METROSIL FOR HIGH IMPEDANCE RELAYS

Maximum protection against internal fault conditions.


Differential relay systems are traditionally used to protect individual pieces of plant. The relay monitors the ingoing
and outgoing current from the equipment, and if a mismatch occurs a secondary current flows through the relay,
causing it to trip. The secondary current can result in high voltages within the relay, so to prevent damage to the
relay or the current transformer, a Relay Metrosil should be used to safely clamp the voltage.

METROSIL FEATURES: METROSIL BENEFITS:


• Industry standard protection varistor for major OEMs • Over 80 years’ manufacturing experience
• Specialist materials to ensure superior longevity • Flexible designs customised to OEM requirements
• High energy varistor design • Exceptional safety record
• Pre-assembled, simple to install • Reduces downtime
RELAY DISCS SPECIFICATION
Recommended Relay Metrosils for Relays on 1A CTs

Maximum Relay Maximum Internal Secondary Fault Current 50 Arms


Setting Voltage Vrms Single Pole Relay Triple Pole Relay
125
175 600-A/S1/256 600-A/S3/l/802
185
300
600-A/S1/1088 600-A/S3/l/1195
325
400 600-A/S1/6315 600-A/S3/l/6324
Recommended Relay Metrosils for Relays on 5A CTs

Maximum Relay Maximum Internal Secondary Fault Current 50 Arms


Setting Voltage Vrms 50 100 150
200 600A/S1/1213 600A/S2/P/1217 600A/S3/P/1219
250 600A/S3/P/1220
600A/S1/1214 600A/S2/P/1215
275 600A/S3/P/1221
300 600A/S1/1223 600A/S2/P/1196 600A/S3/P/1222

DIFFERENTIAL RELAY PROTECTION


Busbar Differential Scheme Earth Fault Differential Scheme

Current Transformer A Current Transformer B


Power
Protected Equipment System
Plant

Metrosil
R

Metrosil
Rstab
Rstab
Relay

metrosil.com

For more information surrounding our varistors for high impedance relays, please contact
the Metrosil team:

SALES ENQUIRIES TECHNICAL ENQUIRIES


Tel: +44 (0)161 864 5456 Tel: +44 (0)161 864 5462
e-mail: [email protected] e-mail: [email protected]

Any recommendation or suggestion relating to the use, storage, handling or properties of the products supplied by M&I Materials Ltd, or any member of
its group, either in sales and technical literature or in response to a specific enquiry or otherwise, is given in good faith but it is for the customer to
satisfy itself of the suitability of the product for its own particular purposes and to ensure that the product is used correctly and safely in accordance
with the manufacturer’s written instructions. © M&I Materials Ltd 2018.

You might also like