Analysis of Short-Circuit Performance of Split-Winding Transformer
Analysis of Short-Circuit Performance of Split-Winding Transformer
2, APRIL 2007
Abstract—The split-winding arrangement requires special reliability. In recent times, field-circuit-coupled formulation has
short-circuit design considerations. During short-circuit condi- become an important tool in design, analysis and nondestructive
tions, there is a considerable distortion of the leakage field, which testing of electromagnetic devices. The field part is generally
in turn produces high axial short-circuit forces. This paper deals
solved by using the well-known finite-element method (FEM)
with the computation and analysis of electromagnetic forces in
windings of split-winding transformers. A nonlinear-transient while the circuit part is solved using nodal or loop circuit anal-
field-circuit coupled finite element model is used to simulate the ysis [1]–[3].
split-winding transformer. A 70-MVA, three-phase, 220/6.9/6.9-kV In the past, classical methods were used to compute the
split-winding transformer is modeled under preset and postset short-circuit forces in windings. These methods use simplified
short-circuit test conditions. Under the preset condition, the trans- configurations and make assumptions such as infinite per-
former is analyzed with one as well as both the LV windings short meability of core material [4]. Although these methods are
circuited to compare the axial forces produced in the windings
for these two cases. The results show that there is a considerable simple, fast and easy to formulate, they are not suitable for
rise in the axial forces when one winding is short circuited as predicting the performance of special types of transformers.
compared with the case when both windings are short circuited. Over the years, many accurate electromagnetic force compu-
The effect of initial magnetization of core on axial short-circuit tation methods have been proposed in the literature mainly
forces is calculated and discussed. It is also shown that even though based on static formulations [5]–[9]. Transient formulations are
postset method eliminates inrush related problems there is not described in [10]–[12]. Analysis of split-winding transformers
much respite in short-circuit forces.
requires a field-circuit approach with magnetic nonlinearity
Index Terms—Field-circuit coupling, finite-element method taken into account.
(FEM), nonlinear transient, split-winding transformer. The split-winding arrangement is particularly used in power
transformers. It usually consists of several pairs of input and
output windings. All the input windings are connected in par-
I. INTRODUCTION allel and all the output windings are independent and galvan-
ically separated from each other. The functions of the input
HE transformer is a very critical and costly equipment in and output windings can be interchanged. One typical config-
T power systems. The addition of more generating capaci-
ties and interconnections in power systems has contributed to
uration is shown in Fig. 1. Two secondary windings are placed
axially with respect to each other (LV1 and LV2). The primary
an increase in short-circuit capacity of networks, making the windings are also split into two parts with center-line lead ar-
short-circuit duty of transformers more severe. Failure of trans- rangement (HV1 and HV2). Advantages of the transformer with
formers due to short circuits is a major concern for power util- split-winding arrangement include saving of space/instrumenta-
ities and manufacturers. An inadequate short-circuit strength tion and decrease in values of short-circuit currents in the indi-
may lead to a mechanical collapse of windings and deformation vidual circuits [13], [14]. However, split-winding transformers
or damage to the clamping structure. The short-circuit design require special short-circuit design considerations since there is
is one of the most important and challenging aspects of trans- a considerable distortion of the leakage field under specific con-
former design. Designers need advanced analysis tools that can ditions, which in turn produces high axial short-circuit forces
simulate short-circuit performance of transformers. These days, and end thrusts in the windings under short circuit [15].
owing to a quantum improvement in computational facilities, Very few published papers have reported the analysis of short-
transient analysis of complex electromagnetic devices has be- circuit performance of the split-winding transformers. Previ-
come feasible, which can help in performing simulation studies ously, this phenomenon was analyzed using a magnetic equiv-
for an in-depth analysis of various phenomena affecting their alent circuit model (MEC) or reluctance network model [14].
Although, such a model is simple and gives a fast solution,
it contains some peculiarities. First, the number of elements
Manuscript received December 22, 2005; revised July 28, 2006. This work employed are small and this may reduce accuracy of the so-
was supported by the Department of Science and Technology, Government of
India, under Project SR/FTP/ET-165/2001. Paper no. TPWRD-00734-2005. lution. Moreover, it is difficult to calculate the field quantities
The authors are with the Department of Electrical Engineering, In- at any specified locations. The second peculiarity is that the
dian Institute of Technology–Bombay, Mumbai 400076, India (e-mail: flux flowing through a reluctance element is assumed to pass
[email protected]; [email protected]).
Color versions of one or more of the figures in this paper are available online
through a specified direction only. On the other hand, FEM is
at http://ieeexplore.ieee.org. very flexible and the directions of flux paths need not be known
Digital Object Identifier 10.1109/TPWRD.2007.893442 in advance. As far as split-winding transformers are concerned,
0885-8977/$25.00 © 2007 IEEE
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on November 29, 2008 at 04:38 from IEEE Xplore. Restrictions apply.
KUMBHAR AND KULKARNI: ANALYSIS OF SHORT CIRCUIT PERFORMANCE 937
(2)
(3)
Fig. 1. Arrangement and electrical winding connections of the split-winding
transformer. where
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on November 29, 2008 at 04:38 from IEEE Xplore. Restrictions apply.
938 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 2, APRIL 2007
(7)
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on November 29, 2008 at 04:38 from IEEE Xplore. Restrictions apply.
KUMBHAR AND KULKARNI: ANALYSIS OF SHORT CIRCUIT PERFORMANCE 939
Fig. 4. Flux density plots when (a) one winding is short circuited and (b) both
Fig. 3. Contour lines of magnetic vector potential for the cases when (a) one windings are short circuited.
winding is short circuited and (b) both windings are short circuited.
and (b) shows plots of the flux densities for the two considered
method (the postset method is not used because of test plant cases at the first peak of the short-circuit current. The flux den-
limitations) [14]. In this method, the LV winding is short cir- sity in the upper part of the limb is very high (about 2.2 T) with
cuited before closing the circuit breaker at the source terminals. a corresponding high inrush current for the HV1 winding [see
The HV windings are connected in parallel and supplied from a Fig. 5(a)], whereas there is no demand for significant magne-
voltage source. tizing current by the HV2 winding since the flux density in the
Two cases are analyzed in the preset test condition. In the bottom part of the limb is very low due to the short-circuited
first case, one LV winding (LV2) is short circuited using a low inner LV2 winding. The upper half of the limb becomes satu-
value resistance, while the other is open circuited using a high rated while the lower part is well below saturation. This phe-
value resistance. In the second case, both the LV windings are nomenon results in heavy distortion of fields in the core and the
short circuited. The initial magnetization of core is assumed to windings, and leads to higher axial short-circuit forces in LV2
be zero during the simulation. The radial and the axial forces and HV2. Fig. 5(b) shows the waveform of the short-circuit cur-
are computed at the first peak of the short-circuit current. rent in the HV2 winding. The values of winding currents are
In the single short-circuited winding case, the flux distribu- given in Table II (per unit values are based on 35 MVA). The in-
tion is completely different in the lower and upper parts of the rush current flows mainly in the HV1 winding due to the reason
core limb. Fig. 3(a) and (b) shows the flux patterns, and Fig. 4(a) explained previously. The simulation results give the terminal
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on November 29, 2008 at 04:38 from IEEE Xplore. Restrictions apply.
940 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 2, APRIL 2007
Fig. 5. (a) Inrush current in HV1 and (b) short-circuit current in HV2.
Fig. 6. Axial forces in LV2 winding (a) inner and (b) outer.
TABLE II
MAXIMUM PEAK WINDING CURRENTS
DURING PRESET METHOD
since the inrush current flows mainly in HV1. Fig. 8(a) and (b)
shows the axial and radial forces along the height of the HV2
winding, respectively.
The total radial forces for the considered windings are sum-
marized in Table III. For the other windings the forces are not
appreciable. It is seen that there is moderate change in the radial
force in the windings because of corresponding small change in
HV current (phasor addition of currents in HV1 and HV2) to be the axial component of flux densities. The negative sign indi-
about 18% higher than the HV2 current. cates negative and directions for the radial and axial forces,
Fig. 6(a) and (b) shows the axial forces along the height of respectively. Table IV gives the axial forces on the windings. It
the winding for the inner and outer LV2 windings, respectively. is seen that the values of net axial forces are much larger in the
The radial force distribution is given in Fig. 7(a) and (b) for case when one winding is short circuited. In the case of HV2,
the inner and outer LV2 windings, respectively. The results are even though it is not explicit from the force distribution plot,
shown for both the considered cases. It is seen that for the same there is a considerable amount of net force acting on it. It is
value of short-circuit current, the axial forces are higher for the also noted that the net axial force acting on the HV2 winding
case in which only one of the LV windings is short circuited is in opposite direction to that acting on the LV2 winding. If
as compared to the case when both the LV windings are short the clamping structures are not designed properly to account for
circuited. There is no appreciable change in the radial forces these net forces, axial displacements of windings may occur.
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on November 29, 2008 at 04:38 from IEEE Xplore. Restrictions apply.
KUMBHAR AND KULKARNI: ANALYSIS OF SHORT CIRCUIT PERFORMANCE 941
Fig. 7. Radial forces in LV2 winding (a) inner and (b) outer. Fig. 8. (a) Axial forces. (b) Radial forces in the HV2 winding.
TABLE III
B. Effect of Initial Magnetization TOTAL RADIAL FORCES IN TONS
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on November 29, 2008 at 04:38 from IEEE Xplore. Restrictions apply.
942 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 2, APRIL 2007
TABLE V
COMPARISON OF MAXIMUM PEAK WINDING CURRENTS FOR
VARIOUS MAGNETIZATION CONDITIONS
TABLE VI
COMPARISON OF AXIAL FORCES FOR VARIOUS MAGNETIZATION CONDITIONS
TABLE VII
MAXIMUM PEAK WINDING CURRENTS TABLE VIII
DURING POSTSET METHOD TOTAL FORCES IN TONS DURING POSTSET METHOD
C. Postset Method
If the short-circuit capacity of the station is high enough maximum positive and negative potential values in the magnetic
to allow the postset method (which eliminates the inrush and vector potential plot.
related problems), there is still one more characteristic of the Thus, although the split-winding configuration helps in lim-
split-winding transformer which makes the short-circuit test iting the rating of circuit breakers, it poses problems for the short
on them more severe than the conventional two winding trans- circuit withstand. The high axial short-circuit forces could lead
formers. With the LV2 winding short circuited, some current to deformation in the end clamping structure and the windings
flows in the HV1 winding which is not directly facing the as well. The end clamping structure plays an important role in
short-circuited LV2 winding. The transformer when simulated resisting axial forces during short circuit. This puts emphasis on
for the postset short-circuit condition, LV2 is short circuited accurate evaluation of these axial forces.
after decay of inrush currents in the HV1 and HV2 windings.
Table VII gives the values of short-circuit currents in the wind- V. CONCLUSION
ings during the postset method. The calculated value of current This paper has presented a detailed formulation and modeling
in HV1 is 4.78% of the short-circuit current flowing in HV2. It to evaluate the short-circuit performance of the split-winding
is generally small, in the range of 3% to 5% of that flowing in transformers. A 70-MVA, three-phase, 220/6.9/6.9-kV
the HV2 winding due to a much higher impedance between the
split-winding transformer is modeled under short-circuit
HV1 and LV2 windings, but it is sufficient to cause ampere-turn
test conditions. A 2-D axisymmetric field-circuit-coupled
unbalance along the height of the windings. The ampere-turns
nonlinear transient finite-element model has been developed
of HV2 are smaller than that of LV2, and corresponding to the
to investigate transient axial and radial forces in the windings.
ampere-turns of HV1 there are no balancing ampere-turns in
LV1 (since it is open circuited). Hence, there is considerable The results of the model have been verified with the 3-D model.
distortion of the leakage field (see Fig. 9) resulting into higher Simulation results are reported for both preset (with various
axial short-circuit forces. Table VIII gives the values of forces initial magnetization conditions) and postset short-circuit test
during the postset short-circuit method. Even though the postset conditions.
method eliminates the inrush related problems, there is not much Under the preset short-circuit condition, the axial and radial
respite in the short-circuit stresses (as compared to the case of forces are computed for two cases, viz. only one winding short
both the windings short circuited). circuited and both windings short circuited. In the former case,
It can be also noted that the effect of short-circuit current there is considerable distortion of leakage field resulting in
share between HV1 and HV2 (approximately 5% and 95%) is higher axial short-circuit forces. For the same value of short-cir-
also present in the preset method. Thus, the current shown in cuit current, the forces are higher for this case as compared to
Fig. 5(a) is actually a superposition of inrush current and the the latter case in which both the windings are short circuited.
HV1 share. Currents such as this HV1 current or inrush cur- Also, the beneficial effect of deliberate pre-magnetization with
rents (in the HV1 and HV2 windings) create asymmetry in the opposite polarity is demonstrated.
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on November 29, 2008 at 04:38 from IEEE Xplore. Restrictions apply.
KUMBHAR AND KULKARNI: ANALYSIS OF SHORT CIRCUIT PERFORMANCE 943
TABLE IX REFERENCES
TRANSFORMER DATA
[1] R. Tang, S. Wang, L. Yan, X. Wang, and C. Xiang, “Transient simu-
lation of power transformers using 3–D finite element model coupled
to electric circuit equations,” IEEE Trans. Magn., vol. 36, no. 4, pp.
1417–1420, May 2000.
[2] J.-S. Wang, “A nodal analysis approach for 2D and 3D magnetic-circuit
coupled problems,” IEEE Trans. Magn., vol. 32, no. 3, pp. 1074–1077,
May 1996.
[3] I. A. Tsukerman, A. Konrad, and J. D. Lavers, “A method for circuit
connections in time-dependent eddy current problems,” IEEE Trans.
Magn., vol. 28, no. 2, pp. 1299–1302, Mar. 1992.
[4] M. Waters, The Short Circuit Strength of Power Transformers.
London, U.K.: Macdonald, 1966.
[5] K. Najdenkoski and D. Manov, “Electromagnetic forces calculation on
power transformer winding under short circuit,” Int. J. Comput. Math.
Elect. Electron. Eng., vol. 17, no. 1/2/3, pp. 374–377, 1998.
[6] C. M. Arturi, “Electromagnetic force calculation on a 3-phase auto-
transformer under time-varying fault by 3-D non-linear finite element
code,” IEEE Trans. Magn., vol. 29, no. 2, pp. 2010–2013, Mar. 1993.
[7] C. M. Arturi, “3-D FE analysis of the axial forces on the step-up trans-
former winding with helical LV,” IEEE Trans. Magn., vol. 31, no. 3,
pp. 2032–2035, May 1995.
[8] M. G. Kladas, M. P. Papadopoulos, and J. A. Tegopoulos, “Leakage
flux and force calculation on power transformer windings under short
circuit: 2D and 3D models on the theory of images and the finite el-
ement method compared to measurements,” IEEE Trans. Magn., vol.
30, no. 5, pp. 3487–3490, Sep. 1994.
[9] S. Salon, B. LaMattina, and K. Sivasubramaniam, “Comaparison of
short ciruit forces in transformers,” IEEE Trans. Magn., vol. 36, no. 5,
pp. 3521–3523, Sep. 2000.
[10] C. M. Arturi, “Electromagnetic force calculation on a 3-phase auto-
transformer under time-varying fault by 3-D non-linear finite element
code,” IEEE Trans. Magn., vol. 29, no. 2, pp. 2010–2013, Mar. 1993.
Fig. 10. Geometry details of analyzed split winding transformer (Courtesy: [11] T. Renyan, L. Yan, L. Dake, and T. Lijian, “Numerical calculation of
Crompton Greaves Ltd.). 3D transient eddy current field and short ciruit electromagnetic force in
large transformers,” IEEE Trans. Magn., vol. 28, no. 2, pp. 1418–1421,
Mar. 1992.
TABLE X [12] S. L. Ho, Y. Li, H. C. Wong, S. H. Wang, and R. Y. Tang, “Numerical
B–H CURVE DATA simulation of transient force and eddy current loss in a 720-MVA power
transformer,” IEEE Trans. Magn., vol. 40, no. 2, pp. 687–690, Mar.
2004.
[13] P. Stuchl, I. Dolezel, A. Zajic, J. Hruza, and O. Weinberg, “Perfor-
mance of transformer with split winding under nonstandard operation
conditions,” in Proc. CIGRE, 2000, pp. 12–103.
[14] G. Leber, “Investigation of inrush current during a short circuit test on
In the case of the postset method (with one winding short a 440 MVA, 400 kV GSU-transformer,” in Proc. CIGRE, 2000, pp.
circuited), noticeable percentage of short-circuit current flows 12–104.
[15] S. V. Kulkarni and S. A. Khaparde, Transformer Engineering: Design
through the HV winding not facing directly the short circuited and Practice. New York: Marcel Dekker, May 2004.
LV winding. This current is responsible for field distortion and [16] M. Steurer and K. Frohlich, “The impact of inrush current on the me-
increased axial forces. chanical stress of high voltage power transformer coils,” IEEE Trans.
Power Del., vol. 17, no. 1, pp. 155–160, Mar. 1993.
Thus, the challenges posed while designing the split-winding [17] J. Jin, The Finite Element Method in Electromagnetics. New York:
transformers are exemplified in this work. The results obtained Wiley, 2000.
by such accurate coupled field-circuit analysis can be used to [18] M. V. K. Chari and S. J. Salon, Numerical Methods in Electromag-
netism. London, U.K.: Academic, 2000.
determine the electrical design parameters and the mechanical
support structures for the windings. G. B. Kumbhar received the B.E. degree in electrical engineering from the
Government College of Engineering, Maharashtra, India, in 1999 and the
M.Tech. degree from the Indian Institute of Technology–Madras, Chennai, in
2002.
He is presently a Research Scholar at the Indian Institute of Technology-
APPENDIX Bombay, Mumbai, working in the area of coupled field formulations in trans-
TRANSFORMER DESIGN AND NAMEPLATE DATA formers.
Ratings of considered split-winding transformer: 70 MVA,
three-phase, 220/6.9/6.9 kV, Y/Y/Y.
Nameplate and geometrical details are given in Table IX and S. V. Kulkarni (M’99) is Associate Professor, Department of Electrical Engi-
Fig. 10, respectively. The material used for core is M3H and neering, Indian Institute of Technology, Bombay, India. Previously, he worked
at Crompton Greaves Ltd., and specialized in the design and development of
corresponding B–H curve data is given in Table X. transformers up to the 400-kV class. He authored the book Transformer Engi-
neering: Design and Practice (New York: Marcel Dekker). His research inter-
ACKNOWLEDGMENT ests include transformer design and analysis, computational electromagnetics,
and distributed generation.
The authors would like to thank Crompton Greaves Ltd. for Mr. Kulkarni is the recipient of the Young Engineer Award (2000) from the
providing practical data on the split-winding transformer. Indian National Academy of Engineering.
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on November 29, 2008 at 04:38 from IEEE Xplore. Restrictions apply.