Addc
Addc
Electricity Wiring
Regulations
Issued by:
the Regulation and Supervision Bureau
for the Water, Wastewater and Electricity Sector
in the Emirate of Abu Dhabi
www.rsb.gov.ae
December 2007
Regulation and Supervision Bureau
for
the Water, Wastewater and Electricity
Sector in the Emirate of Abu Dhabi
The Bureau has drafted these Regulations to promote the installation and
operation of safe electricity wiring systems in all customers’ premises.
These Regulations are based on the general principles defined in
British Standard BS 7671 (otherwise known as the IEE Wiring
Regulations, UK) which are also similar to the International Standard
IEC 60364. Such principles have been common practice in Abu Dhabi
and were adopted in previous documents, including the first Wiring
Regulations issued by WED in 1972.
Government organisations:
Abu Dhabi Water and Electricity Authority
Al Ain Distribution Company
Abu Dhabi Distribution Company
Abu Dhabi Municipality
Al Mirfa Power Company
Dubai Electricity and Water Authority (DEWA)
Dubai Municipality (Central Laboratory)
Sharjah Electricity and Water Authority
(SEWA) Federal Electricity and Water
Authority (FEWA)
Emirates Standardisation and Metrology Authority (ESMA)
Private organisations:
Benchmark Electrical Safety Technology
Ltd Parsons International Ltd
Schneider Electric FZE
Voltas Limited, UAE
Ian Banham Associates
Pell Frischmann Consultants
Gibb Ltd
Power Economy Middle East
WSP Middle East Ltd
GHD Ltd (Aust/UAE)
ABB Industries LLC
(Dubai) Power Connections
Ltd Reed Smith Richards
Butler British Standards
Institute Electrium Ltd
Chapter
Regulation
Note
Clause
ED/R01/010
Dec 2007 TK LH Publication
Issue 1
1 Introduction 11
1.1 Citation and commencement 11
1.2 Purpose and document structure 11
1.3 Scope and enforcement 12
2 Definitions 15
2.1 Interpretation 15
5 Protection 41
6 Earthing 53
6.1 General principles 53
6.2 Systems of earthing 53
6.3 Main earth terminal 54
6.4 Earth electrodes 55
6.5 Earth conductors 56
6.6 Exposed-metallic-parts 58
6.7 Earth fault loop impedance 59
6.8 Lightning protection 60
6.9 Functional earthing and high
leakage currents 60
Appendices 101
1.3.10 These Regulations and the rights and duties of any parties
thereunder shall be governed by, construed and applied
in accordance with the Laws of Abu Dhabi Emirate and
the Federal Laws of the UAE as applied by the Courts of
Abu Dhabi.
Words which are defined under this section are used in the
Regulations beginning with capital letters. For example, “all Earth
Conductors within a Premises shall be ...”.
Terms in common use are not defined here and normal dictionary
definitions apply (e.g. circuit-breaker, plug, conduit).
Words using the singular or plural number also include the plural or
singular number, respectively.
Principl
accordance with Regulation 3.2.
Principl
of isolating the electricity supply at suitable sections,
subsections and Circuits, and at points where Appliances
are used, see Regulation 5.6.
Principl
expected operating environment. The following
environmental conditions may be used as a guide if no
other special factors apply:
3
(a) maximum ground temperature (at 1 m depth): 35˚C;
(b) soil resistivity: according to local conditions;
(c) weather: mainly sunny, occasional fog (causing
condensation on outdoor equipment), and occasional
sandstorms;
(d) air quality: frequently dusty;
(e) maximum humidity: 100%;
(f) maximum ambient (air) temperatures:
• outdoor (shaded): 50˚C
• outdoor (unshaded): temperature rise due to solar
gain must be calculated for the relevant equipment
or the maximum ‘black bulb’ temperature may be
used (typically 10 ˚C above ambient temperature)
• indoor (not air conditioned): 40˚C
• indoor (air conditioned): 30˚C
[Note: in some situations the ambient temperature for indoor
non-air-conditioned situations may reach the outdoor shaded
temperature e.g. a small prefabricated building with little
ventilation, or a garage which is open to the atmosphere.]
4.2.6 The use of Supply Intake rooms as storage rooms for any
Supply
tools, equipment or other materials is prohibited.
4.2.7 The Supply Intake must not be located on the reverse side
of a bathroom or kitchen wall, or below a bathroom or
kitchen. The Supply Intake must not be located below any 4
water services or pipes, such as mains water supply,
storage tanks, air conditioning chillers, or other liquids or
hazardous materials.
Supply
all Customers in a Premises.
(a) overload;
(b) short-circuits (phase to phase or phase to Earth); and
(c) electric shock (due to Direct or Indirect Contact with
electricity).
Direct contact
Protectio
(d) Protective Extra-Low Voltage (PELV) system.
[Note: SELV conductors at voltages of 12 V a.c. or 30 V d.c.
may be un-insulated but must be provided with overload and
short circuit protection.]
5
5.3.2 Residual Current Devices with a residual current rating of
30 mA and complying with IEC 60898 or BS 3871 may
be used as a means of supplementary protection against
Direct Contact. However, RCDs may not be used as the
sole means of protection against Direct Contact i.e. one
of items (a) to (d) above must be used in addition to RCD
protection.
[Note: RCD devices with a residual current rating above 30 mA
are not considered to provide adequate protection against
Direct Contact but may be used to provide protection against
Indirect Contact – see Regulation 5.4. It should also be noted
that earth leakage devices do not protect against electric shock
between phase conductors or between phase and neutral.]
Protectio
performance characteristic complying with IEC 60898 or
BS 3871. This requires that the device must operate
within 200 milliseconds at its residual current rating and
within 40 milliseconds at 5 times its residual current
rating. It must not operate below 50% of its residual
current rating, see Guidance Note G5(a). 5
Protectio
equipment or industrial machinery) may be provided with
ELP devices with higher residual current ratings, up to
500 mA. These must be clearly stated on the Electrical
Installation Certificate.
Protectio
(a) do not pose any risk of providing a conductive path
to Earth (are isolated from Earth); or
(b) do not pose any risk of providing a conductive path
to any other Earthed part of the Installation; or
(c) do not pose any risk of becoming live as a result of
5
an electrical fault in the Installation (i.e. are
sufficiently remote from any Circuit or Appliance);
or
(d) are out of reach of any person.
[Note: such items may include metal doors, window frames,
inaccessible structural beams, small metallic fixings such as
screws and brackets, etc.]
Protectio
5.7 Insulation
6.2.3 In all cases the neutral and Earth Conductors must be kept
separate and not connected together at the MET or at any
other point in the Customer’s Installation.
Earthi
6.4.3 Earth Electrodes will normally comprise of 15 mm
diameter steel-cored copper rods driven to a minimum
depth of 3 m. The top of each Earth Electrode must be 6
housed inside a 300 mm x 300 mm x 300 mm inspection
pit which is clearly labelled and accessible for routine
testing, see Appendix A5(d). Alternative types of Earth
Electrodes may be used with prior approval of the
Distribution Company (e.g. plate or wire mesh type, or
structural steelwork in a building).
6.4.7 Metallic service pipes (such as water, gas, etc) must not be
used as Earth Electrodes.
Earthi
Terminal must be made using purpose made lugs or other
fixings and the connection must be clearly labelled as shown
in Appendix A5(d).
6
6.5.7 All Circuits must have a Circuit Earth Conductor sized in
accordance with Appendix A5(j).
6.6 Exposed-metallic-parts
Earthi
Appliance Earth Conductor);
(b) the Main Earth Terminal;
(c) the main Earth Conductors connecting to local Earth
Electrodes (TT system) or the Distribution Company
6
Earth (TN-S system);
(d) the path of earth fault current through the general
mass of Earth, or through the earth sheath or
armouring of the Distribution Company cable;
(e) in the case of a Customer Earthed System (TT system)
the neutral earth connection at the Distribution
Company transformer;
(f) the distribution transformer winding; and
(g) the phase conductors of the Circuit back to the point
of fault.
6.7.2 All Installations must be designed and tested such that the
Earth Fault Loop Impedance at any point in the
Installation is of a sufficient value to operate Protective
Devices within
0.4 seconds for Final Circuits supplying Appliances which
Earthi
equipment. Alternatively, Circuit Earth Conductors in a Ring
Circuit are also accepted as providing a duplicate earth path.
This requirement safeguards against electric shock due to
Indirect Contact if only one Circuit Earth was provided and was
damaged or broken.] 6
7.1.3 The use of 2-pin plugs such as the ‘Euro’ CEE7/16 plug
and the ‘Shuko’ CEE7/7 plug is strictly prohibited, unless
provided with an approved adaptor converting such plugs
for use on BS 1363 type sockets, see Appendix A17(a).
[Note: adapters must be approved by a recognised international
approvals authority such as KEMA, NSAI, ASTA, etc.]
Componen
inductive effects.
7.2.4 For areas with higher than normal risk of fire or explosion
gas-sealed switches must be used (BS 5345). For example, in
gas storage areas, battery rooms, etc.
7.3 Lighting
Componen
in an easily accessible position.
[Note: such switches may be marked “Fireman’s Switch for
Neon Sign” or similar wording.]
7.3.9 Luminaires and other light fittings must be installed with due
consideration to the weight taken by fixings and supports,
and the need for adequate ventilation and heat dissipation.
7.3.11 Where light switch boxes contain more than one phase
(for large groups of lighting) they must be labelled to
indicate the presence of a 400 V supply, and suitable
phase barriers should be provided inside the box.
7.4.2 All metal conduit and trunking must comply with either
BS 4568, BS EN 60423 or BS EN 50086. Cable tray must
comply with BS EN 61537.
Componen
7.4.6 Where conduit is buried in a wall, floor or ceiling it must
be installed at a minimum depth of 50 mm from the
surface. If installed at a shallower depth, then metal
conduit must be used. See Guidance Note G7(e).
7
7.4.7 Conduit, trunking and cable tray must be installed so as
to provide ease of access to cable Circuits throughout the
route. Sufficient inspection plates and pulling points must
be provided to enable inspection, repair and drawing out
of cables throughout the life of the Installation.
Componen
7.5 Cables
7.5.3 For locations with higher than normal fire risk either
cables must be installed in metal conduit or mineral-
insulated- copper-clad (MICC) cables must be used
(complying with BS 6207). In addition, safety Circuits
such as fire alarms, emergency lighting and control
Circuits, which are required to remain operational in the
event of a fire, must be installed in metal conduit or
supplied by MICC cables.
7.5.9 Cables for meter tails (at 230 V) shall be single-core, PVC
insulated, with oversheath, and comply with BS 6004.
Componen
7.5.15 Exceptions to clause 7.5.12 may be allowed only for
sheathed or flexible cables which will remain accessible
but in locations free from undue risk of damage or
interference (e.g. above head height, or in unoccupied
areas). Such cables must be securely supported by cable
clips, cable tray or other fixings at suitable intervals. 7
[Note: although flexible cords must not be used as fixed wiring
this clause covers Appliance connection cables which should be
limited to 3 m in length where practicable. In addition, proprietary
plug and fit connection systems may be installed from a suitable
connection point in the fixed wiring system, provided they are
suitably supported, mechanically protected, or otherwise
located in areas where there is minimal risk of damage or
interference. See Guidance Note G7(h).]
7.5.19 Cables must not be installed in lift shafts other than those
serving lift functions.
[Note: although a lift shaft may be a convenient means of
providing a cable route through a building this creates
unwarranted risk when accessing such Circuits for
maintenance and also provides a vulnerable route for the
propagation of fire.]
7
7.5.20 The colour identification for cables is given in
Appendix A8.
[Note: although the identification colours for cables has
recently been changed in European countries a similar change
is not currently proposed for Abu Dhabi Emirate. For fixed
wiring in an Installation the phase colours remain as red,
yellow and blue whilst neutral remains as black. However, for
flexible sheathed cables supplying single-phase Appliances
brown is used for live and blue is used for neutral – see
Appendix A8.]
7.6.1 The sizing of Final Circuits must take into account the
diversity of use of Appliances and equipment as well as
possible increases in load requirements. See Guidance
Note G2 for advice on load diversity factors.
Componen
day. Ring Circuits would typically be installed in
bedrooms, living rooms, kitchens (except major
Appliances such as cookers), partitioned office areas, etc.
7.7.2 Busways, bus ducts and busbar risers shall comply with
the relevant reference standards given in Appendix A3.
7.7.3 Busways, bus ducts and busbar risers shall be totally enclosed
(non-perforated) for protection against mechanical
damage, moisture, dust and other environmental effects.
7.7.4 Busways, bus ducts and busbar risers shall not be located
in areas prone to mechanical damage or where they may
be exposed to hazardous materials, liquids or gases, unless
special precautions are taken.
7 7.7.6 Busways, bus ducts and busbar risers shall have neutral
conductors of equal size to the phase conductors and shall
have a dedicated Earth Conductor. The use of the metal
casing as an Earth Conductor shall not be permitted.
7.7.7 The current rating of busways, bus ducts and busbar risers
shall be based on the Connected Load of the relevant part
of the Installation being supplied. However, additional
diversity factors may be applied for high-rise buildings
or other large installations rather than taking the sum of
Connected Loads. Any applied diversity factors must be
justified and submitted with the design for approval by the
Distribution Company, see Regulation 3.2.
Componen
7.8.2 Distribution Boards must be of robust construction,
capable of withstanding expected electrical, thermal, and
environmental stresses in normal service and during
faults.
7.8.5 Each Distribution Board must have an Earth bar which has
a means of connection to the incoming Earth Conductor
and cable gland of the incoming cable, see Appendix
A5(e) and A12(c).
Componen
rooms), within 2 metres of any pipe or other source of
water, or in difficult-to-access positions (such as
stairways).
7.9 LV switchboards
Internal External
Installation Installation
Non-domestic
3 years 3 years
(commercial, industrial, farms, etc)
Special locations
1 year 1 year
(construction sites, swimming
pools and fountains, street lighting)
Inspectio
8.2.2 Electrical Installations which were constructed before the
date of commencement of these Regulations (clause 1.1.2)
shall be inspected and tested within the time indicated
above from the date of commencement.
8
8.2.3 Routine inspection and testing shall be recorded on the
standard forms shown in Appendices A20(b) – A20(d)
and shall include:
(a) Earth;
(b) any Earthed Metallic Part of another system or
Extraneous-Metallic-Part; or
(c) an Earth Conductor of any system.
similar location.
person;
person;
10.1.6 For induction motors, the capacitor rating must not exceed
90% of the no-load reactive power of the motor.
[Note: this is required in order to avoid the high overvoltage
across the terminals due to the occurrence of self excitation on
run-down condition of the motor.]
10
1 HP to 5 HP 5 x full-load current
A5. Earthing
(a) Distribution company earthed system (TN-S) 123
(b) Customer earthed system (TT) 124
(c) Distribution company earthed system with
additional earth (TN-S-TT) 125
(d) Earth electrode pit and standard labels 126
(e) Main earth terminal (MET) at main
distribution board (MDB) 127
(f) Main earth conductors (MEC) and circuit earth
conductors (CEC) 128
(g) Components of earth fault loop impedance 129
(h) Earth fault loop impendance values required for
MCBs (at 230 V) 130
(i) Resistance per metre of copper conductors for
calculation of R1+R2 131
(j) Sizing of earth conductors and equiptential bonding
conductors 132
(k) Minimum number of earth electrodes 134
(l) Mandatory connections to earth
conductors 135
A Amps or Amperes A1
a.c. alternating current
ADWEA Abu Dhabi Water and Electricity Authority
The Association of Short-circuit Testing Authorities
AS (UK)
BS British Standard
British Standard which has been published under
BS the European Normalisation procedure
BSI British Standards Institute
CB Circuit-Breaker
CCP Customer Connection Point (see definitions)
CEC Circuit Earth Conductor (see definitions)
Circuit Protective Conductor (see definition
C
for
CEC)
d.c. direct current
Earth Continuity Conductor (see definition for
E CEC)
EEB Earthed Equipotential Bonding (see definitions)
Earthed Equipotential Bonded System (see
EE definitions)
E/F Earth Fault (protective device)
ELCB Earth Leakage Circuit-Breaker (see definitions)
ELP Earth Leakage Protection (see definitions)
ELV Extra-Low Voltage (see definitions)
EN European Normalisation standard document
ELPS Earth Leakage Protected System (see
definitions) ESMA Emirates Standardisation & Metrology
Authority FDB Final Distribution Board (see definitions)
HP Horse-Power (= 0.746 kW)
Table
s of HE
seconds A1
S cross-sectional area (of conductors, mm*)
SDB Sub Distribution Board (see definitions)
SELV Separated Extra-Low Voltage (see
definitions)
a Distribution Company earthed Installation (see
TN definitions)
a Distribution Company earthed Installation with
TN-S- additional Customer Earths (see definitions)
TT a Customer Earthed Installation (see definitions)
Uo nominal phase voltage
WED Water and Electricity Department (Abu Dhabi)
Ze External Earth Fault Loop Impedance
Zs Total Earth Fault Loop Impedance (see definitions)
Z
R1+R2 Internal Loop Impedance (R1 = resistance of circuit
conductor, R2 = resistance of earth conductor)
A2 Books:
Regulations:
Reference Papers:
A3
Components BS IEC
Cables
Power & lighting (70˚C PVC,
6004 502
thermoplastic)
Power and lighting (90˚C rubber,
6007, 7889
thermosetting)
Mineral insulated (copper-clad) 6207 702
Flexible cables & cords (domestic) 6500 227
Flexible cables & cords (industrial) 7919 245
Flexible cables (high temperature) 6141
Armoured cables (70˚C PVC,
6346
thermoplastic)
Low smoke (90˚C rubber, 7486, 7211,
thermosetting) 6724, 7629
Armoured cables (90˚C rubber,
5467
thermosetting)
Switchgear and control wiring 6231
Flexible cables for lifts 6977
Cable glands, crimp connectors 6121, 4579
Conduits & trunking
4568, 60423*,
Steel 423, 614
50086*, 31
PVC 4607
Flexible Steel 731
Cable tray 61537*
Trunking 4678
Electrical accessories
General 5733
Ceiling roses 67
Cooker Control Units 4177
Components BS IEC
Accessories continued...
Household Appliances 3456, 60355*
546, 196, 1363,
Plugs & Socket-outlets (domestic)
4573
Plugs & Socket-outlets (industrial) 4343, 60309*
Switches (domestic) 3676, 60669*
Lighting 4533, 60598*
Emergency lighting 5266
Signs and discharge lighting 559
3535, 60742*,
Isolating (safety) transformers
61558*
LV switchgear & assemblies
General 60439*, 5486 439
Contactors & motor starters 60947* 947
Circuit-Breakers (MCB, MCCB) 60898*, 3871 898
4293, 61008*,
Circuit-Breakers (RCD, RCBO) 755
61009*
88, 1361,
Fuses
60269*
Busbar trunking systems 60439-2 439-2
General
Fire / combustibility test 476, 6458
Degrees of protection & ingress 60529* 529
Assemblies for construction Sites 4363 364-7-704
5345, 60079*,
Hazardous areas
50014*, 5501
Lightning protection 6651
Earthing 7430, 951, 4444 364-5-54
Wiring diagram symbols 60617*
A3 Identification and marking of the
60446*
man-machine interface
Note: 1: British Standards marked with an asterix * are also issued as European A3
Standards under the same number (labelled as BS EN).
Note: 2: For compliance requirements under the Regulations see clause 3.1.2
and 3.1.4.
A4(a) The Electricity Wiring Regulations are effective from 1 January 2008.
For any installations which were constructed prior to this date, the
following Regulations and clauses either:
Note 1: The requirement for Earth Leakage Protection was introduced in Abu
Dhabi Emirate in 2001 by implementation of the Earth Leakage Protection
Regulations (issued by the Bureau). The Electricity Wiring Regulations
reiterate this same requirement and replace the ELP Regulations.
(2) protect the general public from danger related to electrical and
water works and installations;
(3) require plans, maps etc to be kept and made available for
inspection and copying;
(4) relieve the Abu Dhabi Water and Electricity Company and
classes of licensed operators specified in the regulations
from obligations to supply water and electricity in specified
circumstances;
1
Article 68 relates to Street Works and Access Regulations
A4(b) (5) require compliance with notices served by the Regulation and
Supervision Bureau which –
(13) forbid the use or installation of fittings which have not been
approved;
The court with the appropriate jurisdiction shall hear disputes relating
to regulations made under Article (62) of this Law.
Article 12
The Bureau, when performing its functions and duties under this Law,
is committed to execute in its best ways, functions that achieve the
following:
2
unofficial translation
Article (13)
Paragraphs (1), (4), (6), (7) and (8) of Article (55) of Law No. (2) of 1998,
shall be replaced by the following paragraphs:
Article (15)
"In consultation with the Authority" in Article (62) of Law No. (2) of
1998, is replaced by "in consultation with who sees appropriate".
Paragraphs (1), and (2) of Article (63) of Law No. (2) of 1998, is
replaced by the following two paragraphs:
Article (17)
Provisions of Paragraphs (2), and (4), and (14) of Article (65) of Law No.
(2) of 1998, is replaced by the following paragraphs:
Article (18)
A5(a)
[ see Regulation 6.2 ]
Distribution
Distribution
Company
Network
Transformer
Conductors
L1 L2 L3 N
E
A
Transformer
Neutral Point Earth
Customer’s Main Distribution Board
Earth fault
Main Earth in Appliance
Terminal Earth fault current
L1 L2 L3 N
E
Transformer
Neutral Point Earth
Insulated cable
gland
L1 L2 L3 N
E
Transformer
Neutral Point Earth
A
Earth fault current shared between Customer Earth Electrode and Distribution Company Earth
Customer’s Main Distribution
Board
A5(d)
SAFETY EARTH
CONNECTION
DO NOT REMOVE
Standard safety label for
Main Earth Connections
A5(e)
Circuit Earth Conductors for sub-main
circuits
CEC To SDB1
To SDB2
MET
Neutral Bar
Earth conductor
Alabels at MET
Test Link
B
Distribution
Company Earth
A5(f)
CEC to switches and
Accessories
Final Distribution
Board
CEC to fixed Appliance
Earth Bar
MEC
Main Distribution
Board
MEC
Note: Common terminology (outside these Regulations) includes CPC (Circuit Protective
Conductor) and ECC (Earth Continuity Conductor ) in place of CEC illustrated above.
[ see Regulation 6.2 ]
9 L1
L2
L3
N
E
6 11
Transformer Neutral8 Supply Intake Circuit Breaker
Point Earth
X
7
1 N
5
L
E
2
4 MET 3 Earth fault in Appliance
Main Earth Terminal
1.0 18.1
1.5 12.1
2.5 7.41
4.0 4.61
6.0 3.08
10.0 1.83
16.0 1.15
25.0 0.73
Note: To allow for the increase in resistance with increased temperature under
fault conditions these values must be multiplied by 1.2 for PVC
insulated cables.
Note 1: For Main Earth Conductors between S Earth Electrodes andSthe / 2Main Earth
<= 16 of an Installation,(not
STerminal less than (not less thanarea
S should be taken as the cross-sectional 4 of
the conductors of the 2.5incoming
see note 2)supply cable.or 6,For
seeother
note 3)
Earth
Conductors S should be taken as the cross-sectional area of the circuit
16 phase
< S <=conductors.
35 16 10
Note 2: Earth Conductors should always be insulated and a cross-sectional area
of less than 2.5 mm2 should not be used unless they are an integral part
of a sheathed cable (e.g. an Appliance flexible S / 4 cord).
S > 35 S/2
Precautions should be taken against corrosion (but not
andexceeding
damage 25)(e.g.
installed in conduit or ducts).
Note 4: As an alternative to using the above selection table, the sizing A5(j)
of Earth Conductors and Equipotential Bonding Conductors
may be calculated using the adiabatic equation provided in the
IEE Wiring Regulations BS7671:2001 paragraph 543-01-03.This normally
allows smaller sizes of Earth Conductor to be used.
60/100 1 16
200 1 50
300 1 50
400 1 70
500 2 70
600 2 70
800 2 70
1000 2 70
1600 2 70
2000 2 150
2500 2 150
Switchgear: exposed-metallic-parts
(frame, door etc)
Luminaires: exposed-metallic-parts
Note 1: The earthing of cover plates should not rely solely on the connection
of fixing screws to an earthed mounting box (due to the
possibility of poor connections, corrosion etc); a short flexible
Earth Conductor should be connected between the mounting box
and the plate. See Guidance Note G7(d).
A5(m)
Residual operating
Equipment
current settings (mA)
13 A switched-socket outlets 30
Note: Where two values are indicated the higher value is allowed only where the
Water heaters 30
equipment is not normally accessible to any person.
Kitchen fixed Appliances
30
(e.g. washing machine)
The table opposite shows the required residual operating current A5(m)
values for RCDs and other Earth Leakage Protection devices. These
are intended to provide for electric shock protection (Direct and
Indirect Contact), particularly in high-risk areas, as well as protection
against high resistance earth faults which may not operate overcurrent
devices and pose a risk of overheating or fire, see Regulation 5.4.
All Final Circuits where Appliances may be used by any person must
be provided with Earth Leakage Protection (clause 5.3.5 ) and back-
up Earth Leakage Protection must be provide at the main Supply
intake for Installations classed as an Earth Leakage Protected System,
see Regulation 5.4.
A6(a)
2 HRS
1 HR
1,000
100
10
OPERATING TIME IN
1.0
0.1
TypeTypeType
BCD
0.01
0.001
Reproduced with
permission of Crabtree /
Electrium Ltd.
A
0
10
A
5
12
1
A
3
6
A
0
8
6
10 000
Time / current characteristics
for Type B circuit-breakers to
BS EN 60898
and RCBOs to BS EN
61009
Current for time 0.1 sec to 5
secs
Rating Current
1000
6A 30 A
The Electricity Wiring Regulations
10 A 50 A
16 A 80 A
20 A 100 A
100
25 A 125 A
32 A 160 A
40 A 200 A
TIME,
50 A 250 A
10 63 A 315 A
80 A 400 A
100 A 500 A
125 A 625 A
1
0.1
A
0
10
A
5
12
1
A
3
6
A
0
8
6
10 000 Time / current characteristics
for Type C circuit-breakers to
BS EN 60898
and RCBOs to BS EN
61009
Current for time 0.1 sec to 5 secs
Rating Current
1000
6A 60 A
The Electricity Wiring Regulations
10 A 100 A
16 A 160 A
20 A 200 A
100
25 A 250 A
32 A 320 A
40 A 400 A
TIME,
50 A 500 A
10 63 A 630 A
80 A 800 A
100 A 1000 A
125 A 1250 A
1
0.1
A
0
10
A
5
12
1
A
3
6
A
0
8
6
10 000 Time / current characteristics
for Type D circuit-breakers to
BS EN 60898
and RCBOs to BS EN 61009
Current for time 0.1 sec to 5 secs
Rating Current
1000
6A 120 A
10 A 200 A
16 A 320 A
The Electricity Wiring Regulations
20 A 400 A
100
25 A 500 A
32 A 640 A
40 A 800 A
TIME,
50 A 1000 A
10 63 A 1260 A
80 A 1600 A
100 A 2000 A
125 A 2500 A
1
0.1
A6(
A6(e) Typical energy let-
through characteristics of
MCBs
A6(e)
105
50&63A
40A 2.5mm2
32A
I2t energy let-through in A2s (50Hz sine wave)
20A
one complete 1/2 cycle
16A
10A
1.5mm2
TOTAL LET-THROUGH ENERGY
6A
1.0mm2
104
CABLE CONDUCTOR
103
0.1 1.0 10 16 100.0
Operating characteristics of MCB types and the required earth fault A6(f)
loop impedance values are given in Appendix A6(a) to A6(d) and
Appendix A5(h). MCBs for common cable sizes and Circuits are
shown in the following table:
Radial Circuit
32.0 27.8
20 4.0 to fixed
(6.3) (5.4)
appliance
(e.g. a/c unit)
41.0 35.7 Ring Circuit to
32 6.0
(8.0) (7.0) socket-outlets
Radial Circuit
6.0 41.0 35.7
32 to large
(8.0) (7.0)
Appliance (e.g.
cooker)
Radial Circuit
57.0 49.6
40 10.0 to machinery
(11.1) (9.7)
(e.g. chiller
unit)
Note: Cable rating should be at least 20% greater than MCB nominal rating
to afford overload protection for the cable. Cable ratings are taken from
Appendix A7(a) with temperature correction factors applied from
Appendix A7(g) and assuming 2 cables cores installed in conduit.
kW ratings assume 0.85 power factor at 230V.
A6(g)
15 plate Moving
arc chamber contact
Fixed
contact
Thermo-metal
element
Calibration
mechanism
Operating
handle
A7(a) Standard cable ratings and Voltage drop for single core, PVC (70˚C
thermoplastic), non-armoured, stranded copper conductor (BS6004
and BS6346), with or without sheath, installed in buried or surface
conduit or trunking.
2.5 19.5 18 24 21 18 15
4.0 26 24 32 28 11 9.5
10 46 42 57 50 4.4 3.8
16 61 56 76 68 2.8 2.4
25 80 73 101 89 - -
35 99 89 125 110 - -
Note 2: For voltage drop for cables above 25 mm2 refer to BS 7671.
Standard cable ratings and voltage drop for PVC (70˚C thermoplastic) A7(b)
multi-core cables (sheathed), non-armoured, stranded copper
conductor (BS6004), installed in buried or surface mounted conduit or
trunking, or on exposed, perforated cable tray.
On perforated
In conduit on wall Clipped direct
Cross cable tray or in
or in concrete to a wall
sectional free air
(A) (A)
area (A)
(mm²)
2 core 3 or 4 2 core 3 or 4 2 core 3 or 4
core core core
2.5 23 20 27 24 30 25
4 30 27 36 32 40 34
6 38 34 46 41 51 43
10 52 46 63 57 70 60
16 69 62 85 76 94 80
A7(b)
Cable size (mm²)
Voltage drop
1.0 1.5 2.5 4 6 10 16
(mV/A/m)
Note 1: For voltage drop for cables above 16 mm² refer to BS 7671.
Standard cable ratings and Voltage drop for multi-core armoured, A7(c)
PVC (70˚C thermoplastic) cables, stranded copper conductor (BS
6346 and BS 5467), installed exposed (clipped to a wall) or on
perforated cable tray.
1.5 21 18 22 19 29 25
2.5 28 25 31 26 18 15
4 38 33 41 35 11 9.5
6 49 42 53 45 7.3 6.4
10 67 58 72 62 4.4 3.8
16 89 77 97 83 2.8 2.4
25 118 102 128 110 - -
35 145 125 157 135 - -
50 175 151 190 163 - -
70 222 192 241 207 - -
95 269 231 291 251 - -
120 310 267 336 290 - -
150 356 306 386 332 - -
185 405 348 439 378 - -
240 476 409 516 445 - -
300 547 469 592 510 - -
A7(d) Standard cable ratings and voltage drop for multi-core, 90˚C
thermosetting plastic insulated, armoured cable, stranded copper
conductor (BS6004), surface mounted or on cable tray
1.5 27 23 29 25 31 27
2.5 36 31 39 33 19 16
4 49 42 52 44 12 10
6 62 53 66 56 7.9 6.8
10 85 73 90 78 4.7 4.0
16 110 94 115 99 2.9 2.5
25 146 124 152 131 - -
35 180 154 188 162 - -
50 219 187 228 197 - -
70 279 238 291 251 - -
95 338 289 354 304 - -
120 392 335 410 353 - -
150 451 386 472 406 - -
185 515 441 539 463 - -
240 607 520 636 546 - -
300 698 599 732 628 - -
Note 2: For voltage drop for cables above 16 mm² refer to BS 7671.
Standard cable ratings and voltage drop for mineral insulated copper- A7(e)
clad cables installed on a wall (clipped direct). PVC sheathed cable
assumes 70˚C sheath temperature, bare copper-clad cable assumes
105˚C sheath temperature.
(70˚C) 3
2 x single
3 x single
PVC sheath
PVC sheath
area
core
or twin
Note 1: For MICC cable installed in perforated cable tray the current rating is
approximately 5 - 10%, greater than shown above, see BS 7671 table
4J1A and 4J2A.
Note 2: Where the sheath temperature may be above 70˚C care should
be taken that the cable is not within reach of any person or in contact
with combustible materials.
A7(f) Standard current ratings and voltage drop for flexible cords–60˚C
conductor temperature (PVC or rubber insulated), stranded copper
conductors to BS 6500 (domestic applications).
0.5 3 3 93 80 2
0.75 6 6 62 54 3
1.0 10 10 46 40 5
1.25 13 - 37 - 5
1.5 16 16 32 27 5
2.5 25 20 19 16 5
4.0 32 25 12 10 5
A7(h) Because of mutual heating effects the following correction factors should
be applied to the tables in Appendix A7(a) to A7(e) for situations
where a number of cables are installed close together. These factors
assume all cables are fully loaded; however, if an individual cable is
loaded below 30% of its rating it may be excluded from the total
number in the group.
Method of installation
Horizontal
Touching
Touching
surface
Spaced
Spaced
Vertical
2 0.80 0.85 0.94 0.86 0.91 0.90 0.85
3 0.70 0.79 0.90 0.81 0.89 0.85 -
4 0.65 0.75 0.90 0.77 0.88 - -
5 0.60 0.73 0.90 0.75 0.87 - -
6 0.57 0.72 0.90 0.74 0.87 - -
7 0.54 0.72 0.90 0.73 - - -
8 0.52 0.71 0.90 0.73 - - -
9 0.50 0.70 0.90 0.72 - - -
10 0.48 - 0.90 0.71 - - -
12 0.45 - 0.90 0.70 - - -
14 0.43 - 0.90 - - - -
16 0.41 - 0.90 - - - -
18 0.39 - 0.90 - - - -
20 0.38 - 0.90 - - - -
A8
Conductor Colour
Phase 1 Red
Phase 2 Yellow
Phase 3 Blue
Neutral Black
Phase 1 Brown
Neutral Blue
1.5 7 12 -
2.5 5 9 12
4.0 3 6 9
6.0 - 5 8
10.0 - 3 6
16.0 - - 4
A9
25.0 - - 3
Note: For cable trays and trunking the space factor (total cross-sectional area of
cables compared with the interior cross-sectional area of trunking) must
not exceed 50%.
A10
Ingress protection : IP codes
0 No protection 0 No protection
3 Objects > 2.5mm (e.g. tools or 3 Sprays of water < 60˚ from
wires) vertical
7 Temporary immersion
8 Total immersion
Symbol Description
Fuse
Link
A11
A11
Symbol Description
A12(a)
A12(b)
Meters
13A socket outlet
Capac ban
Main Supply Cable
A12(c)
Load distribution schedule
fixed to door
R
Y
B
R
Y
B
R
Y
B
Main
Earth
Terminal
Main
Isolator
RCD 1
100mA RCD 2
30mA Neutral
Bar
“earth tail’
for door
buried conduits
Customer Notice
A12(d)
Emergency light
Outgoing (2 hour battery)
busbar risers
min 0.75 m
Outgoing
HRC
fuses
min 0.75 m
rear clearance
capacitor bank
automatic
control panel
min 1.5 m
front
clearance
Incoming cables
from Distribution Company
Transformer
A13
FDB
Meter
LV Feeder Pillar MDB B
FD
Distribution Network
“Electricity Supply Regulations 2007” Customer’s Installation
“Electricity Wiring Regulations 2007”
A14
Spur socket-outlet
Fused spur to fixed appliance
Spur socket-outlets
To Final
Distribution Board
15A BS 546
socket-outlet (non-domestic premises only)
A15
Minimum number of outlets for
Room domestic premises
Note: Socket-outlets should be located to avoid the need for customers
Single Doubleto use
extension cables and doubling adapters.15 A BS 546 socket-outlets are
Kitchen:not permitted in domestic Premises, see clause 7.1.1.
13 A switched socket-outlets
4
(BS 1363)
Bedrooms 4
Lounge or dining 4
Hall or corridor 1
A16
Min 450mm
Flex outlet
Note: Mounting height may be varied for special circumtances such as access for disabled
persons or children, etc.
[ see clause 7.1.7 , 7.2.5 and 7.1.9 ]
(non-domestic
only)
A17(b)
A17(c)
230V
230V
115V
N
Isolating transformer
complying with BS 3535
shavers only
A18(a)
Earth fault
Earth fault
Live conductors
are double insulated
or enclosed in plastic case
Unearthed
metallic part (see
note)
Plastic Case
Live conductors
are double insulated
or enclosed in plastic case
Note: Metallic parts of Class II appliances are sufficiently remote from live
conductors so as not to require a connection to earth.
A18(c)
N
E
overcurrent protection
A18(d)
230V
max 50V a.c.
or 120V d.c.
A18(e)
55V
230V
110V
55V
A19(a)
Red
Yellow
P Green
E
5 - 10m5 - 10m
Earthed Electrode under test
Auxilliary Earth Spikes
MCCB MCCB
+ +
E/F E/F
Main Earthed
Equipotential Bonding
To Earth Electrode
A Earth Bar
Test Link removed
and Earth Electrode
Connection removed
Notes:
1. Caution: this test is carried out under live conditions but with the main isolator secured in
the off position.
2. Ze may be measured directly at the Supply Intake with a specialist Earth Loop Impedance
tester. Such devices apply a resistance (typically 10 ohms) between a phase conductor
and the earth conductor of the incoming supply. The test draws a current of around 20A
but is only applied for a few cycles (e.g. 40ms). The device measures the drawn current
and divides this into the measured supply voltage to give the loop impedance (the test
resistance applied by the device is subtracted).
3. As an alternative Ze may be calculated from measurement of the total earth fault
loop impedance measured within the installation (see A19c) using the formula:
Where:
Zs = total Earth Fault Loop Impedance ZS = Ze + ZR1+R2
Ze = Distribution Company supply impedance
ZR1+R2 = impedance of the longest circuit in the Installation, taken by measuring a circuit
phase conductor impedance R1, and the same circuit’s Earthing Conductor impedance
R2.
4. For further advice see reference book “ Advanced Testing Technique”.
R Y B R Y
B R Y
B
RCDRCD
Bonding Conductors
to Test Instrument
Earth Electrode
to light
(bulb removed from pendant)
Notes:
1. Caution: this test is carried out under live conditions with the circuits under test energised
but no load is connected. The Main Earth Conductor to the local earth electrode (if any) is
disconnected and the Main Equipotential Bonding Conductors are also disconnected.
2. A specialist instrument is used which measures the total Earth Loop Impedance Zs using
a similar principle as described in A19(b). The instrument must not operate any RCD in
circuit.
3. The instrument may be directly connected to a socket-outlet (using the test plug provided) and
should be used at the farthest point on a radial circuit or the mid point of a ring circuit.
Alternatively, the instrument may be used at an accessory connection point (e.g. lighting
ceiling rose) with the appropriate test probes.
4. For further advice see reference book “Testing Electrical Installations”.
178 The Electricity Wiring Regulations 2007
A19(d) Circuit continuity tests
A19(d)
Final DB A
R Y B R Y
B R Y
B
Neutral Bar
B
Test Instrument
Earth Bar
Notes:
1. This test is carried out on dead circuits. The main isolator must be secured in the off positio
2. Circuit continuity tests must be measured for all circuits and the resistance values
recorded on the test report, see Appendix A20(d). Alternative methods are illustrated as
above.
3. Method A tests the combined phase and earth resistance (R1 + R2) for each circuit by
shorting together the two conductors at the distribution board, and measuring from the
terminals of the farthest connection point or socket-outlet. For ring circuits the two
phase and earth conductors from the ring are cross connected as illustrated above.
4. In method B a shorting cable is applied between the neutral and earth bar at the
distribution board. Measurement at any connection point gives a value Rn + R2 (neutral
conductor resistance + circuit earth conductor) which approximates to R1 + R2.
A19(e)
To Final To switch
DB (must be ON)
To Light holder
Final DB
to
Test
Device
OFF
Notes:
1. This test is carried out on dead circuits. The main isolator must be secured in the
OFF position.
2. The polarity test is required to confirm that all single pole devices, and lamp holders with
an outer neutral contact (i.e. ES screw type) are correctly connected
3. Single pole devices ( eg. light switches ) must only be connected in the live conductor.
4. The test is carried out by measuring continuity between the earth terminal and live
terminal at an accessory such as an ES pendant light fitting , after a shorting cable has
been applied between the relevant phase conductor and earth bar at the Final Distribution
Board.
A19(g)
Correct sequence for safe testing
……………………………………………………………………………...................
A20(a)
Electricity account no. / contact details: ……………………………………………………………………………...
Supply Characteristics:
Earthing System: (TT, TN-S, TN-S-TT); .........………… Earth Electrode(s )Resistance: ............………
Incoming Cable Size & Type: .........………… Earth Electrode(s) Location: ............………
Main CB type & rating: .........………… Main Earth Conductor Size: ............………
Protective System (ELPS, EEBS); .........………… Earth Fault Loop Impedance: ............………
………………………..………..……
………………………………………………………………………….....
Earthing System: (TT, TN-S, TN-S-TT); .........……… Earth Electrode(s) Resistance: ............………..
Incoming Cable Size & Type: .........……… Earth Electrode(s) Location: ............………..
Main CB type & rating: .........……… Main Earth Conductor Size: ............………..
Protective System (ELPS, EEBS): .........……… Earth Fault Loop Impedance: ............………..
Any dangerous conditions or urgent work required (give details over leaf): No Yes
.......................................................................................
Distribution Cables (between DBs): .......................................................................................
.......................................................................................
Main Earth Leakage Protective
Device(s):
.......................................................................................
.......................................................................................
.......................................................................................
Polarity
size size R1 R2 Ring L-L Live-Earth Impen- RCD Other
T
1
1
Wiri
Reg
ti
20
Deviation from Wiring Regulations & Special Notes: Testing carried out by:
.................................................................................
Company name/stamp:
.................................................................................
Date:
.................................................................................
Note1: for L-L or L-E insulation resistance tests enter the lowest value measured for either R-Y, Y-B, R-B.
Load distribution schedule
A20(
188 The Electricity Wiring Regulations 2007
Guidance notes
G3. Photographs
(a). Photograph of busbar riser 196
(b). Photograph of final distribution board 197
225.6240 254.4
-6%+6% Old UK supply voltage
range previously used in
Applied
1: loadThe diversity factors
Note of
Type indicated
Assumed in column
connected load 3 may be applied to
diversity
G2 each group of loads in order to calculate the 'diversified
factor
connected load'.
• sum offactor
Note 2: A 90% diversity wattage
mayofbeallapplied
luminaries or assume
for split or window type
100 W units; diversity factors for central a/c units
air conditioning
75%
Lighting should befor based
each lighting point (except chandelier
on manufacturers data orpoints)
load readings
taken •from
chandelier
other lighting
similarpoints – 1,000 W(during summer
installations
• 1.8 conditions).
temperature x lamp wattage for fluorescent lighting
• 200 watts per socket-outlet (except kitchen)
13A socket-
• for kitchen worktop socket-outlets 100%
outlets
assume 1,000W each
G3
G3
G4(a)
G4(b)
MDB
MET
EEB Conductor
Supply Cable
CEC
Earth Fault
Extraneous Extraneous
Metallic Part Metallic Part
(water pipe) (building
structure)
Note: Illustration shows TN-S supply system i.e. Distribution Company Earthed with
Earthed Equipotential Bonding (EEB) of Extraneous metalwork. Live conductors are
not shown for clarity.
MCCB FDB
CECCIRCUIT B
MCCB MCCB
CEC
MEC CIRCUIT A
MET
Isolator
Supplementary EEB
Main EEB
Supply
Cable
(TN-S)
FDB
G4(d)
RCD RCD
MEC CEC
MCCB
+
E/F
MCCB MCCB
+ +
E/F E/F
MET
Isolator
Main
Supply
(TN-S-TT)
System
Note: Main Distribution Board includes MCCB with sensitive earth fault setting (provides
backup to RCDs in Final Distribution Board). Live conductors are not shown for
clarity.
G4(e)
MDB FDB
Note 1: Type S RCDs provide time delayed operation in order to discriminate with RCDs at the Final
Distribution Board. Alternatively, for high current applications a MCCB with sensitive earth
fault (E/F) relay may be used.
Note 2: 30mA RCD protection is required for socket-outlets serving portable appliances; 100mA
RCD protection is required for fixed appliances and circuits
G4(f)
SDB
with MCCBs
R Y B R Y
B R
Y B
RCD RCD
100mA 30mA
R2
MET V VtVf
F
Ze
Notes
2. Ze is the resistance of the earth electrode (TT system) or the incoming supply earth
fault loop impedance (TN-S) system.
MET
Main EEB
VtV R2
Ze
RMET
Notes:
Without supplementary EEB the touch voltage Vt is approximately equal to the voltage drop across
the Circuit Earth Conductor resistance R2 .
To calculate Vt :
Vt VR2 = IF x R2 = Uo x R2
Zs
Where :
UO = supply voltage to earth
Zs = total earth fault loop impedance
Example:
For an appliance supplied by an MCB (type C) of nominal rating 16A the maximum
earth fault loop impedance to give a 0.4 sec disconnection time, given under appendix
A5(h) is 1.5 Ohms. R2 is measured as 0.9 Ohms.
5,000
2,000
1,000
1 2 3 4
500
Time in
200
100
50
20
Threshold of feeling,
1 mA 100 V 1V
tingling sensation
Accepted as maximum
5 mA 500 V 5V
harmless current
Beginning of sustained
10-20 mA muscular contraction 1000 V 10 V
("Can't let go" current.)
Ventricular fibrillation,
fatal if continued.
100-300 mA 10000 V 100 V
Respiratory function
continues
Three-phase RCD:
Test button
Test resistor
L1 L2 L3 N L1 L2 L3 N
Load circuits
Incoming supply
Trip relay
Single-phase RCD:
Test button
Test resistor
L L
N N
Load circuits
Incoming supply
Trip relay
TYPE AC TYPE A
normal ac sensitivity pulsating dc sensitivity
Min 100mm
Note: cables should be installed in ducts to allow for future removal (clause 7.5.8)
G7(a)
G7(b)
G7(c)
30mA
PU
SH
H
IP66 weather protected socket outlet with 30mA RCD
G7(d)
Double socket-outlet
G7(e)
Min 50mm
Buried plastic conduits in walls or ceilings must be min 50mm depth or metal conduit
must be used (see clause 7.4.6 )
G7(f)
G7(g)
G7(h)
G7(i)
G7(j)
G7(k)
Slot
Steel Plate
G7(l)
Note: Single core cables in a steel enclosure will cause electromagnetic currents
in the steel and possible overheating. This can be avoided by ensuring that a
non-ferromagnetic material is used around the cables (e.g. brass plate) or slots
are cut in the steel between the phase conductors.