c200h Alpha (Ingles)
c200h Alpha (Ingles)
BUILD YOUR
CPU RACK
OWN CONTROL
AND DATA
PROCESSING
SYSTEM
CPU
p.19
Choose from 11 CPU models
CPU BACKPLANE
C200HW-BC031 C200HW-BC051
Separate CPU and power supply C200HW-BC081 C200HW-BC101
Communications
All CPUs include a multifunctional
peripheral port to communicate
to programming peripherals
Standard Host Link port is built
into selected CPUs
One of six communications
boards can also be installed in p.21 p.18 p.19
the CPU. When used with the I/O CONNECTING POWER SUPPLY EXPANSION 1/O BACKPLANE
CABLE MODULE C200HW-BI031
protocol macro function, these C200H-CN❏❏1 C200HW-PA204 C200HW-BI051
(30cm,70cm,2m,5m,10m) C200HW-PA204S C200HW-BI081
boards provide a simple way to C200HW-PD024 C200HW-BI101
connect with a SYSMAC Link or
SYSMAC Net Link module, to
communicate with a Modem, SLAVE RACKS
operator interface, bar code
reader, Process Controller or any
kind of RS-232C, RS-422 or RS-
485 device.
Software Support
Supported by both SYSMAC
Support Software Version 1.2 or
greater and SYSWIN version 3.0
or greater
p.84 p.20
REMOTE I/O SLAVE MODULE SLAVE I/O BACKPLANE
Fiber-optic, 100/200 VAC C200H-RT001-P C200H-BC031-V2
Fiber-optic, 24 VDC C200H-RT002-P C200H-BC051-V2
4 Wired, 100/200 VAC C200H-RT201 C200H-BC081-V2
Wired, 24 VDC C200H-RT202 C200H-BC101-V2
SYSTEM COMPONENTS
COMMUNICATIONS MODULES
CPU Rack
Backplane
I/O Modules
Special I/O Modules
Communication CPU
Modules Power Supply
Module
NOTE:
Memory SELECT THE APPROPRIATE BACKPLANE FOR THE CPU RACK,
Cassette EXPANSION I/O RACK, AND SLAVE RACK. EACH TYPE OF
BACKPLANE IS A DIFFERENT MODEL.
Communications Board
For blackplane dimensions, refer to the Backplanes
subsection found later in this section.
To order, refer to the specific information provided
separately in the Standard Parts section of this catalog.
CPU Rack
The CPU Rack is the master controller rack for the control sys-
tems and contains the system communications ports. It may be
expanded using Expansion Racks and Slave Racks.
A fully configured C200Hα CPU Rack includes a CPU, Backplane,
Power Supply Module, I/O Modules, Special I/O Modules and
Communication Modules, as appropriate for the application.
A complete system may also include connecting cables and pro-
gramming software or hardware.
A total of two SYSMAC LINK or SYSMAC NET Link Modules can
be mounted to the CPU if the C200HW-COM01 or C200HW-
COM04-E Communications Board is connected to the CPU.
Only two C200HS-INT01 Interrupt Input Modules can be mounted
on a CPU Rack.
6
SYSTEM OVERVIEW
BASIC CONFIGURATION -- C200HX/HG/HE
Backplane
7
SYSTEM OVERVIEW
C200HX/HG/HE SPECIFICATIONS
8
CPU
YOUR INTRODUCTION TO THE C200HX/HG/HE CPU
Features
LED
Indicators
Select from Eleven C200Hα CPUs within Alpha’s
SYSMAC C200HX
Three Basic Model Types Programmable Controller Memory cassette
Each model has different program capacities, processing CPU64
Versatile Communications
Install one of six C200Hα Communications Boards to have addi- Indicators
tional communications ports. The boards fit into the communica-
INDICATOR ON THE CPU FUNCTION
tions slot in the CPU and enable communication with SYSMAC
LINK or SYSMAC NET modules, a PC card module or a variety
RUN (green) Lit when the PLC is operating normally.
of serial devices -- including Operator Interfaces. Order the
Communications Board and Memory Cassette separately (not ERR (red) Flashes if the PLC in operation detects any
non-fatal error. (The PLC will continue
provided with the CPU). operating.) Lit if the PLC in operation detects any
fatal error. (The PLC will stop operating. ) After
the PLC stops operating, the RUN indicator will
be off, and all output signals of the Output
Protocol Macro Modules will be interrupted.
Three C200Hα Communications Boards offer the Protocol Mac-
INH (orange) Lit when the Load OFF flag (AR bit) is ON. (All
ro Instruction that controls data transfer with various commu- output signals of the Output Modules will be
nications devices and components equipped with RS-232C or interrupted.)
RS-422/-485 ports. With the Protocol Macro Function built into COMM (orange) Flashes when the CPU is communicating with the
the C200HW-COM04, C200HW-COM05-E and C200HW- device connected to the peripheral port or
RS-232C port.
COM06-E Communications Boards, communications se-
quences (data transfer procedures) may be modified with Om-
ron’s Protocol Support Software.
Although seven Omron Communications sequences are built-in,
you can use the Protocol Support Software to create other com-
munications sequences. For more details, refer to the Commu-
nication Board section that follows.
9
CPU
C200HX/HG/HE CPU SELECTION GUIDE
10
CPU
SPECIFICATIONS, CHARACTERISTICS
11
CPU
SPECIFICATIONS, CHARACTERISTICS
12
CPU
SPECIFICATIONS, CHARACTERISTICS
DM 1000
DM 2599
DM 6000
DM 6144
DM 6600
DM 6655
DM 7000
DM 9999
Fixed DM (512
Normal Data Memory (DM) 6,144 words Fixed
words)
System expansion
Special I/O Error PLC DM area I/O
reserved Ladder program area
Module log Setup (0 to 3,000 comment
area
default area area area words) area
Ladder program A user program is stored in the ladder program area. If part of the UM is used as a fixed expansion DM area or I/O comment area, the capacity
area of the ladder program area storing the user program will be reduced accordingly.
I/O comment area I/O comments are stored in the I/O comment area. The I/O comments can be stored with a program. The I/O comments can be monitored
without loading the comment, just as with conventional comments.
Fixed expansion DM The default values of the Special I/O Module, Programmable Terminal, the character string of the Programmable Terminal, and operation data
area are stored in the fixed expansion DM area. By changing the I/O monitor present value of the Programming Console or using the DM edit transfer
operation of the Ladder Support Software, the default values can be written to DM 7000 to DM 9999.
System reserved The system reserved area is used by the system only.
area
PLC Setup area The settings required for the operation of the PLC are stored in the PLC Setup area.
Normal DM area The user can freely use the normal DM as a data area for arithmetic operations. If the Special I/O Module is used, DM 1000 to DM 2599 will be a
Special I/O Module default area.
• DM 1000 to DM 2599 can be used as a normal DM if DM 7000 to DM 8599 are set as a Special I/O Module default area with the PLC Setup. DM 6000 to DM 6030 are used
exclusively as an error log area.
• Unlike the normal DM area, nothing can be written to the fixed expansion DM area using ladder programming.
• The capacity of a ladder program will decrease if the size of the fixed expansion DM area and the total capacity of the I/O comments increase.
• The C200HX, C200HG, and C200HE do not have a fixed expansion DM area or I/O comment area before shipping. The user must allocate these areas in the UM according to
the application.
13
COMMUNICATIONS BOARDS
SPECIFICATIONS, SELECTION GUIDE
C200HW-COM01 C200HW-COM02
Specifications
PART NUMBER DESCRIPTION
C200HW-COM05-E C200HW-COM06-E
Memory
Cassette
CPU
Communications
Board
14
COMMUNICATION BOARDS
PROTOCOL MACRO
Simple
communications
sequence
15 m
RS-232C
port B RS-232C
RS-232C
Device with
port A
RS-232C
interface
RS-422/485 (C200HW-COM06-E)
The C200HW-COM06-E connects to one or more devices
through the RS-422 and RS-485 port provided the RS-422 or
RS-485 line between the C200HW-COM06-E and the farthest
device is a maximum of 500 m.
C200HX/HG/HE
15 m
Temperature Controller
Temperature Controller
Temperature Controller
500 m
16
MEMORY CASSETTES
SPECIFICATIONS
EEPROM or EPROM
Memory Cassettes
Each C200Hα CPU can accept a Memory Cassette to provide
back-up or downloading of programs and data. EEPROM mod-
els allow the program to be downloaded to and from the CPU
memory. EPROM models allow the user to write to an EPROM
and insert it into the memory cassette.
17
POWER SUPPLY MODULES
CAPACITIES AND SPECIFICATIONS
18
BACKPLANES
SPECIFICATIONS
Dimensions
W1
W2 118
(4.65)
118
(4.65) 130
130 (5.12)
(5.12)
W1
W2 118
(4.65)
19
BACKPLANES
SPECIFICATIONS
W1
W2 118
(4.65)
20
CONNECTING I/O CABLES
FEATURES, CAPACITIES AND SPECIFICATIONS
Note: The total length of the I/O Connecting Cables used in a network must not
exceed 12 m.
21
DISCRETE I/O MODULES
OVERVIEW
NK APP. <88A120>
MADE IN JAPAN
MADE IN JAPAN
module have solder connectors included with the module. Op-
NK APP. <88A120>
MADE IN JAPAN
tional wiring methods are available using Omron’s I/O blocks,
C200H--OA121--E
29XOF
UNIT
02X2F
No. Corporation
No. Corporation
minimize rack space and wiring time. The Omron I/O Blocks
No. Corporation
OUTPUT
OUTPUT
OMRON
OMRON
LOT
LOT
LOT
point. Replaceable relays and solid-state plug-in modules allow
easy maintenance. There are five styles of discrete I/O modules
in the C200H family. The profiles of each are shown here. Each
module in the following pages is cross-referenced to the module
style. Modules include the appropriate connectors.
Connector Connector Connector
Style A Style B Style C
Features
• Versatile high-density configuration options minimize rack
space and wiring time
• Replaceable relays and solid-state plug-in modules mean
easy maintenance
NK APP. <88A120>
MADE IN JAPAN
No. Corporation
OMRON
LOT
Connector Connector
Style D Style E
22
DISCRETE I/O MODULES
INPUT MODULE SPECIFICATIONS
TYPE NO. OF INPUTS PER INPUT VOLTAGE INPUT OPERATING INPUT RESPONSE TIME MODULE- PART NUMBER
INPUTS COMMON CURRENT VOLTAGE STYLE
ON OFF ON OFF
AC Input 8 pts 8 pts. 100 to 120 VAC 10 mA, 60 VAC 20 VAC 35 ms 55 ms A C200H-IA121
+10%/--15% 100 VAC min
min. max
max. max
max. max
max.
16 pts. 16 pts. B C200H-IA122
8 pts. 8 pts. 200 to 240 VAC 10 mA, 120 VAC 40 VAC A C200H-IA221
+10%/--15%
10%/ 15% 200 VAC min.
i max.
16 pts. 16 pts. B C200H-IA222
DC Input 8 pts. 8 pts. 12 to 24 VDC 10 mA, 10.2 3.0 VDC 1.5 ms 1.5 ms A C200H-ID211
+10%/--15% 24 VDC VDC max. max. max.
min.
16 pts. 16 pts. 24 VDC 7 mA, 14.4 5.0 VDC B C200H-ID212
+10%/--15% 24 VDC VDC max.
min.
AC/DC 8 pts. 8 pts. 12 to 24 VAC/DC 10 mA, 10.2 3.0 VDC 15 ms 15 ms A C200H-IM211
Input +10%/--15% 24 VDC VDC max. max. max.
min.
16 pts. 16 pts. 24 VAC/DC 7 mA, 14.4 5.0 VDC B C200H-IM212
+10%/--15% 24 VAC/ VDC max.
DC min.
Note: 1. All models feature photocoupler isolation and LED indicator.
2. Each Discrete I/O Module has a removable terminal block. See the above STYLE column for a reference to the module style/connector type and refer to the accom-
panying drawing and chart for specific connector details.
IN C R2 IN R
Internal circuits
Internal circuits
18 kΩ
~ +
R1 +
910Ω COM 0.01 µF
COM
R1 C R2 V (AC) R V (DC)
IA121, IA122: 330 kΩ 0.33 µF 470 Ω 100 to 120 ID211: 2 kΩ 12 to 24
IA221: 680 kΩ 0.15 µF 820 Ω 200 to 240 ID212: 3 kΩ 24
IA222: 680 kΩ 0.15 µF 680 Ω 200 to 240
IN R
Internal circuits
18 kΩ
+ ~
+
COM 0.01 µF
R V
IM211: 2 kΩ 12 to 24 VAC/DC
IM212: 3 kΩ 24 VAC/DC
23
DISCRETE I/O MODULES
OUTPUT MODULE SPECIFICATIONS
24
DISCRETE I/O MODULES
OUTPUT MODULE SPECIFICATIONS
Internal circuits
L
Internal circuits
+ COM
X
+
Fuse blowout
COM detector
OA222V: no fuse blowout detector
L
+
COM COM
Fuse Fuse
OUT
Internal circuits
Source OUT
driver
L L
+ + 24 VDC
+
COM COM
Fuse
Reset switch
Fuse blowout
“F” Alarm output LED
LED detector
Transistor Output (Protective Circuit for Load Transistor Output (Source Type with Protective
Short-circuit): OD216/OD217 Circuit for Load Short-circuit): OD21A
OUT +V
Output RESET
indicator LED
L
Internal circuits
+
LED
Internal circuits
24 VDC
OUT00
+ L
5 to OUT15
COM 24 VDC L
COM
ALARM
Note: Fuse blowout detection circuit: The F indicator is lit and the 08 bit turns ON. The 08 to 15 bits cannot be used as ordinary IR bits.
25
SPECIAL I/O MODULES
HIGH-DENSITY INPUT MODULE SPECIFICATIONS (GROUP-2)
The High-density Input Modules let you pack more input points
into a single I/O slot for greater space savings. These modules
do not use standard I/O points. Thus, they increase the overall
I/O capacity. They provide 32 or 64 discrete input points. The
modules can be used with Omron’s Terminal Blocks, reducing
wiring between control panels, as well as within control panels.
Features
• Easy cable connection to Omron’s XW2B- Terminal
Blocks using XW2Z- Connecting Cable. Refer to the
C200H-ID216
(32 DC input pts.)
C200H-ID217
(64 DC input pts.)
Standard Parts section for detailed ordering information.
• Up to ten 64-point modules or 32-point modules per PLC
Note: The ambient temperature affects the number of points that can
be ON simultaneously.
Specifications
PART NUMBER C200H-ID216 C200H-ID217
Number of inputs 32 points 64 points
Rated input voltage 24 VDC +10%/--15%
Input current 4.1 mA typical at 24 VDC
Input impedance 5.6 kΩ
ON voltage 14.4 VDC min.
OFF voltage 5.0 VDC max.
Input ON delay 1.0 ms max.
Input OFF delay 1.0 ms max.
Isolation Photocoupler
Input indicator LED
External connections Connector
Number of circuits (see 32 points with one 64 points with two
note) common commons
Internal power consump- 100 mA max. at 120 mA max. at 5
tion 5 VDC VDC
Weight 180 g max. 250 g max.
Manual W302
Circuit Configuration
ID216 ID217
COM
Internal circuits
COM
1000 PF
Internal circuits
IN15 COM
Input indicator IN00 CN2
to
B IN07
IN08
to
IN15 Input indicator
Note: 1. The polarity of the input power supply source can be positive or negative provided that the
polarity of each common is the same. A B
ID111: 820 Ω 2.7 kΩ
2. Although each COM is internally connected, wire them all. ID217: 680 Ω 5.6 kΩ
3. The mountable number of High-density I/O Modules varies with the CPU. No High-density
I/O Module can be mounted to the Slave Rack.
29
SPECIAL I/O MODULES
HIGH-DENSITY OUTPUT MODULE SPECIFICATIONS (GROUP-2)
Features
• Easy cable connection to Omron’s XW2B- Terminal Blocks
using XW2Z- Connecting Cable. Refer to the Standard
Parts section for detailed ordering information.
C200H-OD218 C200H-OD219
(32 DC output pts.) (64 DC output pts.) • Up to ten 64-point modules or 32-point modules per PLC
Specifications
PART NUMBER C200H-OD218 C200H-OD219
Number of outputs 32 points 64 points
Max. switching capacity 16 mA at 4.5 V to 100 mA at 26.4 V
Leakage current 0.1 mA max.
Residual voltage 0.8 V max.
Input ON delay 0.1 ms max.
Input OFF delay 0.4 ms max.
Output indicator LED
External connections Connector
Number of circuits 32 points with one 64 points with two
common commons
Fuse (see note) 3.5 A (one/common)
External power supply 110 mA (3.4 mA per ON 220 mA (3.4 mA per ON
pt) min. at 5 to 24 VDC pt) min. at 5 to 24 VDC
±10% ±10%
Internal power 180 mA max. at 5 VDC 260 mA max. at 5 VDC
consumption
Manual W302
Note: The fuse is not user replaceable.
Circuit Configuration
OD218 OD219
4.5 to 26.4 VDC 4.5 to 26.4 VDC
Internal circuits
OUT00 OUT00
to to
OUT07 OUT07
Internal circuits
Output in-
COM A COM CN1/
dicator CN2
4.5 to 26.4 VDC Fuse 4.5 to 26.4 VDC
OUT08 OUT08
to SW CN1 to
OUT15 OUT15
Display
Output in- COM Output in- COM
switch/
dicator 4.5 to 26.4 VDC fuse CN2
dicator
OUT00 break
Fuse to
3.5A detector F indicator
F indicator OUT07
Fuse COM
break 4.5 to 26.4 VDC B
detec OUT08
tor to Note: The number of Group-2 High-density Out-
OUT15 put Modules is limited by the CPU model.
COM They cannot be used with the Slave Rack.
30
SPECIAL I/O MODULES
HIGH-DENSITY INPUT MODULE
The High-density Input Modules let you pack more input points
into a single I/O slot for greater space savings. Functioning as
as Special I/O modules, they do not use standard I/O points.
Thus, they increase the overall I/O capacity. They provide 32
discrete input points with selectable response times of 2.5 ms or
15 ms. For even shorter signals, 8 inputs can be designated as
quick-response inputs, to receive selectable 1 ms or 4 ms sig-
nals. The modules can also be used with Omron’s Terminal
Blocks, reducing wiring between control panels as well as within
control panels.
Specifications
34
SPECIAL I/O MODULES
HIGH-DENSITY INPUT MODULE
Circuit Configuration
COM
Internal circuits
COM 620 Ω
Internal circuits
5 VDC
24 VDC 1000 pF +
+ 2.4 kΩ
+
+
IN 1.1 kΩ
IN 5.6 kΩ
I/O Refresh Instruction Machine Number Setting and Input Bit No.
The I/O Refresh instruction, IORF(97), can be used with
the quick-response input function to read the input status When set to machine No.: n (0 to 9), words [100+10n+1]
held in the quick-response input buffer whenever needed can be used as input bits. Input bits 08 to 15 of word 1n1
in a program. can be used as quick-response
inputs.
00000
IORF(97)
St
Example: When set to 8,
E input bits 18108 to 18115
become quick-response
When 00000 is ON, all words from St inputs. Machine No.
to E will be refreshed. setting
switch
St and E would be 101 for Unit #0,
making bits IR 10108 to IR 10115
quick-response input bits.
35
SPECIAL I/O MODULES
HIGH-DENSITY OUTPUT MODULE
Features
• Provide 32 outputs per module in static mode
C200H-OD215 • Easy cable connection to Omron’s XW2B- Terminal Blocks
(32 transistor output pts.)
using XW2Z- Connecting Cable. Refer to the Standard
Parts section for detailed ordering information.
C200H-OD501
(32 TTL output pts.) • Provide interface to numeric displays, etc. in dynamic mode
Specifications
36
SPECIAL I/O MODULES
HIGH-DENSITY OUTPUT MODULE
Internal circuits
R3
L
Fuse Common
R1 V
OD501: 4.7 kΩ 5 VDC
OD215: None 5 to 24 VDC
C200HX/HG/HE
M7F
Servomotor
Servodriver
37
SPECIAL I/O MODULES
MIXED I/O MODULE
Features
• Provide 16 inputs and 16 outputs per module in static mode;
128 inputs in dynamic mode
• Easy cable connection to Omron’s XW2B- Terminal Blocks
using XW2Z- Connecting Cable. Refer to the Standard
Parts section for detailed ordering information.
• Selectable input response time
• Up to 10 Special I/O modules per PLC
• Provide interface to keyboards, thumbwheel switches, etc. in
dynamic mode
Specifications
MODULE NAME TTL INPUT/OUTPUT MODULE DC INPUT/TRANSISTOR OUTPUT MODULE
38
SPECIAL I/O MODULES
MIXED I/O MODULE
Circuit Configuration
MD501/MD215/MD115
R1
Internal circuits
L
+
OUT V1
Fuse COM
R3 R2 IN +
C V2
+
COM
STB0
With dynamic inputs, data signals DATA0 to DATA15 are com- (CN1 A1) D C B A
bined with strobe signals STB0 to STB15 to reduce wiring and
greatly increase input capacity. For example, when STB0 is ON,
as shown to the right, data would be read from DATA0 to DATA0 (CN2 A1)
DATA3, and the status of switches A through D would be re- DATA1 (CN2 A2)
flected in bits 00 through 03 of word 1n0, where n is the Special
I/O Module’s unit number. DATA2 (CN2 A3)
39
SPECIAL I/O MODULES
ANALOG INPUT MODULES
Features
• Cost-effective single-slot modules available with 4 or 8
analog inputs
C200H-AD001 • 12-bit resolution
C200H-AD002 • Selectable ranges include 1 to 5 V, 0 to 10 V, and 4 to 20 mA
Specifications
PART NUMBER C200H-AD001 C200H-AD002
Input points 4 8
Voltage input 1 to 5V or 0 to 10 V 1 to 5 V, 0 to 10 V, or
--10 to 10 V
Current 4 to 20 mA
input
External Voltage 1 MΩ min.
System Configuration in ut im
input ed
imped- input
ance
Current 250 Ω
input
Resolution Voltage 1/4,000 FS
Current
Total preci- 25°C ±0.5% FS Voltage: ±0.25% FS
sion 77.0°F Current: ±0.4% FS
0° to ±1.0% FS Voltage: ±0.6% FS
C200HX/HG/HE 55°C Current: ±0.8% FS
Flow (32° to
131°F)
Analog signals, such as voltages and currents, are received Weight 450 g max. 290 g max.
from various sensors through the maximum of 8 inputs Manual W127 W229
(AD002) and converted into 12-bit binary data.
External input signal range can be freely set to cope with
diverse needs.
Built-in functions included: the scaling function, mean func-
tion, peak hold function, square-root extraction function, and
more.
40
SPECIAL I/O MODULES
ANALOG OUTPUT MODULES
Features
• Cost-effective single-slot module offers two or four analog
outputs
• 12-bit resolution
• Selectable ranges include 1 to 5 V, 0 to 10 V, -10 to +10 V,
and 4 to 20 mA
Specifications C200H-DA001
C200H-DA002
PART NUMBER C200H-DA001 C200H-DA002
Output points 2 4
Voltage output 1 to 5V or 0 to 10 V --10 to 10 V
Current 4 to 20 mA
output
Resolution Voltage 1/4,095 FS 1/8,190 FS
Current 1/4,095 FS
Total preci- 25°C ±0.5% FS Voltage: ±0.3% FS System Configuration
sion 77.0°F Current: ±0.5% FS
0° to ±1.0% FS Voltage: ±0.5% FS
55°C Current: ±1.0% FS
(32° to
131°F)
Conversion speed 2.5 ms max./pt
External output imped- 0.5 Ω min.
ance C200HX/HG/HE
Maximum Voltage 15 mA 10 mA
external out- output
put current Analog output
Servomotor driver
Current ---
output
Allowable Voltage ---
load resis- output
tance of ex-
ternal output Inverter
Current 400 Ω 350 Ω M
output
Converted data 12-bit binary Voltage code bit + 12-bit
binary
Current code bit + 12-bit Recorder
binary
I/O words required 10 (Special I/O area)
External connections Terminal block Connector
Current consumption 650 mA max., 5 VDC 600 mA max., 5 VDC
Weight 450 g max. 320 g max. Converts 12-bit binary data into analog signals (voltage or current) for
Manual W127 W260 output to external devices.
Output signal range can be freely set to cope with diverse needs.
Built-in functions such as the output limit, upper- and lower-limit
alarm, and pulse output functions make the C200HX/HG/HE even
more powerful.
41
SPECIAL I/O MODULES
TEMPERATURE SENSOR MODULES
Features
• Available for thermocouple types J and K, or platinum RTD
temperature sensors
• Selectable number of inputs
42
SPECIAL I/O MODULES
TEMPERATURE SENSOR MODULES
+ C200HX/HG/HE A3 A3
B4 B4
-- A4 R0 A4
B5 B5
A
A5 A5
+ B6
G79- C B6
Input 3 B
Connecting A6
A
A6 Input 3
B M7F --
B7
B′ B7
Cable A7 A7
(1-to-1) + B8
B’ A8
B8
Input 4 B A8
Input 4
-- A B′ B9
B9
Temperature Ranges
C200H-TS001 C200H-TS101
Note: Use the IR bit for setting the temperature range. (Common settings for 4 inputs.)
43
COMMUNICATIONS
OVERVIEW
Ethernet
CV 500
C200HX/HG/HE
Bridge
PLANTWIDE INFORMATION
SYSMAC NET
MMI computer
C2000H
Line Server
MMI computer
C200H
C200HX/HG/HE
CV1000 MMI computer CV1000
Master
C200HX/HG/HE
DeviceNet System
Slave
I/O Blocks
Remote
C200H Remote C500 Remote I/O Block
Rack Rack CQM1-DRT21
Branching
Third-party Products
71
PROGRAMMING PERIPHERALS AND CABLES
OVERVIEW
C200H-LK201-V1
C200HX/HG/HE
Mounted
directly
RS-232C Peripheral
port port
Programming Console
Connecting Cable Connecting Cable Connecting Cable
C500-ZL3AT1-EV1.2 SYSWINHL-V3.1
PERIPHERAL SUPPORT
DEVICE SOFTWARE
C200H-PRO27-E CQM1-PRO01-E
97
PROGRAMMING PERIPHERALS AND CABLES
OVERVIEW
Programming Consoles
There are two programming consoles that can be used with the
C200HX/C200HG/C200HE: The C200H-PRO27-E and the
CQM1-PRO01-E. The programming console is a complete on-
line and off-line programming and monitoring hand-held con-
sole. In addition to programming and monitoring with the pro-
gramming console, users can verify programs, compare and
create I/O tables, monitor multiple I/O, force set/reset bits, and
C200H-PRO27-E CQM1-PRO01-E choose from run, monitor, debug or program modes.
Programming Programming Console
Console
The C200H-PRO27-E Programming Console connects to the
C200HX/C200HG/C200HE CPU peripheral port with
C200H-CN222 or C200H-CN422 Connecting Cable (cable
purchased separately).
The CQM1-PRO01-E Programming Console comes with a 2 m
connecting cable which connects to the C200HX, C200HG, or
C200HE CPU peripheral port.
C200H-CN222/422
Programming Console
Connecting Cable
(2 m/4 m)
Connecting Cables
There are several cables which allow you to connect a PC to
the C200HX/HG/HE for programming and monitoring, using
SYSWIN or SSS. The C200HS-CN220-EU (9-pin RS-232C) and
the C200HS-CN229-EU (25-pin RS-232C) cables connect a PC
to a built-in RS-232C port of the C200HX/HG/HE CPU. The
C500-CN221-EU (9-pin RS-232C) and C500-CN222-EU (25-pin
RS-232C) cables connect a PC to a rack-mounted
C200H-LK201-V1.
CQM1-CIF02 C200HS-CN220-EU
Connecting Cable C200HS-CN229-EU
C500-CN221-EU
C500-CN222-EU
Connecting Cable
98
CPU RACK
CPU Rack
ITEM DESCRIPTION PART NUMBER STANDARDS
C Us ((All models
CPUs ode s are
a e provided
o ded with UM DM I/O points RS-232C U, C, N, CE
clock
l k function
f ti and d slots
l t for
f commu- 3.2K words 4K words 640 No C200HE-CPU11-E
nications except CPU11-E.)
CPU11-E )
7.2K words 6K words 880 No C200HE-CPU32-E
8K words Yes C200HE-CPU42-E
15.2K words 12K words No C200HG-CPU33-E
Yes C200HG-CPU43-E
1,184 No C200HG-CPU53-E
Yes C200HG-CPU63-E
31.2K words 24K words 880 No C200HX-CPU34-E
Yes C200HX-CPU44-E
1,184 No C200HX-CPU54-E
Yes C200HX-CPU64-E
Power Supply Modules 100 to 120/200 to 240 VAC C200HW-PA204
24 VDC C200HW-PD024
124 U: UL, C: CSA, N: NK, L: LLOYD, CE: EC Directives -- See OMRON sales representatives for conditions under which UL,
CSA, NK, LLOYD, and CE standards were met.
EXPANSION
Expansion Rack
ITEM DESCRIPTION PART NUMBER STANDARDS
24 VDC C200HW-PD024
5 slots C200HW-BI051
8 slots C200HW-BI081
10 slots C200HW-BI0101
I/O Connecting
/O Co Cables
ec g Cab es 30 cm The
e total
o a length
e g ofo the
e I/O
/O Connecting
Co ec g Cables
Cab es C200H-CN311 ---
70 cm used
d in
i a network
t k mustt b
be 12 m maximum.
i C200H-CN711
200 cm C200H-CN221
500 cm C200H-CN521
1,000 cm C200H-CN131
Slave Rack
Slave Racks Remote I/O Slave 100 to 120/200 to 240 VAC (switchable) APF/ C200H-RT001-P U, C, N, L
Modules PCF
24 VDC C200H-RT002-P N, L
C200H-RT201-C CE
24 VDC C200H-RT202 N, L, CE
8 slots C200H-BC051-V2
10 slots C200H-BC101-V2
I/O Blocks Input Specify either 12 or 24 VDC. G71-IC16 U, C, N, L
Output G71-OD16
I/O
/O AC input Specify either 100 or 200 VAC. G7TC-IA16
T
Terminals
i l DC input Specify either 12 or 24 VDC. G7TC-ID16
Output Specify either 12 or 24 VDC. G7TC-OC16
Link Adapter O/E converter; 1 connector for RS-485, 1 connector each for APF/ B500-AL007-P
PCF
U: UL, C: CSA, N: NK, L: LLOYD, CE: EC Directives -- See OMRON sales representatives for conditions under which UL, 125
CSA, NK, LLOYD, and CE standards were met.
I/O MODULES
Output Relay Output Modules 8 pts 2 A, 250 VAC/24 VDC (for resistive load) C200H-OC221 U, C, N, L
Modules
12 pts 2 A, 250 VAC/24 VDC (for resistive load) C200H-OC222
5 pts 2 A, 250 VAC/24 VDC (for resistive load) C200H-OC223
Independent commons
8 pts 2 A, 250 VAC/24 VDC (for resistive load) C200H-OC224
Independent commons
16 pts 2 A, 250 VAC/24 VDC (for resistive load) C200H-OC225
(see note)
Triac Output Modules 8 pts 1 A, 120 VAC C200H-OA121-E U, C
8 pts 1 A, 200 VAC C200H-OA223 N, L, CE
12 pts 0.3 A, 200 VAC C200H-OA222V CE
Transistor Output 8 pts 1 A, 12 to 48 VDC C200H-OD411 U, C, N, L, CE
Modules
12 pts 0.3 A, 24 VDC C200H-OD211
16 pts 0.3 A, 24 VDC (see note) C200H-OD212
8 pts 2.1 A, 24 VDC C200H-OD213
8 pts 0.8 A, 24 VDC; source type (PNP); w/load short C200H-OD214 U, C, N, L
protection
8 pts 0.3 A, 5 to 24 VDC; source type (PNP) C200H-OD216
12 pts 0.3 A, 5 to 24 VDC; source type (PNP) C200H-OD217
16 pts 1 A, 24 VDC; source type (PNP); w/load short C200H-OD21A CE
protection
Analog Timer Module 4 timers 0.1 to 1 s/1 to 10 s/10 to 60 s/1 min to 10 min C200H-TM001 U, C
(switchable)
Variable Resistor Connector w/lead wire (2 m) for 1 external resistor C4K-CN223 ---
Connector
B7A Interface Modules 15 or 16 Connects to B7A Link Terminals. Standard trans- C200H-B7AI1 U, C, CE
input pts mission delay.
Note: If the Interrupt Input Module is mounted on an Expansion I/O Rack, the interrupt function cannot be used and the Interrupt Input Module will be
treated as an ordinary 8-point Input Module. Moreover, Interrupt Input Modules cannot be used on Slave Racks.
126 U: UL, C: CSA, N: NK, L: LLOYD, CE: EC Directives -- See OMRON sales representatives for conditions under which UL,
CSA, NK, LLOYD, and CE standards were met.
SPECIAL I/O MODULES (INCLUDING GROUP 2 I/O)
High-density
g y DC Input Modules 32 pts 5 VDC (TTL inputs); w/high-speed input C200H-ID501 U,, C,, N,, L,,
I/O M
Modules
d l 32 pts 24 VDC; w/high-speed input C200H-ID215 CE
(see note 1)
Transistor Output 32 pts 0.1 A, 24 VDC (useable as 128-point dynamic C200H-OD215
Modules output unit)
32 pts 35 mA, 5 VDC (TTL outputs) (useable as C200H-OD501
128-point dynamic output unit)
DC Input/Transistor 16 input and 24-VDC inputs; w/high-speed input; 0.1-A, C200H-MD215
Output Modules 16 output pts 24-VDC outputs (useable as 128-point dynamic
input unit)
16 input and 5-VDC TTL inputs; w/high speed input; 35-mA, C200H-MD501
16 output pts 5-VDC TTL outputs (useable as 128-point dy-
namic input unit)
16 input and 12-VDC TTL inputs; w/high speed input; C200H-MD115 N, L
16 output pts 12-VDC TTL outputs (useable as 128-point dy-
namic input unit)
Analog I/O Analog Input 4 to 20 mA, 1 to 5/0 to 10 V (switchable); 4 inputs; 12 bits C200H-AD001 U, C, N, L
Modules Modules
4 to 20 mA, 1 to 5/0 to 10 V/--10 to 10V (switchable); 8 inputs; 12 C200H-AD002
bits or BCD
Analog Output 4 to 20 mA, 1 to 5/0 to 10 V (switchable); 2 outputs C200H-DA001
Modules
4 to 20 mA, --10 to 10 V; 4 outputs C200H--DA002 ---
Fuzzy Logic Module Programmed using the Fuzzy Support Software. C200H-FZ001 N
Fuzzy Support Available on either 3.5” or 5.25” floppy disks. C500-SU981-E ---
Software
U: UL, C: CSA, N: NK, L: LLOYD, CE: EC Directives -- See OMRON sales representatives for conditions under which UL, 127
CSA, NK, LLOYD, and CE standards were met.