COMMERCAIL EXPRESS BROADWAY, Sector A, Plot# 132

Phase VIII DHA Lahore (Existing Data)

Max
Max Load (Connected) No. of Transformer
Feeder # 80% Loading
(KVA)
(KVA)
KW KVA Amp
9 x 630
1 8899.5 10470 549.5 7096
12 x 400
6 x 630
2 8483 9980 523.8 15 x 400 7984
1 x 200
7 x 630
3 9613 11310 593.6 17 x 400 9048
1 x 100
11 x 630
4 8610.5 10130 531.7 8104
8 x 400

8 x 630
5 8789 10340 542.7 13 x 400 8272
1 x 100

10 x 630
6 9095 10700 561.6 8560
11 x 400
6 x 630
7 8313 9780 513.3 7824
15 x 400
12 x 630
8 9146 10760 564.7 8608
8 x 400
7 x 630
9 8508.5 10010 525.4 8008
14 x 400
3 x 630
10 8041 9496 496.5 21 x 400 7568
1 x 200
10 x 630
11 9095 10700 561.6 8560
11 x 400
3 x 630
12 9256.5 10890 571.6 22 x 400 8712
1 x 200
11 x 630
13 9120.5 10730 563.2 9 x 400 8584
1 x 200
Total Load in KVA 106928
Total Load in MVA 106.928
U/L Load of Additional Feeder F#14 (MVA) 1.962
New Grand Total 108.89
The quantity of the transformer in CEBW DHA Phase VIII should be
Note:
3 x 40 MVA or equivalent