School Report
School Report
Calculation Months .................................... Sep to Jun Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads
Total coil load .......................................................... 1.9 Tons Load occurs at .................................................. Jun 1500
Total coil load ........................................................ 23.2 MBH OA DB / WB ................................................... 110.0 / 64.0 °F
Sensible coil load .................................................. 23.2 MBH Entering DB / WB ............................................ 85.9 / 58.2 °F
Coil CFM at Jun 1500 ............................................ 830 CFM Leaving DB / WB ............................................. 58.1 / 47.0 °F
Max block CFM ...................................................... 830 CFM Coil ADP .................................................................... 55.0 °F
Sum of peak zone CFM ......................................... 830 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 1.000 Resulting RH ................................................................ 26 %
ft²/Ton .................................................................. 256.9 Design supply temp. .................................................. 55.0 °F
BTU/(hr-ft²) ............................................................ 46.7 Zone T-stat Check .................................................. 0 of 1 OK
Water flow @ 10.0 °F rise ..................................... 4.64 gpm Max zone temperature deviation ................................. 0.2 °F
Max coil load ......................................................... 13.1 MBH Load occurs at .................................................... Des Htg
Coil CFM at Des Htg .............................................. 830 CFM BTU/(hr-ft²) ................................................................ 26.5
Max coil CFM ......................................................... 830 CFM Ent. DB / Lvg DB ............................................. 61.6 / 77.4 °F
Water flow @ 20.0 °F drop .................................... 1.32 gpm
Actual max CFM .................................................... 830 CFM Fan motor BHP ......................................................... 0.00 BHP
Standard CFM ........................................................ 771 CFM Fan motor kW ........................................................... 0.00 kW
Actual max CFM/ft² ............................................... 1.67 CFM/ft² Fan static .................................................................. 0.00 in wg
Calculation Months .................................... Sep to Jun Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.004 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4412.3 BTU/(hr-CFM)
Site Altitude = 2007.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.004 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4412.3 BTU/(hr-CFM)
Site Altitude = 2007.0 ft
0.016
0.012
0.010
0.008
5 0.006
34 2
1 0.004
0.002
0.000
30 40 50 60 70 80 90 100 110
Temperature ( °F )