swimming pools

9.4.1 The requirements for protection against electric shock for


swimming pools are similar to those of bathrooms, with
some exceptions, as follows:

(a) all Final Circuits must be protected by an RCD


of residual current rating 30 mA and complying
with IEC 60898 or BS 3871. Such protection may
be grouped across several Circuits at the Final
Distribution Board. Exceptions may be allowed for
high current applications where RCD protection
of 100 mA residual current rating may be allowed,
but only where such equipment is out of reach of
persons;
[Note: an example of Circuits where 30 mA RCD protection
may not be practical is floodlighting or large water
pumps. Such items must be out of reach of any person
using the swimming pool or any associated washing
areas.]

(b) no socket-outlets are permitted within Arm’s Reach


from a swimming pool. Socket-outlets may be
provided outside this distance for purposes such as
cleaning of the pool, which must have a minimum
ingress protection of IPX6 and must have an
integral RCD of residual current rating 30 mA, see
Guidance Note G7(c);

(c) all Appliances, Luminares and other Accessories must


have a minimum level of moisture ingress
protection of IPX4;

(d) no Appliances, Luminares or other Accessories may


be installed within Arm’s Reach from a swimming
9 pool. However, such items are permitted within the
swimming pool area (but not shower room area) at
a distance greater than Arm’s Reach from the pool,
provided that the requirements of clauses 9.4.1(a) to

88 The Electricity Wiring Regulations 2007


9.4.1(c) above are complied with; and

person;

The Electricity Wiring Regulations 2007 89


(e) Appliances, Luminares or Accessories which are
within Arm’s Reach from a swimming pool must be
supplied by SELV or PELV and have a minimum level
of ingress protection of IPX7. Underwater lighting
must be supplied by SELV at a maximum voltage of
12 V a.c. or 30 V d.c.

9.4.2 The provision of Earthed Equipotential Bonding is not


required in swimming pools and associated wash facilities
where the Installation is classified as an Earth Leakage
Protected System, as described under Regulation 5.4. In
particular the requirement for Earth Leakage Protection on
Final Circuits, along with back-up earth fault protection at
the Supply Intake, must be met. EEB and Supplementary
Equipotential Bonding will be required where back-up
earth fault protection has not been provided, even where
RCD protection has been provided at the Final
Distribution Board supplying the swimming pool and
associated areas.

9.5 Water fountains

9.5.1 The requirements for protection against electric shock for


water fountains are similar to those required for
swimming pools, with some exceptions, as follows:
[Note: it is assumed that persons may enter a water fountain for
the purpose of maintenance, or other reason, and the exposure
to electric shock is therefore similar to that of swimming pools.]
Special

(a) All Final Circuits must be protected by an RCD


of residual current rating 30 mA and complying
with IEC 60898 or BS 3871. Such protection may
be grouped across several Circuits at the Final
Distribution Board. Exceptions may be allowed for 9
high current applications where RCD protection of
100 mA residual current rating may be allowed, but

88 The Electricity Wiring Regulations 2007


only where such equipment is out of reach of any

person;

The Electricity Wiring Regulations 2007 89


[Note: an example of Circuits where 30 mA RCD protection
may not be practical is floodlighting or large water
pumps. Such items must be out of reach of persons whilst
standing within the water fountain.]
(b) no socket-outlets are permitted within Arm’s Reach
from a water fountain. Socket-outlets may be
provided outside this distance for purposes such as
cleaning of the water fountain, which must have a
minimum ingress protection of IPX6 and must have
an integral RCD of residual current rating 30 mA,
see Guidance Note G7(c);
(c) all Appliances, Luminares and other Accessories must
have a minimum level of moisture ingress
protection of IPX4;
(d) no Appliances, Luminares or other Accessories
may be installed within Arm’s Reach from a water
fountain. However, such items are permitted at a
distance greater than Arm’s Reach from the water
fountain, provided that the requirements of clauses
9.5.1(a) to 9.5.1(c) above are complied with; and
(e) Appliances, Luminares or Accessories which are
within Arm’s Reach from a water fountain must be
supplied by SELV or PELV and have a minimum level
of ingress protection of IPX7. Underwater lighting
and submerged water pumps must be supplied
by SELV at a maximum voltage of 12 V a.c. or
30 V d.c.

9.5.2 The provision of Earthed Equipotential Bonding is not


required for water fountains where the Installation is
classified as an Earth Leakage Protected System, as
described under Regulation 5.4. In particular the
requirement for Earth Leakage Protection on Final
9 Circuits, along with back-up earth fault protection at the
Supply Intake, must be met. EEB and Supplementary
Equipotential Bonding will be required where back-up
earth fault protection has not been provided, even where
RCD protection has been provided at the Final
Distribution Board supplying the water fountain and
associated areas.

90 The Electricity Wiring Regulations 2007


9.6 Construction sites and outdoor supplies

9.6.1 This Regulation applies to construction sites and other


permanent or temporary outdoor supplies such as
exhibitions, wedding tents, parks, gardens, etc.

9.6.2 Due to the additional risks of damage and interference to


outdoor installations the following precautions should be
catered for in the design and construction of such systems:

(a) all cables which are not installed in conduit or trunking


must be armoured and adequately protected against
accidental or deliberate interference by persons, and
against the effects of weather;
[Note: type HO7 RN-F braided or armoured cables
complying with BS 6007 are recommended.]
(b) outdoor Electrical Installations must have a
minimum ingress protection level of IP53 and
switchgear assemblies must comply with BS 4363 and
BS EN 60439-4;
(c) cables passing on or over walkways and access
roads must be adequately enclosed to avoid Danger.
Buried cables must be installed so as to afford
adequate protection against damage, see Guidance
Note G6;
(d) particular attention should be given to the location,
signing and protection of equipment where the
public may have access, in particular children;
Special

(e) equipment should be located and adequate notices


displayed so that emergency disconnection of the
electricity supply can be effected without delay.
Locking arrangements should be such that these can
be removed in an emergency (e.g. panic bar or keys
available in break-out box); 9
(f) the requirements for periodic inspection and testing
must be strictly complied with (Regulation 8.2); and
(g) an Earth Leakage Protected System must be
provided in line with Regulation 5.4. In addition,
outdoor

The Electricity Wiring Regulations 2007 91


socket-outlets must be provided with integral RCD
protection with a residual operating current of 30
mA or less.
[Note: water coolers and drinking fountains must be
provided with individual RCD protection, in addition to
that provided at the Final Distribution Board.]

9.6.3 Consideration should be given to the use of a reduced


voltage supply (RLV) for portable tools where there is a
high exposure to potential damage, or where persons are
required to operate such equipment in confined spaces or
other hazardous circumstances.
[Note: RLV may be preferred on construction sites compared
with supply by ELPS to avoid nuisance tripping and the
potential failure of RCDs in harsh outdoor environments.]

9.7 Street lighting

9.7.1 The detailed installation requirements for supplies to street


lighting and other street equipment (traffic signals, signs,
etc) shall be specified by the Distribution Company.

9.7.2 Protection against electric shock for street lighting shall


be provided by either an Earth Leakage Protected System
(Regulation 5.4) or by an Earthed Equipotential Bonded
System (Regulation 5.5). In the latter case, the street light
column or other structure shall be connected to a means
of Earthing, which will normally be from the Distribution
Company supply cable.

9.7.3 Temporary supplies taken from street lights, such as for


decorative lighting or signboards, must be provided with
9 Earth Leakage Protection using RCDs of residual current
rating no greater than 30 mA where within reach of
persons, or 100 mA where not within reach of persons.
Time delayed devices may be used to avoid nuisance
tripping. Alternatively, such supplies may be provided by
SELV or RLV.

92 The Electricity Wiring Regulations 2007


Capacitors and motors
10
10.1 General requirements

10.1.1 The power factor of every Installation shall be controlled


to between 0.9 lagging and unity by means of power
factor correction capacitors. These may be connected so as
to provide individual compensation, group compensation,
or centralised compensation.

10.1.2 Power factor correction capacitors shall normally be of


dry or oil-filled, encapsulated, sealed type. The use of
oil containing PCB (poly-chlorinated biphenyls) is strictly
prohibited.

10.1.3 Power factor correction capacitors shall be provided with


a means of prompt discharge on disconnection of the
supply voltage. The discharge Circuit shall be
permanently or automatically connected to the capacitor.
Manual means of switching or connecting the discharge
circuit is not permitted.

10.1.4 Air conditioning units, motors, large electrical machines,


fluorescent or discharge lighting, etc, shall be provided
with integral power factor correction.

10.1.5 For group compensation, automatically regulated


capacitor banks shall be used which provide, as far as
reasonably practicable, a smoothed power factor
throughout the range of operation. The rating of each
capacitor step shall be such that the initial steps have less
kVAr rating and the rating of subsequent steps increase
progressively to the desired maximum kVAr.

10.1.6 For induction motors, the capacitor rating must not exceed
90% of the no-load reactive power of the motor.
[Note: this is required in order to avoid the high overvoltage
across the terminals due to the occurrence of self excitation on
run-down condition of the motor.]

The Electricity Wiring Regulations 2007 93


10.1.7 The occurrence of harmonics while employing variable
speed drives, welding machines or similar devices in
Circuits can lead to disturbances in the system and may
cause capacitor failure. To minimise this risk harmonic
filters must be employed in series with capacitors.

10.2 Specifications for capacitors

10.2.1 Capacitors shall be capable of continuous operation


provided that none of the following limitations is
exceeded:

(a) 135% of the rated reactive power;


(b) 110% of the rated voltage (rms), including
harmonics but excluding transients; and
(c) 180% of the rated current (rms), including
fundamental and harmonic current.

10.2.2 Built-in discharge resistors for capacitors shall be sized to


ensure safe discharge of the capacitor to less than 50 V in
one minute after a switch off.

10.2.3 Each capacitor shall be provided with a permanent


nameplate, which includes the following information:

(a) name of the Manufacturer;


(b) serial No;
(c) year of Manufacture;
(d) rated reactive power;
(e) rated voltage (rms);
(f) number of phases;
(g) rated frequency;
(h) statement of discharge device;
10 (i) short-circuit current; and
(j) statement of liquid fill (if any).

94 The Electricity Wiring Regulations 2007


10.2.4 Capacitors shall be able to withstand up to 30 times I n
caused by harmonics.

10.2.5 Capacitors shall have provision for effective Earth


connection of the case to the capacitor mounting frame
and to the Circuit Earth Conductor.

10.2.6 Capacitors and related components such as regulators,


indicating instruments, contactors, etc, shall be capable of
withstanding local environmental conditions.

10.2.7 Contactors shall be designed for capacitive switching and


be able to withstand switching surges. Contactors shall be
rated for 1.5 to 1.8 times the normal rated current of the
capacitor and shall isolate all three phases on switch off.

10.2.8 Each capacitor step shall be protected by means of HRC


fuses (current limiting type).

10.2.9 The capacitor panel must be provided with a suitably rated


main incomer isolating switch. This shall be a three-pole
isolator or MCCB as the case may be. The handle of the
incomer isolator shall be interlocked with the door to
ensure that the capacitor bank is de-energized when the
door is open.

10.2.10 A capacitor bank shall not be a part of the motor control


centre, main LV panel or sub-main panel, but it shall be
accommodated in a separate cubicle.
Capacitors and

10

The Electricity Wiring Regulations 2007 95


10.2.11 Capacitor banks shall conform to the latest relevant
international standards, including the following:

Relevant international standards for capacitors

LV switchboard IEC 60439-1

Degree of protection IEC 60529

LV circuit-breaker and disconnector IEC 60947 (1-5)

Power factor correction capacitors IEC 60831 (1-2)

Power factor regulator IEC 60664 and IEC 1010-1

Capacitor switching contactors IEC 60070 and IEC 60831

Detuning reactors IEC 60289 and IEC 60076

10.3 Electric motors and starters

10.3.1 The installation of electric motors supplied from the LV


distribution system is permitted up to a maximum of
5 HP (3.7 kW) for single-phase and 150 HP (110 kW) for
three-phase. Where it is proposed to install more than one
motor of rating 150 HP the relevant diagrams, operation
information, protection arrangements, etc. must be
provided to the Distribution Company to gain approval for
connection.

10.3.2 All electric motors shall be adequately protected against


overload, short-circuit, loss of one or more phases and
voltage dips, etc. as appropriate for each application.
Emergency fire fighting motors or pumps are excluded
from this clause as they may be required to operate to
failure without the provision of protective devices.
[Note: motor control and protection equipment must be
arranged so that re-starting is not automatic after automatic
1 tripping due to a fault or other disturbance mentioned in clause

96 The Electricity Wiring Regulations 2007


10.3.2 above.

The Electricity Wiring Regulations 2007 97


It is recommended that air conditioning units above 3kW should
be provided with under-voltage tripping relays operating at
75% of the nominal supply voltage and with an auto-reset timer
set at between 5 and 10 minutes.]

10.3.3 All electric motors above 5 HP must be provided with


protection against mechanical overload.

10.3.4 All single-phase motors above 1 HP and three-phase


motors above 3 HP shall be provided with current limiting
starting equipment to effectively keep the starting current
within the following limits:

Rating of motor Maximum permissible


starting current

1 HP to 5 HP 5 x full-load current

Above 5 HP and up to 50 HP 2 x full-load current

Above 50 HP and up to 150 HP 1.5 x full-load current

[Note: any form of motor starter may be used to achieve the


values in the table above, including direct on-line starter,
primary resistance starter, auto transformer or electronic soft
starter.]

10.3.5 Wiring and control diagrams must be permanently fixed


adjacent to motors.

10.4 Standby generators


Capacitors and

10.4.1 Installation and connection of standby generators in any


Installation, for the purpose of maintaining power in the
case of a failure of the incoming supply, shall be
permitted only with the prior approval of the Distribution
Company.

10.4.2 The changeover circuit-breaker shall have 4 poles for a


three-phase generator and 2 poles for a single-phase

96 The Electricity Wiring Regulations 2007


generator, to ensure that all live and neutral conductors are 10
disconnected at the same time.

The Electricity Wiring Regulations 2007 97


10.4.3 The installation and changeover arrangements must ensure
that there is no possibility of paralleling the generator and
incoming mains supply. If paralleling arrangements are
required these must be specifically assessed and approved
by the Distribution Company. The requirements for
such arrangements (including earthing arrangements) are
provided in the Electricity Distribution Code – Annex 1:
“Engineering Recommendation No. 3 – Connection of
Embedded Generation Plant up to 5 MW”.

98 The Electricity Wiring Regulations 2007


Appendices

Capacitors and Motors

The Electricity Wiring Regulations 2007 99


1

100 The Electricity Wiring Regulations 2007


Appendices
A
A1. Glossary of terms and abbreviations 105

A2. Recomended books and references 108

A3. Reference standards 111

A4. Legal references


(a) List of regulations and clauses which do
not apply to existing installations 114
(b) Relevant extracts of Law No (2) of 1998 116

A5. Earthing
(a) Distribution company earthed system (TN-S) 123
(b) Customer earthed system (TT) 124
(c) Distribution company earthed system with
additional earth (TN-S-TT) 125
(d) Earth electrode pit and standard labels 126
(e) Main earth terminal (MET) at main
distribution board (MDB) 127
(f) Main earth conductors (MEC) and circuit earth
conductors (CEC) 128
(g) Components of earth fault loop impedance 129
(h) Earth fault loop impendance values required for
MCBs (at 230 V) 130
(i) Resistance per metre of copper conductors for
calculation of R1+R2 131
(j) Sizing of earth conductors and equiptential bonding
conductors 132
(k) Minimum number of earth electrodes 134
(l) Mandatory connections to earth
conductors 135

The Electricity Wiring Regulations 2007 101


(m) Residual operating current settings for RCDs
and ELP devices 136

A6. MBC characteristics


(a) Time-current characteristic of MCBs as multiple
of rated current 138
(b) Time-current characteristic of Type B MCBs 139
(c) Time-current characteristic of Type C MCBs 140
(d) Time-current characteristic of Type D MCBs 141
(e) Typical energy let-through characteristics
of MCBs 142
(f) MCBs selection criteria 143
(g) Internal construction of MCB 145

A7. Current ratings for cables


(a) Current ratings for PVC single core
cables (non-armoured) 146
(b) Current ratings for PVC multi-core
cables (non-armoured) 147
(c) Current ratings for PVC multi-core
cables (armoured) 149
(d) Current ratings for thermo-setting multi-core
cables (armoured) 150
(e) Current ratings for MICC cable 151
(f) Cable ratings and voltage drop for flexible cords 152
(g) Temperature correction factors for cables 153
(h) Grouping factors for cables 154

A8. Colour identification for cables 155

A9. Capacity of conduits and trunking 156

102 The Electricity Wiring Regulations 2007


A10. IP coding for ingress protection 157

A11. Standard wiring diagram symbols 158

A12. Supply intake


(a) Danger of death sign 160
(b) Typical layout of supply intake room 161
(c) Typical layout of final distribution board (FDB)
and RCD label 162
(d) Typical layout of LV switchroom 163

A13. Boundary of customer connection point


and scope of the Regulations 164

A14. Typical layout for ring circuits and


radial circuits 165

A15. Minimum number of socket-outlets and


connection points 166

A16. Mounting height for accessories


and socket-outlets 167

A17. Plugs and socket outlets


(a) Approved and prohibited plugs and
socket-outlets (domestic) 168
(b) Industrial plugs and socket-outlets 169
(c) BS 3535 shaver socket-outlets for bathrooms 170

A18. Special systems


(a) Class I equipment (earthed metallic parts) 171
(b) Class II equipment (double insulated) 172
(c) Separated extra-low voltage (SELV) supply 173
(d) Protective extra-low voltage (PELV) supply 174

The Electricity Wiring Regulations 2007 103


(e) Reduced low voltage (RLV) supply 175

A19. Test procedures


(a) Measurement of earth electrode resistance 176
(b) Measurement of external earth fault loop
impedance 177
(c) Measurement of internal earth fault loop
impedance 178
(d) Circuit continuity tests 179
(e) Circuit polarity tests 180
(f) Insulation resistance tests 181
(g) Sequence of testing for new installations 182

A20. Forms and certificates


(a) Electrical Installation certificate 183
(b) Inspection report (front) 184
(c) Inspection report (back) 185
(d) Installation testing report 186
(e) Load distribution schedule 187

104 The Electricity Wiring Regulations 2007


A1. Glossary of terms and abbreviations

A Amps or Amperes A1
a.c. alternating current
ADWEA Abu Dhabi Water and Electricity Authority
The Association of Short-circuit Testing Authorities
AS (UK)
BS British Standard
British Standard which has been published under
BS the European Normalisation procedure
BSI British Standards Institute
CB Circuit-Breaker
CCP Customer Connection Point (see definitions)
CEC Circuit Earth Conductor (see definitions)
Circuit Protective Conductor (see definition
C
for
CEC)
d.c. direct current
Earth Continuity Conductor (see definition for
E CEC)
EEB Earthed Equipotential Bonding (see definitions)
Earthed Equipotential Bonded System (see
EE definitions)
E/F Earth Fault (protective device)
ELCB Earth Leakage Circuit-Breaker (see definitions)
ELP Earth Leakage Protection (see definitions)
ELV Extra-Low Voltage (see definitions)
EN European Normalisation standard document
ELPS Earth Leakage Protected System (see
definitions) ESMA Emirates Standardisation & Metrology
Authority FDB Final Distribution Board (see definitions)
HP Horse-Power (= 0.746 kW)

The Electricity Wiring Regulations 2007 105


A1. continued...

A1 HRC High Rupture Capacity (fuse)


HV High Voltage (see definitions)
IEC International Electrotechnical Commission
Nominal current rating or current setting of a
I
n Protective Device
kA kilo-Amps
KEMA Testing Laboratory of Netherlands
kV kilo-Volts
LV Low Voltage (see definitions)
m metres
MCB Miniature Circuit-Breaker
MCCB Moulded Case Circuit-Breaker
MDB Main Distribution Board (see definitions)
MEC Main Earth Conductor (see definitions)
MET Main Earth Terminal (see definitions)
MICC Mineral Insulated Copper-Clad (type of
cable) ms milli-seconds
NSAI National Standards Authority of Ireland
˚C degrees Celsius
PELV Protective Extra-Low Voltage (see definitions)
PVC Poly-vinyl Chloride (insulation for LV cables)
r.m.s root-mean-square (value of voltage, current etc)
Residual Current Breaker (With) Overcurrent
RCB Protection
RCCB Residual Current Circuit-Breaker
RCD Residual Current Device (see definitions)
RLV Reduced Low Voltage (see definitions)

106 The Electricity Wiring Regulations 2007


A1. continued...

Table
s of HE
seconds A1
S cross-sectional area (of conductors, mm*)
SDB Sub Distribution Board (see definitions)
SELV Separated Extra-Low Voltage (see
definitions)
a Distribution Company earthed Installation (see
TN definitions)
a Distribution Company earthed Installation with
TN-S- additional Customer Earths (see definitions)
TT a Customer Earthed Installation (see definitions)
Uo nominal phase voltage
WED Water and Electricity Department (Abu Dhabi)
Ze External Earth Fault Loop Impedance
Zs Total Earth Fault Loop Impedance (see definitions)

Z
R1+R2 Internal Loop Impedance (R1 = resistance of circuit
conductor, R2 = resistance of earth conductor)

The Electricity Wiring Regulations 2007 107


A2. Recomended books and references

A2 Books:

(1) Requirements for Electrical Installations (BS 7671: 2001)


The Institution of Engineering and Technology (formerly the
Institution of Electrical Engineers)

(2) IEE Guidance Note 8 - Earthing & Bonding


The Institution of Engineering and Technology

(3) IEE Guidance Note 7 – Special Locations


The Institution of Engineering and Technology

(4) IEE Guidance Note 5 – Protection Against Electric Shock


The Institution of Engineering and Technology

(5) Exam Success – The IEE Wiring Regulations 2381


The Institution of Engineering and Technology,
City & Guilds

(6) The IEE On-site Guide to BS 7671:2001


The Institution of Engineering and Technology

(7) The Electricians Guide – 8th Edition


John Whitfield, EPA Press

(8) Testing Electrical Installations


A Hinsley, Castleknight Publications

(9) Advanced Testing Techniques


A Hinsley, Castleknight Publications

(10) Inspection, Testing and Certification


The Electrical Safety Council (NICEIC)

(11) Snags and Solutions Part 1 – Earthing & Bonding


The National Inspection Council for Electrical Installation
Contracting (NICEIC)

(l2) Snags and Solutions Part 2 – Wiring Systems


The National Inspection Council for Electrical Installation
Contracting (NICEIC)

108 The Electricity Wiring Regulations 2007


A2. Continued...

(13) Domestic Electrical Installation Guide A2


The National Inspection Council for Electrical Installation
Contracting (NICEIC)

Regulations:

(14) ADWEA Wiring Rules and Regulations for LV


Installations 2003, Abu Dhabi Water and Electricity
Authority

(15) Regulations for Electrical Installation Works 1980


Water and Electricity Department (WED) of Abu Dhabi

(16) The Earth Leakage Protection Regulations 2001


The Regulation and Supervision Bureau

(17) Regulations for Electrical Installations 1997


Dubai Electricity Authority

(18) Rules and Regulations of Electrical Connections


Sharjah Electricity and Water Authority

(19) The Australian & New Zealand Wiring Rules


AS/NZS 3000:2000
Standards Australia/Standards New Zealand

(20) The Electricity Safety (Installations) Regulations 1999


Government of Victoria (Australia)

(21) The Electricity Safety (Network Assets) Regulations 1999


Government of Victoria (Australia)

(22) Industry Standard for Electrical Installations on


Construction Sites Office of the Chief Electrical Inspector,
Victoria (Australia)

(23) New Zealand Code of Practice for Homeowner /


Occupier’s Electrical Wiring Work,
Energy Safety Service, Wellington, New Zealand

(24) Code of Practice for Safe Electrical Work


Office of the Chief Electrical Inspector, Victoria (Australia)

The Electricity Wiring Regulations 2007 109


A2. Continued...

A2 (25) The Electricity Safety, Quality and Continuity


Regulations (2002)
Her Majesty’s Stationary Office, UK

(26) The Plugs and Sockets etc. (Safety) Regulations 1994


Her Majesty’s Stationary Office, UK

(27) The Low Voltage Electrical Equipment (Safety) Regulations


1989 (Adoption of the Low Voltage Directive No.
73/23/EEC)
Her Majesty’s Stationary Office, UK

(28) The Electrical Equipment (Safety) Regulations 1994


Her Majesty’s Stationary Office, UK

Reference Papers:

(29) Cahier Technique no. 172 – Earthing Systems in LV


B Lacroix, R Calvas, Schneider Electric

(30) Cahier Technique no. 173 – Earthing Systems Worldwide


B Lacroix, R Calvas, Schneider Electric

(31) Neutral Earthing in LV Networks


A Robert, J Hoeffelman, CIRED Conference June 2001

(32) Plugs and Sockets Around the World


Conrad H. McGregor, World Standards

(33) The Distribution Code – Annex 1 – E/R 1 – Limits


for Harmonics in the Electricity Supply System
Approved by the Regulation and Supervision Bureau

(34) The Distribution Code – Annex 1 – E/R 7 – Limits for Voltage


Fluctuations in the Electricity Supply System
Approved by the Regulation and Supervision Bureau

(35) The Distribution Code – Annex 1 – E/R 10 – Limits


for Voltage Unbalance in the Electricity Supply System
Approved by the Regulation and Supervision Bureau

(36) Designing for Low Resistance Grounding


Lightning Eliminators & Consultants, Inc

110 The Electricity Wiring Regulations 2007


A3. Reference standards

A3
Components BS IEC

Cables
Power & lighting (70˚C PVC,
6004 502
thermoplastic)
Power and lighting (90˚C rubber,
6007, 7889
thermosetting)
Mineral insulated (copper-clad) 6207 702
Flexible cables & cords (domestic) 6500 227
Flexible cables & cords (industrial) 7919 245
Flexible cables (high temperature) 6141
Armoured cables (70˚C PVC,
6346
thermoplastic)
Low smoke (90˚C rubber, 7486, 7211,
thermosetting) 6724, 7629
Armoured cables (90˚C rubber,
5467
thermosetting)
Switchgear and control wiring 6231
Flexible cables for lifts 6977
Cable glands, crimp connectors 6121, 4579
Conduits & trunking
4568, 60423*,
Steel 423, 614
50086*, 31
PVC 4607
Flexible Steel 731
Cable tray 61537*
Trunking 4678
Electrical accessories
General 5733
Ceiling roses 67
Cooker Control Units 4177

The Electricity Wiring Regulations 2007 111


A3. Continued...

Components BS IEC

Accessories continued...
Household Appliances 3456, 60355*
546, 196, 1363,
Plugs & Socket-outlets (domestic)
4573
Plugs & Socket-outlets (industrial) 4343, 60309*
Switches (domestic) 3676, 60669*
Lighting 4533, 60598*
Emergency lighting 5266
Signs and discharge lighting 559
3535, 60742*,
Isolating (safety) transformers
61558*
LV switchgear & assemblies
General 60439*, 5486 439
Contactors & motor starters 60947* 947
Circuit-Breakers (MCB, MCCB) 60898*, 3871 898
4293, 61008*,
Circuit-Breakers (RCD, RCBO) 755
61009*
88, 1361,
Fuses
60269*
Busbar trunking systems 60439-2 439-2
General
Fire / combustibility test 476, 6458
Degrees of protection & ingress 60529* 529
Assemblies for construction Sites 4363 364-7-704
5345, 60079*,
Hazardous areas
50014*, 5501
Lightning protection 6651
Earthing 7430, 951, 4444 364-5-54
Wiring diagram symbols 60617*
A3 Identification and marking of the
60446*
man-machine interface

112 The Electricity Wiring Regulations 2007


A3. Continued...

Note: 1: British Standards marked with an asterix * are also issued as European A3
Standards under the same number (labelled as BS EN).

Note: 2: For compliance requirements under the Regulations see clause 3.1.2
and 3.1.4.

British Standards are issued by the British Standards Institute (BSI), a


UK National Standards body. The UK Wiring Regulations (BS 7671)
are published jointly by BSI and the IET (formerly known as the IEE).
The BSI represents the UK in international standards work through the
British Electrotechnical Committee (BEC) which is a member of the
International Electrotechnical Commission (IEC) and also a member
of the European Committee for Electrotechnical Standardisation
(CENELEC). There are 24 member countries of CENLEC (formed
in 1973) whose role is to prepare standards for the European market.
CENELEC issues ‘EN’ standards which are adopted by the member
countries, and ‘HD’ standards which are adopted in their general
technical content by member countries. The IEC (formed in 1906) has
48 member countries and IEC standards may be adopted voluntarily
by any country.

The Electricity Wiring Regulations 2007 113


A4(a) List of regulations and clauses which do
not apply to existing installations

A4(a) The Electricity Wiring Regulations are effective from 1 January 2008.
For any installations which were constructed prior to this date, the
following Regulations and clauses either:

(a) do not apply; or


(b) shall apply by 1 January 2010, or the date of the next
inspection or re-certification, whichever is the earlier.

Clause or Regulation Reason Application


Clause 3.1.4 Installation components Does not apply
to meet international retrospectively (see also
standards Clause 3.3.3 referring
to repairs to existing
installations)
Clause 3.5.6, Requirement for Earth ELP is a requirement
Clause 5.3.4, Leakage Protection from 1 January 2008 for
Clause 5.3.5, (ELP) and/or Earthed all Final Circuits where
Equipotential Bonding Appliances may be used
(EEB) by persons (see note 1);
the requirement for
ELP or EEB at the
main Supply Intake
shall be
met by 1 January 2010
Regulation 3.6, Requirement for Shall be met by
Clause 5.4.8, labelling of parts of the 1st January 2010,
Clause 6.5.3 Installation or at the date of
the next
inspection, whichever is
the earlier
Clause 4.2.9 Emergency lighting in Does not apply
Supply Intake rooms retrospectively.
Clause 7.1.1 Prohibition of BS 546 Does not apply
plugs and socket-outlets retrospectively but it
in domestic premised is recommended to
replace BS 546 socket-
outlets with BS 1363
type

114 The Electricity Wiring Regulations 2007


A4(a) Continued ...

Clause / Regulation Reason / Comment Application A4(a)


Clause 7.8.6 Final Distribution Boards Does not apply
to have split busbars to retrospectively if a
allow for minimum of 2 single RCD of residual
RCDs operating current
100 mA is fitted to
cover
the whole DB.
Clause 9.3.2(a) 30 mA Earth Leakage Does not apply
Protection for all retrospectively where
bathroom Circuits. Final Circuits are
covered by 100 mA
RCD protection

Note 1: The requirement for Earth Leakage Protection was introduced in Abu
Dhabi Emirate in 2001 by implementation of the Earth Leakage Protection
Regulations (issued by the Bureau). The Electricity Wiring Regulations
reiterate this same requirement and replace the ELP Regulations.

The Electricity Wiring Regulations 2007 115


A4(b) Relevant extracts of Law No (2) of 1998

A4(b) Relevant Extracts of Law No (2) of 1998 Concerning the


Regulation of the Water, Wastewater and Electricity Sector
(as amended by Law No (19) of 2007)

Article (54) - General Duties

The Regulation and Supervision Bureau shall have the duty to


exercise its functions under this Law in the manner which it considers
best calculated to –

(1) ensure the security of the supply of water and electricity in


the Emirate;

(2) ensure the connection and supply of water and electricity to


all consumers on reasonable demand;

(3) ensure the availability of health and safety guidance in


relation to water and electricity supply to the public;

(6) have special regard to the interestes of those persons whose


lives may be endangered by the lack of potable water and/or
electricity and others with special needs in connection with
the cost and method of supply of water and electricity and the
use of appliances and fitting;

Article (55) - Functions of the Regulation and Supervision


Bureau

(3) the establishment, maintenance, review and amendment as


appropriate of technical and performance standards for the
water and electricity sector and the monitoring and
enforcement of compliance with such technical standards;

Article (60) - Inspectors

(1) The Regulation and Supervision Bureau may appoint qualified


persons whose duties shall include duties to –
...
(c)inspect and test, where required, such plant and equipment
at the consumer's premises;

116 The Electricity Wiring Regulations 2007


A4(b) Continued...

Article (62) - Powers to make regulation A4(b)


The Regulation and Supervision Bureau may, in consultation with the
Authority, make such regulations as it sees fit for the purposes set out
in Articles (63) and (68) of this Law1.

Article (63) - Supply regulations

Regulations made pursuant to Article (62) of this Law may be made


for the following purposes, namely to–

(1) secure regular and efficient supplies of water and electricity;

(2) protect the general public from danger related to electrical and
water works and installations;

(3) eliminate or reduce the risk of personal injury;



(8) ensure water and electricity fittings installed and used by persons
to whom water and electricity are to be supplied are safe; and

(9) promote the conservation of water and the efficient use of


water and electricity.

Article (65) - Contents of supply regulations - specific

Regulations made under Article (62) of this Law may–

(1) prohibit transmission or supply in specified circumstances;

(2) require notification of accidents, failures of supply and/or


transmission or distribution facilities;

(3) require plans, maps etc to be kept and made available for
inspection and copying;

(4) relieve the Abu Dhabi Water and Electricity Company and
classes of licensed operators specified in the regulations
from obligations to supply water and electricity in specified
circumstances;
1
Article 68 relates to Street Works and Access Regulations

The Electricity Wiring Regulations 2007 117


A4(b) Continued...

A4(b) (5) require compliance with notices served by the Regulation and
Supervision Bureau which –

are intended to prevent or end a breach of regulations made


under Chapter Three of Part Four of this Law; or

eliminate/reduce risk of personal injury or property damage


or interference with property;

(6) provide for deemed compliance with technical standards and


requirements;

(7) provide for exemptions from the requirements of regulations


made under Chapter Three of Part Four of this Law;

(8) restrict or require the use of certain, products, substances


or processes or forbid unapproved substances, products and
processes;

(9) require substances, products and processes to comply with


standards or other requirements established by the
regulations;

(10) provide for certain persons/organisations to give approvals


required by the regulations and for such approvals to be
subject to conditions or modification and revocation;

(11) require the provision of information to prescribed persons;

(12) require the publication of water quality information;

(13) forbid the use or installation of fittings which have not been
approved;

(14) require electricity or water fittings to be of a prescribed size,


nature, strength or workmanship;

(15) impose requirements as to installation, arrangement,


connection, testing, disconnection, alteration and repair;

(16) impose requirements regarding earthing of electrical


installations, electrical voltage and frequency; and

118 The Electricity Wiring Regulations 2007


A4(b) Continued...

(17) enable the Regulation and Supervision Bureau to authorise A4(b)


any departures from the regulations as may be required and to
make those departures subject to conditions.

Article (66) - Failure to comply with regulations

[Note: amended by Article (18) of Law No (19) of 2007, see overleaf.]

Article (67) - Regulations disputes

The court with the appropriate jurisdiction shall hear disputes relating
to regulations made under Article (62) of this Law.

Article (106) - Duty to enforce by final order

Subject to Article (107) of this Law, where the Regulation and


Supervision Bureau is satisfied that licensed operator is contravening
or is likely to contravene any condition of its licence, the Regulation
and Supervision Bureau shall as soon as practicable by a final order
make such provision as appears to the Regulation and Supervision
Bureau to be requisite so as to secure compliance with that condition.

Article (114) - Power to fine

A final order may include a requirement on the licence holder to pay


a fine of such amount, being not less than Dirhams 50,000, as the
Regulation and Supervision Bureau determines to be appropriate.

The Electricity Wiring Regulations 2007 119


A4(b) Continued...

A4(b) The following Articles of Law No (19) of 2007 Concerning


the amendment of some provisions of Law No (2) of 1998
Concerning the Regulation of the Water and Electricity
Sector in the Emirate of Abu Dhabi2

Article 12

Article (54) of Law No. (2) of 1998 is replaced by the following


statement:

The Bureau, when performing its functions and duties under this Law,
is committed to execute in its best ways, functions that achieve the
following:

(1) Ensure the security of supply of water, wastewater and


electricity services in the Emirate.

(2) Supply customers with water and electricity and connecting


them to sewerage grids.

(3) Provision of special regulations of health and safety related


to supply of water, electricity and wastewater services to the
general public.

(4) Publish information related to the performance level of


licensed operators.

(5) Take account of local and international standards for the


environment which can have an effect on the water,
wastewater and electricity sector. In addition to, coordination
with concerned parties of environment in the Emirate and the
Country, for the benefit of the Consumer and the Sector.

(6) Take account of people with special needs who can be


threatened by lack of potable water or unavailability of
electricity, whether it was a cost or supply method of water
and electricity, or through use of devices and installations.

(7) Promote competition in the water, wastewater and electricity


sector.

2
unofficial translation

120 The Electricity Wiring Regulations 2007


A4(b) Continued...

(8) Operation and development of a safe, efficient and economic A4(b)


sector for the water, wastewater, and electricity in the Emirate.

(9) Protect the interest of consumers of water and electricity as to


terms and conditions and price of supply (whether
consumption is domestic, commercial or industrial).

(10) Protect the interests of users of sewerage services in the


Emirate.

Article (13)

Paragraphs (1), (4), (6), (7) and (8) of Article (55) of Law No. (2) of 1998,
shall be replaced by the following paragraphs:

(1) Revision of Provision Plans of water, wastewater and electricity


in the Emirate.

(4) Establishment, maintenance, revision and supervision of


safety standards for the water, electricity and sewerage
services supervision of compliance with such safety
standards.

(6) Regulation of tariff applied on water and electricity


customers and consumers of sewerage services, and the
methodology of applying and collecting such tariff.

(7) Approval of conditions and special statements concerning the


supply of water, electricity and sewerage services to domestic
customers and supervision on compliance with such condition
and statements and amending them.

(8) Approval of modifications to water and electricity


transmission and distribution codes, and operating codes of
providing sewerage services.

Article (15)

"In consultation with the Authority" in Article (62) of Law No. (2) of
1998, is replaced by "in consultation with who sees appropriate".

The Electricity Wiring Regulations 2007 121


A4(b) Continued...

A4(b) Article (16)

Paragraphs (1), and (2) of Article (63) of Law No. (2) of 1998, is
replaced by the following two paragraphs:

(1) Ensure supply of water and electricity and provision of regular


and efficient sewerage services.

(2) Protect the general public from danger resulted from


electricity, water and wastewater works and installations.

A new paragraph given number (10) shall be added to this article as


follows:

(10) Ensure compliance of sewerage connections with standards


determined by the Regulation and Supervision Bureau.

Article (17)

Provisions of Paragraphs (2), and (4), and (14) of Article (65) of Law No.
(2) of 1998, is replaced by the following paragraphs:

(2) Notification of any accidents, failures of supply or transport or


distribution of water and electricity when providing sewerage
services.
(4) Relieving ADWEC, in certain circumstances, or any licensed
body from obligations to supply water, electricity and
sewerage services.
(14) Require electricity, water and wastewater installations to be of
a prescribed size, nature, strength and quality.

Article (18)

Article (66) of Law No. (2) of 1998 is replaced by the following:

"Failure of any person to comply with regulations stated under this


Article (62) of this Law shall be punished with a fine of not less than
AED 250,000. In case the same failure is repeated by such person, the
fine is doubled".

122 The Electricity Wiring Regulations 2007


A5(a) Distribution company earthed
system (TN-S)

A5(a)
[ see Regulation 6.2 ]

Distribution
Distribution
Company
Network
Transformer
Conductors

L1 L2 L3 N
E

Earth fault current through Distribution Company cable


Earth sheath or armour of Distribution Company Cable is connected to
Customers Installation

A
Transformer
Neutral Point Earth
Customer’s Main Distribution Board

Earth fault
Main Earth in Appliance
Terminal Earth fault current

The Electricity Wiring Regulations 2007 123


A5(b) Customer earthed system (TT)

A5(b) [ see Regulation 6.2 ]

Distribution Company Distribution Network


Transformer Conductors

L1 L2 L3 N
E

Transformer
Neutral Point Earth

Earth sheath or armour of


Distribution Company Cable not connected to
ACustomers Installation

Customer’s Main Distribution Board


Earth fault current through ground / soil

Earth fault in Appliance


A Earth fault current
Main Earth Terminal

Customer’s Earth Electrode

Insulated cable
gland

124 The Electricity Wiring Regulations 2007


A5(c) Distribution company earthed system
with additional earth (TN-S-TT)

[ see Regulation 6.2 ]


A5(c)

Distribution Company Distribution Network


Transformer Conductors

L1 L2 L3 N
E

Earth fault current

Transformer
Neutral Point Earth

Earth sheath or armour of Distribution Company Cable is connected to


Customers Installation

A
Earth fault current shared between Customer Earth Electrode and Distribution Company Earth
Customer’s Main Distribution
Board

Earth fault in Appliance


A Earth fault current
Main Earth Terminal

Customer’s Earth Electrode

The Electricity Wiring Regulations 2007 125


A5(d) Earth electrode pit
and standard labels

A5(d)

Main Earth Conductor 300 x 300mm Inspection cover

SAFETY EARTH
CONNECTION
DO NOT REMOVE
Standard safety label for
Main Earth Connections

SAFETY EARTH BONDING


DO NOT REMOVE

Standard safety label for main and


supplementary bonding connections

[ see clause 6.4.3, 6.5.6, 5.5.11 ]

126 The Electricity Wiring Regulations 2007


A5(e) Main earth terminal (MET) at main
distribution board (MDB)

A5(e)
Circuit Earth Conductors for sub-main
circuits
CEC To SDB1

To SDB2

Main Circuit Breaker


A

MET
Neutral Bar

MEC to Customer Earth Electrode


Earth connection to metal door

Earth conductor
Alabels at MET

DB2 MAIN EARTH CONDUCTOR

DB1 MAIN EARTH CONDUCTOR

Test Link

CUSTOMER EARTH ELECTRODE

DISTRIBUTION COMPANY EARTH

B
Distribution
Company Earth

Note: Illustration shows Distribution Company Earthed System with additional


Customer Earth (TN-S-TT)

[ see Regulation 6.3 and 6.2 ]

The Electricity Wiring Regulations 2007 127


A5(f) Main earth conductors (MEC)
and circuit earth conductors
(CEC)

A5(f)
CEC to switches and
Accessories

Final Distribution
Board
CEC to fixed Appliance

Earth Bar

CEC in metal or plastic conduit

MEC

Main Distribution
Board

CEC in appliance flexible cord


Main Earth Terminal
Functional Earth (see clause 6.9.2)

MEC

Mainarth ctor to ctrode


E
Condu
Earth Ele

Distribution Company Earth

Note: Common terminology (outside these Regulations) includes CPC (Circuit Protective
Conductor) and ECC (Earth Continuity Conductor ) in place of CEC illustrated above.
[ see Regulation 6.2 ]

128 The Electricity Wiring Regulations 2007


A5(g) Components of earth fault loop
impedance

[ see Regulation 6.7 ]


A5(g)
Distribution
Network
Conductors
Distribution Company Transformer 10

9 L1
L2
L3
N
E
6 11
Transformer Neutral8 Supply Intake Circuit Breaker
Point Earth
X
7

1 N
5
L
E
2
4 MET 3 Earth fault in Appliance
Main Earth Terminal

1 Impedance of Circuit phase conductor


Internal earth loop 2 Resistance of fault
impedance
3 Impedance of Circuit Earth Conductor (CEC)

4 Impedance of Local Earth Electrode

5 Impedance of fault path through ground

6 Impedance of transformer neutral earth point

7 Impedance of supply cable earth conductor / armouring

8 Impedance of network cable earth conductor / armouring


Source earth loop
impedance, Ze 9 Distribution Company transformer winding

10 Live conductor of distribution network cable

11 Live conductor of Supply cable

The Electricity Wiring Regulations 2007 129


A5(h) Earth fault loop impendance values
required for MCBs (at 230 V)

A5(h) [from table 41B2 of BS 7671]


Maximum earth fault loop impedance (Ohms)

Device MCB MCB MCB MCB MCB


Note 1: (A)
rating The above values aretype
type1 given
2 for conductor
type 3 temperatures
type B of 70˚C.
type DAs
measurements are normally taken at room
and temperature the measured
values must be approximately 20% less
typethan tabulated above.
Note 2: The above values are used as an C alternative to calculating the

12.00 time 6.86


5 disconnection for each specific
4.80 situation. - i.e. MCBs- will
operate in the instantaneous mode if the Earth Fault Loop
6 Impedance
10.00 5.71below the 4.00
value is kept above levels.8.00 2.00
For EFL Impedance
values higher than shown above it is still possible to comply with the
10 6.00 3.43 2.40 4.80 1.20
requirement of 0.4 s disconnection for Circuits accessible to persons, and
15 5 s for 4.00
other Circuits2.29
(clause 5.5.2)1.60
if a check is- made against- the
manufacturer’s time-current performance chart.
16 3.75 2.14 1.50 3.00 0.75
Note 3: Circuit-breakers types 1, 2 and 3 to BS 3871 were known as Miniature
20 Circuit-Breakers
3.00 (MCBs).
1.71 Since 1.20 the 1990s 2.40
these have0.60been
superseded by devices to BS EN 60898, i.e. Types B, C and D, which
25 are now2.40 1.37Circuit-Breakers
simply called 0.96 (CBs).1.92The term 0.48
MCB is
commonly used to apply to both types of devices, and is used in this
30 2.00 1.14 0.80 - -
context in these Regulations.
32 1.88 1.07 0.75 1.50 0.38

40 1.5 0.86 0.60 1.20 0.30

130 The Electricity Wiring Regulations 2007


A5(i) Resistance per metre of copper
conductors for calculation of R1+R2

Conductor cross-sectional area Resistance per metre A5(i)


(mm²) (milli-ohms)

1.0 18.1

1.5 12.1

2.5 7.41

4.0 4.61

6.0 3.08

10.0 1.83

16.0 1.15

25.0 0.73

[above values at 20˚C]

Note: To allow for the increase in resistance with increased temperature under
fault conditions these values must be multiplied by 1.2 for PVC
insulated cables.

The Electricity Wiring Regulations 2007 131


A5(j) Sizing of earth conductors and
equiptential bonding conductors

A5(j) [from table 54G of BS 7671]


Minimum cross- Minimum cross-
Cross sectional
sectional area of sectional area of
area of phase and
earth conductors equipotential bonding
neutral conductors
[see note 1] conductors
(S) (mm2)
(mm2) (mm2)

Note 1: For Main Earth Conductors between S Earth Electrodes andSthe / 2Main Earth
<= 16 of an Installation,(not
STerminal less than (not less thanarea
S should be taken as the cross-sectional 4 of
the conductors of the 2.5incoming
see note 2)supply cable.or 6,For
seeother
note 3)
Earth
Conductors S should be taken as the cross-sectional area of the circuit
16 phase
< S <=conductors.
35 16 10
Note 2: Earth Conductors should always be insulated and a cross-sectional area
of less than 2.5 mm2 should not be used unless they are an integral part
of a sheathed cable (e.g. an Appliance flexible S / 4 cord).
S > 35 S/2
Precautions should be taken against corrosion (but not
andexceeding
damage 25)(e.g.
installed in conduit or ducts).

Note 3: Main Equipotential Bonding Conductors should be sized according to the


live conductors of the incoming supply, but should not be less than 6
mm2. Supplementary Bonding Conductors should be sized according to the
live conductors of the circuit to which they are connected but should not
be less than 4 mm2.

132 The Electricity Wiring Regulations 2007


A5(j) Continued...

Note 4: As an alternative to using the above selection table, the sizing A5(j)
of Earth Conductors and Equipotential Bonding Conductors
may be calculated using the adiabatic equation provided in the
IEE Wiring Regulations BS7671:2001 paragraph 543-01-03.This normally
allows smaller sizes of Earth Conductor to be used.

For example: 4.0 mm2 earth for 6 mm2 circuit conductor


2.5 mm2 earth for 4 mm2 circuit conductor
1.5 mm2 earth for 2.5 mm2 circuit conductor

The Electricity Wiring Regulations 2007 133


A5(k) Minimum number of earth electrodes

A5(k) The number of Earth Electrodes required at a Premises will be


determined primarily by the value of Earth Resistance that can be
achieved from each. However, the minimum number in any case shall
be as shown below:

Main incoming circuit- Minimum Minimum size of main


breaker rating (Amps) number earth conductor (mm2)
of earth
electrodes

60/100 1 16

200 1 50

300 1 50

400 1 70

500 2 70

600 2 70

800 2 70

1000 2 70

1600 2 70

2000 2 150

2500 2 150

Note: Standard earth electrode diameters are 9 mm, 12.5 mm or 15 mm for


copper-clad steel, or 16 mm for stainless steel. Standard lengths are
1.2 m or 1.5 m (see also BS 7430).

134 The Electricity Wiring Regulations 2007


A5(l) Mandatory connections to earth
conductors

The following items must be connected to the Circuit Earth A5(l)


Conductor, which should be provided separately for each Final
Circuit, insulated with green/yellow PVC sheath, be of the
appropriate size (Appendix A5(j)) and be installed in the same
conduits or routes as the phase and neutral conductors.

Items where connections must be made to the


Circuit Earth Conductor

Distribution Boards: exposed-metallic-parts


(frame, door etc)

Metal conduits and trunking: at start and end of runs, at


pulling points and inspection boxes

Switchgear: exposed-metallic-parts
(frame, door etc)

Luminaires: exposed-metallic-parts

Switches: exposed-metallic-parts (mounting


boxes, cover plates)

Socket-outlets: exposed-metallic-parts (mounting


boxes, cover plates)

Fixed appliances and exposed-metallic-parts


machinery: (metal casing etc)

Note 1: The earthing of cover plates should not rely solely on the connection
of fixing screws to an earthed mounting box (due to the
possibility of poor connections, corrosion etc); a short flexible
Earth Conductor should be connected between the mounting box
and the plate. See Guidance Note G7(d).

Note 2: The circuit Earth Conductor should be terminated in the connection


box for a Luminaire even if it is plastic (to provide for future use).
See Guidance Note G7(d).

The Electricity Wiring Regulations 2007 135


A5(m) Residual operating current settings for
RCDs and ELP devices

A5(m)
Residual operating
Equipment
current settings (mA)

13 A switched-socket outlets 30
Note: Where two values are indicated the higher value is allowed only where the
Water heaters 30
equipment is not normally accessible to any person.
Kitchen fixed Appliances
30
(e.g. washing machine)

Domestic water pumps 30

Swimming pool pumps, or jacuzzi 30

Underwater lighting SELV only

General fixed lighting 100

Floodlighting 100 - 300

Window or split type air conditioning 100

Air handling, a/c fan coils etc 100

Central or package a/c units 100 - 300

Irrigation pump 100

Electric Cooker (not provided with a


100
13 A socket-outlet)

Industrial machines etc 100 - 300

Elevators, escalators, lifts 300 - 500

Neon signs 300

School areas (e.g. laboratory for


10
children)

LV main circuit breakers or


300 - 500
switchboards

136 The Electricity Wiring Regulations 2007


A5(m) Continued...

The table opposite shows the required residual operating current A5(m)
values for RCDs and other Earth Leakage Protection devices. These
are intended to provide for electric shock protection (Direct and
Indirect Contact), particularly in high-risk areas, as well as protection
against high resistance earth faults which may not operate overcurrent
devices and pose a risk of overheating or fire, see Regulation 5.4.

All Final Circuits where Appliances may be used by any person must
be provided with Earth Leakage Protection (clause 5.3.5 ) and back-
up Earth Leakage Protection must be provide at the main Supply
intake for Installations classed as an Earth Leakage Protected System,
see Regulation 5.4.

The Electricity Wiring Regulations 2007 137


A6(a) Time-current characteristic of MCBs as
multiple of rated current

A6(a)

2 HRS
1 HR

1,000

100

10
OPERATING TIME IN

1.0

0.1

TypeTypeType
BCD
0.01
0.001

1 35 1020 100 1,000

SHORT CIRCUIT CURRENT AS A MULTIPLE OF RATED CURRENT

Reproduced with
permission of Crabtree /
Electrium Ltd.

138 The Electricity Wiring Regulations 2007


A6(b) Time-current characteristic of Type B MCBs

A
0
10
A
5
12
1

A
3
6
A
0
8
6
10 000
Time / current characteristics
for Type B circuit-breakers to
BS EN 60898
and RCBOs to BS EN
61009
Current for time 0.1 sec to 5
secs
Rating Current
1000
6A 30 A
The Electricity Wiring Regulations

10 A 50 A
16 A 80 A
20 A 100 A
100
25 A 125 A
32 A 160 A
40 A 200 A
TIME,

50 A 250 A
10 63 A 315 A
80 A 400 A
100 A 500 A
125 A 625 A
1

0.1

For prospective fault currents in excess


of those providing instantaneous operation
refer to the manufacturer’s let-through energy data.
00.1
1 10 100 1 000 10 000
1

PROSPECTIVE CURRENT, r.m.s. AMPERES


[ from fig. 3.4 of BS 7671 ]
A6(
1

A6(c) Time-current characteristic of Type C MCBs

A
0
10
A
5
12
1

A
3
6
A
0
8
6
10 000 Time / current characteristics
for Type C circuit-breakers to
BS EN 60898
and RCBOs to BS EN
61009
Current for time 0.1 sec to 5 secs
Rating Current
1000
6A 60 A
The Electricity Wiring Regulations

10 A 100 A
16 A 160 A
20 A 200 A
100
25 A 250 A
32 A 320 A
40 A 400 A
TIME,

50 A 500 A
10 63 A 630 A
80 A 800 A
100 A 1000 A
125 A 1250 A
1

0.1

For prospective fault currents in excess


of those providing instantaneous operation
refer to the manufacturer’s let-through energy data.
00.1
1 10 100 1 000 10 000

PROSPECTIVE CURRENT, r.m.s. AMPERES


[ from fig. 3.5 of BS 7671 ]
A6(d) Time-current characteristic of Type D MCBs

A
0
10
A
5
12
1

A
3
6
A
0
8
6
10 000 Time / current characteristics
for Type D circuit-breakers to
BS EN 60898
and RCBOs to BS EN 61009
Current for time 0.1 sec to 5 secs
Rating Current
1000
6A 120 A
10 A 200 A
16 A 320 A
The Electricity Wiring Regulations

20 A 400 A
100
25 A 500 A
32 A 640 A
40 A 800 A
TIME,

50 A 1000 A
10 63 A 1260 A
80 A 1600 A
100 A 2000 A
125 A 2500 A
1

0.1

For prospective fault currents in excess


of those providing instantaneous operation
refer to the manufacturer’s let-through energy data.
00.1
1 10 100 1 000 10 000

PROSPECTIVE CURRENT, r.m.s. AMPERES


[ from fig. 3.6 of BS 7671 ]
1

A6(
A6(e) Typical energy let-
through characteristics of
MCBs

A6(e)

105
50&63A
40A 2.5mm2
32A
I2t energy let-through in A2s (50Hz sine wave)
20A
one complete 1/2 cycle
16A

10A
1.5mm2
TOTAL LET-THROUGH ENERGY

6A
1.0mm2

104

CABLE CONDUCTOR

103
0.1 1.0 10 16 100.0

PROSPECTIVE FAULT CURRENT (kA)

Reproduced with permission


of Crabtree / Electrium Ltd.

142 The Electricity Wiring Regulations 2007


A6(f) MCBs selection criteria

Operating characteristics of MCB types and the required earth fault A6(f)
loop impedance values are given in Appendix A6(a) to A6(d) and
Appendix A5(h). MCBs for common cable sizes and Circuits are
shown in the following table:

MCB Cable Cable


nominal Cable size rating at rating at Typical circuit
rating mm2 30˚C, 40˚C, application
Amps PVC A, PVC A,
(kW) (kW)

17.5 15.2 Lighting


6 1.5
(3.4) (3.0) (light load)

24.0 20.9 Lighting


10 2.5
(4.7) (4.1) (heavy load)

24.0 20.9 Radial Circuit


16 2.5
(4.7) (4.1) to socket-
outlets

Radial Circuit
32.0 27.8
20 4.0 to fixed
(6.3) (5.4)
appliance
(e.g. a/c unit)
41.0 35.7 Ring Circuit to
32 6.0
(8.0) (7.0) socket-outlets

Radial Circuit
6.0 41.0 35.7
32 to large
(8.0) (7.0)
Appliance (e.g.
cooker)

Radial Circuit
57.0 49.6
40 10.0 to machinery
(11.1) (9.7)
(e.g. chiller
unit)

Note: Cable rating should be at least 20% greater than MCB nominal rating
to afford overload protection for the cable. Cable ratings are taken from
Appendix A7(a) with temperature correction factors applied from
Appendix A7(g) and assuming 2 cables cores installed in conduit.
kW ratings assume 0.85 power factor at 230V.

The Electricity Wiring Regulations 2007 143


A6(f) Continued...

A6(f) Circuit-breakers types 1, 2 and 3 to BS 3871 were previously known


as Miniature Circuit-Breakers (MCBs). Since the 1990s these have
been superseded by devices to BS EN 60898, i.e. Types B, C and D,
which in modern terminology are simply called Circuit-Breakers
(CBs). However, the term MCB is commonly used to apply to both
types of devices, and is used in this context in these Regulations.

The difference between Type B, C or D devices is their ability to


handle surge currents without tripping. These are, typically, inrush
currents associated with discharge lighting, induction motors, air
conditioning units, etc.

The classification of Types B, C or D is based on the fault current


rating at which magnetic operation occurs to provide short time
protection (typically less than 100 ms) against short-circuits.
See Appendix A6(a).

• Type B devices are designed to trip at fault currents of 3-5 times


rated current (In). For example a 10 A device will trip at 30-50 A
• Type C devices are designed to trip at 5-10 times In
• Type D devices are designed to trip at 10-20 times In
Type B devices are generally suitable for domestic applications. Type
C devices are the normal choice for commercial and industrial
applications where large groups of fluorescent lighting, motors etc,
are used. Type D devices have more limited applications, where high
inrush currents may be expected. For example, large battery systems,
motors, transformers, etc.

Sometimes failure of tungsten filament lamps can trip Type B circuit-


breakers in domestic and retail environments. This is caused by high
arcing currents occurring at the time of failure and is generally associated
with inferior quality lamps. A Type C device may be substituted for a
Type B device where unwanted tripping persists, especially in commercial
applications. A change from Type C to Type D devices should only
be taken after careful consideration of the installation conditions, in
particular the operating times required by Regulation 5.5.

(Selection criteria for type B, C, D devices referenced from


www.voltimum.co.uk)

144 The Electricity Wiring Regulations 2007


A6(g) Internal construction of MCB

A6(g)

Arc runner 25mm2 max tunnel terminal

15 plate Moving
arc chamber contact

Arc runner Latch


mechanism

Fixed
contact
Thermo-metal
element

Calibration
mechanism
Operating
handle

DIN rail Coil


mounting assembly

25mm2 max ‘Jaw’ terminal Trip


bar

Reproduced with permission


of Wylex / Electrium.

The Electricity Wiring Regulations 2007 145


A7(a) Current ratings for PVC single
core cables (non-armoured)

A7(a) Standard cable ratings and Voltage drop for single core, PVC (70˚C
thermoplastic), non-armoured, stranded copper conductor (BS6004
and BS6346), with or without sheath, installed in buried or surface
conduit or trunking.

In conduit in In conduit on wall


Cross Voltage drop
thermal insulation or in concrete
sectional (mV/A/m)
(A) (A)
area
(mm²)
2 3 or 4 2 3 or 4 2 3 or 4
cables cables cables cables cables cables

1.0 11 10.5 13.5 12 44 38

1.5 14.5 13.5 17.5 15.5 29 25

2.5 19.5 18 24 21 18 15

4.0 26 24 32 28 11 9.5

6.0 34 31 41 36 7.3 6.4

10 46 42 57 50 4.4 3.8

16 61 56 76 68 2.8 2.4

25 80 73 101 89 - -

35 99 89 125 110 - -

50 119 108 151 134 - -

70 151 136 192 171 - -

At 30˚C ambient temperature [see Appendix A7(g) for grouping factors]

Note 1: Data from table 4D1A and 4D1B of BS 7671.

Note 2: For voltage drop for cables above 25 mm2 refer to BS 7671.

146 The Electricity Wiring Regulations 2007


A7(b) Current ratings for PVC multi-
core cables (non-armoured)

Standard cable ratings and voltage drop for PVC (70˚C thermoplastic) A7(b)
multi-core cables (sheathed), non-armoured, stranded copper
conductor (BS6004), installed in buried or surface mounted conduit or
trunking, or on exposed, perforated cable tray.

On perforated
In conduit on wall Clipped direct
Cross cable tray or in
or in concrete to a wall
sectional free air
(A) (A)
area (A)
(mm²)
2 core 3 or 4 2 core 3 or 4 2 core 3 or 4
core core core

1.0 13 11.5 15 13.5 17 14.5

1.5 16.5 15 19.5 17.5 22 18.5

2.5 23 20 27 24 30 25

4 30 27 36 32 40 34

6 38 34 46 41 51 43

10 52 46 63 57 70 60

16 69 62 85 76 94 80

25 90 80 112 96 119 101

35 111 99 138 119 148 126

50 133 118 168 144 180 153

70 168 149 213 184 232 196

95 201 179 258 223 282 238

120 232 206 299 259 328 276

150 258 225 344 299 379 319

At 30˚C ambient temperature [see Appendix A7(g) for grouping factors]

Note 1: Data taken from table 4D2A and 4D2B of BS 7671.

Note 2: 2-core refers to single-phase circuits, 3 or 4-core refers to three-phase


circuits.

The Electricity Wiring Regulations 2007 147


A7(b) Continued...

A7(b)
Cable size (mm²)

Voltage drop
1.0 1.5 2.5 4 6 10 16
(mV/A/m)
Note 1: For voltage drop for cables above 16 mm² refer to BS 7671.

2 core 44 29 18 11 7.3 4.4 2.8

3 or 4 core 38 25 15 9.5 6.4 3.4 2.4

148 The Electricity Wiring Regulations 2007


A7(c) Current ratings for PVC multi-
core cables (armoured)

Standard cable ratings and Voltage drop for multi-core armoured, A7(c)
PVC (70˚C thermoplastic) cables, stranded copper conductor (BS
6346 and BS 5467), installed exposed (clipped to a wall) or on
perforated cable tray.

Clipped direct On perforated


Cross Voltage drop
to a wall cable tray
sectional (mV/A/m)
(A) (A)
area
(mm²)
2 core 3 or 4 2 core 3 or 4 2 core 3 or 4
core core core

1.5 21 18 22 19 29 25
2.5 28 25 31 26 18 15
4 38 33 41 35 11 9.5
6 49 42 53 45 7.3 6.4
10 67 58 72 62 4.4 3.8
16 89 77 97 83 2.8 2.4
25 118 102 128 110 - -
35 145 125 157 135 - -
50 175 151 190 163 - -
70 222 192 241 207 - -
95 269 231 291 251 - -
120 310 267 336 290 - -
150 356 306 386 332 - -
185 405 348 439 378 - -
240 476 409 516 445 - -
300 547 469 592 510 - -

At 30˚C ambient temperature [see Appendix A7(g) for grouping factors]

Note 1: Data taken from table 4D4A and 4D4B of BS 7671.


Note 2: 2 core refers to single-phase circuits, 3 or 4 core refers to three-
phase circuits.
Note 3: For voltage drop for cables above 16 mm² refer to BS 7671.

The Electricity Wiring Regulations 2007 149


A7(d) Current ratings for thermo-setting multi-
core cables (armoured)

A7(d) Standard cable ratings and voltage drop for multi-core, 90˚C
thermosetting plastic insulated, armoured cable, stranded copper
conductor (BS6004), surface mounted or on cable tray

Clipped direct On perforated


Cross Voltage drop
to a wall cable tray
sectional (mV/A/m)
(A) (A)
area
(mm²)
2 core 3 or 4 2 core 3 or 4 2 core 3 or 4
core core core

1.5 27 23 29 25 31 27
2.5 36 31 39 33 19 16
4 49 42 52 44 12 10
6 62 53 66 56 7.9 6.8
10 85 73 90 78 4.7 4.0
16 110 94 115 99 2.9 2.5
25 146 124 152 131 - -
35 180 154 188 162 - -
50 219 187 228 197 - -
70 279 238 291 251 - -
95 338 289 354 304 - -
120 392 335 410 353 - -
150 451 386 472 406 - -
185 515 441 539 463 - -
240 607 520 636 546 - -
300 698 599 732 628 - -

At 30˚C ambient temperature [see Appendix A7(g) for grouping factors]

Note 1: From table 4E4A and 4E4B of BS 7671]


[2 core refers to single-phase circuits, 3 or 4 core refers to three-phase
circuits].

Note 2: For voltage drop for cables above 16 mm² refer to BS 7671.

150 The Electricity Wiring Regulations 2007


A7(e) Current ratings for MICC cable

Standard cable ratings and voltage drop for mineral insulated copper- A7(e)
clad cables installed on a wall (clipped direct). PVC sheathed cable
assumes 70˚C sheath temperature, bare copper-clad cable assumes
105˚C sheath temperature.

Bare sheath 105˚C

Bare sheath 105˚C


(70˚C) 2 x single
Cross-sectional

(70˚C) 3

2 x single

3 x single
PVC sheath

PVC sheath
area

core
or twin

(mm²) (A) (A) (A) (A)


1.0 18.5 15 22 19
Light 1.5 23 19 28 24
duty
2.5 31 26 38 33
500 V
4 40 35 51 44
1 19.5 16 24 20
1.5 25 21 31 26
2.5 34 28 42 35
4 45 37 55 47
Heavy 6 57 48 70 59
duty 10 77 65 96 81
750
V 16 102 86 127 107
25 133 112 166 140
35 163 137 203 171
50 202 169 251 212
At 30˚C ambient temperature [see Appendix A7(g) for grouping factors]

Note 1: For MICC cable installed in perforated cable tray the current rating is
approximately 5 - 10%, greater than shown above, see BS 7671 table
4J1A and 4J2A.

Note 2: Where the sheath temperature may be above 70˚C care should
be taken that the cable is not within reach of any person or in contact
with combustible materials.

The Electricity Wiring Regulations 2007 151


A7(f) Cable ratings and voltage drop for
flexible cords

A7(f) Standard current ratings and voltage drop for flexible cords–60˚C
conductor temperature (PVC or rubber insulated), stranded copper
conductors to BS 6500 (domestic applications).

Voltage Voltage Mass


Cross
Single Three drop drop supportable
sectional
phase phase (single- (three- by twin
area
phase) phase) flexible
cord

(mm²) (A) (A) (mV/A/m) (mV/A/m) (kg)

0.5 3 3 93 80 2

0.75 6 6 62 54 3

1.0 10 10 46 40 5

1.25 13 - 37 - 5

1.5 16 16 32 27 5

2.5 25 20 19 16 5

4.0 32 25 12 10 5

At 30˚C ambient temperature [from table 4H3A of BS 7671]

For Ambient temperatures above 30˚C the following correction factors


may be applied for flexible cords:

Ambient temperature (°C) 35 40 45 50 55

Correction factor 0.91 0.82 0.71 0.58 0.41

152 The Electricity Wiring Regulations 2007


A7(g) Temperature correction factors
for cables

Ambient temperature correction factors (relative to 30°C) for cable A7(g)


ratings shown in Appendices A7(a) to A7(e).

Type of cable insulation

90°C mineral mineral


Ambient 70°
thermosetting insulated insulated
temperature C
plastic (70°C (105°C sheath)
(°C) PVC
sheath)

25 1.03 1.02 1.03 1.02

30 1.00 1.00 1.00 1.00

35 0.94 0.96 0.93 0.96

40 0.87 0.91 0.85 0.92

45 0.79 0.87 0.77 0.88

50 0.71 0.82 0.67 0.84

55 0.61 0.76 0.57 0.80

60 0.50 0.71 0.45 0.75

[from table 4C1 of BS7671:2001]

The Electricity Wiring Regulations 2007 153


A7(h) Grouping factors for cables

A7(h) Because of mutual heating effects the following correction factors should
be applied to the tables in Appendix A7(a) to A7(e) for situations
where a number of cables are installed close together. These factors
assume all cables are fully loaded; however, if an individual cable is
loaded below 30% of its rating it may be excluded from the total
number in the group.

Method of installation

Enclosed Single Single layer Single


in conduit layer, multi-core on layer single-
(surface or clipped to a a perforated core on a
buried) or non-metallic cable tray cable tray
Number of bunched surface (touching)
cables on a non-
metallic

Horizontal
Touching

Touching

surface
Spaced

Spaced

Vertical
2 0.80 0.85 0.94 0.86 0.91 0.90 0.85
3 0.70 0.79 0.90 0.81 0.89 0.85 -
4 0.65 0.75 0.90 0.77 0.88 - -
5 0.60 0.73 0.90 0.75 0.87 - -
6 0.57 0.72 0.90 0.74 0.87 - -
7 0.54 0.72 0.90 0.73 - - -
8 0.52 0.71 0.90 0.73 - - -
9 0.50 0.70 0.90 0.72 - - -
10 0.48 - 0.90 0.71 - - -
12 0.45 - 0.90 0.70 - - -
14 0.43 - 0.90 - - - -
16 0.41 - 0.90 - - - -
18 0.39 - 0.90 - - - -
20 0.38 - 0.90 - - - -

[ - correction factor not tabulated] [taken from table 4B1 of BS7671

154 The Electricity Wiring Regulations 2007


A8. Colour identification for cables

A8
Conductor Colour

Non-flexible fixed wiring and all three-phase cables:

Phase 1 Red

Phase 2 Yellow

Phase 3 Blue

Neutral Black

Earth conductors Green / yellow

Functional Earth Cream

Flexible cables for single-phase Appliances:

Phase 1 Brown

Neutral Blue

Earth conductors Green / yellow

Functional Earth Cream

Note: The harmonised cable colours now implemented in Europe


(BS EN 60446 effective from Jan 2006) of Brown, Black and Grey for
phase 1, phase 2, and phase 3 respectively have not been adopted for the
Emirate of Abu Dhabi.

The Electricity Wiring Regulations 2007 155


A9. Capacity of conduits and trunking

Diameter of Conduit (mm2)


Conductor
20 25 32
( mm2 )
Maximum number of conductors

1.5 7 12 -

2.5 5 9 12

4.0 3 6 9

6.0 - 5 8

10.0 - 3 6

16.0 - - 4
A9
25.0 - - 3

Note: For cable trays and trunking the space factor (total cross-sectional area of
cables compared with the interior cross-sectional area of trunking) must
not exceed 50%.

156 The Electricity Wiring Regulations 2007


A10. IP coding for ingress protection

A10
Ingress protection : IP codes

First digit : protection against ingress Second digit : protection against


by solid objects ingress of water

X Not tested or not applicable X Not tested or not


applicable

0 No protection 0 No protection

1 Human hand or objects > 1 Vertically falling water


50mm

2 Human finger or objects > 2 Sprays of water < 15˚ from


12mm vertical

3 Objects > 2.5mm (e.g. tools or 3 Sprays of water < 60˚ from
wires) vertical

4 Objects > 1.0mm (e.g. small 4 Splashes of water


wires) (from any direction)

5 Limited protection against dust 5 Low pressure jets of water


(to the extent that does not (from any direction)
harm the equipment or impair
safety)

6 Strong jets of water (from


6 Totally protected against dust
any direction)

7 Temporary immersion

8 Total immersion

The IP coding system is specified in BS EN 60529: 1992 (adopted


from IEC 529: 1989). The first digit specifies protection against
ingress of foreign objects of varying size, ranging from human hands
or fingers to fine dust particles. The second digit specifies protection
against ingress of water, ranging from free falling water, to immersion
in water.

BS EN 60529 does not specify protection against the risk of


explosion, humidity or corrosive gases. If enclosures of equipment are
drilled or knockouts removed, suitable measures should be taken to
restore the equipment to the original IP rating.

The Electricity Wiring Regulations 2007 157


A11. Standard wiring diagram symbols

Symbol Description

Main Distribution Board (MDB)

Sub Main Distribution Board (SMDB)

Distribution Board (DB)

Air Circuit Breaker (ACB)

Moulded Case Circuit Breaker (MCCB)

Miniature Circuit Breaker (MCB)

Earth Leakage Protective Device (RCD)

Fuse

Link

kWh meter (direct reading)

kWh meter (ct operated)

Switched line (e.g. connecting all outlets


controlled by one switch)
Circuit line (e.g. connecting all outlets on
the same circuit)

13 A switched socket outlet

15 A switched socket outlet

20 A double pole switch with neon indicator

30 A double pole switch

Shaver socket to BS 3535

Cooker control unit

A11

Note: Additional wiring symbols may be taken from BS EN 60617

158 The Electricity Wiring Regulations 2007


A11. Continued...

A11

Symbol Description

Note: Additional wiring symbols may be taken from BS EN 60617

The Electricity Wiring Regulations 2007 159


A12(a) Danger of death sign

A12(a)

160 The Electricity Wiring Regulations 2007


A12(b) Typical layout of supply intake room

A12(b)

Main Distribution Board


Copy of Installation Certificate and Wiring Diagram
[ see clause 8.1.3 ]

Meters
13A socket outlet
Capac ban
Main Supply Cable

Main Earth Conductor

Main cable pulling pit 600 x 600

Earth cable pit 300 x 300

Louvered door (for


non-air conditioned room

[ see Regulation 4.2 ]

Standard size of supply intake rooms

Main circuit breaker rating Intake room dimensions


(A) (m)

600 - 1000 2.5 x 2.5

350 - 600 2.5 x 2.0

100 - 300 2.0 x 2.0

The Electricity Wiring Regulations 2007 161


A12(c) Typical layout of final distribution
board (FDB) and RCD label

A12(c)
Load distribution schedule
fixed to door

R
Y
B
R
Y
B
R
Y
B

Main
Earth
Terminal
Main
Isolator

RCD 1
100mA RCD 2
30mA Neutral
Bar

“earth tail’
for door

buried conduits

RCD Operation & Test

Customer Notice

This Distribution Board is fitted


with Residual Current Devices
(RCDs) which will detect any fault
current to earth and switch off the
device. Note this Distribution Board
is fitted with number RCDs. If
the device will not switch on after
RCD Operation Label
tripping consult a licensed electrical
contractor or your local Electricity [ see clause 5.4.8 ]
Supply Company.

162 The Electricity Wiring Regulations 2007


A12(d) Typical layout of LV switchroom

A12(d)

Emergency light
Outgoing (2 hour battery)
busbar risers

min 0.75 m

Outgoing

HRC
fuses

min 0.75 m
rear clearance

capacitor bank
automatic
control panel

min 1.5 m
front
clearance

Incoming cables
from Distribution Company
Transformer

Access doors for


equipment delivery
2nd access door for
personnel if switchroom
is greater than 6 m in
length

Note: LV Switchroom to be sized to accomodate the number of panels required


(including spare positions) with minimum access clearances shown
above.

The Electricity Wiring Regulations 2007 163


A13. Boundary of customer connection point
and scope of the Regulations

A13

FDB

Customer Connection Point

Meter
LV Feeder Pillar MDB B
FD

To Distribution Company Transformer 11 kV/400V

Distribution Network
“Electricity Supply Regulations 2007” Customer’s Installation
“Electricity Wiring Regulations 2007”

[ see Regulation 4.3 and clause 1.3.2 ]

164 The Electricity Wiring Regulations 2007


A14. Typical layout for ring circuits
and radial circuits

A14

Spur socket-outlet
Fused spur to fixed appliance

Spur socket-outlets
To Final
Distribution Board

15A BS 546
socket-outlet (non-domestic premises only)

[ see clause 7.6.2 , 7.6.3 ]

The Electricity Wiring Regulations 2007 165


A15. Minimum number of socket-outlets
and connection points

A15
Minimum number of outlets for
Room domestic premises
Note: Socket-outlets should be located to avoid the need for customers
Single Doubleto use
extension cables and doubling adapters.15 A BS 546 socket-outlets are
Kitchen:not permitted in domestic Premises, see clause 7.1.1.

13 A switched socket-outlets
4
(BS 1363)

20 A spur connection points


3
(for washing machine, dryer etc)

45 A cooker control unit 1

Bedrooms 4

Lounge or dining 4

Hall or corridor 1

Bathrooms Only BS3535 shaver socket

166 The Electricity Wiring Regulations 2007


A16. Mounting height for accessories and
socket-outlets

A16

Min. 1.0 m from sink


Min 1.3m

Cooker control unit

Min 450mm

Flex outlet

Note: Mounting height may be varied for special circumtances such as access for disabled
persons or children, etc.
[ see clause 7.1.7 , 7.2.5 and 7.1.9 ]

Min. 100mm from worktop

The Electricity Wiring Regulations 2007 167


A17(a) Approved and prohibited plugs
and socket-outlets (domestic)

[ see Regulation 7.1 ]


A17(a)

Approved BS 1363 plug and socket (13 A fused)

Approved BS 546 plug and socket (15 A or 5 A unfused)

(non-domestic
only)

Prohibited C E7/7 ‘shuko’ plug and socket


EE7/7 ‘shuko’ plug

Type CEE7/16 ‘europlug’ permitted only with a correct adapter

168 The Electricity Wiring Regulations 2007


A17(b) Industrial plugs and socket-outlets

A17(b)

[ BS 4343 and BS EN 60309 ]

[ see clause 7.1.6 ]

The Electricity Wiring Regulations 2007 169


A17(c) BS 3535 shaver socket-outlets
for bathrooms

A17(c)

230V
230V

115V
N

Isolating transformer
complying with BS 3535

shavers only

[ see Regulation 9.3 and clause 7.1.4 ]

170 The Electricity Wiring Regulations 2007


A18(a) Class I equipment (earthed metallic
parts)

A18(a)

Earth fault

Earth fault

[ see clause 6.6.3 ]

The Electricity Wiring Regulations 2007 171


A18(b) Class II equipment (double insulated)

A18(b) Dummy (plastic)


earth pin

Live conductors
are double insulated
or enclosed in plastic case

Unearthed
metallic part (see
note)

Plastic Case

Live conductors
are double insulated
or enclosed in plastic case

2-pin plug for use


in BS 3535 socket-outlet
(see A17c)

Note: Metallic parts of Class II appliances are sufficiently remote from live
conductors so as not to require a connection to earth.

(see clause 6.6.3)

172 The Electricity Wiring Regulations 2007


A18(c) Separated extra-low voltage (SELV)
supply

A18(c)

Isolated metallic parts

max 50V a.c.


230V or 120V d.c.

N
E

overcurrent protection

Symbol for safety


isolating transformer complying
with BS EN 60742 or BS 3535

[ see clause 5.3.1 , 5.7.4 , 7.3.13 and 9.1.1 ]

The Electricity Wiring Regulations 2007 173


A18(d) Protective extra-low voltage (PELV)
supply

A18(d)

Earthed metallic parts

230V
max 50V a.c.
or 120V d.c.

[ see clause 9.2.1 ]

174 The Electricity Wiring Regulations 2007


A18(e) Reduced low voltage (RLV) supply

A18(e)

55V

230V
110V
55V

[ see clause 5.3.1 and 9.6.3 ]

The Electricity Wiring Regulations 2007 175


A19(a) Measurement of earth electrode
resistance

A19(a)

Red
Yellow
P Green
E

5 - 10m5 - 10m
Earthed Electrode under test
Auxilliary Earth Spikes

(i) a proprietary earth electrode test device should be used


(ii) auxiliary earth spikes should be applied at least 5 m apart and 5 m distant from
the electrode under test
(iii) an earth resistance value of less than 10 ohms is required for a Customer Earthed
System [ see Regulation 6.2 ].
(iv) an additional number of electrodes may be required (or deeper electrodes) to
achieve the required earth resistance value
(v) due consideration should be given to future changes in soil condition (e.g.
drying out)
(vi) sufficient time should be allowed if special chemicals or salts are added to
the ground to improve the earth resistance values

Earth Pit Earth Test Spike

176 The Electricity Wiring Regulations 2007


A19(b) Measurement of external earth fault
loop impedance

Main Distribution Board


A19(b)

MCCB MCCB
+ +
E/F E/F

External Earth Loop


Impedance Tester

Main Earth Terminal

Main Earthed
Equipotential Bonding

To Earth Electrode
A Earth Bar
Test Link removed
and Earth Electrode
Connection removed

Notes:
1. Caution: this test is carried out under live conditions but with the main isolator secured in
the off position.
2. Ze may be measured directly at the Supply Intake with a specialist Earth Loop Impedance
tester. Such devices apply a resistance (typically 10 ohms) between a phase conductor
and the earth conductor of the incoming supply. The test draws a current of around 20A
but is only applied for a few cycles (e.g. 40ms). The device measures the drawn current
and divides this into the measured supply voltage to give the loop impedance (the test
resistance applied by the device is subtracted).
3. As an alternative Ze may be calculated from measurement of the total earth fault
loop impedance measured within the installation (see A19c) using the formula:

Where:
Zs = total Earth Fault Loop Impedance ZS = Ze + ZR1+R2
Ze = Distribution Company supply impedance
ZR1+R2 = impedance of the longest circuit in the Installation, taken by measuring a circuit
phase conductor impedance R1, and the same circuit’s Earthing Conductor impedance
R2.
4. For further advice see reference book “ Advanced Testing Technique”.

The Electricity Wiring Regulations 2007 177


A19(c) Measurement of internal earth fault
loop impedance

Final Distribution Board

R Y B R Y
B R Y
B

Main Distribution Board

RCDRCD

to switch (must be ON)


from FDB

Bonding Conductors

to Test Instrument
Earth Electrode

A19(c) Incoming Supply Cable

to light
(bulb removed from pendant)
Notes:

1. Caution: this test is carried out under live conditions with the circuits under test energised
but no load is connected. The Main Earth Conductor to the local earth electrode (if any) is
disconnected and the Main Equipotential Bonding Conductors are also disconnected.
2. A specialist instrument is used which measures the total Earth Loop Impedance Zs using
a similar principle as described in A19(b). The instrument must not operate any RCD in
circuit.
3. The instrument may be directly connected to a socket-outlet (using the test plug provided) and
should be used at the farthest point on a radial circuit or the mid point of a ring circuit.
Alternatively, the instrument may be used at an accessory connection point (e.g. lighting
ceiling rose) with the appropriate test probes.
4. For further advice see reference book “Testing Electrical Installations”.
178 The Electricity Wiring Regulations 2007
A19(d) Circuit continuity tests

A19(d)

Final DB A

R Y B R Y
B R Y
B

Neutral Bar

B
Test Instrument

Earth Bar

Ring Circuit Radial Circuit

Notes:
1. This test is carried out on dead circuits. The main isolator must be secured in the off positio
2. Circuit continuity tests must be measured for all circuits and the resistance values
recorded on the test report, see Appendix A20(d). Alternative methods are illustrated as
above.
3. Method A tests the combined phase and earth resistance (R1 + R2) for each circuit by
shorting together the two conductors at the distribution board, and measuring from the
terminals of the farthest connection point or socket-outlet. For ring circuits the two
phase and earth conductors from the ring are cross connected as illustrated above.
4. In method B a shorting cable is applied between the neutral and earth bar at the
distribution board. Measurement at any connection point gives a value Rn + R2 (neutral
conductor resistance + circuit earth conductor) which approximates to R1 + R2.

The Electricity Wiring Regulations 2007 179


A19(e) Circuit polarity tests

A19(e)
To Final To switch
DB (must be ON)

To Light holder

Final DB

to
Test
Device

OFF

Earth Bar Shorting cable applied at Final


DB between phase conductor
and earth conductor of circuit
under test

Notes:

1. This test is carried out on dead circuits. The main isolator must be secured in the
OFF position.
2. The polarity test is required to confirm that all single pole devices, and lamp holders with
an outer neutral contact (i.e. ES screw type) are correctly connected
3. Single pole devices ( eg. light switches ) must only be connected in the live conductor.
4. The test is carried out by measuring continuity between the earth terminal and live
terminal at an accessory such as an ES pendant light fitting , after a shorting cable has
been applied between the relevant phase conductor and earth bar at the Final Distribution
Board.

180 The Electricity Wiring Regulations 2007


A19(f) Insulation resistance tests

Circuit Nominal Test Minimum insulation A19(f)


Voltage Voltage resistance (M ohms)
(d.c.)

SELV and PELV 250 0.25

up to 500 V 500 0.5

1. Insulation resistance should be checked between all live conductors,


and between live conductors and Earth. For SELV and PELV systems
insulation resistance should be measured between the extra-low voltage
and higher voltage conductors at 500 V.

2. The test instrument should be capable of producing a d.c. test voltage


of 500 V when loaded to 1 mA and be capable of measurement of up to
200 M ohm.

3. The minimum acceptable value of insulation resistance for any test is


0.5 M ohm for LV systems and 0.25M ohm for SELV and PELV systems.

4. The supply should be disconnected and all current-using equipment


switched off (including neon indicator lamps, voltmeters, electronic devices
such as dimmer switches, starters, RCDs with amplifiers etc).
Alternatively, a limited test can be carried with the phase and neutral
conductors connected together and testing to earth.

5. Insulation measurements should be made at each Distribution Board


between each pair of phases in turn, between each phase and neutral, and
between each phase and Earth.
6. A final test should be made between the neutral bar and Earth; if
a reading of less than 2 M ohm is observed, then each neutral
conductor should be tested separately to Earth.

The Electricity Wiring Regulations 2007 181


A19(g) Sequence of testing for new
installations

A19(g)
Correct sequence for safe testing

Before supply is connected:


Note: Safety precautions must be observed during testing, including locking off
isolators and switches, safeguarding against contact with test voltages,
1. replacement
Continuity of
of earth conductors
test links (MainofEarth
and removal tools Conductors and The order
after completion.
ofCircuit
test sequence must be observed, in particular testing of Earth
Earth Conductors)
Conductors (dangerous test voltages can appear on the installation
2. Continuity of main and supplementary bonding conductors
metalwork if Earth Conductors are inadvertently disconnected or
3. broken).
Continuity of Ring Circuit conductors
4. Insulation resistance
5. Polarity tests
6. Earth electrode resistance

After supply is connected:

1. External earth fault loop impedance test


2. Re-confirm polarity
3. Earth fault loop impedance
4. Operation of RCD and earth fault devices
5. Operation of switches and isolators
6. Prospective fault current measurement

182 The Electricity Wiring Regulations 2007


Electrical Installation certificate

Project / Building Name:................................................................................ Certificate No. / Ref:

Address / Location: .............................................................................................. ………………….......

Details of Client / Customer: ……………………………………………………………………………...................

……………………………………………………………………………...................
A20(a)
Electricity account no. / contact details: ……………………………………………………………………………...

New or modified installation: New:  Modification:  Existing: 

Brief description of work carried out: ……………………………………………………………………………………

………………………………………………………………………. Previous Certificate number:.........................

Supply Characteristics:

Earthing System: (TT, TN-S, TN-S-TT); .........………… Earth Electrode(s )Resistance: ............………

Incoming Cable Size & Type: .........………… Earth Electrode(s) Location: ............………

Main CB type & rating: .........………… Main Earth Conductor Size: ............………

Protective System (ELPS, EEBS); .........………… Earth Fault Loop Impedance: ............………

Max Prospective Fault Current: .........………… Total Connected Load: ............………

Meter ref. no’s and type: ................................................................................................................................

Details of Designer: ……………………………………………………………………………...................................

Contact Details: ……………………………………………………………………………...................................


We hereby declare that the work completed by us in relation to the above named installation, and detailed
in the reference drawings and documents listed below, has been carried out with due skill and care, and in
accordance with the Electricity Wiring Regulations 2007 published by the Regulation & Supervision Bureau for
the Water, Wastewater and Electricity Sector in Abu Dhabi:

Authorised signatory & name: ……………………………..…..…… Date: …………………….....................

………………………..………..……

Reference drawings and schedules: ………………………….. Company Stamp: …………................

Details of Installer: ...............…………………………… Licence Number: ………………….....................

Contact Details: ……………………………………………………………………..…………………..................


We hereby declare that the work completed by us in relation to the above named installation, and detailed
in the reference drawings and documents listed below, has been carried out with due skill and care, and in
accordance with the Electricity Wiring Regulations 2007 published by the Regulation & Supervision Bureau for
the Water, Wastewater and Electricity Sector in Abu Dhabi:

Authorised signature & name: ………………………………………… Date: ……………….…....................

………………………………………………………………………….....

Reference drawings and schedules: .....……………………………… Company Stamp: ……………............

The Electricity Wiring Regulations 2007 183


Inspection report (front)

Project / Building Name:................................................................................ Report No

Address / Location: ..............................................................................................

Details of Client / Customer: ……………………………………………………………………………...................


A20(b)
……………………………………………………………………………...................

Electricity account no. / contact details: ……………………………………………………………………………...

New or modified installation: New:  Modification:  Existing: 

Reason for Inspection (first inspection, routine inspection, other):


.....................................................................

............................................................................................... Installation Certificate number: …………..


Supply Characteristics:

Earthing System: (TT, TN-S, TN-S-TT); .........……… Earth Electrode(s) Resistance: ............………..

Incoming Cable Size & Type: .........……… Earth Electrode(s) Location: ............………..

Main CB type & rating: .........……… Main Earth Conductor Size: ............………..

Protective System (ELPS, EEBS): .........……… Earth Fault Loop Impedance: ............………..

Max Prospective Fault Current: .........……… Total Connected Load: ............………..

Meter ref. no’s and type: .............................................................................................................................

General Details of Inspection & Testing:

Date of last inspection & test: .......................................................................................................

Any modifications noted: No  Yes  Details: ........................................................................

Estimated age of installation & estimated age of modifications:


...............................................................
Date of next planned inspection: .......................................................................................................

Any dangerous conditions or urgent work required (give details over leaf): No  Yes 

Any work or improvements recommended (give details over leaf): No  Yes 

Extent of inspection: All:  Part:  Areas not tested / inspected:...........................................................

Inspection carried out by: .…………………………………………………………………………................

Contact Details: …………………………………………………………………………….............


We hereby declare that the inspection and testing completed by us in relation to the above named
installation, and detailed over leaf, has been carried out with due skill and care, and in accordance with the
Electricity Wiring Regulations 2007 published by the Regulation & Supervision Bureau for the Water,
Wastewater and
Electricity Sector in Abu Dhabi:

Authorised signature & name:……………………………..…..…… Date:……………………....................

………………………………………….………………………..…… Company Stamp: .............................


184 The Electricity Wiring Regulations 2007
Inspection report (back)
Equipment Inspected:  satisfactory  not satisfactory (give details /comments)

 not applicable  urgent work required

Main intake room condition: .......................................................................................   A20(c)

Metering Equipment: .......................................................................................  


Main Distribution Board: .......................................................................................  
Main Isolation Device (CB): .......................................................................................  
Main LV switchboard (if any): .......................................................................................  
Incoming supply cable(s): .......................................................................................  
Main earth conductor, earth pits,
and MET;
.......................................................................................  

Sub Distribution Boards (give ref. no’s): .......................................................................................  


.......................................................................................

.......................................................................................  
Distribution Cables (between DBs): .......................................................................................  
.......................................................................................  
Main Earth Leakage Protective
Device(s):
.......................................................................................  

Circuit cables (where visible): .......................................................................................  


Power factor correction equipment: .......................................................................................  
Standby generation equipment: .......................................................................................  
Power points & socket outlets: .......................................................................................  
.......................................................................................  
Internal Inspection of sample points (10% sample):

List circuits/connections inspected .......................................................................................  

.......................................................................................  

.......................................................................................  

The Electricity Wiring Regulations 2007 185


A20(
1

Installation testing report

Project/Building Name: ................................................................................. Document No./Ref................................... Test Instruments ( serial no.s)

Address/Location: ................................................................................. Tested by................................................. Loop impedance tester:.....................

Distribution Board No./Ref: ................................................................................ Date:....................................................... Continuity tester:................................

Fed from: ................................................................................. Date:....................................................... Insulation tester:.................................

CCT CCT MCB Phase Eart Continuity Test Total Functional


(ohms) Insulation Resistance
Identity ref. rating & h Earth Test
No. No. (A) Neutral wire Loop
Circuit name Remarks

Polarity
size size R1 R2 Ring L-L Live-Earth Impen- RCD Other
T

mm2 mm2 + R2 ance time


see note see note (zs) (ms)
Electric

1
1
Wiri
Reg
ti
20

Deviation from Wiring Regulations & Special Notes: Testing carried out by:
.................................................................................
Company name/stamp:
.................................................................................
Date:
.................................................................................
Note1: for L-L or L-E insulation resistance tests enter the lowest value measured for either R-Y, Y-B, R-B.
Load distribution schedule

Project/Building Name ..........................................................................................................................................................................................................................


................................................................................. Incoming Cable size / type and ECC:
Address/Location .........................................................
..........................................................................................................................................................................................................................
Distribution Board No./Ref ................................................................................. Main breaker type & rating:
..........................................................................................................................................................................................................................
Fed from: .........................................................
..........................................................................................................................................................................................................................
CCT CCT MCB Phase Earth Circuit Load in Watts
Identity ref. rating & Conductor Watt
No.
No. No (Amps) Neutral size Circuit name / Point reference s per Remarks
of R Y B
. Size point
mm 2 points
mm2
Th Electric
Wiri
Reg
ti
20

TOTAL CONNECTED LOAD ............................KW Remarks:

TOTAL LOAD AFTER DIVERSITY ............................KW Remarks:


1

A20(
188 The Electricity Wiring Regulations 2007
Guidance notes

The Electricity Wiring Regulations 2007 189


190 The Electricity Wiring Regulations 2007
Guidance notes
G
G1. Guidance note on supply voltage change 193

G2. Estimation of connected load and


diversity factors 194

G3. Photographs
(a). Photograph of busbar riser 196
(b). Photograph of final distribution board 197

G4. Electric shock, ELP and EEB systems


(a) Direct contact with electricity 198
(b) Indirect contact with electricity 199
(c) Main and supplementary earthed
equipotential bonding (EEB) 200
(d) Illustration of earth leakage protected
system (ELPS) 201
(e) Grading of RCDs in an ELP system 202
(f) ELP system supplied from LV switchroom 203
(g) Calculation of touch voltage (ELP system) 204
(h) Calculation of touch voltage (EEB system) 205

G5. Electric shock and RCD characteristics


(a) RCD operating characteristics and electric shock 206
(b) Typical values of body resistance and
physiological effects 207
(c) RCD operating principle 208
(d) Types of RCDs 209
(e) Sources of nuisance tripping of RCDs 210

G6. Protection of buried cables 211

The Electricity Wiring Regulations 2007 191


G7. Common errors
(a) Exposed unsheathed cables at termination points 212
(b) Protection of high temperature connections 213
(c) Weather protected outdoor socket-outlets 214
(d) Earth tails in accessories and connection boxes 215
(e) Minimum depth of buried plastic conduit 216
(f) Circuit identification numbers on
accessories and earth conductors 217
(g) Missing grommets and sharp edges on cable
tray 218
(h) Cables in ceiling-voids 219
(i) Cable glands for earthing of armoured cable 220
(j) Earth continuity connections across cable
tray and conduit 221
(k) Prohibited terminal blocks and taped connections 222
(l) Slotting of steel gland plates for single core cables 223

192 The Electricity Wiring Regulations 2007


G1. Guidance note on supply voltage change

Distribution Companies in the UAE have traditionally based the


design of their networks on the UK power system. Previously, the
voltage of supply was declared to be 240 V single-phase or 415 V
three phase, with an allowed variation in voltage of +/- 6%. With the
harmonization of supply voltages in Europe (in line with IEC 38) the
G1
UK has adopted a supply voltage of 230 V or 400 V +/- 10% .

These Regulations have adopted the same nominal voltage of supply,


but with a narrower range of +10% - 6% (clause 4.1.3). This range
has been adopted to allow existing distribution network assets to
continue to operate without modification, and also provides a superior
voltage range to Customers. With an allowed voltage drop of 4%
within a Customer's Installation (clause 7.5.10) this ensures the total
voltage drop to Appliances will not exceed 10% of the nominal
voltage of 230/400 V.

225.6240 254.4
-6%+6% Old UK supply voltage
range previously used in

207.0 230 253.0


-10%+10%
IEC.38 supply

216.2 230 253.0


-6% IEC.38 supply voltage operated
+10% under a restricted range as adopted
in the Wiring Regulations (2007)

200 210 220 230 240 250 260

The Electricity Wiring Regulations 2007 193


G2. Estimation of connected load and
diversity factors

Estimation of connected load for domestic premises

Applied
1: loadThe diversity factors
Note of
Type indicated
Assumed in column
connected load 3 may be applied to
diversity
G2 each group of loads in order to calculate the 'diversified
factor
connected load'.
• sum offactor
Note 2: A 90% diversity wattage
mayofbeallapplied
luminaries or assume
for split or window type
100 W units; diversity factors for central a/c units
air conditioning
75%
Lighting should befor based
each lighting point (except chandelier
on manufacturers data orpoints)
load readings
taken •from
chandelier
other lighting
similarpoints – 1,000 W(during summer
installations
• 1.8 conditions).
temperature x lamp wattage for fluorescent lighting
• 200 watts per socket-outlet (except kitchen)
13A socket-
• for kitchen worktop socket-outlets 100%
outlets
assume 1,000W each

• kitchen appliance connection points (flex


outlet) assume 3,000 W each (e.g.
Kitchen power
washing machine, dryer, dishwasher, 75%
points etc)
• cooker – rating of oven plus 2 larzgest rings
• fridge – full rating (e.g. 300 W)
Other power • water heater – full rating
30-
points • motors (e.g. lifts) – full rating
50%

• split air conditioning units – full rating


Air conditioning • window air conditioning units – full rating 90%
• central a/c units, (see note 2)

194 The Electricity Wiring Regulations 2007


G2. Continued...

The total estimated load at a Premises must be calculated and


submitted to the Distribution Company in order to make an
application for a new supply of electricity or alteration of an existing
supply (clause 3.2.5).

Normal practice is to calculate the ‘Diversified Connected Load’


G2
rather than simply take the sum of all equipment and Appliances in the
Installation. This method avoids oversizing of the Installation as well
as the Distribution Company supply.

Firstly, the design and layout of an installation should be detailed in


the format of load distribution schedules as shown in Appendix
A20(e). These schedules should list all connection points and fixed
Appliances in each circuit.

For domestic Premises the total ‘Diversified Connected Load’ can be


derived using the guidelines in the table above.

For non-domestic Premises the above rules and diversity factors do


not apply and estimation of loads must be made by a qualified
designer or engineer with knowledge of the proposed usage of the
Installation.

For example, the connected load of industrial machinery in


continuous operation would be taken as 100%. In contrast, equipment
operating in short duration cycles (e.g. a few minutes) could have a
diversity factor as low as 20%. Another example could be a warehouse
with automatic motion-operated lighting, which may result in a
diversity factor as low as 10%. Alternatively, the average load per m2
of floor area can be used if such data is available from other similar
Premises e.g. 50 W or m2 for normal use offices, 100 W or m2 for high
density offices, 150 W or m2 for computer rooms, etc. Floor area
loading data normally excludes central air conditioning demand which
is calculated separately.

The Electricity Wiring Regulations 2007 195


G3(a). Photograph of busbar riser

G3

Typical busbar riser system including plug-in circuit breaker

196 The Electricity Wiring Regulations 2007


G3(b). Photograph of final distribution board

G3

The Electricity Wiring Regulations 2007 197


G4(a) Direct contact with electricity

G4(a)

[ see Regulation 5.3 ]


198 The Electricity Wiring Regulations 2007
G4(b) Indirect contact with electricity

1. Contact between Exposed-Metallic-Part and Extraneous-Metallic-Part


2. Contact with Exposed-Metallic-Part
3. Contact with Extraneous-Metallic-Part

G4(b)
MDB

MET

EEB Conductor

Supply Cable

CEC

Earth Fault

Extraneous Extraneous
Metallic Part Metallic Part
(water pipe) (building
structure)

Note: Illustration shows TN-S supply system i.e. Distribution Company Earthed with
Earthed Equipotential Bonding (EEB) of Extraneous metalwork. Live conductors are
not shown for clarity.

[ see Regulation 5.3 and 5.5 ]

The Electricity Wiring Regulations 2007 199


G4(c) Main and supplementary earthed
equipotential bonding (EEB)

G4(c) Distribution Circuits

MCCB FDB
CECCIRCUIT B

MCCB MCCB
CEC

MEC CIRCUIT A

MET

Isolator
Supplementary EEB

Main EEB

Supply
Cable
(TN-S)

Note 1. Live conductors are not shown for clarity.


Note 2. Characteristics of MCBs for Final Distribution Boards must be coordinated against earth
loop impedance values to give a maximum of 0.4 sec tripping for circuit A (socket-outlet
supplying portable appliances) and 5 sec for circuit B (fixed appliances only). Also,
MCCBs must coordinate to give a maximum of 5 sec tripping time for distribution
circuits. ( see clause 5.5.2 and 5.5.3 )

[ see Regulation 5.5 ]

200 The Electricity Wiring Regulations 2007


G4(d) Illustration of earth leakage protected
system (ELPS)

FDB

G4(d)

RCD RCD

MEC CEC

MCCB
+
E/F
MCCB MCCB
+ +
E/F E/F

MET

Isolator

Main
Supply
(TN-S-TT)
System

Note: Main Distribution Board includes MCCB with sensitive earth fault setting (provides
backup to RCDs in Final Distribution Board). Live conductors are not shown for
clarity.

[ see Regulation 5.4, clause 5.4.7 ]

The Electricity Wiring Regulations 2007 201


G4(e) Grading of RCDs in an ELP system

G4(e)

MDB FDB

RCD RCD 100mA


type S (see Note 1)

RCD 30mA 30mA

Outdoor socket-outlet with


30mA RCD

Note 1: Type S RCDs provide time delayed operation in order to discriminate with RCDs at the Final
Distribution Board. Alternatively, for high current applications a MCCB with sensitive earth
fault (E/F) relay may be used.

Note 2: 30mA RCD protection is required for socket-outlets serving portable appliances; 100mA
RCD protection is required for fixed appliances and circuits

[ see Regulation 5.4, clause, 5.4.5, 5.4.6 ]

202 The Electricity Wiring Regulations 2007


G4(f) ELP system supplied from
LV switchroom

G4(f)

SDB
with MCCBs

R Y B R Y
B R
Y B

RCD RCD

100mA 30mA

Final DB with 100mA and 30mA RCDs

Earth Leakage Protection Relay

Main Circuit Breaker

Incoming Supply Cables

[ see clause 5.4.5 and 5.4.6 ]

The Electricity Wiring Regulations 2007 203


G4(g) Calculation of touch voltage
(ELP system)

Extraneous Metallic Part


G4(g) NL
V
t
I
F

R2

MET V VtVf
F

Ze

Notes

1. Touch Voltage Vt is approximately equal to the fault voltage Vf assuming that


the Extraneous-Metallic-Part is in good contact with Earth.

2. Ze is the resistance of the earth electrode (TT system) or the incoming supply earth
fault loop impedance (TN-S) system.

3. The illustration shows unbonded Extraneous-Metallic-Parts, such as in a Earth


Leakage Protected System (ELPS).

[ see Regulation 5.5 ]

204 The Electricity Wiring Regulations 2007


G4(h) Calculation of touch voltage
(EEB system)

NL Extraneous Metallic Part


G4(h)
R1 V
t
I
F
Rs
R2
VR2 Supplementary EEB

MET
Main EEB
VtV R2

Ze

RMET

Notes:

Without supplementary EEB the touch voltage Vt is approximately equal to the voltage drop across
the Circuit Earth Conductor resistance R2 .

To calculate Vt :

Vt VR2 = IF x R2 = Uo x R2
Zs
Where :
UO = supply voltage to earth
Zs = total earth fault loop impedance

Example:

For an appliance supplied by an MCB (type C) of nominal rating 16A the maximum
earth fault loop impedance to give a 0.4 sec disconnection time, given under appendix
A5(h) is 1.5 Ohms. R2 is measured as 0.9 Ohms.

Hence: Vt = 230 x R2 = 138 V


1.5
If the measured earth loop impedance is higher than 1.5 Ohms the time-current characteristic of
the MCB will need to be checked to see if a disconnection time of 0.4sec can be achieved (the
touch voltage will be higher), otherwise RCD protection will be required. If supplementary bonding
is applied then the touch voltage is dramatically reduced (the voltage drop equates to the current
passing through the supplementary bonding times the resistance of the supplementary bonding
Rs).

The Electricity Wiring Regulations 2007 205


G5(a) RCD operating characteristics and
electric shock

These Regulations include a compulsory requirement for provision of


Earth Leakage Protection (ELP) on all Final Circuits where Appliances
may be used by any persons (clause 5.3.5). This is normally achieved
with RCD devices complying with IEC 60898 or BS 3871 which
must operate within 200 ms at their residual current rating (tripping
G5(a) current) and within 40 ms at 5 times their residual current rating.
RCDs must not operate at below 50% of their residual current rating.
RCD devices with a residual operating current of 30 mA or less may be
used for supplementary protection against Direct Contact, whilst devices
rated above this value provide protection against Indirect Contact only
(see clause 5.3.2).
ELP devices do not protect against electric shock between phase
conductors or between phase and neutral. The response of the human
body depends on the time and magnitude of current that may pass at the
time of an electric shock incident. The ‘low risk’ and ‘high risk’ range of
current against time is illustrated below, along with the operating times of
typical RCD devices (from IEC 60479).
A B C1 C2 C3 IEC 60479
10,000

5,000

2,000

1,000
1 2 3 4
500
Time in

200

100

50

20

due to body resistance at 230V.


10 30mA RCD 100mA RCD
0.1 0.2 0.3 0.5 12 3 510 20 30 50 100 200 300 500 1,000 2,000 3,000 5,000 10,000
Current in milliamperes (RMS)
Typical current
Response of humanlimits body vs. RCD characteristics:

Zone 1: usually no reaction


Zone 2: shock sensation, but usually no harmful effects
Zone 3: likelihood of muscular contraction, and temporary cardiac arrest without ventricular
fibrillation
Zone 4: in addition to the effects of zone 3, the probability of ventricular fibrillation is increased
by 5% for curve C2 and 50% for curve C3; harmful effects such as cardiac arrest,
breathing arrest and burns are likely to occur

206 The Electricity Wiring Regulations 2007


G5(b) Typical values of body resistance and
physiological effects

Human Resistance for Various Skin Contact Conditions (k Ohms)

Touch area Dry Wet

Finger touch 40 – 4 – 15 G5(b)


1,000
Hand hold on wire 15 – 50 3–6

Hand hold on pipe 1–3 0.5 –


1.5
Palm touch 3–8 1–2

Internal body resistance (including skin) = 0.2 – 1 k Ohms

Voltage required to produce


Electric Current the current with assumed
(1 second Physiological Effect body resistance:
contact)
100 k Ohms 1 k Ohms

Threshold of feeling,
1 mA 100 V 1V
tingling sensation

Accepted as maximum
5 mA 500 V 5V
harmless current

Beginning of sustained
10-20 mA muscular contraction 1000 V 10 V
("Can't let go" current.)

Ventricular fibrillation,
fatal if continued.
100-300 mA 10000 V 100 V
Respiratory function
continues

The Electricity Wiring Regulations 2007 207


G5(c) RCD operating principle

RCD devices measure the vector sum of currents passing through


the phase and neutral conductors in a circuit, via a magnetic coil and
electronic amplifier. The device will trip if these are out of balance
by more than the residual operating current, in accordance with the
manufacturer's time-current performance curve. See Guidance Note
G5(c)
G5(a).

The older type of voltage-operated earth leakage devices (ELCB) are


not permitted (clause 5.4.2) since they operate by detecting fault
voltage and require a connection between a Main Earth Conductor and
an Earth Electrode; these devices are therefore vulnerable to
maloperation due to parallel earth paths.

Three-phase RCD:
Test button

Test resistor

L1 L2 L3 N L1 L2 L3 N
Load circuits

Incoming supply

Trip relay

Single-phase RCD:
Test button

Test resistor

L L

N N
Load circuits

Incoming supply

Trip relay

208 The Electricity Wiring Regulations 2007


G5(d) Types of RCDs

Because of the use of semiconductor devices in an Installation there


may be situations when an earth fault current is not purely sinusoidal
but contains a d.c. or ‘chopped’ waveform. This may de-sensitise or
disable standard a.c. operated RCDs. Special devices are available
which are designed to continue to function for non-sinusoidal supply
waveforms, complying with IEC1008, IEC1009 (indicated by the G5(d)
symbols shown below).

For RCD devices installed at a Main Distribution Boards time delayed


operation is usually required to avoid tripping when a fault occurs in
a Final Circuit (the FDB RCD should trip first). Time delayed RCD
devices are labelled 'S type'.

TYPE AC TYPE A
normal ac sensitivity pulsating dc sensitivity

Reproduced with permission


of Wylex / Electrium.

The Electricity Wiring Regulations 2007 209


G5(e) Sources of nuisance tripping of RCDs

Type of fault Reason

G5(e) • Direct contact by persons


• Indirect contact (during earth fault)
• Incorrect discrimination with series
Note: RCDs may also trip (correctly) because of Direct Contact by a person or
connected RCDs (e.g. between MDB and
Indirect Contact (during earth fault)
FDB)
• Loose connections
• Crossed neutral connections
on split busbar distribution
board
Downstream of • Neutral to earth fault
RCD
• High earth conductor currents
(e.g. IT equipment, filters, etc)
• Moisture in circuit
conductors (especially joints
in MICC cables)
• Moisture in appliances (e.g. cooker
heating element)
• Double pole switching (capacitive effects)
• Transient voltages caused by
large inductive loads (e.g.
industrial motors)
• Damage circuits (e.g. nails in walls)
• Loose connections
• Mains borne disturbances (e.g.
surges, lightning, transients from
Upstream of RCD
overhead lines)

210 The Electricity Wiring Regulations 2007


G6. Protection of buried cables

Cable marker plate


G6
Concrete or steel
protective tiles

Min 600mm in footpath


Min 750mm in road

Min 100mm

Note: cables should be installed in ducts to allow for future removal (clause 7.5.8)

The Electricity Wiring Regulations 2007 211


G7(a) Exposed unsheathed cables at
termination points

G7(a)

[ see clause 7.4.8 and 7.5.12 ]

212 The Electricity Wiring Regulations 2007


G7(b) Protection of high temperature
connections

G7(b)

Heat resistant sleeve required


for high temperature
connections
[ see clause 7.5.17 ]

The Electricity Wiring Regulations 2007 213


G7(c) Weather protected outdoor
socket- outlets

G7(c)

30mA

PU
SH
H
IP66 weather protected socket outlet with 30mA RCD

[ see clause 7.1.14, 9.4.1(b), 9.5.1(b), 9.6.2(g) ]

214 The Electricity Wiring Regulations 2007


G7(d) Earth tails in accessories and
connection boxes

G7(d)

Double socket-outlet

Plastic light switch

[ see clause 6.6.4 ]

The Electricity Wiring Regulations 2007 215


G7(e) Minimum depth of buried plastic
conduit

G7(e)

Min 50mm

Buried plastic conduits in walls or ceilings must be min 50mm depth or metal conduit
must be used (see clause 7.4.6 )

216 The Electricity Wiring Regulations 2007


G7(f) Circuit identification numbers on
accessories and earth conductors

G7(f)

(Circuit identification numbers,


See clause 3.6.4 , 3.6.5)

[ see clause 6.5.3 ]

The Electricity Wiring Regulations 2007 217


G7(g) Missing grommets and sharp edges on
cable tray

G7(g)

[ see clause 7.4.8 ]

218 The Electricity Wiring Regulations 2007


G7(h) Cables in ceiling-voids

G7(h)

See clause 7.3.8 and 7.5.15

(flexible connections to be limited to 3m in length


and securely fixed; ‘plug & fit’ connection systems
may be used after the main supply connection)

The Electricity Wiring Regulations 2007 219


G7(i) Cable glands for earthing
of armoured cable

G7(i)

Earth conductor size must be in accordance with


Appendix A5(j)

[ see clause 7.5.18 ]

220 The Electricity Wiring Regulations 2007


G7(j) Earth continuity connections across
cable tray and conduit

G7(j)

[ see clause 6.6.1 and 7.4.4 ]

The Electricity Wiring Regulations 2007 221


G7(k) Prohibited terminal blocks and taped
connections

G7(k)

[ see clause 7.5.16 ]

222 The Electricity Wiring Regulations 2007


G7(l) Slotting of steel gland plates for single
core cables

Slot

Steel Plate

G7(l)

Note: Single core cables in a steel enclosure will cause electromagnetic currents
in the steel and possible overheating. This can be avoided by ensuring that a
non-ferromagnetic material is used around the cables (e.g. brass plate) or slots
are cut in the steel between the phase conductors.

[ see clause 7.5.11 ]

The Electricity Wiring Regulations 2007 223


224 The Electricity Wiring Regulations 2007

You might also like