Hga Relay
Hga Relay
GE Multilin 1
HGA Hinged Armature Auxiliary
2 www.GEindustrial.com/Multilin
HGA Hinged Armature Auxiliary
Percentage of Rated V or A
Pickup
Relay Pickup Value Dropout Value
Classification
AC DC AC DC
HGA 11 Standard 80% 80% 40-50% 2-10%
HGA14 Low 40% 30% 20-30% 2-10%
HGA17A,B,C Time 30-40% 20-30% 2-10% 2-10%
HGA17D,H Time 80% Max. 60% Max. 5-15% 2-10%
Selection Guide
DC AC AC Pickup Time DC Res. AC Res. Approx. Wt. in lbs (kg)
Group Contact
Volt. 50 Hz 60 Hz (cycles) Ohms @ 25°C Ohms
Net Ship
51 250 15500
52 125 3650
53 62.5 830
54 48 512
55 32 250
56 24 2 N.O. 160
57 12 2 N.C Approx 40 2 3
58 6 2 10 (0.9) (1.4)
59 220 9600
60 110 2460
70 115 1000
71 230 3960
74 115 830
75 230 4270
www.GEindustrial.com/Multilin 3
HGA Hinged Armature Auxiliary
Selection Guide
Drawout Case Relays
Each Unit
Pickup Approx. Wt. in
Pickup DC VAC lbs (kg)
Group VAC 60 Hz DC Ohms AC Time Case
Option Volt. 50 Hz Contact
@25°C Z (cycles)
Net Ship
11N 1A 24 160
11N 32A 48 512
11N 63A 62.5 830
11N 94A 125 3650
11N 125A 250 15550 9 11
11N 156A 115 90 ➀ 2 S2 (4.1) (5)
11N 187A 115 99
11N 249A 230 376
11N 280A 230 512
11N 342A 6 10
11N 373A 12 40
11R 1A 24 160
11R 2A 48 512
11R 3A 62,5 830
11R 4A 125 3650
11R 5A 250 15550 S1 7 9
11R 6A 115 90 ➀ 2 (3.2) (4.1)
11R 7A 115 99
11R 9A 230 512
11R 10A 230 512
11R 15A 6 10
11R 16A 12 40
14A 1A 24 160
14A 2A 48 512
14A 3A 62.5 830
14A 4A 125 3650
14A 5A 250 15550 7 9
14A 6A 115 90 1 S1 (3.2) (4.1)
14A 7A 115 99
14A 9A 230 512
14A 10A 230 512
14A 15A 6 10
14A 16A 220 9600
14AB 1A 24 160
14AB 32A 48 512
14AB 63A 62.5 830
14AB 94A 125 3650
14AB 125A 250 15550 S2 9 11
14AB 156A 115 90 (4.1) (5)
14AB 187A 115 99
14AB 249A 230 376
14AB 280A 230 512
14AB 342A 12 40
17J 1A 12 25
2A 24 98
3A 32 153 9 11
4A 48 375 2 S1 (4.1) (5)
5A 62.5 585
6A 125 2280
7A 250 10300
10A 115 115 1700
➀ HGA11 (standard pickup) double pole, double throw {2 normally open/two normally closed} per unit.
HGA14 (low pickup) one single pole, double throw. HGA17 (time delay) plus one normally open contact per unit.
4 www.GEindustrial.com/Multilin
HGA Hinged Armature Auxiliary
Selection Guide
HGA14 ** **
AM Back connected with cover
AL Front connected with cover
XX Electrical data (see Group column under Selection guide)
Selection Guide
Pick- Approx. Wt. in
DC Contact For 3 2 A For 3 1 A For 3 0.6 A For 3 0.2 A For Carrier lbs (kg)
Group up GCX or GCY
Volt. Targets Targets Targets Targets
Volts
Net Ship
1 250 AL,AM
2 125 AL,AM
3 48 AL,AM
4 32 AM
5 24 AL,AM
6 250 AL,AM
7 125 AL,AM
8 48 AL,AM
9 32 AL,AM
10 24 2 N.O. AL,AM
11 250 1 N.C AL,AM
80%
12 125 AL,AM 2 3
or
13 48 AL,AM (0.9) (1.4)
Less
14 32 AM
15 24 AL,AM
16 250 AL,AM
17 125 AL,AM
18 48 AL,AM
19 32 AL,AM
20 24 AL,AM
25 250 AL,AM
26 125 AL,AM
28 48 AL,AM
29 24 AL
www.GEindustrial.com/Multilin 5
HGA Hinged Armature Auxiliary
Selection Guide
Selection Guide
6 www.GEindustrial.com/Multilin
HGA Hinged Armature Auxiliary
Selection Guide
DC AC Pickup Time Pickup Volts DC Res. AC Res. Approx. Wt. in lbs (kg)
Group Contact (cycles) Ohms @ 25°C Ohms
Volt. 50/60 Hz
Net Ship
51 250 10300
52 125 2280
53 62.5 585
54 48 2 N.O. 375
55 32 2 N.C 153
Approx 60% 2 3 5
56 24 98
3.5 (0.9) (1.4)
57 12 24.5
68 220 10300
70 110 1700
63 115 1700
80%
64 230 1700
Order online –
save time
www.GEindustrial.com/pm
www.GEindustrial.com/Multilin 7