GENERAL NOTES:

1. ALL WORKS SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE


PHILIPPINE ELECTRICAL CODE, THE LOCAL ORDINANCES, THE RULES AND
LEGEND: SD SMOKE DETECTOR
REGULATIONS OF THE LOCAL ENFORCING AUTHORITY, AND THE
Sa SINGLE POLE SWITCH ONE GANG
REQUIREMENTS OF THE LOCAL POWER COMPANY. HD HEAT DETECTOR
2. ALL WORKS HEREIN SHALL BE DIRECTLY SUPERVISED BY A DULY LICENSED
ELECTRICAL ENGINEER AS ENFORCED BY THE NEW ELECTRICAL Sab TWO-SINGLE SWITCH IN ONE GANG
ENGINEERING LAW OR RA. 7920. Sabc THREE-SINGLE SWITCH IN ONE GANG B FIRE ALARM BELL
3. ALL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE PLANS AND
SPECIFICATIONS. S3W TWAY SWITCH IN ONE GANG
4. ALL MATERIALS TO BE USED SHALL BE BRAND NEW, OF THE BEST QUALITY M FIRE ALARM MANUAL STATION
AND OF THE APPROVED TYPE AND SHALL BEAR THE MANUFACTURER'S 240W FLUORESCENT LIGHTING
NAME INCLUDING THE "PSA" MARK, PULL BOXES SHALL BE PROVIDED IN FIXTURE WITH HPF BALLAST, DUST
APPROPRIATE AREAS EVEN IF NOT INDICATED IN THE PLAN. PROOF RECESSED-MOUNTED WALL EXIT LIGHT
5. POWER SUPPLY TO THE BUILDING SHALL BE THREE PHASE, 3-WIRE AND CEILING MOUNTED LED CIRCULAR
GROUND, 230 VOLTS. DOWN LIGHT EMERGENCY LIGHT
6. RACEWAY SCHEDULE SHALL BE AS FOLLOWS:
A. CONCRETE PEDESTAL TO MDP-RIGID STEEL DIRECTIONAL HANGING EXIT LIGHT
CONDUIT. EMERGENCY LIGHT
B. MOP TO DISTRIBUTION PANEL BOARDS- uPVC PIPE SCHEDULE 40.
C. BRANCH CIRCUITS FOR POWER, LIGHTING AND AUXILIARY MINIMUM SIZE OF BUZZER
RACEWAY SHALL BE 15 MM. DIAMETER
SPEAKER
PULL BOX
7. OUTLET BOXES SHALL HAVE A MINIMUM THICKNESS OF GA 16 WITH 1/2 SP PB
KO AND SHALL BE PAINTED WITH RED LEAD PAINT PRIOR TO INSTALLATION
8. WIRES AND CABLES SHALL BE OF THE APPROVED TYPE AND BEARING THE MAN HOLE
MH
PS MARK UNLESS SPECIFIED OR INDICATED OTHERWISE, ALL POWER CEILING FAN
AND LIGHTING CONDUCTORS SHALL BE INSULATED FOR 600 VOLTS MINIMUM.
CCTV OUTLET
9. WIRING DEVICES SHALL HAVE MINIMUM RATING OF 10 AMPERES, 250 CIRCUIT HOMERUN
VOLTS. CEILING MOUNTED CASSETTE
1 DUPLEX COVINIENCEOUTLET,
GROUNDING TYPE TYPE EXHAUST FAN
10. LIGHTING FIXTURES SHALL CONFORM WITH THE SCHEDULE AS ROUND FLOOR
PREPARED BY THE ARCHITECT. RECEPTACLE ROUND FLOOR RECEPTACLE ANNUNCIATOR
DITTO BUT COUNTER HEIGHT
11. PANEL BOARDS SHALL CONFORM TO THE LOAD SCHEDULE AS SHOWN ON GROUND EARTH
PLANS WITH RESPECT TO BREAKER PHASE ARRANGEMENT, RATING,
CAPACITY AND SHORT CIRCUIT CONSIDERATION. SPECIAL PURPOSE OUTLET SERVICE ENTRANCE, POWER
12. FIRE ALARM DEVICES SHALL COMPLY WITH THE NEPA PROVISIONS AND SERVICE ENTRANCE,
SHALL BEAR THE "UL" STANDARD MARK. AIR CONDITIONING OUTLET COMMUNICATION
13. ALL NON-CURRENT CARRYING METALLIC PARTS, CABINETS AND EQUIPMENT
RANGE
M KILOWATT-HOUR METER
FRAMES SHALL BE PROPERLY GROUNDED IN ACCORDANCE WITH THE R
GROUNDING REQUIREMENTS OF THE LATEST EDITION OF THE PHILIPPINE PANEL BOARD
ELECTRICAL CODE. TV OUTLET
TV
LAN NETWORK SWITCH PORT
14. MOUNTING HEIGHTS SHALL BE AS FOLLOWS: T
TELEPHONE OUTLET
A. WALL SWITCHES1400 MM AFF TO CENTER OF DEVICE. D U UP-RISER
LOCAL AREA NETWORK
B. WALL OUTLETS300 MM AFF TO CENTER OF DEVICE. D DOWN-RISER
C. COUNTERTOP OUTLETS150 MM TOP OF COUNTER TO CENTER OF DEVICE. D
NURSE CALL BUTTON
D. INTERCOM OUTLETS1400 MM AFF TO CENTER OF BOX.
E. CONTROL CABINETS1500 MM AFF TO TOP OF ENCLOSURE (VERTICAL).
FACP FIRE ALARM CONTROL PANEL
MTS MANUAL TRANSFER SWITCH
F. MANUAL STATION1400 MM AFF TO CENTER OF DEVICE
G. BELL200 MM BELOW BEAM OR FINISHED CEILING. TTC TELEPHONE TERMINAL CABINET
ATS AUTOMATIC TRANSFER SWITCH
H. EMERGENCY LIGHT300 MM BELOW BEAM OR FINISHED CEILING.
I. EXIT LIGHT 150 MM ABOVE DOOR JAMB. NCP NURSE CONTROL PANEL MDP MAIN DISTRIBUTION PANEL
ISABELA STATE UNIVERSITY- CHECKED BY: SUBJECT: PREPARED BY: PROJECT TITLE: SHEET CONTENT: SHEET NO.
CITY OF ILAGAN CAMPUS
ELECTRICAL ENGINEERING
ENGR. FREDERICK GALLO EE 113 - COMPUTER DIAZ, DENMARK R. ELECTRICAL LAYOUT LEGEND & GENERAL 1
DEPARTMENT
INSTRUCTOR AIDED DRAFTING YEAR/SECTION: BSEE 1B NOTES / SPECIFICATION