NetSure™ Control Unit (NCU)

M830B, M830D

Benefits The advanced NetSure™ Control Unit (NCU) from Vertiv™


takes remote monitoring and control to the next level with a
yy Easily monitor and adjust system user-friendly color interface, secure connectivity, data
parameters with a simple,
graphic user interface accessed
statistics and multiple communication options.
through an on-board color
display or web pages supported
by all major browsers. Description
yy Numerous connectivity options The NetSure Control Unit (NCU) Network element management support
that support integration into a is an advanced controller designed for data communication is also available
wide variety of networks – IPv4,
for a wide range of DC power applications, via standard protocols, such as SNMP
IPv6, Modbus, SNMP, TL1, EEM,
YDN23 and dual network port
enabling remote monitoring and control version 2 or 3, or Modbus. In addition,
option for permanent and local of modern communication sites. Modbus device integration for many
craft port connections. The factory-installed (standard) or industry standard monitoring devices is
field-added NCU is backward compatible now possible with the versatile NCU
yy Leverage advanced battery and with existing NetSure power systems, controller.
generator management controls,
controlling all aspects of the power chain,
including soft start, time controls, Patented Intelligent Load Management
starter battery check with
including AC mains, DC power plant,
battery backup, diesel generator, and from Vertiv enables you to see power
recharge, bad-grid equalization usage down to the fuse or circuit breaker
recovery, current limiting, fuel the local site environment. The addition
of optional interface boards enables level. To prevent site overload, load levels
monitoring with theft alarms and
the user to access an even greater set of each rack can be measured in relation
support for multiple battery
technologies, including lithium. of site parameters. to rack capacity. Rack load monitoring
requires optional system distribution
yy Rapidly turn-up system Battery management features include measurement devices for the fuse or
with easily uploaded/ temperature compensation, thermal circuit breaker positions.
downloaded pre-programmed runaway management, recharge current
configuration files. limit, reserve time prediction, and optional
yy Decrease energy costs by midpoint monitoring. Battery testing
effectively managing multiple options include scheduled battery
energy sources such as testing and short duration battery
generators and solar panels. testing. Thresholds for battery current
measurement, detailed alarms, inventory
management and three LVD levels can M830B
be programmed easily through the
controller. Control of rectifiers (24V, 48V
and 400V) and converters (24V, 48V,
400V and solar) is possible in this
convenient pluggable module.
Expanded information and alarm data can
be monitored or controlled via password
protected and encrypted web browsers,
including Internet Explorer, Firefox, Google
M830D
Chrome, and Apple Safari.
NetSure™ Control Unit (NCU)

Technical Specifications
General
Power Supply 19 VDC to 60 VDC
Power Consumption 18 W maximum, 4W typical

Environmental
-20°C to +65°C (nominal), -40°C to +75°C (extended conditions) /
Operating
-4°F to +149°F (nominal), -40°F to +167°F (extended conditions)
Relative Humidity 0 to 90%

Safety and Standards Compliance


Electrical IEC 60950-1, EN 60950-1, UL 60950-1
NetSure™ Control Unit User Interface
EMC EN 300 386, 2001 Class B; FCC Part 15, Class B
Environmental CE; NEBS Level 3

Mechanical Data M830B M830D


43.4 x 86 x 208 (mm) 86.2 x 87 x 208 (mm)
Dimensions (H x W x D)
1.65 x 3.41 x 8.33 (inches) 3.41 x 3.42 x 8.33 (inches)
Standard Installation Methods Hot pluggable in stand-alone or embedded power plants
Weight 1 kg / 2.2 lbs.

Inputs/Outputs M830B M830D


Display 128 x 160 Pixels TFT LCD 320 x 240 Pixels TFT LCD
Communication RS232, RS485, Ethernet, USB (for software upgrades)
Protocol IPv4, IPv6, HTTPS, SNMP V 2/ V 3, EEM, SocTpe, Rsoc, Modbus
Web Interface Home Page
2 battery currents, 1 load current, 1 bus voltage, 2 battery voltages,
Analog Inputs
2 temperatures, fuel level sensor and much more with additional interface boards
1 input for status of surge protective device auxiliary contacts, 12 load fuses,
Digital Inputs
6 battery fuses, bi-stable contactor status
Outputs 3 LVD mono or bistable contactors

Ordering Information
Model Model Number Description
M830B 1M830BXX NCU3.0+ controller, 1 x 2 RU
M830D 1M830DXX NCU3.0+ controller, 2 x 2 RU
Optional Interface Board
EIB 5 relay outputs, 8 DC voltages, 3 DC currents, 2 temperatures
IB1 4 relay outputs, 4 digital inputs
IB2 8 relay outputs, 8 digital inputs, 2 temperatures
IB4 1 additional Ethernet port
Supervision Modules
SMDU 4 shunts, 1 voltage input, 20 fuse alarms, and 2 LVD controls
SMDU+ 25 shunts, and 25 fuse alarms
SMTEMP Temperature concentrator with up to 8 temperature sensors
SMDUH 20 Hall effect sensors to measure DC distribution load current from 0 A to 100 A

Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2019 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every
precaution has been taken to ensure accuracy and completeness here, Vertiv Group Corp. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications, rebates and other promotional
offers are subject to change at Vertiv’s sole discretion upon notice.

NCU Controller (R08/19)

You might also like