Ordering data

DATA SHEET

AO523
Analog Output Module

1 Ordering data
Part no. Description Product life cycle phase *)
1SAP 250 200 R0001 AO523, analog output module, 16 AO, Active
U/I, 12 bits including sign, 2-wires
1SAP 450 200 R0001 AO523-XC, analog output module, Active
16 AO, U/I, 12 bits including sign,
2-wires, XC version

*) Modules in lifecycle Classic are available from stock but not recommended for
planning and commissioning of new installations.

2024/01/05 3ADR010034, 12, en_US 1


Technical data
Technical data of the module

2 Dimensions

1 Din rail 15 mm
2 Din rail 7.5 mm

The dimensions are in mm and in brackets in inch.

3 Technical data
3.1 Technical data of the module
The system data of AC500 and S500 are applicable to the standard version Ä Chapter 4 “System
data AC500” on page 4.
The system data of AC500-XC are applicable to the XC version Ä Chapter 5 “System data AC500-
XC” on page 7.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.

Parameter Value
Process voltage
Connections Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V
(UP) as well as 1.9, 2.9, 3.9 and 4.9 for 0 V
(ZP)
Rated value 24 V DC

2 3ADR010034, 12, en_US 2024/01/05


Technical data of the analog outputs

Parameter Value
Max. ripple 5%
Protection against reversed voltage Yes
Rated protection fuse on UP 10 A fast
Galvanic isolation Yes, per module
Current consumption
From 24 V DC power supply at the terminals Ca. 2 mA
UP/L+ and ZP/M of the CPU/communication
interface module
Current consumption from UP at normal opera- 0.15 A + output loads
tion
Inrush current from UP (at power up) 0.040 A2s
Max. length of analog cables, conductor cross section 100 m
> 0.14 mm2
Weight 300 g
Mounting position Horizontal or vertical with derating (output
load reduced to 50 % at +40 °C per group)
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in
the control cabinet.

NOTICE!
All I/O channels (digital and analog) are protected against reverse polarity, reverse
supply, short circuit and temporary overvoltage up to 30 V DC.

3.2 Technical data of the analog outputs


Parameter Value
Number of channels per module 16, of which channnels O0 ... O3 and O8 ... O11 for
voltage and current, and channels O4 ... 7 and O12 ...
15 only for voltage
Distribution of channels into groups 1 group
Channels O0- ... O7- Terminals 1.0 ... 1.7
Channels O0+ ... O7+ Terminals 2.0 ... 2.7
Channels O8- ... O15- Terminals 3.0 ... 3.7
Channels O8+ ... O15+ Terminals 4.0 ... 4.7
Output type Bipolar with voltage, unipolar with current
Galvanic isolation Against internal supply and other modules
Configurability -10 V ... +10 V, 0 mA ... 20 mA, 4 mA ... 20 mA (each
output can be configured individually), current outputs
only channels 0 ... 3 and 8 ... 11
Output resistance (load), as current output 0 W ... 500 W
Output loadability, as voltage output Max. ± 10 mA
Indication of the output signals One LED per channel
Resolution 12 bits including sign

2024/01/05 3ADR010034, 12, en_US 3


System data AC500
Environmental conditions

Parameter Value
Settling time for full range change (resis- Typ. 5 ms
tive load, output signal within specified tol-
erance)
Conversion error of the analog values Typ. ± 0.5 % of full scale
caused by non-linearity, adjustment error
at factory and resolution within the normal at +25 °C
range Max. ± 1 % of full scale (all ranges)
at 0 °C ... +60 °C or EMC disturbance
Relationship between output signal and
hex code
Unused outputs Can be left open-circuited

4 System data AC500


4.1 Environmental conditions
Table 1: Process and supply voltages
Parameter Value
24 V DC
Voltage 24 V (-15 %, +20 %)
Protection against reverse polarity Yes
100 V AC...240 V AC wide-range supply
Voltage 100 V ... 240 V (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
Allowed interruptions of power supply, according to EN 61131-2
DC supply Interruption < 10 ms, time between 2 interrup-
tions > 1 s, PS2
AC supply Interruption < 0.5 periods, time between 2 inter-
ruptions > 1 s

NOTICE!
Risk of damaging the PLC due to improper voltage levels!

– Never exceed the maximum tolerance values for process and supply voltages.
– Never fall below the minimum tolerance values for process and supply voltages.
Observe the system data Ä Chapter 4 “System data AC500” on page 4 and the
technical data of the module used.

NOTICE!
Improper voltage level or frequency range which cause damage of AC inputs:
– AC voltage above 264 V
– Frenquency below 47 Hz or above 62.4 Hz

4 3ADR010034, 12, en_US 2024/01/05


Power supply units

NOTICE!
Improper connection leads cause overtemperature on terminals.
PLC modules may be destroyed by using wrong cable type, wire size and cable
temperature classification.

Parameter Value
Temperature
Operating 0 °C ... +60 °C: Horizontal mounting of modules.
0 °C ... +40 °C: Vertical mounting of modules.
Output load reduced to 50 % per group.
Storage -40 °C ... +70 °C
Transport -40 °C ... +70 °C
Humidity Max. 95 %, without condensation
Air pressure
Operating > 800 hPa / < 2000 m
Storage > 660 hPa / < 3500 m

4.2 Creepage distances and clearances


The creepage distances and clearances meet the requirements of the overvoltage category II, pollu-
tion degree 2.

4.3 Power supply units

AC500 and AC500-eCo PLC devices are Class II/Class III devices and do not require
a Protective Earth (PE) connection.
For proper EMC performance, all metal parts, DIN rails, mounting screws, and cable
shield connection terminals are connected to a common ground and provide Func-
tional Earth (FE). This is typically connected to a common reference potential, such
as equipotential bonding rails.
Signal Grounds (SGND or GND) are used for signal reference and must not be
connected to cable shields, FE or other signals unless otherwise specified in the
specific device description.

For the supply of the modules, power supply units according to SELV or PELV specifications must be
used.

Safety Extra Low Voltage (SELV) and Protective Extra Low Voltage (PELV)
To ensure electrical safety of AC500/AC500-eCo extra low voltage circuits, 24 V DC
supply, communication interfaces, I/O circuits, and all connected devices must be
powered from sources meeting requirements of SELV, PELV, class 2, limited voltage
or limited power according to applicable standards.

2024/01/05 3ADR010034, 12, en_US 5


Electromagnetic compatibility

WARNING!
Improper installation can lead to death by touching hazardous voltages!
To avoid personal injury, safe separation, double or reinforced insulation and separa-
tion of the primary and secondary circuit must be observed and implemented during
installation.
– Only use power converters for safety extra-low voltages (SELV) with safe galvanic
separation of the primary and secondary circuit.
– Safe separation means that the primary circuit of mains transformers must be
separated from the secondary circuit by double or reinforced insulation. The pro-
tective extra-low voltage (PELV) offers protection against electric shock.

4.4 Electromagnetic compatibility


Table 2: Electromagnetic compatibility
Parameter Value
Device suitable only as Control Equipment for Industrial Applications, including marine applications.
IEC 61131-2, zone B
Ä Chapter 4.6 “Approvals and certifications” on page 7
Radiated emission according to Yes
IEC 61000-6-4 CISPR11, class A
Conducted emission according to Yes
IEC 61000-6-4 CISPR11, class A
Electrostatic discharge (ESD) according to Air discharge: 8 kV
IEC 61000-4-2, criterion B Contact discharge: 6 kV
Fast transient interference voltages (burst) Power supply (DC): 2 kV
according to
Digital inputs/outputs (24 V DC): 1 kV
IEC 61000-4-4, criterion B
Digital inputs/outputs (240 V AC): 2 kV
Analog inputs/outputs: 1 kV
Communication lines shielded: 1 kV
High energy transient interference voltages Power supply (DC):
(surge) according to
- Line to ground: 1 kV
IEC 61000-4-5, criterion B
- Line to line: 0,5 kV
Digital inputs/outputs/relay:
(24 V DC):
- Line to ground: 1 kV
(AC):
- Line to ground: 2 kV
- Line to line: 1 kV
Analog inputs/outputs:
- Line to ground: 1 kV
Communication lines:
- Line to ground: 1 kV

6 3ADR010034, 12, en_US 2024/01/05


System data AC500-XC
Environmental conditions

Parameter Value
Influence of radiated disturbances Test field strength: 10 V/m
IEC 61000-4-3, criterion A
Influence of line-conducted interferences Test voltage: 10 V
IEC 61000-4-6, criterion A
Power frequency magnetic fields 30 A/m 50 Hz
IEC 61000-4-8, criterion A 30 A/m 60 Hz

4.5 Mechanical data


Parameter Value
Mounting Horizontal/Vertical
Wiring method Spring/screw terminals
Degree of protection PLC system: IP 20
● with all modules or option boards plugged in
● with all terminals plugged in
● with all covers closed
Housing Classification V-2 according to UL 94
Vibration resistance (sinusoidal) acc. to IEC All three axes
60068-2-6
2 Hz ... 8.4 Hz, 3.5 mm peak,
8.4 Hz ... 150 Hz, 1 g
Shock test acc. to IEC 60068-2-27 All three axes
15 g, 11 ms, half-sinusoidal
Mounting of the modules:
Mounting Rail Top Hat according to IEC 60715 35 mm, depth 7.5 mm or 15 mm
Mounting with screws M4
Fastening torque 1.2 Nm

4.6 Approvals and certifications


The PLC Automation catalog contains an overview of the available approvals and certifications.

5 System data AC500-XC


5.1 Environmental conditions
Table 3: Process and supply voltages
Parameter Value
24 V DC
Voltage 24 V (-15 %, +20 %)
Protection against reverse polarity Yes
100 V AC...240 V AC wide-range supply

2024/01/05 3ADR010034, 12, en_US 7


Environmental conditions

Parameter Value
Voltage 100 V ... 240 V (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
Allowed interruptions of power supply, according to EN 61131-2
DC supply Interruption < 10 ms, time between 2 interrup-
tions > 1 s, PS2
AC supply Interruption < 0.5 periods, time between 2 inter-
ruptions > 1 s

NOTICE!
Risk of damaging the PLC due to improper voltage levels!

– Never exceed the maximum tolerance values for process and supply voltages.
– Never fall below the minimum tolerance values for process and supply voltages.
Observe the system data Ä Chapter 4 “System data AC500” on page 4 and the
technical data of the module used.

NOTICE!
Improper voltage level or frequency range which cause damage of AC inputs:
– AC voltage above 264 V
– Frenquency below 47 Hz or above 62.4 Hz

NOTICE!
Improper connection leads cause overtemperature on terminals.
PLC modules may be destroyed by using wrong cable type, wire size and cable
temperature classification.

8 3ADR010034, 12, en_US 2024/01/05


Environmental conditions

Parameter Value
Temperature
Operating -40 °C ... +70 °C
-40 °C ... 0 °C: Due to the LCD technology, the
display might respond very slowly.
-40 °C ... +40 °C: Vertical mounting of modules
possible, output load limited to 50 % per group
+60 °C ... +70 °C with the following deratings:
● System is limited to max. 2 communication
modules per terminal base
● Digital inputs: maximum number of simultane-
ously switched on input channels limited to
75 % per group (e.g. 8 channels => 6 chan-
nels)
● Digital outputs: output current maximum
value (all channels together) limited to 75 %
per group (e.g. 8 A => 6 A)
● Analog outputs only if configured as
voltage output: maximum total output cur-
rent per group is limited to 75 %
(e.g. 40 mA => 30 mA)
● Analog outputs only if configured as current
output: maximum number of simultaneously
used output channels limited to 75 % per
group (e.g. 4 channels => 3 channels)
Storage / Transport -40 °C ... +85 °C
Humidity Operating / Storage: 100 % r. H. with condensa-
tion
Air pressure Operating:
-1000 m .... 5000 m (1080 hPa ... 620 hPa)
> 2000 m (< 795 hPa):
● Max. operating temperature must be reducted
by 10 K for each 1000 m exceeding 2000 m
● I/O module relay contacts must be operated
with 24 V nominal only
Immunity to corrosive gases Yes, according to:
ISA S71.04.1985 Harsh group A, G3/GX
IEC60068-2-60
Method 4 with following concentrations:
● H2S 100 ± 10ppb
● NO2 1250 ± 20ppb
● CL2 100 ± 10ppb
● SO2 300 ± 20ppb
Immunity to salt mist Yes, horizontal mounting only, according to IEC
60068-2-52 severity level: 1

2024/01/05 3ADR010034, 12, en_US 9


Power supply units

NOTICE!
Risk of corrosion!
Unused connectors and slots may corrode if XC devices are used in salt-mist environ-
ments.
Protect unused connectors and slots with TA535 protective caps for XC devices.

NOTICE!
Risk of malfunctions!
Unused slots for communication modules are not protected against accidental phys-
ical contact.
– Unused slots for communication modules must be covered with dummy communi-
cation modules to achieve IP20 rating.
– I/O bus connectors must not be touched during operation.

5.2 Creepage distances and clearances


The creepage distances and clearances meet the requirements of the overvoltage category II, pollu-
tion degree 2.

5.3 Power supply units

AC500 and AC500-eCo PLC devices are Class II/Class III devices and do not require
a Protective Earth (PE) connection.
For proper EMC performance, all metal parts, DIN rails, mounting screws, and cable
shield connection terminals are connected to a common ground and provide Func-
tional Earth (FE). This is typically connected to a common reference potential, such
as equipotential bonding rails.
Signal Grounds (SGND or GND) are used for signal reference and must not be
connected to cable shields, FE or other signals unless otherwise specified in the
specific device description.

Safety Extra Low Voltage (SELV) and Protective Extra Low Voltage (PELV)
To ensure electrical safety of AC500/AC500-eCo extra low voltage circuits, 24 V DC
supply, communication interfaces, I/O circuits, and all connected devices must be
powered from sources meeting requirements of SELV, PELV, class 2, limited voltage
or limited power according to applicable standards.

10 3ADR010034, 12, en_US 2024/01/05


Electromagnetic compatibility

WARNING!
Improper installation can lead to death by touching hazardous voltages!
To avoid personal injury, safe separation, double or reinforced insulation and separa-
tion of the primary and secondary circuit must be observed and implemented during
installation.
– Only use power converters for safety extra-low voltages (SELV) with safe galvanic
separation of the primary and secondary circuit.
– Safe separation means that the primary circuit of mains transformers must be
separated from the secondary circuit by double or reinforced insulation. The pro-
tective extra-low voltage (PELV) offers protection against electric shock.

5.4 Electromagnetic compatibility


Table 4: Electromagnetic compatibility
Parameter Value
Device suitable only as Control Equipment for Industrial Applications, including marine applications.
IEC 61131-2, zone B
Ä Chapter 5.6 “Approvals and certifications” on page 12
Radiated emission according to Yes
IEC 61000-6-4 CISPR11, class A
Conducted emission according to Yes
IEC 61000-6-4 CISPR11, class A
Electrostatic discharge (ESD) according to Air discharge: 8 kV
IEC 61000-4-2, criterion B Contact discharge: 6 kV
Fast transient interference voltages (burst) Power supply (DC): 4 kV
according to
Digital inputs/outputs (24 V DC): 2 kV
IEC 61000-4-4, criterion B
Digital inputs/outputs (240 V AC): 4 kV
Analog inputs/outputs: 2 kV
Communication lines shielded: 2 kV
High energy transient interference voltages Power supply (DC):
(surge) according to
- Line to ground: 1 kV
IEC 61000-4-5, criterion B
- Line to line: 0,5 kV
Digital inputs/outputs/relay:
(24 V DC):
- Line to ground: 1 kV
(AC):
- Line to ground: 2 kV
- Line to line: 1 kV
Analog inputs/outputs:
- Line to ground: 1 kV
Communication lines:
- Line to ground: 1 kV

2024/01/05 3ADR010034, 12, en_US 11


Approvals and certifications

Parameter Value
Influence of radiated disturbances Test field strength: 10 V/m
IEC 61000-4-3, criterion A
Influence of line-conducted interferences Test voltage: 10 V
IEC 61000-4-6, criterion A
Power frequency magnetic fields 30 A/m 50 Hz
IEC 61000-4-8, criterion A 30 A/m 60 Hz

5.5 Mechanical data


Parameter Value
Mounting Horizontal/vertical (no application in salt mist
environment)
Wiring method Spring terminals
Degree of protection PLC system: IP 20
● with all modules or option boards plugged in
● with all terminals plugged in
● with all covers closed
Housing Classification V-2 according to UL 94
Vibration resistance (sinusoidal) acc. to IEC 2 Hz ... 8.4 Hz, 3.5 mm peak,
60068-2-6
8.4 Hz ... 500 Hz, 2 g
Vibration resistance (broadband random) acc. to 5 Hz ... 500 Hz, 1,9 g rms (operational)
IEC 60068-2-64
5 Hz ... 500 Hz, 4 g rms (non operational)
Shock resistance All three axes
15 g, 11 ms, half-sinusoidal
Mounting of the modules:
Mounting Rail Top Hat according to IEC 60715 35 mm, depth 7.5 mm or 15 mm
Mounting with screws M4
Fastening torque 1.2 Nm

5.6 Approvals and certifications


The PLC Automation catalog contains an overview of the available approvals and certifications.

— —
new.abb.com/plc © Copyright 2017-2024 ABB.
We reserve all rights in this document and in the information contained
therein. Reproduction, use or disclosure to third parties without express
authority is strictly forbidden.

12 3ADR010034, 12, en_US 2024/01/05