MI 023-154 en
MI 023-154 en
MI 023-154 en
Master Instruction
: IMPRINT ::::::::::::::::::::::::::::::::::::::::::::
All rights reserved. It is prohibited to reproduce this documentation, or any part thereof, without
the prior written authorisation of Schneider Electric Systems USA, Inc.
1 Safety instructions 7
2 Device description 19
3 Installation 24
4 Electrical connections 50
5 Start-up 59
6 Operation 65
7 Service 131
10 Appendix 178
11 Notes 193
Data about software revisions is shown in menu 1.1.0 IDENT. For more data, refer to Function
description on page 85. If it is not possible to refer to the device menu, record the serial number
of the device (given on the device nameplate) and speak to the supplier.
NOTICE!
The manufacturer is not liable for any damage resulting from improper use or use for other
than the intended purpose.
This radar level transmitter measures distance, level, mass, volume and reflectivity of liquids,
pastes and slurries.
1.3 Certification
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
CE marking
The manufacturer certifies successful testing of the product by applying the CE marking. For
more data about the EU Directives and European Standards related to this device, refer to the EU
Declaration of Conformity. You can download this document free of charge from the website.
All devices are based on the CE marking and meet the requirements of NAMUR
Recommendations NE 21, NE 43, NE 53 and NE 107.
NOTICE!
LPR (Level Probing Radar) devices measure level in the open air or in a closed space (a metallic
tank etc.). TLPR (Tank Level Probing Radar) devices measure level in a closed space only. You
can use LPR devices for TLPR applications. The LPR and TLPR devices meet the requirements
of the RED (Radio Equipment Directive) for use in the member countries of the EU.
For more data about the order code, refer to Order code on page 178.
This level transmitter is approved to be used outside metallic tanks. If you use the device in the
open air, read the device nameplate to make sure that the device can be used for your
application. Only the antennas that follow are permitted for open-air applications:
S/N: xxxxxxxxxxxxxxxxxxx
Manufacturing date: YYYY-MM-DD
Tag No:
• TLPR (Tank Level Probing Radar) are required to be installed at a permanent fixed position at
a closed (not open) metallic tank or reinforced concrete tank, or similar enclosure structure
made of comparable attenuating material;
• flanges and attachments of the TLPR equipment shall provide the necessary microwave
sealing by design;
• sight glasses shall be coated with a microwave-proof coating when necessary (i.e. electrically
conductive coating);
• manholes or connection flanges at the tank shall be closed to ensure a low-level leakage of
the signal into the air outside the tank;
• whenever possible, mounting of the TLPR equipment shall be on top of the tank structure
with the orientation of the antenna to point in a downward direction;
• installation and maintenance of the TLPR equipment shall be performed by professionally
trained individuals only.
For data about how to install EMI/RFI shielding gaskets, refer to the instructions supplied with
this accessory.
• The antenna must always point downwards. The boresight direction of the antenna must be
vertical. No other angles are permitted.
• Install the device more than 4 km / 2.485 mi away from radio astronomy sites.
• If the device is 4...40 km / 2.485...24.855 mi away from radio astronomy sites, do not install the
device more than 15 m / 49.21 ft above the ground.
CAUTION!
If it is necessary to install the device less than 4 km / 2.485 mi from radio astronomy sites, you
must get the approval of the national regulatory authority before installation (e.g. ANFR
(France), Bundesnetzagentur (Germany), Ofcom (United Kingdom) etc.).
Radio quiet zones: locations of radio astronomy sites (stations) in Europe and northern Eurasia
Country Name of the station Location
Latitude, ϕ Longitude, λ
Finland Metsähovi 60°13'04" N 24°23'37" E
Tuorla 60°24'56" N 22°26'31" E
France Plateau de Bure 44°38'01" N 05°54'26" E
Germany Effelsberg 50°31'32" N 06°53'00" E
Hungary Penc 47°47'22" N 19°16'53" E
Italy Medicina 44°31'14" N 11°38'49" E
Noto 36°52'34" N 14°59'21" E
Sardinia 39°29'50" N 09°14'40" E
Latvia Ventspils 57°33'12" N 21°51'17" E
Poland Kraków – Fort Skala 50°03'18" N 19°49'36" E
Russia Dmitrov 56°26'00" N 37°27'00" E
Kalyazin 57°13'22" N 37°54'01" E
Pushchino 54°49'00" N 37°40'00" E
Zelenchukskaya 43°49'53" N 41°35'32" E
Spain Yebes 40°31'27" N 03°05'22" W
Robledo 40°25'38" N 04°14'57" W
Switzerland Bleien 47°20’26" N 08°06’44" E
Sweden Onsala 57°23’45" N 11°55’35" E
UK Cambridge 52°09'59" N 00°02'20" E
Darnhall 53°09'22" N 02°32'03" W
Jodrell Bank 53°14'10" N 02°18'26" W
Knockin 52°47'24" N 02°59'45" W
Pickmere 53°17'18" N 02°26'38" W
NOTICE!
LPR (Level Probing Radar) devices measure level in the open air or in a closed space (a metallic
tank etc.). TLPR (Tank Level Probing Radar) devices measure level in a closed space only.
For more data about the order code, refer to Order code on page 178.
This level transmitter is approved to be used outside metallic tanks. If you use the device in the
open air, read the device nameplate to make sure that the device can be used for your
application. Only the antennas that follow are permitted for open-air applications:
LEGAL NOTICE!
FCC
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two
conditions:
1. This device may not cause harmful interference, and
2. this device must accept any interference received, including interference which may cause un-
desired operation.
Changes or modifications made to this equipment not expressly approved by the manufacturer
may void the FCC authorizations to operate this equipment.
This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation. This equipment generates, uses and
can radiate radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning
the equipment off and on, the user is encouraged to try to correct the interference by one or
more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
• Consult the dealer or an experienced radio/TV technician for help.
LEGAL NOTICE!
IC
This device complies with Industry Canada licence-exempt RSS standard(s).
Operation is subject to the following conditions:
1. This device may not cause harmful interference, and
2. this device must accept any interference received, including interference that may cause un-
desired operation.
This device and the handbook complies with the requirements of RSS-Gen. Operation is subject
to the conditions that follow:
1. The installation of the LPR/TLPR device shall be done by trained installers, in strict compliance
with the manufacturer’s instructions.
2. The use of this device is on a "no-interference, no-protection" basis. That is, the user shall ac-
cept operations of high-powered radar in the same frequency band which may interfere with or
damage this device. However, devices found to interfere with primary licensing operations will
be required to be removed at the user’s expense.
3. The TLPR device shall be installed and operated in a completely enclosed container to prevent
RF emissions, which can otherwise interfere with aeronautical navigation.
4. LPR devices: Ensure a vertically downward orientation of the transmit antenna and an instal-
lation only at fixed locations.
5. The installer / user of this device shall ensure that it is at least 10 km from the Dominion Radio
Astrophysical Observatory (DRAO) near Penticton, British Columbia. The coordinates of the
DRAO are latitude 49°19'15" N and longitude 119°37'12" W. For devices not meeting this 10 km
separation (e.g. those in the Okanagan Valley, British Columbia) the installer / user must coor-
dinate with, and obtain the written concurrence of, the Director of the DRAO before the equip-
ment can be installed or operated. The Director of the DRAO may be contacted at 250-497-2300
(tel.) or 250-497-2355 (fax). Alternatively, the Manager, Regulatory Standards, Industry Canada,
may be contacted.
The Product Marketing Name (PMN) of this device is "LRx4 Free Space Radar series".
S/N: xxxxxxxxxxxxxxxxxxx
Manufacturing date: YYYY-MM-DD
Tag No:
Figure 1-2: U.S.A. and Canada: radio approval information on the nameplate
1 Type code (defined in order). For more data.
2 HVIN (Hardware Version Identification Number). This number gives the radar signal frequency (24GHZ = 24 GHz), the
location of the device (T=TLPR or L=LPR) and the type of signal converter (compact (C))
TLPR device: HVIN: 24GHZ-T-C
LPR device: HVIN: 24GHZ-L-C
3 FCC ID and IC number
TLPR device: FCC-ID:Q6BFMCW24G74T, IC number: 1991D-FMCW24GX4T
LPR device: FCC-ID: Q6BFMCW24G74L, IC number: 1991D-FMCW24GX4L
The contents and works in this document are subject to copyright. Contributions from third
parties are identified as such. Reproduction, processing, dissemination and any type of use
beyond what is permitted under copyright requires written authorisation from the respective
author and/or the manufacturer.
The manufacturer tries always to observe the copyrights of others, and to draw on works created
in-house or works in the public domain.
The collection of personal data (such as names, street addresses or e-mail addresses) in the
manufacturer's documents is always on a voluntary basis whenever possible. Whenever
feasible, it is always possible to make use of the offerings and services without providing any
personal data.
We draw your attention to the fact that data transmission over the Internet (e.g. when
communicating by e-mail) may involve gaps in security. It is not possible to protect such data
completely against access by third parties.
We hereby expressly prohibit the use of the contact data published as part of our duty to publish
an imprint for the purpose of sending us any advertising or informational materials that we have
not expressly requested.
1.5.2 Disclaimer
The manufacturer will not be liable for any damage of any kind by using its product, including,
but not limited to direct, indirect or incidental and consequential damages.
This disclaimer does not apply in case the manufacturer has acted on purpose or with gross
negligence. In the event any applicable law does not allow such limitations on implied warranties
or the exclusion of limitation of certain damages, you may, if such law applies to you, not be
subject to some or all of the above disclaimer, exclusions or limitations.
Any product purchased from the manufacturer is warranted in accordance with the relevant
product documentation and our Terms and Conditions of Sale.
The manufacturer reserves the right to alter the content of its documents, including this
disclaimer in any way, at any time, for any reason, without prior notification, and will not be liable
in any way for possible consequences of such changes.
If this document is not in your native language and if you have any problems understanding the
text, we advise you to contact your local office for assistance. The manufacturer can not accept
responsibility for any damage or injury caused by misunderstanding of the information in this
document.
This document is provided to help you establish operating conditions, which will permit safe and
efficient use of this device. Special considerations and precautions are also described in the
document, which appear in the form of icons as shown below.
DANGER!
This warning refers to the immediate danger when working with electricity.
DANGER!
This warning refers to the immediate danger of burns caused by heat or hot surfaces.
DANGER!
This warning refers to the immediate danger when using this device in a hazardous
atmosphere.
DANGER!
These warnings must be observed without fail. Even partial disregard of this warning can lead
to serious health problems and even death.
WARNING!
Disregarding this safety warning, even if only in part, poses the risk of serious health problems.
There is also the risk of damaging the device or parts of the operator's plant.
CAUTION!
Disregarding these instructions can result in damage to the device or to parts of the operator's
plant.
NOTICE!
These instructions contain important information for the handling of the device.
LEGAL NOTICE!
This note contains information on statutory directives and standards.
• HANDLING
This symbol designates all instructions for actions to be carried out by the operator in the
specified sequence.
i RESULT
This symbol refers to all important consequences of the previous actions.
NOTICE!
Antenna extensions are available for this device. These are supplied attached to the device. If
the antenna extensions are too long, the device will be supplied in two parts. For more data
about the assembly procedure, refer to How to attach antenna extensions on page 43.
Radar level transmitters use an antenna to emit a signal to the surface of the measured product.
The device has many antennas available. Thus, it can measure most products even in difficult
conditions. Also refer to Technical data on page 137.
If the device is ordered with the applicable options, it can be certified for use in hazardous areas.
The signal converter is attached directly to the process connection and the antenna. The
illustration that follows shows the types of antenna.
NOTICE!
The DN65 (2½¨) Metallic Horn antenna option is specially made for level chambers.
NOTICE!
Accessories:
For more data about general items, refer to Accessories: general items on page 187. For more
data about process connections, refer to Accessories: process connection kits on page 188.
NOTICE!
Inspect the packaging carefully for damages or signs of rough handling. Report damage to the
carrier and to the local office of the manufacturer.
Figure 2-4: Symbols for the supplied gasket material (on the side of the process connection)
1 EPDM
2 Kalrez® 6375
If the device is supplied with an FKM/FPM gasket, there is no symbol on the side of the process
connection.
NOTICE!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
NOTICE!
Compare the material references on the side of the process connection with the order.
2.4 Nameplates
NOTICE!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
NOTICE!
Do a check of the packing list to make sure that you have all the elements given in the order.
NOTICE!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
3.2 Storage
WARNING!
Do not keep the device in a vertical position. This will damage the antenna and the device will
not measure correctly.
3.3 Transport
WARNING!
Lift the device carefully to prevent damage to the antenna. If you remove the signal converter to
lift the device, do not interchange this part with a different signal converter. This can have an
effect on the performance of the device.
We recommend that you prepare the installation when the tank is empty.
Figure 3-4: Recommended nozzle position for liquids, pastes and slurries
1 Nozzle or socket for the DN40 or DN50 Metallic Horn antennas
2 Nozzle or socket for the DN80 or DN100 Metallic Horn antenna, and the DN80 Drop antenna
3 Nozzle or socket for the DN150 or DN200 Metallic Horn antenna, and the DN100 or DN150 Drop antenna
4 Tank diameter
5 Minimum distance of the nozzle or socket from the tank wall (depends on the antenna type and size – refer to items
1, 2 and 3 in this list):
– DN40 or DN50 Metallic Horn: 1/5 × tank height
– DN80 or DN100 Metallic Horn: 1/10 × tank height
– DN80 Drop: 1/10 × tank height
– DN150 or DN200 Metallic Horn: 1/20 × tank height
– DN100 or DN150 Drop: 1/20 × tank height
Maximum distance of the nozzle or socket from the tank wall (depends on the antenna type and size – refer to items
1, 2 and 3 in this list):
– Metallic Horn or Drop: 1/3 × tank diameter
6 Tank height
NOTICE!
If there is a nozzle on the tank before installation, the nozzle must be a minimum of 200 mm /
7.9¨ from the tank wall. The tank wall must be flat and there must not be obstacles adjacent to
the nozzle or on the tank wall.
Point the device in the correct direction to get the best performance
Figure 3-5: Point the device in the correct direction to get the best performance
1 Cable entry
2 Nearest tank wall
3 Tank centerline
Point the cable entries on the housing in the direction of the tank centerline.
Figure 3-6: There is no maximum limit to the number of devices that can be operated in the same tank
There is no maximum limit to the number of devices that can be operated in the same tank. They
can be installed adjacent to other radar level transmitters.
We recommend that you prepare the installation when the tank is empty.
CAUTION!
Do not install the device above objects in the tank (ladder, supports etc.) or pit. Objects in the
tank or pit can cause interference signals. If there are interference signals, the device will not
measure correctly.
If it is not possible to install the device on another part of the tank or pit, do an empty spectrum
scan. For more data, refer to Empty spectrum recording on page 111.
NOTICE!
If possible, do not install a nozzle on the tank centerline.
Figure 3-8: Equipment and obstacles: how to prevent measurement of interference signals
1 Do not tilt the device more than 2°
2 We recommend that you do an empty spectrum recording if there are too many obstacles in the radar beam (for more
data, refer to Empty spectrum recording on page 111).
3 If there are too many obstacles in the tank, you can install the device on a standpipe. For more data about how to install
the device on standpipes, refer to Standpipes (stilling wells and bypass chambers) on page 38.
4 Beam radius of the antenna: refer to the table below. The beam radius increases by increments of "x" mm for each
metre of distance from the antenna.
[mm/m] [in/ft]
Metallic Horn, DN40 (1½¨) 17° 150 1.8
Metallic Horn, DN50 (2¨) 16° 141 1.7
Metallic Horn, DN65 (2½¨) 10° 1 1 1
Metallic Horn, DN80 (3¨) 9° 79 0.9
Metallic Horn, DN100 (4¨) 8° 70 0.8
Metallic Horn, DN150 (6¨) 6° 53 0.6
Metallic Horn, DN200 (8¨) 5° 44 0.5
PP Drop DN80 (3¨) 9° 79 0.9
PP Drop, DN100 (4¨) 7° 61 0.7
PP Drop, DN150 (6¨) 5° 44 0.5
1 This antenna option is specially made for level chambers
Product inlets
CAUTION!
Do not put the device near to the product inlet. If the product that enters the tank touches the
antenna, the device will measure incorrectly. If the product fills the tank directly below the
antenna, the device will also measure incorrectly.
NOTICE!
For more data about the measuring range of each type of antenna, refer to Measuring accuracy
on page 146.
Equipment needed:
• Device
• Flange gasket (not supplied)
• Wrench (not supplied)
• Make sure that you point the device in the correct direction. For more data, refer to General
notes on page 27 ("Point the device in the correct direction").
• Tighten the flange bolts. Refer to local rules and regulations for the correct torque to apply to
the bolts.
i End of the procedure.
If the antenna diameter is larger than the process connection size (flange)
Figure 3-11: How to attach the device if the antenna diameter is larger than the process connection size
WARNING! If you attach the antenna in a closed space, make sure that there is a good airflow
in the area. Make sure that a person not in the tank can always hear you. Only authorized
personnel trained to work in confined spaces should be allowed to go inside the tank.
NOTICE!
If the antenna is larger than the process connection, we recommend that you use an antenna
extension. It is possible that there is not sufficient space to tighten the antenna locking screw.
• Attach the antenna to the part below the flange. We recommend that a person holds the device
on the top of the tank.
• Go to the top of the tank. Lift the device a small distance.
• Drop antennas without an antenna extension: Attach the three locking screws to the antenna
with a 3 mm Allen wrench.
• Metallic Horn antennas without an antenna extension: Attach the locking screw to the antenna
with a 3 mm Allen wrench.
• All antennas with one or more antenna extensions: Attach the locking screw to the top
antenna extension with a 3 mm Allen wrench.
• Put the device carefully on the tank flange.
• Make sure that you point the device in the correct direction. For more data, refer to General
notes on page 27 ("Point the device in the correct direction").
• Tighten the flange bolts. Refer to local rules and regulations for the correct torque to apply to
the bolts.
i End of the procedure.
NOTICE!
Antenna extensions for devices with flanges
If the device has antenna extensions, this option extends the maximum nozzle height. Each
antenna extension has a length of 105 mm / 4.1¨. The maximum number of antenna extensions
that can be attached to the device are:
• Metallic Horn antenna: 10
• PP Drop antenna without PP flange plate protection: 5
• PP Drop antenna with PP flange plate protection: 5
If the device has antenna extensions, this option extends the maximum socket height. Add the
length of the antenna extensions attached to the device to this value.
Equipment needed:
• Device
• Gasket for G 1½ connection (not supplied)
• Thread seal tape (PTFE) for 1½ NPT connection (not supplied)
• 50 mm open-end wrench (not supplied)
Figure 3-13: How to attach the device if the antenna is larger than the process connection
WARNING! If you attach the antenna in a closed space, make sure that there is a good airflow
in the area. Make sure that a person not in the tank can always hear you. Only authorized
personnel trained to work in confined spaces should be allowed to go inside the tank.
NOTICE!
If the antenna is larger than the process connection, we recommend that you use an antenna
extension. It is possible that there is not sufficient space to tighten the antenna locking screw.
• ISO 228-1 (G) connection: Make sure that you use the applicable gasket for the connection
dimensions and the process.
• ISO 228-1 (G) connection: Align the gasket correctly.
• NPT connection: Wind the thread seal tape around the process connection in agreement with
good engineering practice.
• Put the device carefully on the tank process connection. Do not attach the threaded connection
to the tank yet.
• Go inside the tank. If you attach the antenna in a closed space, make sure that there is good
airflow in the area.
• Attach the antenna to the part below the threaded connection. We recommend that a person
holds the device on top of the tank.
• Go to the top of the tank. Lift the device a small distance.
• Drop antennas without an antenna extension: Attach the three locking screws to the antenna
with a 3 mm Allen wrench.
• Metallic Horn antennas without an antenna extension: Attach the locking screw to the antenna
with a 3 mm Allen wrench.
• All antennas with one or more antenna extensions: Attach the locking screw to the top
antenna extension with a 3 mm Allen wrench.
• Attach the antenna locking screw to the antenna extension. Tighten the antenna locking
screw.
• Attach the device to the tank process connection.
• Tighten the connection to the correct torque (not more than 40 N·m / 29.5 lbf·ft).
• Make sure that you point the device in the correct direction. For more data, refer to General
notes on page 27 ("Point the device in the correct direction").
i End of the procedure.
NOTICE!
Antenna extensions for devices with threaded connections
If the device has antenna extensions, this option extends the maximum nozzle height. Each
antenna extension has a length of 105 mm / 4.1¨. The maximum number of antenna extensions
that can be attached to the device are:
• Metallic Horn antenna: 10
• PP Drop antenna: 5
3.7.3 LPR devices: recommendations for pits and tanks made of non-conductive materials
WARNING!
These instructions are for LPR equipment only. For more data, refer to Radio approvals on
page 8.
If the device cannot go in the tank and the tank is made of a non-conductive material (plastic
etc.), you can attach a support to the top of the tank without a hole in the tank roof. We
recommend that you put the antenna as near as possible to the top of the tank.
CAUTION!
If the tank is outdoors, we recommend that you seal the support. If rain is on the top of the tank
and directly below the device, this can have an effect on the device performance.
CAUTION!
If device is used in dusty conditions, we recommend that you seal the support. If dust is on the
top of the tank and directly below the device, this can have an effect on the device performance.
Open pits
If the device must measure the level of product in a pit, you can attach a support to the side of the
pit or above the pit.
Figure 3-16: Installation recommendations for standpipes (stilling wells and bypass chambers)
1 A stilling well solution
2 A bypass chamber solution
3 Air circulation hole
4 Level of the liquid
CAUTION!
• The standpipe must be electrically conductive.
• The inside diameter of the standpipe must not be more than 5 mm / 0.2¨ over the diameter
of the antenna (for a high-dielectric constant liquid).
• The standpipe must be straight. There must be no sudden changes in internal diameter
greater than 1 mm / 0.04¨.
• The standpipe must be vertical.
• Recommended surface roughness: <±0.1 mm / 0.004¨.
• Make sure that there are no deposits at the bottom of the standpipe.
• Make sure that there is liquid in the standpipe.
CAUTION!
If the device is installed in horizontal cylindrical tank that contains a high dielectric constant
liquid without a stilling well, do not put it on the tank centerline. This will cause multiple
reflections and the device will not measure accurately. Log into Program mode as an "Expert"
and set the C2.7 Mult. Refl. Enable function to "Enable" to keep the effects of multiple
reflections to a minimum. For more data, refer to Function description on page 85 (C. Full
Setup).
Bypass chambers
Installation next to tanks containing one liquid and foam
• The top process connection of the bypass chamber must be above the maximum level of
liquid.
• The bottom process connection of the bypass chamber must be below the lowest measured
level of liquid.
Figure 3-19: Installation recommendations for bypass chambers that contain more than one liquid
1 Bypass chamber
2 Additional process connection
Equipment needed:
• 3 mm Allen wrench (not supplied)
• 36 mm open-end or box-end wrench (not supplied)
CAUTION!
Metallic Horn antennas: Make sure that there are not more than 10 antenna extensions
attached to a device with a Metallic Horn antenna. If there are more than 10 antenna
extensions, the device will not measure correctly.
i Each antenna extension is 105 mm long. If the device has 3 antenna extensions, they have a
total length of 315 mm. In this example, enter the value "315".
• If you changed the antenna extension value, also change the blocking distance value. Push
[^
^], 3 × [
], [>
>] to go to menu item C1.5 Blocking Distance.
Distance
• Push [>>] to change the value. Push [>>] to change the position of the cursor. Push [
] to
decrease the value or [ ] to increase the value. Minimum recommended blocking distance =
antenna length + (antenna extension length × number of extensions) + 0.1 m / 4¨.
• Push 3 × [^^] to go back to the "Save Configuration?" screen.
• Push [] or [] to set the screen to Yes and push [^
^] to store and use the changed settings.
i End of the procedure.
NOTICE!
Drop antenna: Antenna extensions can only be attached below flanges without the PP flange
plate option.
CAUTION!
Drop antenna: Make sure that there are not more than 5 antenna extensions attached to a
device with a Drop antenna. If there are more than 5 antenna extensions, the device will not
measure correctly.
Make sure that you put an O-ring 4 into the groove at the top of each antenna extension.
CAUTION!
Locking screws
The lengths of the locking screws for the antenna extensions and the Drop antenna are
different. Make sure that you use the correct screw when you assemble the device. For more
data, refer to the list that follows.
Equipment needed:
• Cover wrench
• Display extractor
CAUTION!
Disconnect the power supply.
NOTICE!
The cover wrench and display extractor are supplied with the device. If it is necessary to send
an order for the cover wrench or the display extractor, refer to Accessories: general items on
page 187.
1 Put the weather protection clamp around the top of the device.
2 Attach the two locking nuts to the threads on the weather protection clamp. Tighten the lock-
ing nuts with a 10 mm socket wrench.
3 Lower the weather protection cover onto weather protection clamp until the hole for the lock
is in the slot at the front of the cover.
4 Put the R-clip into the hole at the front of the weather protection cover.
5 End of the procedure.
1 Remove the R-clip from the hole at the front of the weather protection cover.
2 Remove the weather protection cover.
3 Lift the display screen cover. End of the procedure.
DANGER!
Observe the national regulations for electrical installations!
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
WARNING!
Observe without fail the local occupational health and safety regulations. Any work done on the
electrical components of the measuring device may only be carried out by properly trained
specialists.
NOTICE!
Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.
NOTICE!
Devices with the FOUNDATION™ fieldbus output option:
For electrical connection data, refer to the "Description of FOUNDATION™ fieldbus interface"
supplementary instructions.
NOTICE!
Devices with the PROFIBUS PA output option:
For electrical connection data, refer to the "Description of PROFIBUS PA interface"
supplementary instructions.
NOTICE!
Electrical power to the output terminal energizes the device. The output terminal is also used
for HART® communication.
CAUTION!
• Use the applicable electrical cables with the cable glands.
• Make sure that the current is not more than 5 A or that there is 5 A-rated fuse in the
electrical circuit that energizes the device.
Equipment needed:
• 3 mm Allen wrench (not supplied)
• Cover wrench
Procedure
1 Loosen the lock screw with a 3 mm Allen wrench.
2 Remove the cover stop.
3 Turn the cover counterclockwise with the cover wrench.
4 Remove the cover.
Equipment needed:
• POZIDRIV® PZ1 screwdriver (not supplied)
Procedure
1 Loosen the cable gland. Put the electrical wires into the cable entry. Loosen the terminal
screws with a POZIDRIV® PZ1 screwdriver. Connect the electrical wires to the connector.
2 Tighten the terminal screws with a POZIDRIV® PZ1 screwdriver.
3 Tighten the cable gland.
Equipment needed:
• 3 mm Allen wrench (not supplied)
Figure 4-5: Terminals for electrical installation: 4-pin male M12 connector
1 Pin 1: current output +
2 Pin 2: not connected
3 Pin 3: current output -
4 Pin 4: not connected
5 Grounding terminal (external thread of the connector)
6 Location of the external grounding terminal (at the bottom of the converter)
NOTICE!
Electrical power to the output terminal energizes the device. The output terminal is also used
for HART® communication.
DANGER!
For electrical data for device operation in hazardous locations, refer to the related certificates
of compliance and supplementary instructions (ATEX, IECEx etc.). This documentation can be
downloaded from the website.
DANGER!
Make sure that the cable gland is watertight.
Figure 4-7: How to make the installation agree with protection category IP68
The diameter of the outer sheath of the electrical cable (for the power supply and current output)
must be 6…10 mm or 0.24…0.39¨.
4.7 Networks
4.7.1 General information
The device uses the HART® communication protocol. This protocol agrees with the HART®
Communication Foundation standard. The device can be connected point-to-point. It can also
have a polling address of 1 to 63 in a multi-drop network.
DANGER!
Before you energize the device, make sure that the supply voltage and polarity are correct.
DANGER!
If the device has a Hazardous Locations approval, make sure that the device and the installation
agrees with the requirements of the certificate of compliance.
CAUTION!
If the manufacturer received data about the installation, the device will display readings
correctly. If not, go to sub-menu A.4 Application Assistant in the configuration menu to select
the correct settings.
The output percentage bar graph is only shown if you set "One Value and Bar" or "Two Values
and Bar" in menu items C6.4.1 Function (1st Meas. page) or C6.5.1 Function (2nd Meas. Page). If
menu item C6.4.2 1st Value Variable (1st Meas. page) is set to "Level", then the device shows
"Level" as the current output percentage in Normal mode (refer to item 1 in the illustration).
For more data on keypad functions, refer to Keypad functions on page 73.
Figure 5-3: How to push the keypad buttons with your hand
Equipment needed
• Cover wrench
1 Remove the housing cover with the cover wrench supplied with the device.
2 Push the buttons on the keypad.
i This will operate the device.
Figure 5-4: How to operate the keypad buttons with a bar magnet
Equipment needed
• Bar magnet
NOTICE!
It is not necessary to remove the display housing cover to do this procedure.
You can download the latest version of PACTware™ and the DTM from our website.
Program mode Use this mode to read and change parameters, commission the device,
create tables for volume or mass measurement, and change critical values
to measure in difficult process conditions. To change settings in Program
mode, you must use the device with the correct access level (user, operator
or expert). For more data about menu items, refer to Function description
on page 85.
All users can read the settings in Program mode, but only users with
"Operator" and "Expert" access levels can change settings. For more data
about access levels, refer to Protection of the device settings (access
levels) on page 70.
There are 5 options to show the measurement data on the display screen. Refer to the
illustration that follows:
NOTICE!
Current output and LCD display settings
When you do the Standard setup procedure, the measurement value on the first measurement
page of the LCD display (in Normal mode) automatically uses settings with the same
parameters and values as the current output settings (measurement variable, 0% range and
100% range). The first measurement page shows "one value and bar" by default. If you must
show one or more measurement values that are different to the transmitted output signal,
change the settings in the C6.4 1st Meas. Page and C6.5 2nd Meas. Page menus. For more data,
refer to Function description on page 85 – table C. Full Setup menu (C6 Display).
Measurement data includes different measurement types (level, distance, volume, ullage
volume, mass etc.). Some measurement types will only be available in Normal mode if you
entered the correct parameters in Program mode. Normal mode shows abbreviations of
measurement types if the measurement page is configured to show more than one
measurement value. For a list of the abbreviations used in Normal mode, refer to the table that
follows:
Figure 6-2: Error symbol: the number of digits and decimal places is not sufficient for the measurement data
1 Error symbol: the number of digits and decimal places is not sufficient for the measurement data. It is possible that
the length units must be changed from "mm" to "m".
In this example, the device measures a distance of 10.001 m, but C7.5.1 Length is set to "mm"
and C6.4.5 Format 1st Value is set to "X.XXX" (four digits with three decimal places). This is not
sufficient to show a measurement value of 10.001 m. If the measurement value is equal to or
more than 10 m, set C6.4.5 Format 1st Value to "Automatic".
You can change the number of digits and decimal places in the measurement values shown in
Normal mode.
NOTICE!
How to change the number of digits and decimal places in the measurement values shown in
Normal mode
1st Measurement Page: Go to menu C6.4 1st Measur. Page and then change the number of
digits and decimal places in C6.4.5 Format 1st value
value, C6.4.7 Format 2nd value or C6.4.9 Format
3rd value.
value
2nd Measurement Page: Go to menu C6.5 2nd Measur. Page and then change the number of
digits and decimal places in C6.5.5 Format 1st value
value, C6.5.7 Format 2nd value or C6.5.9 Format
3rd value.
value
If there is a large change in a measurement value, set the related menu item to "Automatic".
• Use the A Quick Setup menu to change the display language, change the tag name, log in to
change settings, do standard setup and empty spectrum recording procedures.
• Use the B Test menu to run diagnostic tests, read measurement and spectrum data.
• Use the C Full Setup menu to change settings. You can set up a conversion table for volume
or mass measurement, change current output values, change HART® settings, change how
the measurement data is shown in Normal mode, read device identification data, change
critical parameters for difficult process conditions, change the password, change
measurement units or reset the device to factory default settings.
CAUTION!
If you did not supply all installation data to the supplier before the delivery, the standard setup
procedure in the Quick Setup menu is mandatory.
NOTICE!
It is not possible to enter the D Service menu. This menu is for factory calibration and approved
personnel only.
Operator 0009 • Read: Measurement data and error messages available at the
"User" access level (Normal mode and menu items B2 Actual
Values and C7.3.1 Message View)
• Change: All HART® settings (C5) – but not C5.1.1 Current Loop
Mode
NOTE: You can change the password for the "Operator" access level
in menu item C7.2.2 Change Password. Refer to the INFORMATION!
note that follows.
User — • Read: Measurement data and error messages (Normal mode and
men items B2 Actual Values and C7.3.1 Message View)
• Read: All settings in menus A Quick Setup, B Test and C Full Setup
• Change: All settings in menu C6 Display (language, backlight
on/off, screen contrast and measurement data display options
(Normal mode, pages 1 and 2)) and C7.5 Units (length, volume,
mass and custom units)
• Change: Access level. Go to menu item A3 Login or C7.2.1 Login to
change from "User" to "Operator" or "Expert" access levels
If your access level is too low, the display will show a "lock" symbol adjacent to menu items in
Program mode. If it is necessary to change a setting, move the cursor to the menu item, push [> >]
and enter the password used at this time for that menu item.
NOTICE!
Each access level has a four-digit hexadecimal password.
The first three digits of the password for the "Operator" access level must be zero (000x). The
last digit can be a number (1...9) or a letter (A...F).
The first two digits of the password for the "Expert" access level must be zero (00xx). The last
two digits can be a number (1...9) or a letter (A...F).
NOTICE!
Make a note of the password and keep it in a safe place. If you lose the password, please speak
or write to your supplier.
NOTICE!
If you de-energize the device and then energize it again, the access level will go back to "User".
If you do not touch the keypad for 5 minutes, the device goes back to Normal mode and the
access level will go back to "User".
CAUTION!
If you did not supply all installation data to the supplier before the delivery, the standard setup
procedure in the Quick Setup menu is mandatory.
Menu navigation
This is what you see when you are in Program mode. The functions of the buttons are given in the
table that follows:
Down • Scroll down the menu list (for example, from menu C1 to menu C2.
• Scroll down the sub-menu list (for example, from sub-menu C2.1
to sub-menu C2.2).
Up • Scroll up the menu list (for example, from menu C2 to menu C1).
• Scroll up the sub-menu list (for example, from sub-menu C2.2 to
sub-menu C2.1).
This is what you see when you select a menu item that has a list of parameters. The functions of
the buttons are given in the table that follows:
Esc (Escape) If you push these buttons immediately after you change a parameter,
the device also ignores this change and goes back to the menu.
Down Scroll down the list
This is what you see when you select a menu item that has a value.
NOTICE!
If menu items have values that you can change, very large and very small values can be written
as a value with an exponent (bn). For example, if the value shown on the display is 100.00+03,
this value is equal to 100 × 103or 100000.
The functions of the buttons are given in the table that follows:
Esc (Escape) If you push these buttons immediately after you change a value, the
device also ignores this change and goes back to the menu.
Down If the cursor is on a number, this button decreases the digit value. If
the cursor is on the decimal point, this button moves the decimal
point to the left (this decreases the value by a factor of 10).
Up If the cursor is on a number, this button increases the digit value. If
the cursor is on the decimal point, this button moves the decimal
point to the right (this increases the value by a factor of 10).
NOTICE!
Values in menu items
If the digit is part of a custom unit name, then refer to the list of available characters that
follows:
Numbers
0 1 2 3 4 5 6 7 8 9
Special characters
2 3 _ - / .
Menu A Submenus
Menu B Submenus
Menu C Submenus
Normal Program
Menu C Submenus
Normal Program
Menu C Submenus
Normal Program
Menu C Submenus
Normal Program
Menu C Submenus
B – Test menu
Menu Function Function description Selection list Default
No.
B1 Simulation
B1.1 Set Value
B1.1.2 Level This sets the device to a given test level min-max: 1
value. Make sure that menu item -4900.0...+5100.0 m /
C4.1.1 Current Out. 1 Var. is set to -192.91+03...+200.79+03 in /
"Level" before the device simulates a -16076...+16732 ft
level value. This procedure sends an
output signal that agrees with the test
reading. Output will change to the
selected value, independent of the
measurement data.
B2 Actual Values
B2.1 Operating Time This is the total time that the device is Read only —
[s] energized in seconds.
B2.4 Level This menu item shows the level Read only —
readings measured at this time. This
measurement data is shown with the
units set in menu C7.5 Units.
Units
B2.5 Distance This menu item shows the distance Read only —
readings measured at this time. This
measurement data is shown with the
units set in menu C7.5 Units.
Units
B2.6 Reflection This menu item shows the percentage Read only —
of the emitted radar signal which
makes a reflection on the surface of
the tank contents and is received by the
device. If the distance measured is less
than 1 metre, then the reflection value
is 0%.
B3 Power Spectrum
B3.2 Power Spectrum This menu item shows the raw spectra Read only —
data of the radar signal which makes a
reflection on the surface of the tank
contents and is received by the device.
This data is shown as a graph of the
percentage of the full-scale signal
against distance.
C1 Install. Parameters
C1.1 Tank Type The conditions in which the device is used. If Agitator, Stilling Well, Process 1
the surface of the product is flat, select Process, Storage
"Storage". If the surface of the product is
disturbed, select "Process". If the surface of
the product is agitated with vortexes and
foam, select "Agitator". If the device is
installed in a stilling well, select "Stilling
Well".
C2 Process
C2.1 Tracking This menu item sets the maximum rate of min-max: 500-03 m/min /
Velocity change of level in metres per minute or feet 1.2-03…60.0 m/min / 1.64042 ft/min
per minute. The measured value cannot
change faster than the tracking velocity. 3.94-03...196.85 ft/min
C3 Conversion
C3.1 Edit Table
C3.1.1 Erase Table? Before you can make a conversion table, you Yes, No No
must delete the data that is stored in the
device at this time. If you set this menu item
to "No" you will go back to menu C3.1. If you
set it to "Yes", you will go to menu item
C3.1.3 Select Conversion.
C4 Output
C4.1 Current Output 1
C4.1.1 Current Out. 1 Make a selection from the available output Level, Distance, Level 1
Var. functions to scale the current output values. Sensor Value,
This is not shown in Normal mode. Reflection 2
C5 Communication
C5.1 HART
C5.1.1 Current Loop Set this menu item to "On" if the "Primary On, Off On
Mode Variable" for current output 1 must also be
transmitted as a 4…20 mA signal. If this
menu item is set to "Off', this stops the
4…20 mA signal and starts HART® multi-
drop mode.
C6 Display
C6.1 Language Data can be shown in one of the languages English, German, English
stored in the device. Make a selection from French, Italian,
the list. Portuguese, Spanish,
Czech, Polish, Chinese
Minimum access level to change the (simplified), Japanese,
setting: User Russian, Turkish
C6.2 Backlight If you set this menu item to "Enabled", a Disabled, Enabled Enabled
light comes on when you push a button on
the display keypad and if the loop current is
more than 6 mA.
C7 Device
C7.1 Information
C7.1.1 Tag Use this menu item to read the Tag name. Read only TANK01 1
C7.1.2 Serial Number This is the device fabrication number Read only —
C7.1.3 Device Name This gives the device family name and model Read only —
code.
C7.1.4 V Number This is the manufacturer's option code for Read only —
device configuration.
C7.1.5 Electronic This is the hardware revision number. This Read only —
Revision number agrees with NAMUR NE 53
Guidelines.
C7.1.6 Software This is the software revision number. This Read only —
Revision number agrees with NAMUR NE 53
Guidelines.
C7.1.7 Electronic This is the hardware fabrication number. Read only —
Serial No. This number agrees with NAMUR NE 53
Guidelines.
C7.1.8 Production Date This the date that the manufacturer finished Read only —
the device. The date format is: Year-Month-
Day.
C7.1.9 Calibration Date This the date that the manufacturer Read only —
calibrated the device. The date format is:
Year-Month-Day.
C7.2 Security
C7.2.1 Login Enter the appropriate password here to 4-digit hexadecimal Refer to
change settings. If you do not enter the password "Function
password, you can only change settings for description"
the "user" access level. For more data and
the default passwords for the "operator"
and "expert" access levels, refer to
Protection of the device settings (access
levels) on page 70.
C7.2.2 Change This changes the password for the 4-digit hexadecimal Refer to
Password "operator" and "expert" access levels. For password "Function
the procedure to change the password, description"
refer to Protection of the device settings
(access levels) on page 70 (How to change
the password).
CAUTION!
Make sure that you do this procedure before you use the device. The settings in this procedure
have an effect on the performance of the device.
NOTICE!
Current output and LCD display settings
When you do the Standard setup procedure, the measurement value on the first measurement
page of the LCD display (in Normal mode) automatically uses settings with the same
parameters and values as the current output settings (measurement variable, 0% range and
100% range). The first measurement page shows "one value and bar" by default. If you must
show one or more measurement values that are different to the transmitted output signal,
change the settings in the C6.4 1st Meas. Page and C6.5 2nd Meas. Page menus. For more data,
refer to Function description on page 85 – table C. Full Setup menu (C6 Display).
Procedure
Screen Steps Description
• 2 × [>>], 2 × [
] and [>
>]. Default screen.
• If it is the default password: 2 × [>>], Enter the password used at this time for
5 × [
], [>
>] and 8 × [
] the "Expert" access level. If it is the default
• [^
^] to confirm. password, enter "0058".
• [
] and 2 × [>
>] Push these buttons to start the Standard
• [
] or [
] for the selection of the Setup procedure.
length unit (m, Cst., in, ft, mm or
Length unit. Make a selection from the list
cm). of parameters.
• [^
^] to confirm.
• [
] or [
] for the selection of the Tank type. Make a selection from the list of
tank type (Storage, Stilling Well, parameters. If the surface of the product is
Agitator or Process). flat, select "Storage". If the surface of the
product is disturbed, select "Process". If
• [^
^] to confirm. the surface of the product is agitated with
vortexes and foam, select "Agitator". If the
device is installed in a stilling well, select
"Stilling Well".
• [
] or [
] for the selection of the Current output 1 variable. The
measurement name (Distance, manufacturer sets the current output
Level, Sensor Value or Reflection, variable (for current output 1) to "Distance”
before delivery.
Volume (Mass), Ullage Volume
(Ullage Volume). If it is necessary to measure volume, ullage
• [^
^] to confirm. volume, mass or ullage mass, refer to How
to configure the device to measure volume
or mass on page 119.
• [>>] to change the position of the 0% range. Use this step to give the 0%
cursor. output setting in the tank.
• [
] to decrease the value (or move
Refer to the illustrations that follow. When
the decimal point one digit to the menu item A4.1.3.1 Current Out. 1 Var. is
left) or [
] to increase the value (or set to "Level", illustration 1 shows the
move the decimal point one digit to position of 0% output as a level above the
the right). tank bottom. When menu item A4.1.3.1
Current Out. 1 Var. is set to "Distance",
• [^
^] to confirm. illustration 2 shows the position of 0%
output as a distance below the flange facing
or thread stop of the process connection.
• [
] or [
] for the selection of the Current output range. This menu item gives
current output range (3.8-20.5 mA current output values to the measuring
(NAMUR), 4-20 mA, 3.8-20.5 mA range between 0% and 100% values given
in the "0% range" and "100% range" steps.
(reversed) or 4-20 mA (reversed). If you set this menu item to "4-20 mA" or
• [^
^] to confirm. "3.8-20.5 mA":
• 0% Range = 4 mA
• 100% Range = 20 mA
If you set this menu item to "4-20 mA
(reversed)" or "3.8-20.5 mA (reversed)":
• 0% Range = 20 mA
• 100% Range = 4 mA
Use this procedure (menu item A4.2 Empty Spectrum) if there are fixed and moving objects in the
tank that can cause interference signals. The device does a scan for objects that do not change
their vertical positions in the tank (heating tubes, agitators, fuel assemblies etc.) and records the
data. The device can then use this data to put the measurement signal through a filter (empty
spectrum).
When the empty spectrum filter is on (when menu item C2.8 Empty Spectrum Enable is set to
"Enable"), it will ignore the interference signals.
CAUTION!
Make sure that the tank is empty or only filled to the minimum level.
NOTICE!
Because the device records the empty spectrum data, it is not necessary to do the procedure
again if you de-energize the device.
Before you do the empty spectrum recording procedure, install the device on the tank. For more
data about how to install the device, refer to Installation on page 24.
Values and parameters that can be changed are shown between the « ... » marks in the
illustrations that follow. Push the keypad buttons in the correct sequence:
Procedure
Screen Steps Description
• 2 × [>>], 2 × [
] and [>
>]. Default screen.
• If it is the default password: 2 × [>>], Enter the password used at this time for
5 × [
], [>
>] and 8 × [
] the "Expert" access level. If it is the default
• [^
^] to confirm. password, enter "0058".
• [
], [>
>], [
] and 2 × [>
>]. Push these buttons to start the Record
• [
] or [
] for the selection of the Spectrum (Empty Spectrum) procedure.
empty spectrum type (Full
Empty spectrum type. Make a selection
(Average), Full (Max), Partial from the list of parameters. If you can
(Average), Partial (Max)). empty the tank, set this menu item to "Full,
• [^
^] to confirm. Average" or "Full, Max". If you cannot
empty the tank, set this menu item to
"Partial, Average" or "Partial, Max".
• [
] or [
] to change the parameter Start recording? Set this menu item to
("No" or "Yes"). "Yes" to continue to the subsequent step.
• [^
^] to confirm. Set this menu item to "No" to go back to the
menu.
• [^
^] to confirm. Graph with the results of the empty
9 spectrum recording.
• [
] or [
] to change the parameter Save spectrum? If you set the menu item to
("No" or "Yes"). "Yes", the device will keep this empty
• [^
^] to confirm. spectrum recording. If you set the menu
item to "No", the device will reject this data.
• [
] or [
] to change the parameter Empty Spectrum Enable. If you set the
("Disable" or "Enable"). menu item to "Enable", the device will use
• [^
^] to confirm. the empty spectrum recording data. If you
set the menu item to "Disable", the device
will not use the empty recording data at
this time.
• 4 × [^
^] to confirm. Save Configuration? screen.
• [
] or [
] for the selection of the
save option (Yes, No or Back). Set to "Yes" to save and use the settings
and data and go back to Normal mode. Set
• [^
^] to confirm. to "No" to cancel the changes to the device
settings and go back to Normal mode. Set
to "Back" to stay in Program mode.
NOTICE!
For more data, refer to Networks on page 57.
CAUTION!
Make sure that the address for this device is different from others in the multi-drop network.
NOTICE!
Make sure that menu item C5.1.1 Current Loop Mode is set to "On".
The display screen of the device can show distance measurement readings if one or more of the
"Value Variable" menu items in the C6.4 1st Measurement Page or C6.5 2nd Measurement Page
menu are set to "Distance".
The flange facing is the reference point for distance measurement (0 m / 0 ft / 0¨). The position of
the measurement scale (specified by the 0% Range and 100% Range settings) is related to this
reference point. If you configured a measurement scale for the current output signal in the C4.1
Current output 1 menu, you can use a "standard scale" or a "reversed scale". On the standard
scale, the 0% Range measurement value agrees with an output of 4 mA and the 100% Range
measurement value agrees with an output of 20 mA. On the reversed scale, the 0% Range
measurement value agrees with an output of 20 mA and the 100% Range measurement value
agrees with an output of 4 mA.
You can change the reference point from which distance is measured. Use this menu
item:
• Reference Offset (C1.10)
NOTICE!
Menu item C1.10 Reference Offset
If you move the reference point above the flange, make sure that you add the value given in
menu item C1.10 Reference Offset when you give a distance for the C4.1.2 0% Range and C4.1.3
100% Range settings. If you move the reference point below the flange, subtract the value given
in menu item C1.10 Reference Offset when you give a distance for the C4.1.2 0% Range and
C4.1.3 100% Range settings.
CAUTION!
If C4.1.1 Current Out. 1 Var. is set to "Distance" and C4.1.2 0% Range (standard scale) is set in
the blocking distance, then the device will not be able to use the full current output range.
For more data about the menu items, refer to Function description on page 85 – table C. Full
Setup menu.
NOTICE!
Bar graph function in Normal mode
There is an optional bar graph shown on the two measurement pages in Normal mode (set
C6.4.1 / C6.5.1 (Function) to "One Value & Bar" or "Two Values & Bar"). By default, the bar
graph on the 1st Measurement Page shows a value related to the measurement scale specified
in the C4.1 Current output 1 menu. It is possible to give different measurement scales and
measurement variables for the bar graphs in Normal mode. For more data, refer to Function
description on page 85 – table C. Full Setup menu (C6 Display). The bar graph range is related
to the parameters given in the menu item C6.4.2 and C6.5.2 (1st Value Variable) and menu C1
Install. Parameters.
If you change C1.10 Reference Offset, then we recommend that you change C6.4.3 / C6.5.3 (0%
Range) and C6.4.4 / C6.5.4 (100% Range) by the same quantity.
The display screen of the device can show level measurement readings if one or more of the
"Value Variable" menu items in the C6.4 1st Measurement Page or C6.5 2nd Measurement Page
menu are set to "Level".
The tank bottom (specified in menu item C1.2 Tank Height) is the reference point for level
measurement (0 m / 0 ft / 0¨). The position of the measurement scale (specified by the 0% Range
and 100% Range settings) is related to this reference point. If you configured a measurement
scale for the current output signal in the C4.1 Current output 1 menu, you can use a "standard
scale" or a "reversed scale". On the standard scale, the 0% Range measurement value agrees
with an output of 4 mA and the 100% Range measurement value agrees with an output of 20 mA.
On the reversed scale, the 0% Range measurement value agrees with an output of 20 mA and the
100% Range measurement value agrees with an output of 4 mA.
You can change the reference point from which level is measured. Use this menu item:
• Tank Bottom Offset (C1.11)
NOTICE!
C1.11 Tank Bottom Offset
If you move the tank bottom offset below the tank bottom, add the value given in C1.11 Tank
Bottom Offset when you give a level for the C4.1.2 0% Range and C4.1.3 100% Range settings. If
you move the tank bottom offset above the tank bottom, subtract the value given in C1.11 Tank
Bottom Offset when you give a level for the C4.1.2 0% Range and C4.1.3 100% Range settings.
CAUTION!
If C4.1.1 Current Out. 1 Var. is set to "Level" and C4.1.3 100% Range (standard scale) is set in
the blocking distance, then the device will not be able to use the full current output range.
For more data about the menu items, refer to Function description on page 85 – table C. Full
Setup menu.
NOTICE!
Bar graph function in Normal mode
There is an optional bar graph shown on the two measurement pages in Normal mode (set
C6.4.1 / C6.5.1 (Function) to "One Value & Bar" or "Two Values & Bar"). By default, the bar
graph on the 1st Measurement Page shows a value related to the measurement scale specified
in the C4.1 Current output 1 menu. It is possible to give different measurement scales and
measurement variables for the bar graphs in Normal mode. For more data, refer to Function
description on page 85 – table C. Full Setup menu (C6 Display). The bar graph range is related
to the parameters given in the menu item C6.4.2 and C6.5.2 (1st Value Variable) and menu C1
Install. Parameters.
If you change C1.11 Tank Bottom Offset, then we recommend that you change C6.4.3 / C6.5.3
(0% Range) and C6.4.4 / C6.5.4 (100% Range) by the same quantity.
CAUTION!
Enter the data in numerical sequence (strapping table entry number 01, 02 etc.).
The device will give more accurate volume readings if you give more conversion data in these
areas:
You can offset the tank bottom reference point to find the delayed radar reflection. Obey the
instructions that follow:
NOTICE!
For more data on menu items, refer to Function description on page 85 – table C: Full Setup.
NOTICE!
We recommend that you do an empty spectrum scan when the tank is empty and all the moving
parts (agitators etc.) are in operation.
• After you enter Program mode, set the access level to "Expert". For more data about the
procedure, refer to Protection of the device settings (access levels) on page 70.
• Push [], [>>], [
] and [>
>] to go to the menu item A4.2 Empty Spectrum.
• Push [>>] to start the empty spectrum recording procedure. For more data, refer to Empty
spectrum recording on page 111. Push [^ ^] at the end of each step of the procedure to
continue to the next step.
NOTICE!
For more data on empty spectrum scans, refer to Function description on page 85 – table A.
Quick Setup menu (menu item A4.2).
Each status message (or status signal) has a special symbol which agrees with the NAMUR
Guidelines. This symbol is shown with the message.
NOTICE!
The status group name and the status signal (F/S/M/C) are shown. For more data, refer to the
table that follows.
Push the [
] or [
] button to make a selection from the list of status messages.
Figure 6-13: Device status and error messages (C7.3.1 Message View)
1 Device status letter code (NAMUR NE 107). In this example, M = Maintenance required.
2 Device status symbol (NAMUR NE 107)
3 Error message
If the device shows an error message, refer to the table that follows for more data and to find a
solution to a problem.
NOTICE!
For more data about regular inspections and maintenance procedures for devices with Ex and
other approvals, refer to the related supplementary instructions.
You must remove the device for cleaning only if the antenna does not have the purging system
option. If it is necessary to clean the device, obey the instructions given in the handbook.
CAUTION!
Use multi-purpose grease that is applicable for the operating temperature range of the O-ring
with the properties that follow:
• Operating temperature range of -40...+130°C / -40...+266°F without a negative effect on the
lubrication of the O-ring
• Without silicone
• The bonding properties must be satisfactory
• Lithium-saponified
• Water-resistant
• Agrees with the O-ring material
WARNING!
Do not let more than 5 mm / 0.2¨ of dust collect on the top surface of the device. This is a
possible source of ignition in a potentially explosive atmosphere.
DANGER!
Risk of electrostatic discharge from the gray plastic sun cover.
WARNING!
Purge the antenna with a dry gas or liquid that is applicable to the process.
CAUTION!
Purge the antenna at intervals to make sure that the inner surface of the antenna stays clean
and the device measures accurately.
For more data on how to prepare the device before you send it back, refer to Returning the
device to the manufacturer on page 134.
This regulation only applies to spare parts which are subject to wear and tear under normal
operating conditions.
NOTICE!
For more precise information, please contact your local sales office.
WARNING!
Should you nevertheless need to return a device for inspection or repair, please pay strict
attention to the following points:
• Due to statutory regulations on environmental protection and safeguarding the health and
safety of the personnel, the manufacturer may only handle, test and repair returned devices
that have been in contact with products without risk to personnel and environment.
• This means that the manufacturer can only service this device if it is accompanied by the
following certificate (see next section) confirming that the device is safe to handle.
WARNING!
If the device has been operated with toxic, caustic, radioactive, flammable or water-
endangering products, you are kindly requested:
• to check and ensure, if necessary by rinsing or neutralising, that all cavities are free from
such dangerous substances,
• to enclose a certificate with the device confirming that it is safe to handle and stating the
product used.
LEGAL NOTICE!
In compliance with U.S. Federal OSHA Standard 29CFR1910.1200 process information must be
reviewed previous to receiving authorization to return material to Schneider Electric Systems
USA, Inc.
Explain what steps were taken to decontaminate the unit: (was unit steam cleaned, rinsed out with water,
chemically cleaned etc.)
Form completed by: _________________________ _________________________
Print name Signature
Date: ________________
CLEANING STATEMENT
(Note: Your item will not be serviced unless the following cleaning statement has been signed):
I certify that the above referenced item has been properly purged and cleaned, complies with U.S.
Department of Transportation shipping requirements and DOES NOT present a health and/or safety hazard
(as defined by OSHA) to our Customer Repair personnel.
7.6 Disposal
LEGAL NOTICE!
Disposal must be carried out in accordance with legislation applicable in your country.
Separate collection of WEEE (Waste Electrical and Electronic Equipment) in the European Union:
According to the directive 2012/19/EU, the monitoring and control instruments marked with the
WEEE symbol and reaching their end-of-life must not be disposed of with other waste
waste.
The user must dispose of the WEEE to a designated collection point for the recycling of WEEE or
send them back to our local organisation or authorised representative.
The FMCW-radar transmits a high frequency signal whose frequency increases linearly during
the measurement phase (called the frequency sweep). The signal is emitted, reflected on the
measuring surface and received with a time delay, t. Delay time, t=2d/c, where d is the distance
to the product surface and c is the speed of light in the gas above the product.
For further signal processing the difference Δf is calculated from the actual transmitted
frequency and the received frequency. The difference is directly proportional to the distance. A
large frequency difference corresponds to a large distance and vice versa. The frequency
difference Δf is transformed via a Fast Fourier Transform (FFT) into a frequency spectrum and
then the distance is calculated from the spectrum. The level results from the difference between
the tank height and the measured distance.
Measurement modes
"Direct" mode
If the dielectric constant of the liquid is high (εr ≥1.4), the level signal is the reflection on the
surface of the liquid.
CAUTION!
"TBF FULL" AND "TBF AUTO" MODES
It is important to enter the correct dielectric constant value in menu item C2.2 Epsilon R
Product. If this value is incorrect, the device will not measure level accurately.
NOTICE!
• The following data is provided for general applications. If you require data that is more
relevant to your specific application, please contact us or your local sales office.
• Additional information (certificates, special tools, software,...) and complete product
documentation can be downloaded free of charge from the website.
Measuring system
Measuring principle 2-wire loop-powered level transmitter; FMCW radar
Frequency range K-band (24...26 GHz)
Max. radiated power (EIRP) < -41.3 dBm according to ETSI EN 307 372 (TLPR) and ETSI EN 302 729 (LPR)
Application range Level measurement of liquids, pastes and slurries
Primary measured value Distance and reflection
Secondary measured value Level, volume and mass
Design
Construction The measurement system consists of a measuring sensor (antenna) and a signal
converter
Options Integrated LCD display (-20..+70°C / -4…+158°F); if the ambient temperature is not
in these limits, then this condition can stop the display
Straight antenna extensions (length 105 mm / 4.1¨)
Max. extension length, Metallic Horn antenna: 1050 mm / 41.3¨
Max. extension length, Drop antenna: 525 mm / 20.7¨
Antenna purging system for Metallic Horn antennas (supplied with a 1/8 NPTF
connection)
PP flange plate protection and extension protection (PP protective layer for antenna
extensions)
Weather protection
Max. measuring range Metallic Horn, DN40 (1½¨): 15 m / 49.2 ft
(antenna)
Metallic Horn, DN50 (2¨): 20 m / 65.6 ft
Metallic Horn, DN65 (2½¨): 25 m / 82 ft – for level chambers
Metallic Horn, DN80 (3¨): 50 m / 164 ft
Metallic Horn, DN100 (4¨): 80 m / 262.5 ft
Metallic Horn, DN150 (6¨) and DN200 (8¨): 100 m / 328.1 ft
PP Drop, DN80 (3¨): 50 m / 164 ft
PP Drop, DN100 (4¨): 80 m / 262.5 ft
PP Drop, DN150 (6¨): 100 m / 328.1 ft
Refer also to "Measuring accuracy" on page 146
Min. tank height 0.2 m / 8¨
Recommended minimum Antenna extension length + antenna length + 0.1 m / 4¨
blocking distance
Min. distance for reflection 1 m / 3.3 ft
measurement
Measuring accuracy
Resolution 1 mm / 0.04¨
Repeatability ±1 mm / ±0.04¨
Accuracy Standard: ±2 mm / ±0.08¨, when distance ≤ 10 m / 33 ft;
±0.02% of measured distance, when distance > 10 m / 33 ft. For more data, refer to
Measuring accuracy on page 146.
Reference conditions acc. to EN 61298-1
Temperature +15...+25°C / +59...+77°F
Pressure 1013 mbara ±50 mbar / 14.69 psia ±0.73 psi
Relative air humidity 60% ±15%
Target Metal plate in an anechoic chamber
Operating conditions
Temperature
Ambient temperature -40…+80°C / -40…+176°F
Ex: see supplementary operating instructions or approval certificates
Relative humidity 0...99%
Storage temperature -40…+85°C / -40…+185°F
Process connection temperature Metallic Horn antenna:
(higher temperature on request) -50…+130°C / -58…+266°F (the process connection temperature must agree with
the temperature limits of the gasket material. Refer to "Materials" in this table.)
Ex: see supplementary operating instructions or approval certificates
Drop antenna (PP):
-40…+100°C / -40…+212°F (the process connection temperature must agree with
the temperature limits of the gasket material. Refer to "Materials" in this table.)
Ex: see supplementary operating instructions or approval certificates
Pressure
Process pressure Drop antenna (PP):
-1…16 barg / -14.5…232 psig
Metallic Horn antenna:
-1…16 barg / -14.5…232 psig
Subject to the process connection used and the process connection temperature.
For more data, refer to Guidelines for maximum operating pressure on page 150.
Other conditions
Dielectric constant (εr) Direct mode: ≥1.4
TBF mode: ≥1.1
Ingress protection IEC 60529: IP66 / IP68 (0.1 barg / 1.45 psig)
NEMA 250: NEMA type 4X - 6 (housing) and type 6P (antenna)
Maximum rate of change 60 m/min / 196 ft/min
Installation conditions
Process connection size The nominal diameter (DN) should be equal to or larger than the antenna diameter.
If the nominal diameter (DN) is smaller than the antenna, either:
– provide the means to adapt the device to a larger process connection on the tank
(for example, a plate with a slot), or
– use the same process connection, but remove the antenna from the device before
installation and fit it from inside the tank.
Process connection position Make sure that there are not any obstructions directly below the process
connection for the device. For more data, refer to Installation on page 24.
Dimensions and weights For dimensions and weights data, refer to Dimensions and weights on page 154.
Materials
Housing Standard: Polyester-coated aluminium
Option: Stainless steel (1.4404 / 316L) – non-Ex devices only. Ex approvals will be
2020.
available in the second quarter of 2018.
Wetted parts, including antenna Metallic Horn antenna: Stainless steel (1.4404 / 316L)
Standard for Drop antenna: PP
Option for Drop antenna: PP flange plate protection and PP protective layer for
antenna extensions
Process connection Stainless steel (1.4404 / 316L) – a PP flange plate protection option is also available
for the Drop antenna
Gaskets (and O-rings for the PP Drop antenna:
sealed antenna extension option) FKM/FPM (-40…+100°C / -40…+212°F); Kalrez® 6375 (-20…+100°C / -4…+212°F);
EPDM (-40°C…+100°C / -40…+212°F) 1
Metallic Horn antenna:
FKM/FPM (-40…+130°C / -40…+266°F); Kalrez® 6375 (-20…+130°C / -4…+266°F);
EPDM (-50°C…+130°C / -58…+266°F)
Feedthrough PEI (-50...+130°C / -58...+266°F)
This is the maximum range. The feedthrough temperature limits must agree with
the temperature limits of the gasket material and antenna type.
Cable gland Standard: none
Options: Plastic (Non-Ex: black, Ex i-approved: blue); nickel-plated brass; stainless
steel; M12 (4-pin connector)
Weather protection (Option) Stainless steel (1.4404 / 316L)
Process connections
Thread G 1 A...1½ A (ISO 228); 1...1½ NPT (ASME B1.20.1)
Flange version
EN 1092-1 Low-pressure flanges: DN50...200 in PN01;
Standard flanges: DN40 in PN40, DN50...200 in PN16 and PN40 (Type B1); others on
request
Optional flange facing for standard flanges: Type A
ASME B16.5 Low-pressure flanges: 2¨...8¨ in 150 lb (max. 15 psig);
Standard flanges: 1½¨…8¨ in 150 lb RF and 300 lb RF; others on request
Optional flange facing for standard flanges: FF (Flat Face)
JIS B2220 40…200A in 10K RF; others on request
Other Others on request
Electrical connections
Power supply Terminals output – Non-Ex / Ex i:
12…30 V DC; min./max. value for an output of 21.5 mA at the terminals
Terminals output – Ex d:
16…36 V DC; min./max. value for an output of 21.5 mA at the terminals
Maximum current 21.5 mA
Current output load Non-Ex / Ex i: RL [Ω] ≤ ((Uext -12 V)/21.5 mA). For more data, refer to Minimum
power supply voltage on page 148.
Ex d: RL [Ω] ≤ ((Uext -16 V)/21.5 mA). For more data, refer to Minimum power supply
voltage on page 148.
Cable entry Standard: M20×1.5; Options: ½ NPT; 4-pin male M12 connector
Cable gland Standard: none
Options: M20×1.5 (cable diameter: 7…12 mm / 0.28…0.47¨); others are available on
request
Cable entry capacity (terminal) 0.5…3.31 mm² (AWG 20...12)
Explosion protection
ATEX (EU Type Approval) II 1/2 G Ex ia IIC T6...T* Ga/Gb; 3
II 1/2 D Ex ia IIIC T85°C...T*°C Da/Db; 4
II 1/2 G Ex db ia IIC T6...T* Ga/Gb; 3
II 1/2 D Ex ia tb IIIC T85°C...T*°C Da/Db 4
ATEX (Type Approval) II 3 G Ex ic IIC T6...T* Gc; 3
II 3 D Ex ic IIIC T85°C...T*°C Dc 4
IECEx Ex ia IIC T6...T* Ga/Gb; 3
Ex ia IIIC T85°C...T*°C Da/Db; 4
Ex db ia IIC T6...T* Ga/Gb; 3
Ex ia tb IIIC T85°C...T*°C Da/Db; 4
Ex ic IIC T6...T* Gc; 3
Ex ic IIIC T85°C...T*°C Gc 4
cQPSus Division ratings
XP-IS, Class I, Div 1, GPS ABCD, T6...Tx;
DIP, Class II, III, Div 1, GPS EFG, T85°C...T*°C; 4
IS, Class I, Div 1, GPS ABCD, T6...Tx;
IS, Class II, III, Div 1, GPS EFG, T85°C...T*°C; 4
NI, Class I, Div 2, GPS ABCD, T6...Tx;
NI, Class II, III, Div 2, GPS FG, T85°C...T*°C 4
Zone ratings
Class I, Zone 1, AEx db ia [ia Ga] IIC T6...T* Gb (US) – antenna suitable for Zone 0;
Ex db ia [ ia Ga] IIC T6...T* Gb (Canada) – antenna suitable for Zone 0; 3
Class I, Zone 0, AEx ia IIC T6...T* Ga (US);
Ex ia IIC T6...T* Ga (Canada); 3
Zone 20, AEx ia IIIC T85°C...T*°C Da (US);
Ex ia IIIC T85°C...T*°C Da (Canada); 4
Zone 21, AEx ia tb [ia Da] IIIC T85°C...T*°C Db (US) – antenna suitable for Zone 20
Ex ia tb [ia Da] IIIC T85°C...T*°C Db (Canada) – antenna suitable for Zone 20 4
NEPSI Ex ia IIC T*~T6 Ga/Gb; 3
- pending
Ex d ia IIC T*~T6 Ga/Gb; 3
Ex iaD 20/21 T85...T*; 5
Ex iaD 20/21 tD A21 IP6X T85°C...T*°C 4
3
1
2
0
0.1 0.2 5 10 15 20
-1
-2
-3
-4
Figure 8-2: Measuring accuracy (graph of measuring accuracy in mm against measuring distance in m)
X: Measuring distance from the thread stop or flange facing of the process connection [m]
Y: Measuring accuracy [+yy mm / -yy mm]
1 Minimum recommended blocking distance = antenna extension length + antenna length +
0.2
1
0.1
0
0.33 20 30 40 50 60 70 80
-0.1
-0.2
Figure 8-3: Measuring accuracy (graph of measuring accuracy in inches against measuring distance in ft)
X: Measuring distance from the thread stop or flange facing of the process connection [ft]
Y: Measuring accuracy [+yy inches / -yy inches]
1 Minimum recommended blocking distance = antenna extension length + antenna length + 3.94¨
NOTICE!
To calculate the accuracy at a given distance from the antenna, refer to Technical data on page
139 (measuring accuracy).
Figure 8-4: Minimum power supply voltage for an output of 21.5 mA at the terminals (Non-Ex and Hazardous Location
approval (Ex i / IS))
X: Power supply U [V DC]
Y: Current output load RL [Ω]
Figure 8-5: Minimum power supply voltage for an output of 21.5 mA at the terminals (Hazardous Location approval
(Ex d / XP/NI))
X: Power supply U [V DC]
Y: Current output load RL [Ω]
Figure 8-6: Pressure / temperature de-rating (EN 1092-1), flange and threaded connection, in °C and barg
Figure 8-7: Pressure / temperature de-rating (EN 1092-1), flange and threaded connections, in °F and psig
1 Process pressure, p [barg]
2 Process connection temperature, T [°C]
3 Process pressure, p [psig]
4 Process connection temperature, T [°F]
5 Threaded connection, G (ISO 228-1)
6 Threaded connection, G (ISO 228-1). Flange connection, PN40.
7 Flange connection, PN16
NOTICE!
CRN certification (pending)
There is a CRN certification option for devices with process connections that agree with ASME
standards. This certification is necessary for all devices that are installed on a pressure vessel
and used in Canada.
Figure 8-8: Pressure / temperature de-rating (ASME B16.5), flange and threaded connections, in °C and barg
Figure 8-9: Pressure / temperature de-rating (ASME B16.5), flange and threaded connections, in °F and psig
1 Process pressure, p [barg]
2 Process connection temperature, T [°C]
3 Process pressure, p [psig]
4 Process connection temperature, T [°F]
5 Threaded connection, NPT (ASME B1.20.1). Flange connection, Class 300.
6 Flange connection, Class 150
NOTICE!
• The diameter of the outer sheath of the cable must be 7…12 mm or 0.28…0.47¨.
• Cable glands for cQPSus-approved devices must be supplied by the customer.
• A weather protection cover is available as an accessory with all devices.
NOTICE!
• The diameter of the outer sheath of the cable must be 7…12 mm or 0.28…0.47¨.
• Cable glands for cQPSus-approved devices must be supplied by the customer.
• A weather protection cover is available as an accessory with all devices.
NOTICE!
• The diameter of the outer sheath of the cable must be 7…12 mm or 0.28…0.47¨.
• Cable glands for cQPSus-approved devices must be supplied by the customer.
• A weather protection cover is available as an accessory with all devices.
G NPT G NPT
DN40/1½¨ 151 215 247 138 1 328 1 385 1 39
DN50/2¨ 151 215 247 152 1 342 1 399 1 43
DN65/2½¨ 151 215 247 227 417 474 65
DN80/3¨ 151 215 247 262 1 452 1 507 1 75
DN100/4¨ 151 215 247 331 1 521 1 578 1 95
DN150/6¨ 151 215 247 486 1 675 1 733 1 140
DN200/8¨ 151 215 247 657 1 847 1 904 1 190
1 This is the dimension without the antenna extension option. A maximum of 10 antenna extensions are available. Each antenna exten-
sion is 105 mm long.
G NPT G NPT
DN40/1½¨ 5.94 8.46 9.72 5.43 1 12.91 1 15.16 1 1.54
DN50/2¨ 5.94 8.46 9.72 5.98 1 13.46 1 15.71 1 1.69
DN65/2½¨ 5.94 8.46 9.72 8.94 1 16.42 1 18.66 2.56
DN80/3¨ 5.94 8.46 9.72 10.31 1 17.80 1 19.96 1 2.95
DN100/4¨ 5.94 8.46 9.72 13.03 1 20.51 1 22.76 1 3.74
DN150/6¨ 5.94 8.46 9.72 19.13 1 26.57 1 28.86 1 5.51
DN200/8¨ 5.94 8.46 9.72 25.87 1 33.35 1 35.59 1 7.48
1 This is the dimension without the antenna extension option. A maximum of 10 antenna extensions are available. Each antenna exten-
sion is 4.1¨ long.
NOTICE!
• The diameter of the outer sheath of the cable must be 7…12 mm or 0.28…0.47¨.
• Cable glands for cQPSus-approved devices must be supplied by the customer.
• A weather protection cover is available as an accessory with all devices.
NOTICE!
• The diameter of the outer sheath of the cable must be 7…12 mm or 0.28…0.47¨.
• Cable glands for cQPSus-approved devices must be supplied by the customer.
• A weather protection cover is available as an accessory with all devices.
NOTICE!
• The diameter of the outer sheath of the cable must be 7…12 mm or 0.28…0.47¨.
• Cable glands for cQPSus-approved devices must be supplied by the customer.
• A weather protection cover is available as an accessory with all devices.
G NPT G NPT
DN80/3¨ 151 188 220 136 1 324 1 356 1 74
DN100/4¨ 151 188 220 159 1 347 1 379 1 94
DN150/6¨ 151 188 220 217 1 405 1 437 1 144
1 This is the dimension without the antenna extension option. A maximum of 5 antenna extensions are available. Each antenna extension
is 105 mm long.
G NPT G NPT
DN80/3¨ 5.94 7.40 8.66 5.35 1 12.76 1 14.01 1 2.91
DN100/4¨ 5.94 7.40 8.66 6.26 1 13.66 1 14.92 1 3.70
DN150/6¨ 5.94 7.40 8.66 8.54 1 15.94 1 17.20 1 5.67
1 This is the dimension without the antenna extension option. A maximum of 5 antenna extensions are available. Each antenna extension
is 4.1¨ long.
Purging option
NOTICE!
Purging system
This option is available for all Metallic Horn antennas. Flange connections must have a
pressure rating of PN16 (EN 1092-1), PN40 (EN 1092-1), Class 150 (ASME B16.5), Class 300
(ASME B16.5), or must be a low-pressure flange (PN01 / 15 psig).
a b c
Converter weight
Type of housing Weights
[kg] [lb]
Compact aluminium housing 2.1 4.6
Compact stainless steel housing 4.5 9.9
[kg] [lb]
[kg] [lb]
DN80 PP Drop antenna with process connection, standard length 1 2.7...59.1 5.9...130
DN100 PP Drop antenna with process connection, standard length 1 3.1...59.5 6.8...131.2
DN150 PP Drop antenna with process connection, standard length 1 4.5...60.9 9.9..134
Other options
Flange plate option, DN80 PP Drop antenna +0.1 +0.22
Flange plate option, DN100 PP Drop antenna +0.2 +0.44
Flange plate option, DN150 PP Drop antenna +0.3 +0.66
1 Standard length = without antenna extensions
2 This option is for Metallic Horn and Drop antennas
3 This option is for Metallic Horn antennas
There are 2 classes of devices which support the HART® Protocol: operating devices and field
devices. There are 2 classes of operating devices (Master): PC-supported workstations (Primary
Master) and manual control units (Secondary Master). These can be used in control centres and
other locations. HART® field devices include sensors, converters and actuators. Field devices
include 2-wire and 4-wire devices, and also intrinsically-safe versions for use in hazardous
areas.
There are 2 primary operation modes for HART-compatible devices: point-to-point mode and
multi-drop mode.
If the device is used in point-to-point mode, the HART® Protocol uses the Bell 202 Frequency
Shift Keying (FSK) standard to put a digital signal on top of the 4...20 mA signal. The connected
device sends and receives digital signals that agree with the HART® Protocol, and sends analog
signals at the same time. Only 1 device can be connected to the signal cable.
If the device is used in multi-drop mode, the network only uses a digital signal that agrees with
the HART® Protocol. The loop current is set to 4 mA. You can connect a maximum of 63 devices
to the signal cable.
An FSK or HART® modem is included in field devices and manual control units. It is necessary to
have an external modem for PC-supported workstations. The external modem is connected to
the serial or USB interface.
For data on communication in multi-drop mode, refer to HART® network configuration on page
114.
The HART® dynamic variables PV (Primary Variable), SV (Secondary Variable), TV (Third Variable)
and QV (Fourth Variable) can be assigned to any of the device variables.
The HART® dynamic variable PV is always connected to the HART® current output which is, for
example, assigned to level measurement.
9.5.1 Installation
CAUTION!
The Field Communicator cannot be used to correctly configure, operate or read data from the
device unless the Device Description (DD) file is installed.
9.5.2 Operation
NOTICE!
The Field Communicator will not give you access to the service menu. A simulation is only
possible for current outputs.
The Field Communicator and the device's local display use almost the same procedures to
operate the signal converter. The online help for each menu item refers to the function number
given to each menu item on the local device display. Protection of settings is the same as on the
device's local display.
The Field Communicator always saves a complete configuration for communication with AMS.
9.6.1 Installation
Please read the README.txt file in the Installation Kit.
If the Device Description has not been installed at this time, install the Installation Kit HART®
AMS. You can download this .exe file from our website.
For installation data, refer to the "AMS Intelligent Device Manager Books Online" section "Basic
AMS Functionality > Device Configurations > Installing Device Types > Procedures > Install
device types from media".
9.6.2 Operation
NOTICE!
For more data, refer to HART® menu tree for AMS on page 170.
9.7.1 Installation
Before you operate the device, the Device Type Manager (Device DTM) must be installed in the
Field Device Tool Container. You can download this .msi file from our website. For installation
and configuration data, refer to the documentation that is supplied with the Device DTM in the
"Downloads" section of the website.
9.7.2 Operation
The DTM and the device's local display use almost the same procedures to operate the signal
converter. For more data, refer to Operation on page 65.
Configure / Setup
Quick Setup General Language / Tag / Long Tag
Security Login / Change Password / Reset Passwords / Lock
StatusRd / Lock / Unlock Device / Write ProtectRd /
(De)activate Write Protection / Unlock Extended Range
Units Unit Length / Unit Volume / Unit Mass
Application Standard Setup / Record Empty Spectrum
Assistant
Full Setup Process Install. Parameters Tank Type / Tank Height /
Blocking Distance / Time
Constant / Antenna Type /
Antenna Extension / Distance
Piece / Reference Offset / Tank
Bottom Offset
Process Tracking Velocity / Epsilon R
Product / Epsilon R Gas /
Measuring Mode / Overfill
Detection / Overfill ThresholdOpt /
Mult. Refl. Enable / Empty
Spectrum Enable / Min. Peak
Required / Min Plausibility
Window
Conversion Select Conversion / Entry
CountRd / Conversion Table
Full Setup Output General Type IO channel ARd / Type IO
Channel BRd
Current Output 1 Current Out 1 Variable / 0%
Range / 100% Range / Current Out
Range / Error Function / Low
Error Current / High Error
Current / D/A Trim PVOpt
Full Setup Display General Language / Backlight
1st Measurement Function / 1st Value Variable /
Page Format 1st Value / 2nd Value
VariableOpt / Format 2nd
ValueOpt / 3rd Value VariableOpt /
Format 3rd ValueOpt / 0%
RangeOpt / 100% RangeOpt
2nd Measurement Function / 1st Value Variable /
Page Format 1st Value / 2nd Value
VariableOpt / Format 2nd
ValueOpt / 3rd Value VariableOpt /
Format 3rd ValueOpt / 0%
RangeOpt / 100% RangeOpt
Device Diagnostics
Device Status Condensed Status (NE 107) Condensed Status (NE 107)Rd /
Device Simulation ActiveRd
Standard Device StatusRd / Ext. Device
StatusRd / Write ProtectRd / Device
Diagnostic Status 0Rd / Device
Diagnostic Status 1Rd / AO
SaturatedRd / AO FixedRd
Additional Device Status SimulationRd /
Failure (F)Rd / Function Check
(C)Rd / Out of Specification (S)Rd /
Maintenance Required (M)Rd /
Electronics InformationRd /
Sensor InformationRd
Cluster Check Cluster NumberRd / Failed Cluster
CheckRd
Actual Values Operating TimeRd / Sensor ValueRd / Media LevelRd / DistanceRd /
ReflectionRd / Level LinearizationRd, Opt / VolumeRd, Opt / MassRd, Opt /
Distance LinearizationRd, Opt / UllageRd, Opt / Ullage MassRd, Opt / Sensor
TempRd / Converter TempRd
Simulation Process Variables Simulation Values
Device Status Enable/Disable Status
Simulation / Status SimulationOpt
I/O Loop Test
Test / Reset Device Reset / Reset Configuration Changed Flag
Information TagRd / Long TagRd / Serial NumberRd / ManufacturerRd / Device NameRd / V
NumberRd / Electronic RevisionRd / Field Device RevisionRd / Software
RevisionRd / Hardware RevisionRd / Electronics Serial No.Rd / Production
DateRd / Calibration DateRd / Operating TimeRd
Process variables
Measured Value Sensor ValueRd / Media LevelRd / DistanceRd / ReflectionRd / Level
LinearizationOpt, Rd / VolumeOpt, Rd / MassOpt, Rd / Distance LinearizationOpt,
Rd / UllageOpt, Rd / Ullage MassOpt, Rd
Overview: Diagnosis
Device Status Condensed Status (NE 107)
Standard
Additional
Cluster Check
Actual Values
Simulation Process Variables
Device Status
I/O
Test / Reset
Information
Download To Device...
Upload To PG/PC...
Quick Setup
General Language / Tag / Long Tag
Security Login / Change Password / Reset Passwords / Lock StatusRd / Lock/Unlock
Device / Write ProtectRd / (De)activate Write Protection / Unlock Extended
Range
Units Unit Length / Unit Volume / Unit Mass
Application Assistant Standard Setup / Record Empty Spectrum
Full Setup
Process Install. Parameters Tank Type / Tank Height / Blocking Distance / Time
Constant / Antenna Type / Antenna Extension /
Distance Piece / Reference Offset / Tank Bottom
Offset
Process Tracking Velocity / Epsilon R Product / Epsilon R
Gas / Measuring Mode / Overfill Detection / Overfill
ThresholdOpt / Mult. Refl. Enable / Empty Spectrum
Enable / Min. Peak Required / Min Plausibility
Window
Conversion Select Conversion / Entry CountRd / Conversion
Table
Output General Type IO channel ARd / Type IO Channel BRd
Current Output 1 Current Out 1 Variable / 0% Range / 100% Range /
Current Out Range / Error Function / Low Error
Current / High Error Current / D/A Trim PVOpt
Service
Calibration Calibration Current Output 1
Sensor Manual Correction Offset / Manual Correction
Factor / Correction OffsetRd / Correction FactorRd /
Correction Offset ExtendedRd, Opt / Correction
Factor ExtendedRd, Opt
View Menu
Measurement Value
Sensor ValueRd / Media LevelRd / DistanceRd / ReflectionRd / Level LinearizationOpt, Rd / VolumeOpt, Rd /
MassOpt, Rd / Distance LinearizationOpt, Rd / UllageOpt, Rd / Ullage MassOpt, Rd
Input / Outputs
PVRd / PV % RangeRd / PV output currentRd / SVRd / TVRd / QVRd
Diagnosis
Device Status
Condensed Status Condensed Status (NE 107)Rd / Device Simulation ActiveRd
(NE 107)
Standard Device StatusRd / Ext. Device StatusRd / Write ProtectRd / Device Diagnostic
Status 0Rd / Device Diagnostic Status 1Rd / AO SaturatedRd / AO FixedRd
Additional Device Status SimulationRd / Failure (F)Rd / Function Check (C)Rd / Out of
Specification (S)Rd / Maintenance Required (M)Rd / Electronics
InformationRd / Sensor InformationRd
Cluster Check Cluster NumberRd / Failed Cluster CheckRd
Actual Values
Operating TimeRd / Sensor ValueRd / Media LevelRd / DistanceRd / ReflectionRd / Level LinearizationRd,
Opt
/ VolumeRd, Opt / MassRd, Opt/ Distance LinearizationRd, Opt / Ullage VolumeRd, Opt / Ullage MassRd, Opt /
Sensor TempRd / Converter TempRd
Simulation
Process Variables Simulation Values
Device Status Enable/Disable Status Simulation / Status SimulationOpt
I/O Loop Test
Test / Reset
Device Reset / Reset Configuration Changed Flag
Information
TagRd / Long TagRd / Serial NumberRd / ManufacturerRd / Device NameRd / V NumberRd / Electronic
RevisionRd / Field Device RevisionRd / Software RevisionRd / Hardware RevisionRd / Electronics Serial
No.Rd / Production DateRd / Calibration DateRd / Operating TimeRd
184
LR54 APPENDIX 10
188
LR54 APPENDIX 10
10.5 Glossary
D
Dielectric constant An electrical property of the product. Also known as εr, DK and relative
permittivity. This property defines the strength of the wave reflected back
to the device's signal converter.
Distance The distance from the face of flange to the level (1 product) or the surface
of the top product (2 or more products). See the diagrams at the end of this
section.
Drop antenna A new generation of antenna made of PP. It has an ellipsoidal shape for a
more precise emission of radar signals.
DTM Device Type Manager. A driver for use in the PACTware™ program. All data
and functions of the device are included in it.
E
Electromagnetic compatibility Defines how much a device influences or is influenced by other devices that
(EMC) generate electromagnetic fields during operation. Refer to European
standard EN 61326-1 for further details.
F
FMCW Frequency-modulated continuous-wave radar technology. The signal is
continuously present, but the frequency is modulated, usually in
successive linear ramps over time (frequency sweeps).
H
Hazardous area An area with a potentially explosive atmosphere. Trained personnel can
install and use a device in this area. The device must be ordered with the
appropriate options. The device requires approvals (ATEX, IECEx, cQPSus,
NEPSI etc.) related to site specifications. You can find more data about
hazardous areas in the Ex Manuals and Ex Certificates of Compliance.
Horn (cone) antenna A common antenna for most applications. It is used for the controlled
emission and collection of radar signals.
I
Interference signals False radar reflections usually caused by equipment in the tank.
L
Level Height from the bottom of the tank (user-defined) to the surface of the top
product (Tank height – distance). See the diagrams at the end of this
section.
M
Mass Total mass of tank contents.
P
PACTware™
PACTware Software that operates and configures field devices from a remote
workstation. It is not necessary to use fieldbus software or programs
developed by the manufacturer.
R
Radar reflection Signal reflected from the surface of the tank contents.
S
Signal converter A set of electronic components in the device that send the measurement
signal through some signal filters. They identify and measure the level of
the tank contents.
T
TBF Tank Bottom Following (TBF) mode is an alternative measurement mode. It
allows the device to measure tank contents with very low dielectric
constants. TBF mode uses the reflection of the tank bottom to indirectly
measure the level of the tank contents.
U
Ullage volume Unfilled volume. See the diagrams at the end of this section.
V
Volume Total volume of tank contents.
Schneider Electric Systems USA, Inc. Global Customer Support Copyright 2019 Schneider Electric Systems USA, Inc.
38 Neponset Avenue Inside U.S.: 1-866-746-6477 All rights reserved.
Foxboro, MA 02035 Outside U.S.: 1-508-549-2424
United States of America https://pasupport.schneider-electric.com Foxboro and Schneider Electric are trademarks of
http://www.schneider-electric.com Schneider Electric Systems USA, Inc., its subsidiaries,
and affiliates. All other trademarks are the property of
their respective owners.