CSSP Report

1. Project Information

Date 2023-5-10
Project name Air Defense Institute
Project address
Country Egypt
State
City CAIRO
Client name
Client address
Designed by
Reference
Revision
Altitude(m) 74
Indoor DB temperature in cooling(℃) 24
Indoor WB temperature in cooling(℃) 17
Outdoor DB temperature in cooling(℃) 40
Outdoor WB temperature in cooling(℃) 24
Indoor DB temperature in heating(℃) 21
Indoor WB temperature in heating(℃) 14
Outdoor DB temperature in heating(℃) 7.6
Outdoor WB temperature in heating(℃) 6.9

2. Overall Material List

2.1 Equipment List

Model Quantity Description


38VF032H119016 1 Super X (380V)
38VF028H119016 1 Super X (380V)
38VF022H119016 2 Super X (380V)
38VF012H119016 1 Super X (380V)
BJC-02E-CM(i) 1 Branch joint
FQZHD-03 1 Branch joint
BJC-03E-CM(i) 1 Branch joint
FQZHD-04 4 Branch joint
AHUKZ-02B 2 AHU Kit(Standard wired controller WR-29B-CM)
AHUKZ-03B 5 AHU Kit(Standard wired controller WR-29B-CM)

2.2 Field Providing List

2.2.1 Refrigerant Piping Materials

Model Quantity Unit Description


Φ12.7 15 m Copper pipe
Φ15.9 42 m Copper pipe
Φ19.1 22 m Copper pipe
Φ22.2 7 m Copper pipe

CSSP 3.1005 1
Φ25.4 3 m Copper pipe
Φ31.8 6 m Copper pipe
Φ38.1 7 m Copper pipe
Φ41.3 3 m Copper pipe
Φ44.5 1 m Copper pipe
Insulation casing for piping All refrigerant piping and branch joints should be completely insulated.
Recommended insulation casing thickness:
Thickness
Piping size Humidity<80%RH Humidity≥80%RH
Φ6.35~Φ38.1mm ≥15mm ≥20mm
Φ41.3~Φ38.1mm ≥20mm ≥25mm

2.2.2 Refrigerant charge

System name Model Quantity Unit Description


OU-FA-01 R410A 12.41 kg Extra Refrigerant Added
OU-FA-02 R410A 5.76 kg Extra Refrigerant Added
Total(R410A) R410A 18.17 kg Extra Refrigerant Added

2.2.3 Electrical cables

Type Size Length


Power supply cable Select based on MCA of each unit According to the actual system design
Communication cable 0.75mm2 3-core shielded According to the actual system design

3. Overall Electrical Characteristics

Model Quantity Power supply MCA(A) MFA(A)


38VF032H119016 1 380-415V-3ph-50/60Hz 66.90 80
38VF028H119016 1 380-415V-3ph-50/60Hz 58.70 63
38VF022H119016 2 380-415V-3ph-50/60Hz 47.90 63
38VF012H119016 1 380-415V-3ph-50/60Hz 26.40 32
Notes:
1. MCA: Minimum Circuit Amps. MCA is used to select wire size.The value in above table is for one unit.
2. MFA: Maximum Fuse Amps. MFA is used to select overcurrent circuit breakers and residual-current circuit
breakers.The value in above table is for one unit.

CSSP 3.1005 2
4. OU-FA-01

4.1 BOM List (OU-FA-01)

Model Quantity Unit Description


38VF032H119016 1 Super X (380V)
38VF028H119016 1 Super X (380V)
38VF012H119016 1 Super X (380V)
BJC-03E-CM(i) 1 Branch joint
FQZHD-04 3 Branch joint
AHUKZ-03B 4 AHU Kit(Standard wired controller WR-29B-CM)
R410A 12.41 kg Extra Refrigerant Added
Φ12.7 3 m Copper pipe
Φ15.9 24 m Copper pipe
Φ19.1 18 m Copper pipe
Φ22.2 7 m Copper pipe
Φ25.4 3 m Copper pipe
Φ38.1 6 m Copper pipe
Φ41.3 3 m Copper pipe
Φ44.5 1 m Copper pipe

4.2 Indoor Unit Details (OU-FA-01)

4.2.1 Indoor Unit Details Table

4.2.2 Table of Abbreviations

Abbreviation code Description


Tmp-C Indoor temperature in cooling (Dry bulb temp. / Wet bulb temp. / RH)
RTC Required total cooling capacity
ATC Available total cooling capacity
RSC Required sensible cooling capacity
ASC Available sensible cooling capacity
Tmp-H Indoor temperature in heating (Dry bulb temp.)
RHC Required heating capacity
AHC Available heating capacity
Tdis-H Indoor unit discharge air temperature in heating
Airflow Indoor unit airflow (High/Medium/Low)
ESP External static pressure
Sound-Pr Sound pressure level (High/Medium/Low)
Sound-Po Sound power level (High/Medium/Low)
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
PI-C Power input in cooling
PI-H Power input in heating
Power supply Power supply
Dimension(WxHxD) Net Dimension (WxHxD) mm
Weight Weight

4.3 Outdoor Unit Details (OU-FA-01)

CSSP 3.1005 3
4.3.1 Outdoor Unit Details Table

Model 38VF072H119016
Module 38VF012H119016 38VF028H119016 38VF032H119016
Tmp-C ℃ 40
RTC kW
ATC kW 200
PI-C kW 68.58
EER 2.92
Tmp-H ℃/℃ 7.6/6.9
RHC kW
AHC kW 220
PI-H kW 56.08
COP 3.92
CR 99.0
Airflow m^3/h 11000 25000 24000
Sound-Pr 60 64 64
Sound-Po
Bas-Refr kg 58.00
Ex-Refr kg 12.41
TCO2 eq. 147.02
MCA A 26.4 58.7 66.9
MFA A 32 63 80
Power supply V/ph/Hz 380-415V-3ph-50/60Hz 380-415V-3ph-50/60Hz 380-415V-3ph-50/60Hz
Dimension (WxHxD) mm 990*1635*790 1730*1830*850 1730*1830*850
Weight kg 227 430 475

4.3.2 Table of Abbreviations

Abbreviation code Description


Tmp-C Outdoor conditions in cooling (Dry bulb temp.)
RTC Required cooling capacity
ATC Available cooling capacity
PI-C Power input in cooling
EER EER
Tmp-H Indoor conditions in heating (Dry bulb temp. / Wet bulb temp. / RH)
RHC Required heating capacity
AHC Available heating capacity
PI-H Power input in heating
COP COP
CR Combination ratio
Airflow Outdoor unit airflow
Sound-Pr Sound pressure level
Sound-Po Sound power level
Bas-Refr Standard factory refrigerant charge
Ex-Refr Extra refrigerant charge
TCO2 eq. Tonnes of CO2 equivalent
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
Power supply Power supply
Dimension (WxHxD) Net Dimension (WxHxD) mm

CSSP 3.1005 4
Weight Weight

4.4 Piping Limitations (OU-FA-01)

4.4.1 Piping Limitations

Item Capability Actual Value


Total piping length 1000.00(m) 82.00(m)
Longest actual length 175.00(m) 16.00(m)
Longest equivalent length 200.00(m) 18.50(m)
Longest equivalent length after first branch 90.00(m) 15.00(m)
Indoor unit to nearest branch length 40.00(m) 1.00(m)
Length difference between longest and shortest distance to indoor units 40.00(m) 0.00(m)
Height difference between indoor and outdoor unit(ODU up) 90.00(m) 0.00(m)
Height difference between indoor and outdoor unit(ODU down) 110.00(m) 0.00(m)
Height difference between indoor units 30.00(m) 0.00(m)
Combination ratio 50-100% 99.01%
IDU quantity 64 1

4.4.2 Correction Factors

Item Correction factor


Altitude (indoor unit) 0.999
Altitude (outdoor unit) 0.999
Piping (cooling) 0.997
Piping (heating) 1.000
Defrost (heating) 1.000

4.4.3 Piping Details Table

No. Length(m) Piping diameter


(1) 3.00 Φ/Φ22.2
(2) 3.00 Φ/Φ19.1
(3) 3.00 Φ/Φ19.1
(4) 3.00 Φ/Φ15.9
(5) 3.00 Φ/Φ15.9
(6) 3.00 Φ/Φ15.9
(7) 3.00 Φ/Φ15.9
(8) 3.00 Φ/Φ15.9
(9) 3.00 Φ/Φ15.9
(10) 3.00 Φ/Φ15.9
(11) 3.00 Φ/Φ15.9
(12) 3.00 Φ/Φ19.1
(13) 3.00 Φ/Φ19.1
(14) 1.00 Φ/Φ22.2
(15) 1.00 Φ44.5/Φ

4.4.4 Branch Joints Details Table

No. Load(kW) Model

CSSP 3.1005 5
(1) 200 FQZHD-04
(2) 112 FQZHD-04
(3) 112 FQZHD-04

4.4.5 Reducer Details Table

4.4.6 Combined Outdoor Units Details Information

Outdoor branch joint model


Outdoor branch Model name
L+M BJC-03E-CM(i)
Outdoor unit-Branch/Branch-Branch
Piping Piping diameter(mm) Piping length(m)
L1 Φ25.4,Φ12.7 3
L2 Φ38.1,Φ19.1 3
L3 Φ38.1,Φ19.1 3
L4 Φ41.3,Φ22.2 3

CSSP 3.1005 6
4.5 Piping Diagrams (OU-FA-01)

CSSP 3.1005 7
4.6 Wiring Diagrams (OU-FA-01)

CSSP 3.1005 8
5. OU-FA-02

5.1 BOM List (OU-FA-02)

Model Quantity Unit Description


38VF022H119016 2 Super X (380V)
BJC-02E-CM(i) 1 Branch joint
FQZHD-03 1 Branch joint
FQZHD-04 1 Branch joint
AHUKZ-03B 1 AHU Kit(Standard wired controller WR-29B-CM)
AHUKZ-02B 2 AHU Kit(Standard wired controller WR-29B-CM)
R410A 5.76 kg Extra Refrigerant Added
Φ12.7 12 m Copper pipe
Φ15.9 18 m Copper pipe
Φ19.1 4 m Copper pipe
Φ31.8 6 m Copper pipe
Φ38.1 1 m Copper pipe

5.2 Indoor Unit Details (OU-FA-02)

5.2.1 Indoor Unit Details Table

5.2.2 Table of Abbreviations

Abbreviation code Description


Tmp-C Indoor temperature in cooling (Dry bulb temp. / Wet bulb temp. / RH)
RTC Required total cooling capacity
ATC Available total cooling capacity
RSC Required sensible cooling capacity

CSSP 3.1005 9
ASC Available sensible cooling capacity
Tmp-H Indoor temperature in heating (Dry bulb temp.)
RHC Required heating capacity
AHC Available heating capacity
Tdis-H Indoor unit discharge air temperature in heating
Airflow Indoor unit airflow (High/Medium/Low)
ESP External static pressure
Sound-Pr Sound pressure level (High/Medium/Low)
Sound-Po Sound power level (High/Medium/Low)
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
PI-C Power input in cooling
PI-H Power input in heating
Power supply Power supply
Dimension(WxHxD) Net Dimension (WxHxD) mm
Weight Weight

5.3 Outdoor Unit Details (OU-FA-02)

5.3.1 Outdoor Unit Details Table

Model 38VF044H119016
Module 38VF022H119016 38VF022H119016
Tmp-C ℃ 40
RTC kW
ATC kW 122
PI-C kW 39.57
EER 3.08
Tmp-H ℃/℃ 7.6/6.9
RHC kW

CSSP 3.1005 10
AHC kW 134.2
PI-H kW 31.87
COP 4.21
CR 99.2
Airflow m^3/h 17000 17000
Sound-Pr 63 63
Sound-Po
Bas-Refr kg 34.00
Ex-Refr kg 5.76
TCO2 eq. 83.03
MCA A 47.9 47.9
MFA A 63 63
Power supply V/ph/Hz 380-415V-3ph-50/60Hz 380-415V-3ph-50/60Hz
Dimension (WxHxD) mm 1340*1635*825 1340*1635*825
Weight kg 348 348

5.3.2 Table of Abbreviations

Abbreviation code Description


Tmp-C Outdoor conditions in cooling (Dry bulb temp.)
RTC Required cooling capacity
ATC Available cooling capacity
PI-C Power input in cooling
EER EER
Tmp-H Indoor conditions in heating (Dry bulb temp. / Wet bulb temp. / RH)
RHC Required heating capacity
AHC Available heating capacity
PI-H Power input in heating
COP COP
CR Combination ratio

CSSP 3.1005 11
Airflow Outdoor unit airflow
Sound-Pr Sound pressure level
Sound-Po Sound power level
Bas-Refr Standard factory refrigerant charge
Ex-Refr Extra refrigerant charge
TCO2 eq. Tonnes of CO2 equivalent
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
Power supply Power supply
Dimension (WxHxD) Net Dimension (WxHxD) mm
Weight Weight

5.4 Piping Limitations (OU-FA-02)

5.4.1 Piping Limitations

Item Capability Actual Value


Total piping length 1000.00(m) 56.50(m)
Longest actual length 175.00(m) 16.00(m)
Longest equivalent length 200.00(m) 18.50(m)
Longest equivalent length after first branch 90.00(m) 15.00(m)
Indoor unit to nearest branch length 40.00(m) 1.00(m)
Length difference between longest and shortest distance to indoor units 40.00(m) 0.00(m)
Height difference between indoor and outdoor unit(ODU up) 90.00(m) 0.00(m)
Height difference between indoor and outdoor unit(ODU down) 110.00(m) 0.00(m)
Height difference between indoor units 30.00(m) 0.00(m)
Combination ratio 50-100% 99.19%
IDU quantity 64 1

5.4.2 Correction Factors

CSSP 3.1005 12
Item Correction factor
Altitude (indoor unit) 0.999
Altitude (outdoor unit) 0.999
Piping (cooling) 0.997
Piping (heating) 1.000
Defrost (heating) 1.000

5.4.3 Piping Details Table

No. Length(m) Piping diameter


(1) 3.00 Φ/Φ19.1
(2) 3.00 Φ/Φ15.9
(3) 3.00 Φ/Φ15.9
(4) 3.00 Φ/Φ12.7
(5) 3.00 Φ/Φ12.7
(6) 3.00 Φ/Φ12.7
(7) 3.00 Φ/Φ12.7
(8) 3.00 Φ/Φ15.9
(9) 3.00 Φ/Φ15.9
(10) 1.00 Φ/Φ19.1
(11) 1.00 Φ38.1/Φ

5.4.4 Branch Joints Details Table

No. Load(kW) Model


(1) 122 FQZHD-04
(2) 56 FQZHD-03

5.4.5 Reducer Details Table

CSSP 3.1005 13
5.4.6 Combined Outdoor Units Details Information

Outdoor branch joint model


Outdoor branch Model name
L+M BJC-02E-CM(i)
Outdoor unit-Branch/Branch-Branch
Piping Piping diameter(mm) Piping length(m)
L1 Φ31.8,Φ15.9 3
L2 Φ31.8,Φ15.9 3

CSSP 3.1005 14
5.5 Piping Diagrams (OU-FA-02)

CSSP 3.1005 15
5.6 Wiring Diagrams (OU-FA-02)

CSSP 3.1005 16
6. Centralized Control Solution

6.1 Centralized Controller List

The centralized control system of this project is full output regardless of whether the system is selected.