TERMINAL BOX BOM TAG LABEL Solution Specification

IECEx certificate IECEx SIM 09.0001X


Item Qty Description Model No Manufacture Certification Marking Certification No (IECEx) Certification coding Ex e II T6 IP66
ES4050S-1H 1.5mm Thick Enclosure with hinged and removable REFER TO SOLUTION REFER TO SOLUTION Zone Zone 1 & 2
1 1 no ES4050S-1H Pepperl+Fuchs Enclosure T amb range -20 to +65°C @ T6
door, captive clamp SPECIFICATION SPECIFICATION
2 1 no Gland Plate 3mm thick SS316L - Pepperl+Fuchs - -
3A 1 no Name plate SS316 - Pepperl+Fuchs - - IP rating IP66
3B 1Set Equipment Identification Label SS316 - Rowmark - - Enclosure material 316L STAINLESS STEEL
3C 1Set Captive Clamp Warning Label SS316 - Rowmark - - Finish ELECTRO POLISHED
769-812-RTU-DJB-001
3D 1Set ESD Warning Label Traffolyte (Red-White-Red) Rowmark Gasket material Neoprene
24VDC
1Set M10 Internal / External Earth Stud SS316 - - Gross weight 16 kg
4 RTU JUNCTION BOX
1Set M6 Cover,Bottom Gland Plate Earth Stud SS316 - - - - Supply voltage 24VDC
ELECTROSTATIC HAZARD
5 1 no Internal Mounting Plate 2mm thick SS316 - - - - CLEAN ONLY
Max. power dissipation 16W
WITH A DAMP CLOTH
Terminal 2.5 Sqmm Feed through Screw clamp type Gray Colour Min. Cable CSA 1mm2 @ Max Current 3A
6 41nos UT 2.5 Phoenix Ex e IIC IECEx KEM 06.0027U
marked both side as shown Max. Cable CSA 2.5mm2 @ Max Current 3A
7 2nos Terminal End Cover D-UT 2.5/10 Phoenix - -
8 4nos Terminal End Clamp CLIPFIX 35-5 Phoenix - - WARNING!
DO NOT OPEN WHEN ENERGIZED
9 2 nos Tag Holder / Carrier 496119(GE) KLEMSAN - -
10 2Set Din Rail / SS316 TS35 Phoenix - - Entry Details
11 1 no M20 Drain / Breather Plug BDRVX-1MXS Pepperl+Fuchs Exe IIC IP66 IECEx IMQ 14.0003X Size / Quantity
12 3set PVC WIRE DUCT 40x80mm SIZE M20 1
2 " NPT 3
4 " NPT 1" NPT 1 41 " NPT 1 21 " NPT 2" NPT
13 1 no SS 316L DATA POCKET Entry Type
OD Ø20.5 Ø21.34 Ø26.67 Ø33.4 Ø42.16 Ø48.26 Ø60.33

Face A - - - - - - - -
Face B Clearance Hole 1 19 - - 2 - -
Face C - - - - - - - -
Face D - - - - - - - -
Terminal Layout

8 8
9 TB1
7 9 TB2
7

3B
769-812-RTU-DJB-001
6 6
24VDC

TB1 TB2
RTU JUNCTION BOX

3D
ELECTROSTATIC HAZARD
CLEAN ONLY
WITH A DAMP CLOTH

13

12 12 12
3C

10 10

4 4

FRONT VIEW L.H.S. VIEW INTERNAL VIEW R.H.S. VIEW

INTERNAL EARTH WIRE


6Sqmm YELLOW/GREEN

B B B B B B B

A B B B B B B B E E

B B B B B B

TAG NUMBERS E
FACE B / BOTTOM VIEW
EPS23006-E-103 EPS23007-E-103
769-812-RTU-DJB-001 769-812-RTU-DJB-011
769-811-RTU-DJB-001 769-811-RTU-DJB-011
TORQUE VALUE FOR FASTENERS VALUE in Nm 752-812-RTU-DJB-001 752-812-RTU-DJB-011
M3 NUT & BOLT(NAME / TAGPLATE) 1 Nm
752-811-RTU-DJB-001 752-811-RTU-DJB-011
M5 & M6 NUT & BOLT(BASE PLATE) 2 Nm
3 M6 GLAND PLATE 2 Nm
753-812-RTU-DJB-001 753-812-RTU-DJB-011
4 EXe/EXde/WEATHER PROOF COVER(M6) 2 Nm 753-811-RTU-DJB-001 753-811-RTU-DJB-011
5 TERMINAL BLOCK 2.5sqmm 0.5/0.6Nm Min/Max

PO L/I: 8 OF 10
Notes: E Certified Final 26/09/2024 VCV VCV NIN This document contains safety-relevant information. It must not be altered without the authorization of the norm expert! ALL DIMENSIONS ARE IN MM
1. OBSERVE TAG PLATE SCREW FIXING AS PER P+F DOCUMENT QSP/PRD/01-05 D Certified Final 18/09/2024 VCV VCV NIN
CONFIDENTIAL acc. to ISO 16016 Only valid as long as released in EDM or with a valid production documentation! Tolerance acc: DIN ISO 2768-cK
MAINTAINING IP66 C Issued for approval 22/08/2024 VCV VCV NIN
B Issued for approval 16/04/2024 VCV VCV NIN GENERAL ASSEMBLY DRAWING P.O. No.: EL PO24-022908-1 Drawing No Rev.
2. ALL UNUSED ENTRIES SHOULD BE PLUGGED WITH SUITABLE CERTIFED STOPPING Scale: PFG24 279Ex_c
PLUGS IN ORDER TO MAINTAIN Ex e / IP66 Protection. A Issued for approval 21/03/2024 VCV VCV NIN JUNCTION BOX W.O.No.: DO NOT SCALE E
ES4050S 1H PFG/2297/2024 IF IN DOUBT ASK NTS Sheet 1
Rev Description Date Drawn Approved Norm EX of 1