Reference No.

PROTECTION RELAY TEST RECORD


Page No.: 1
OVERCURRENT PROTECTION RELAY DATA
Brand : THYTRONIC Language : ENGLISH
Model : NA011 Frequency : 60HZ
Serial Number : 314384 Aux. Voltage : 48VDC
Designation : Site Location : TEKTITE BLDG. PASIG CITY

CURRENT TRANSFORMER DATA

Rated Voltage : 4.16KV Relaying Accuracy Class : 1


Rated Primary Current : 300A Rated Secondary Current : 5A

OCR RELAY PARAMETER SETTINGS

A. Phase Overcurrent Settings (ANSI Code: 50/51)

I> : Prim. 180.42A Sec. 3.007A I>> : Prim. 1082.52A Sec. 18.042A I>>> : Prim. Sec.
Trip Curve : IEC BS/B Trip Curve : IEC BS/B Trip Curve :
TMS : DEFINITE TMS : DEFINITE TMS :

B. Earth Overcurrent Settings (ANSI Code : 50N/51N)

Ie> : Prim. 54.126A Sec. 0.9021A Ie>> : Prim. 324.756A Sec. 5.4126A
Trip Curve : IEC BS/B Trip Curve : IEC BS/B
TMS : DEFINITE TMS : DEFINITE

OVERCURRENT OPERATION TEST RESULTS

Tripping Time (s)


Phase A Input Test Current (A) Remarks
Theoretical Actual
150% 4.5105 8.1 8.0345 PASSED
200% 6.0140 4.05 4.0250 PASSED
300% 9.0210 2.025 2.0128 PASSED
INSTANTANEOUS 18.0420 0.05 0.0480 PASSED

Tripping Time (s)


Phase B Input Test Current (A) Remarks
Theoretical Actual
150% 4.5105 8.1 8.1523 PASSED
200% 6.0140 4.05 4.0242 PASSED
300% 9.0210 2.025 2.0591 PASSED
INSTANTANEOUS 18.0420 0.05 0.0501 PASSED

Tripping Time (s)


Phase C Input Test Current (A) Remarks
Theoretical Actual
150% 4.5105 8.1 8.1621 PASSED
200% 6.0140 4.05 4.0250 PASSED
300% 9.0210 2.025 2.0812 PASSED
INSTANTANEOUS 18.0420 0.05 0.0510 PASSED

Tripping Time (s)


Earth/Ground Input Test Current (A) Remarks
Theoretical Actual
150% 1.3532 8.1 8.0912 PASSED
200% 1.8042 4.05 4.0257 PASSED
300% 2.7063 2.025 2.0341 PASSED
INSTANTANEOUS 5.4126 0.05 0.0493 PASSED

Test Equipment Used : PONOVO Universal Test Relay Set, Model: PW336i, S.N.:PH146121102
Overall Remarks : The test results and settings are initial only and is subject to approval by customer / end-user

Tested by: KIEN RYAN AQUINO Witnessed by: DARIUS PEREZ Witnessed by:
Date : JUNE 24, 2023 Date : JUNE 24, 2023 Date :
Reference No.:

PROTECTION RELAY TEST RECORD


Page No.: 2
OVERCURRENT PROTECTION RELAY DATA
Brand : THYTRONIC Language : ENGLISH
Model : NA011 Frequency : 60HZ
Serial Number : 314385 Aux. Voltage : 48VDC
Designation : Site Location : TEKTITE BLDG. PASIG CITY

CURRENT TRANSFORMER DATA

Rated Voltage : 4.16KV Relaying Accuracy Class : 1


Rated Primary Current : 300A Rated Secondary Current : 5A

OCR RELAY PARAMETER SETTINGS

A. Phase Overcurrent Settings (ANSI Code: 50/51)

I> : Prim. 180.42A Sec. 3.007A I>> : Prim. 1082.52A Sec. 18.042A I>>> : Prim. Sec.
Trip Curve : IEC BS/B Trip Curve : IEC BS/B Trip Curve :
TMS : DEFINITE TMS : DEFINITE TMS :

B. Earth Overcurrent Settings (ANSI Code : 50N/51N)

Ie> : Prim. 54.126A Sec. 0.9021A Ie>> : Prim. 324.756A Sec. 5.4126A
Trip Curve : IEC BS/B Trip Curve : IEC BS/B
TMS : DEFINITE TMS : DEFINITE

OVERCURRENT OPERATION TEST RESULTS

Tripping Time (s)


Phase A Input Test Current (A) Remarks
Theoretical Actual
150% 4.5105 8.1 8.0147 PASSED
200% 6.0140 4.05 4.0199 PASSED
300% 9.0210 2.025 2.0110 PASSED
INSTANTANEOUS 18.0420 0.05 0.0483 PASSED

Tripping Time (s)


Phase B Input Test Current (A) Remarks
Theoretical Actual
150% 4.5105 8.1 8.0344 PASSED
200% 6.0140 4.05 4.0256 PASSED
300% 9.0210 2.025 2.0259 PASSED
INSTANTANEOUS 18.0420 0.05 0.0486 PASSED

Tripping Time (s)


Phase C Input Test Current (A) Remarks
Theoretical Actual
150% 4.5105 8.1 8.0860 PASSED
200% 6.0140 4.05 4.0252 PASSED
300% 9.0210 2.025 2.0128 PASSED
INSTANTANEOUS 18.0420 0.05 0.0480 PASSED

Tripping Time (s)


Earth/Ground Input Test Current (A) Remarks
Theoretical Actual
150% 1.3532 8.1 8.0331 PASSED
200% 1.8042 4.05 4.0272 PASSED
300% 2.7063 2.025 2.0129 PASSED
INSTANTANEOUS 5.4126 0.05 0.0499 PASSED

Test Equipment Used : PONOVO Universal Test Relay Set, Model: PW336i, S.N.:PH146121102
Overall Remarks : The test results and settings are initial only and is subject to approval by customer / end-user

Tested by: KIEN RYAN AQUINO Witnessed by: DARIUS PEREZ Witnessed by:
Date : JUNE 24, 2023 Date : JUNE 24, 2023 Date :
Reference No.:

PROTECTION RELAY TEST RECORD


Page No.: 3
OVERCURRENT PROTECTION RELAY DATA
Brand : THYTRONIC Language : ENGLISH
Model : NA011 Frequency : 60HZ
Serial Number : 314386 Aux. Voltage : 48VDC
Designation : Site Location : TEKTITE BLDG. PASIG CITY

CURRENT TRANSFORMER DATA

Rated Voltage : 4.16KV Relaying Accuracy Class : 1


Rated Primary Current : 300A Rated Secondary Current : 5A

OCR RELAY PARAMETER SETTINGS

A. Phase Overcurrent Settings (ANSI Code: 50/51)

I> : Prim. 180.42A Sec. 3.007A I>> : Prim. 1082.52A Sec. 18.042A I>>> : Prim. Sec.
Trip Curve : IEC BS/B Trip Curve : IEC BS/B Trip Curve :
TMS : DEFINITE TMS : DEFINITE TMS :

B. Earth Overcurrent Settings (ANSI Code : 50N/51N)

Ie> : Prim. 54.126A Sec. 0.9021A Ie>> : Prim. 324.756A Sec. 5.4126A
Trip Curve : IEC BS/B Trip Curve : IEC BS/B
TMS : DEFINITE TMS : DEFINITE

OVERCURRENT OPERATION TEST RESULTS

Tripping Time (s)


Phase A Input Test Current (A) Remarks
Theoretical Actual
150% 4.5105 8.1 8.0414 PASSED
200% 6.0140 4.05 4.0285 PASSED
300% 9.0210 2.025 2.0137 PASSED
INSTANTANEOUS 18.0420 0.05 0.0474 PASSED

Tripping Time (s)


Phase B Input Test Current (A) Remarks
Theoretical Actual
150% 4.5105 8.1 8.0945 PASSED
200% 6.0140 4.05 4.0266 PASSED
300% 9.0210 2.025 2.0124 PASSED
INSTANTANEOUS 18.0420 0.05 0.0483 PASSED

Tripping Time (s)


Phase C Input Test Current (A) Remarks
Theoretical Actual
150% 4.5105 8.1 8.0641 PASSED
200% 6.0140 4.05 4.0269 PASSED
300% 9.0210 2.025 2.0249 PASSED
INSTANTANEOUS 18.0420 0.05 0.0494 PASSED

Tripping Time (s)


Earth/Ground Input Test Current (A) Remarks
Theoretical Actual
150% 1.3532 8.1 8.0832 PASSED
200% 1.8042 4.05 4.0591 PASSED
300% 2.7063 2.025 2.0123 PASSED
INSTANTANEOUS 5.4126 0.05 0.0512 PASSED

Test Equipment Used : PONOVO Universal Test Relay Set, Model: PW336i, S.N.:PH146121102
Overall Remarks : The test results and settings are initial only and is subject to approval by customer / end-user

Tested by: KIEN RYAN AQUINO Witnessed by: DARIUS PEREZ Witnessed by:
Date : JUNE 24, 2023 Date : JUNE 24, 2023 Date :