Pepperl Fuc Interface Module
Pepperl Fuc Interface Module
VAA-4E4A-KE-ZEJQ/E2L
< Housing with removable, mechanical and color coded terminals
< Communication monitoring
< Inputs for 2- and 3-wire sensors
< Addressing jack
< Power supply of outputs from the external auxiliary voltage
< Selectable supply to the sensors: External or from the module
< Function display for bus, external auxiliary voltage, internal
sensor supply, inputs, and outputs
< Red LED per channel, lights up in the event of output overload
< Switchable lead breakage detection (outputs)
Function
The AS-Interface I/O module VAA-4E4A-KE-ZEJQ/E2L is a control cabinet module with 4 inputs and 4 electronic outputs. The housing is only 22.5
mm wide and takes up little space in the control cabinet. The module is mounted by snapping onto the 35-mm DIN rail in compliance with EN
50022.
The connection is made via plug-in terminals. Four-terminal blocks (black) are used for the inputs and outputs. The connection of the external bulk
power and the AS Interface is via 2-terminal blocks (bulk power grey, AS-Interface yellow). Terminals for the inputs and outputs are mechanically
coded to prevent incorrect connection.
The supply to the inputs and the connected sensors can be fed either from the internal supply of the module (from the AS-Interface) or via an
external voltage source. A switch located on the side of the module changes the supply source. The choice of internal input supply is displayed via
the INT LED. The IN and OUT LEDs display the current switching status of the relevant inputs and outputs. The OUT LED also indicates an
overload or a lead breakage at the associated output.
Note:
The device is equipped with a communication monitor, which deactivates the outputs if the AS-Interface does not communicate with the module
for more than 40 ms. The communication monitor can be deactivated via the parameter P0. Filters that suppress pulses with a duration of 2 ms or
less at the inputs can be connected via the parameter P1.
Parameter P2 activates a lead breakage detection system for the outputs. This function detects and reports a missing load, providing the relevant
output is deactivated. The associated OUT LED and the 'peripheral fault' function display the signal transmitted to the AS-Interface master. A
signal indicating an overload of the internal input supply or the outputs is also transmitted to the AS-Interface master via the 'peripheral fault'
function. Communication via the AS-Interface continues even if a peripheral fault is set.
Dimensions
22.5 7 99
Release date: 2023-03-28 Date of issue: 2023-03-28 Filename: 209759_eng.pdf
102
Technical Data
General specifications
Node type Standard node
AS-Interface specification V3.0
Required gateway specification ≥ V2.0
Connection
Switch position
"INT" "EXT"
EXT
4 inputs IN1 ... IN4
I+ UEXT
AS-Interface - INT IN
AS-Interface + IN
EXT
I-
INT
for 3-wire for 3-wire
sensors sensors
ADDR
PWR
AUX
Load
Release date: 2023-03-28 Date of issue: 2023-03-28 Filename: 209759_eng.pdf
AUX +
AUX -
O-
Connection
Do not connect inputs and outputs, which are supplied via the module from AS-interface or via auxiliary power, with power supply and signal
circuits with external potentials.
I- 1 I- 2 I- 3 I- 4
IN1 IN2 IN3 IN4 label field
I+ 1 I+ 2 I+ 3 I+ 4
ATT E NT I O N
Do not connect the terminals I+, IN and I- with
any external potential when switch set to "INT" 1 2 3 4
IN
Sensor supply: FAULT INT
INT = internal sensor supply (from AS-i)
EXT = external sensor supply PWR AUX
INT ADDR
1 2 3 4
EXT OUT
O1 O-1 O2 O-2
O3 O-3 O4 O-4
AS-i+ AS-i- AUX+ AUX-
Programming
Data bits
(function via AS-Interface)
Data bit Input Output
D0 IN1 O1
D1 IN2 O2
D2 IN3 O3
D3 IN4 O4
Parameter bits
(programmable via AS-Interface)
Parameter bit Function
P0 Communication monitoring
P0=0 monitoring off, the outputs maintain the status if communication fails
P0=1 monitoring on, if communication fails, the outputs are deenergised, default setting
P1 Input filter
P1=0 input filter on, pulse suppression ≤ 2 ms
P1=1 input filter off, default setting
P2 Lead breakage outputs
P2=0 lead breakage on
P2=1 lead breakage off, default setting
P3 not used
Accessories
VBP-HH1-V3.0-KIT AS-Interface Handheld with accessory
Release date: 2023-03-28 Date of issue: 2023-03-28 Filename: 209759_eng.pdf
VAZ-CHAIN- 25-point wiring link for control cabinet modules with screw terminals
BU/BN70MM/1,0-25