Model: Performance Data Sheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Project Name

Model Ref.
Subject
CRA Date
PERFORMANCE DATA SHEET
Unit Tag Qty Offered Model Offered Air Flow Offered Total Duty Offered Sens. Duty
CRA CR-06A 585 - m³/h 6.9 - kW 4.0 - kW
General Data
Unit Type : Cooling Only Specified Speed : Low
Series / Range : CRA Coil Material : Cu / Al
Motor Type : Permanent Split Capacitor PSC Motor Voltage : 220V/1Ph/50 Hz
Specified ESP : 75 Identification : FCU-FR(10:17) , NC3
Unit Data
FCU Range Standard Type : Ceiling Concealed with Back Plenum Coil Tube Diameter : 9 mm
Selected Model Size : CR-06A Inlet Direction : Back No. of fins [FPI] / Rows : 8/3
Fan Plenum : Yes Filter Media : Aluminium Header Material : Copper
No. of Fans(s) / Motor(s) : 2/1 Filter Rail : 25mm Coil Connection : Left
Options & Accessories

Selection
Cooling Heating
High Medium Low
Total Capacity : kW 8.9 6.9 6.1 Total Capacity : W -
Sensible Capacity : kW 5.5 4.0 3.7 No. Of Rows -
No. Of Rows 3 3 3
Air Side Air Side
Flow : m³/h 791 585 504 Inlet Air Temperature : °C -
Inlet Air Temperature : °C 40.0 40.0 40.0 Outlet Air Temperature : °C -
Relative Humidity : % 32.2 32.2 32.2
Outlet Air Temperature : °C 18.3 18.6 17.2
Relative Humidity : % 70.4 63.3 69.0
External Static Pressure : Pa 75 75 75
Fluid Side Fluid Side
Inlet Fluid Temperature : °C 5.0 5.0 5.0 Inlet Fluid Temperature : °C -
Outlet Fluid Temperature : °C 10.6 10.6 10.6 Outlet Fluid Temperature : °C -
Flow : l/h 1358 1056 940 Flow : m³/h -
Fluid Pressure Drop : kPa 53.6 33.3 27.1 Fluid Pressure Drop : kPa -
Sound Pressure Level [Induct at distance 2m] Electrical Data
Frequency 125 250 500 1K 2K 4K 8K Global Rated Power Supply 220V/1Ph/50 Hz
High dBA 25 31 29 30 28 24 21 36 Motor Power 81 W
Medium dBA 20 27 24 26 23 19 16 32 Motor Insulaiton B
Low dBA 19 25 23 24 22 18 15 30 Motor IP Rating IP21
Dimensional Drawings

Water Content l 1.08


Outlet Connection Dim. mm 19.05
Drain Connection Dim. mm 12.7
Unit Weight kg 27
Pack Weight kg 32
We Reserve the right to make any changes in the
specifications and performance data