ZR94KC-TFD

HCFC, R-22, 50 Hz, 3 - Phase, 380/420 V


Air Conditioning
Production Status: Available for sale to all U.S. customers. Please check with your local Copeland representative for international
availability.

Performance Mechanical
Evap(°F)/Cond(°F) 45/130 45/100 Number of Cylinders: 0 CIR (in^3/Rev): 7.757
RG(°F)/Liq(°F) 65/115 65/85 Bore Size (in): 0.0 CFH (ft^3/hr): 781.0833
Stroke(in): 0.0
Capacity (Btu/hr): 79800 94100
Power (Watts): 6900 4910 Overall Length (in): 10.38 Mounting Length (in): 7.5
Current (Amps): 12.4 9.7 Overall Width (in): 11.19 Mounting Width (in): 7.5
EER (Btu/Wh): 11.6 19.2 Overall Height (in): 18.8 Mounting Height (in): 19.57
Mass Flow (lbs/hr): 1170 1210
Suction Size (in): 1 1/8 Stub
Discharge Size (in): 7/8 Stub
Sound Power (dBA): 75.0 Ave 80.0 Max
Initial Oil Charge (oz): 85
Vibration (mils(peak-peak)): 2.5 Ave 3.5 Max
Oil Recharge (oz): 81
Net Weight (lbs): 132.0

Electrical
RLA: 16.4 MCC (Amps): 23.0 UL File No.: SA-2337
LRA-Low: 86.0 RPM: 2900 UL File Date: 27-Sep-1996
LRA-High: 95.0 Max Operating Current: 15.6 CSA File No.: LR3104C
LRA-Half Winding:

Alternate Applications
Refrigerant Frequency (Hz) Phase Voltage Application
R-22 HCFC 60 3 460 Air Conditioning

Eddie , Hung . Page 1 of 1


9/23/2003

Copyright © 2002 Copeland Corporation. All rights reserved.


ZR94KC-TFD
HCFC, R-22, 50 Hz, 3 - Phase, 380/420 V
Air Conditioning
Production Status: Available for sale to all U.S. customers. Please check with your local Copeland representative for international
availability.

Performance Mechanical
Evap(°C)/Cond(°C) 7.2/54.4 7.2/37.8 Number of Cylinders: 0 CIR (cm^3/Rev): 0.127
RG(°C)/Liq(°C) 18.3/46.1 18.3/29.4 Bore Size (mm): 0 CFH (cm^3/hr): 22117.81
Stroke(mm): 0
Capacity (Watts): 23400 27600
Power (Watts): 6900 4910 Overall Length (mm): 263.652 Mounting Length (mm): 190.5
Current (Amps): 12.4 9.7 Overall Width (mm): 284.226 Mounting Width (mm): 190.5
EER (COP): 3.4 5.63 Overall Height (mm): 477.52 Mounting Height (mm): 497.078
Mass Flow (g/s): 147 152
Suction Size (in): 1 1/8 Stub
Discharge Size (in): 7/8 Stub
Sound Power (dBA): 75 Ave 80 Max
Initial Oil Charge (liters): 2.514
Vibration (mm(peak-peak)): 0.063 Ave 0.089 Max
Oil Recharge (liters): 2.395
Net Weight (kg): 59.874

Electrical
RLA: 16.4 MCC (Amps): 23.0 UL File No.: SA-2337
LRA-Low: 86.0 RPM: 2900 UL File Date: 27-Sep-1996
LRA-High: 95.0 Max Operating Current: 15.6 CSA File No.: LR3104C
LRA-Half Winding:

Alternate Applications
Refrigerant Frequency (Hz) Phase Voltage Application
R-22 HCFC 60 3 460 Air Conditioning

Eddie , Hung . Page 1 of 1


9/23/2003

Copyright © 2002 Copeland Corporation. All rights reserved.


ZR94KC-TFD
HCFC, R-22, 60 Hz, 3 - Phase, 460 V
Air Conditioning
Production Status: Available for sale to all U.S. customers. Please check with your local Copeland representative for international
availability.

Performance Mechanical
Evap(°F)/Cond(°F) 45/130 45/100 Number of Cylinders: 0 CIR (in^3/Rev): 7.757
RG(°F)/Liq(°F) 65/115 65/85 Bore Size (in): 0.0 CFH (ft^3/hr): 942.6926
Stroke(in): 0.0
Capacity (Btu/hr): 95600 112000
Power (Watts): 8250 5950 Overall Length (in): 10.38 Mounting Length (in): 7.5
Current (Amps): 12.8 10.4 Overall Width (in): 11.19 Mounting Width (in): 7.5
EER (Btu/Wh): 11.6 18.8 Overall Height (in): 18.8 Mounting Height (in): 19.57
Mass Flow (lbs/hr): 1400 1450
Suction Size (in): 1 1/8 Stub
Discharge Size (in): 7/8 Stub
Sound Power (dBA): 78 Ave 83 Max
Initial Oil Charge (oz): 85
Vibration (mils(peak-peak)): 2.5 Ave 3.5 Max
Oil Recharge (oz): 81
Net Weight (lbs): 132.0

Electrical
RLA: 16.4 MCC (Amps): 23.0 UL File No.: SA-2337
LRA-Low: RPM: 3500 UL File Date: 27-Sep-1996
LRA-High: 95.0 Max Operating Current: 15.6 CSA File No.: LR3104C
LRA-Half Winding:

Alternate Applications
Refrigerant Frequency (Hz) Phase Voltage Application
R-22 HCFC 50 3 380/420 Air Conditioning

Eddie , Hung . Page 1 of 1


9/23/2003

Copyright © 2002 Copeland Corporation. All rights reserved.


ZR94KC-TFD
HCFC, R-22, 60 Hz, 3 - Phase, 460 V
Air Conditioning
Production Status: Available for sale to all U.S. customers. Please check with your local Copeland representative for international
availability.

Performance Mechanical
Evap(°C)/Cond(°C) 7.2/54.4 7.2/37.8 Number of Cylinders: 0 CIR (cm^3/Rev): 0.127
RG(°C)/Liq(°C) 18.3/46.1 18.3/29.4 Bore Size (mm): 0 CFH (cm^3/hr): 26694.08
Stroke(mm): 0
Capacity (Watts): 28000 33000
Power (Watts): 8250 5950 Overall Length (mm): 263.652 Mounting Length (mm): 190.5
Current (Amps): 12.8 10.4 Overall Width (mm): 284.226 Mounting Width (mm): 190.5
EER (COP): 3.4 5.51 Overall Height (mm): 477.52 Mounting Height (mm): 497.078
Mass Flow (g/s): 176 183
Suction Size (in): 1 1/8 Stub
Discharge Size (in): 7/8 Stub
Sound Power (dBA): 78 Ave 83 Max
Initial Oil Charge (liters): 2.514
Vibration (mm(peak-peak)): 0.063 Ave 0.089 Max
Oil Recharge (liters): 2.395
Net Weight (kg): 59.874

Electrical
RLA: 16.4 MCC (Amps): 23.0 UL File No.: SA-2337
LRA-Low: RPM: 3500 UL File Date: 27-Sep-1996
LRA-High: 95.0 Max Operating Current: 15.6 CSA File No.: LR3104C
LRA-Half Winding:

Alternate Applications
Refrigerant Frequency (Hz) Phase Voltage Application
R-22 HCFC 50 3 380/420 Air Conditioning

Eddie , Hung . Page 1 of 1


9/23/2003

Copyright © 2002 Copeland Corporation. All rights reserved.


RATING CONDITIONS ZR94KC 3 PHASE
20° F Superheat
AIR SCROLL® HCFC-22
15° F Sub Cooling COMPRESSOR
95° F Ambient Air Over CONDITIONING 380/420-3-50 -TFD
50 Hz Operation 200/220-3-50 -TF5

Condensing CAPACITY (BTU/HR) Evaporating Temperature


Temperature -10 0 10 20 30 40 45 50 55
°F (°C) (-23.3) (-17.8) (-12.2) (-6.7) (-1.1) (4.4) (7.2) (10.0) (12.8)
80 (26.7) 30000 39600 50400 62800 77000 93300 102300 112000 122400
90 (32.2) 27400 36900 47600 59700 73600 89500 98300 107700 117700
100 (37.8) 24700 34200 44700 56600 70100 85600 94100 103200 112900
110 (43.3) . 31100 41600 53200 66400 81500 89700 98600 108000
120 (48.9) . . 38000 49500 62400 77000 85000 93600 102700
130 (54.4) . . . 45200 57800 72000 79800 88100 97000
140 (60.0) . . . . 52600 66400 74000 82000 90600
150 (65.6) . . . . . 60000 67400 75200 83500

Condensing EER (BTU/WATT-HR) Evaporating Temperature


Temperature -10 0 10 20 30 40 45 50 55
°F (°C) (-23.3) (-17.8) (-12.2) (-6.7) (-1.1) (4.4) (7.2) (10.0) (12.8)
80 (26.7) 8.2 10.6 13.5 16.7 20.2 23.9 25.7 27.6 29.3
90 (32.2) 6.6 8.8 11.3 14.1 17.2 20.5 22.3 24.0 25.7
100 (37.8) 5.2 7.2 9.4 11.9 14.6 17.6 19.2 20.8 22.3
110 (43.3) . 5.8 7.7 9.9 12.3 15.0 16.4 17.9 19.3
120 (48.9) . . 6.2 8.1 10.3 12.6 13.9 15.2 16.5
130 (54.4) . . . 6.5 8.4 10.5 11.6 12.8 14.0
140 (60.0) . . . . 6.7 8.6 9.5 10.6 11.6
150 (65.6) . . . . . 6.8 7.7 8.6 9.5

Condensing POWER (WATTS) Evaporating Temperature


Temperature -10 0 10 20 30 40 45 50 55
°F (°C) (-23.3) (-17.8) (-12.2) (-6.7) (-1.1) (4.4) (7.2) (10.0) (12.8)
80 (26.7) 3680 3720 3740 3770 3810 3910 3980 4060 4170
90 (32.2) 4160 4200 4220 4240 4280 4360 4410 4490 4590
100 (37.8) 4710 4750 4770 4780 4800 4860 4910 4970 5060
110 (43.3) . 5380 5390 5390 5400 5430 5470 5520 5590
120 (48.9) . . 6110 6090 6080 6100 6120 6160 6210
130 (54.4) . . . 6910 6880 6870 6880 6900 6940
140 (60.0) . . . . 7800 7770 7760 7760 7780
150 (65.6) . . . . . 8800 8780 8770 8770

Condensing CURRENT (AMPS) @ 380 Volts (Multiply by 1.7 for 220 V)


Temperature -10 0 10 20 30 40 45 50 55
°F (°C) (-23.3) (-17.8) (-12.2) (-6.7) (-1.1) (4.4) (7.2) (10.0) (12.8)
80 (26.7) 8.2 8.3 8.3 8.3 8.4 8.5 8.6 8.7 8.8
90 (32.2) 8.8 8.8 8.9 8.9 8.9 9.0 9.1 9.2 9.3
100 (37.8) 9.5 9.5 9.5 9.5 9.6 9.7 9.7 9.8 9.9
110 (43.3) . 10.3 10.3 10.3 10.4 10.4 10.5 10.5 10.6
120 (48.9) . . 11.3 11.3 11.3 11.3 11.3 11.4 11.5
130 (54.4) . . . 12.4 12.4 12.4 12.4 12.4 12.5
140 (60.0) . . . . 13.7 13.7 13.7 13.7 13.7
150 (65.6) . . . . . 15.2 15.2 15.1 15.1

Condensing MASS FLOW (LBS/HR) Evaporating Temperature


Temperature -10 0 10 20 30 40 45 50 55
°F (°C) (-23.3) (-17.8) (-12.2) (-6.7) (-1.1) (4.4) (7.2) (10.0) (12.8)
80 (26.7) 402 515 641 783 943 1120 1220 1330 1450
90 (32.2) 383 501 630 773 935 1120 1220 1330 1440
100 (37.8) 362 484 616 763 927 1110 1210 1320 1440
110 (43.3) . 461 598 749 916 1100 1210 1310 1430
120 (48.9) . . 573 728 900 1090 1190 1300 1420
130 (54.4) . . . 699 874 1070 1170 1290 1400
140 (60.0) . . . . 838 1040 1140 1260 1380
150 (65.6) . . . . . 992 1100 1220 1340
Nominal Performance Values (±5%) based on minimum 24 hours run-in. Subject to change without notice.

©2002 Copeland Corporation #2.22AC50-194.3


Printed in U.S.A. Issued 04-18-2002
01-977
RATING CONDITIONS PLEASE NOTE:
20° F Superheat ZR94KC Compressor requires a
15° F Sub Cooling minimum of 24 hours
3 PHASE "run-in" to attain specified
95° F Ambient Air Over
HCFC-22 performance.
50 Hz Operation

CAPACITY
130
Cond. Cond.
120
Temp. Press.
110 (°F) (PSIG)
CAPACITY (BTUH X 1000)

100 80 144
90 90 168
100 196
80 110 226
70 120 260
130 297
60 140 337
50 150 382

40

30

20
-10 -5 0 5 10 15 20 25 30 35 40 45 50 55 Evap. Temp. (°F)
16.5 20.1 24.0 28.2 32.8 37.7 43.0 48.8 54.9 61.5 68.5 76.0 84.0 92.6 Evap. Press. (PSIG)

CURRENT @ 380 Volts (Multiply by 1.7 for 220 V)


16

15 150 382

14 140 337
CURRENT (AMPS)

13
130 297

12 120 260

11 110 226
100 196
90 168
10
80 144

9
-10 -5 0 5 10 15 20 25 30 35 40 45 50 55 Evap. Temp. (°F)
16.5 20.1 24.0 28.2 32.8 37.7 43.0 48.8 54.9 61.5 68.5 76.0 84.0 92.6 Evap. Press. (PSIG)

#2.22AC50-194.3 Copeland Corporation


Issued 04-18-2002 Sidney, Ohio 45365-0669
USE COPPER CONDUCTORS ONLY. USE THIS
EQUIPMENT ON A GROUNDED SYSTEM ONLY. USE
MINIMUM 75C WIRE FOR AMPACITY
DETERMINATION. INTERNAL MOTOR PROTECTION-
ALLOW TIME FOR RESET. PRIMARY SINGLE PHASE
FAILURE PROTECTION IS PROVIDED. CRANKCASE
HEATER, WHEN APPLIED, MUST BE CONNECTED
ONLY TO ITS RATED VOLTAGE. OVERCURRENT
PROTECTION DEVICE RATING AND TYPE MUST BE
IN ACCORDANCE WITH REGULATORY AGENCY END
PRODUCT APPROVALS -SEE SYSTEM NAMEPLATE
TO CORRECT IMPROPER MOTOR ROTATION. XX
SWITCH ANY TWO SUPPLY LINES.
1 005-0922-00
L1
3-98
L2

2 3
L3
MOTOR
WINDING CONNECTION