No.OC128
REVISED EDITION-A
CONTENTS
1. COMBINATION OF INDOOR AND OUTDOOR UNITS ·····3
2. PART NAMES AND FUNCTIONS·····················4
3. DATA··································································5
4. OUTLINES AND DIMENSIONS ························6
5. WIRING DIAGRAM ·········································10
6. REFRIGERANT SYSTEM DIAGRAM················18
7. DISASSEMBLY PROCEDURE ·······················20
8. PARTS LIST ····················································22
9. OPTIONAL PARTS ··························Back cover
OUTDOOR UNIT
PUH-3K
Revision
• PUH-5TKSA, 6TKSA are added.
• Please destroy OC128. The Slim Line.
From Mitsubishi Electric.
1 COMBINATION OF INDOOR AND OUTDOOR UNITS
Indoor unit Outdoor unit
Service 1.6 2 2.5 3 4 5 6 5 6
Service Ref.
Manual No. VKA2 VKA2 VKA2 VKA2 YKA2 YKSA3 YKSA3 YKSA3 TKSA TKSA
PLH-GKH(S)B1 OC139 — — —
PLH-KKHC OC123 — — — — — — —
PCH-GKH(S)A1 OC135 —
PEH-EKH(S)A2.TH OC153 — — — —
PKH-FKH(S)A3 OC130 — — — —
PSH-GJH(S)(1) OC144 — — —
3
2 PART NAMES AND FUNCTIONS
123456789
Air outlet Air outlet
(Expels warm air during cooling)
Air intake
Air intake
PUH-2.5VKA2
PUH-1.6VKA2 PUH-3YKA2
PUH-2VKA2 PUH-3VKA2
Air outlet
Air outlet
Air intake
Air intake
PUH-5YKSA3
PUH-4YKSA3
PUH-6YKSA2
PUH-5TKSA
PUH-6TKSA
CHARGELESS SYSTEM
PRE-CHARGED REFRIGERANT IS SUPPLIED FOR MAXIMUM PIPING LENGTH AT SHIPMENT.
The unique refrigerant circuit and a large accumulator always control the optimal refrigerant level regardless of the length
(30m max. and 5m min.) of piping. The additional refrigerant charging work during installation often causes problems.
Heretofore it is completely eliminated. This unique system improves the quality and reliability of the work done. It also helps
to speed up the installation time.
4
3 DATA
1. REFILLING REFRIGERANT CHARGE (R-22 : kg)
Refrigerant piping length (one way)
Service Ref.
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
PUH-1.6VKA2 1.5 1.7 1.8 1.9 2.1 2.2 2.3 2.4 — —
PUH-2VKA2 1.5 1.7 1.8 1.9 2.1 2.2 2.3 2.4 — —
PUH-2.5VKA2 2.1 2.3 2.4 2.5 2.7 2.8 2.9 3.0 3.1 3.3
PUH-3VKA2 2.5 2.7 2.8 2.9 3.1 3.2 3.3 3.4 3.6 3.7
PUH-3YKA2 2.5 2.7 2.8 2.9 3.1 3.2 3.3 3.4 3.6 3.7
PUH-4YKSA3 3.5 3.6 3.8 3.9 4.1 4.2 4.4 4.5 4.6 4.8
PUH-5YKSA3 4.7 4.8 5.0 5.1 5.3 5.4 5.6 5.7 5.9 6.0
PUH-6YKSA2 4.3 4.4 4.6 4.7 4.9 5.0 5.2 5.3 5.5 5.6
PUH-5TKSA 4.7 4.8 5.0 5.1 5.3 5.4 5.6 5.7 5.9 6.0
PUH-6TKSA 4.3 4.4 4.6 4.7 4.9 5.0 5.2 5.3 5.5 5.6
at 25˚C
Compressor Model ZR61K3TFD ZR68KCTFD ZR61KCTF5 ZR68KCTF5
5
6
Outdoor Unit-Necessary surrounding clearance
4
200
Outdoor Unit-Necessary surrounding clearance 185 185
(Concentrated installation) The upper side must be open. (7-9/32) 500(19-11/16) (7-9/32) Note:Allow adequate
upper clearance
17
Air intake 10 10
Front opening
Air intake
330(13)
150
200
39.5 27.5
362(14-1/4)
500
100 10
PUH-1.6VKA2/PUH-2VKA2
10
Air outlet Service space
15
For 10 units or less 1000
500
Handle
870(34-1/4) Ground terminal
for moving
7 295(11-5/8) 24(1) 302
Outlet guide Handle for moving
installation hole
Rear fresh Service panel
air intake
Handle for moving Refrigerant-pipe flared
Side air intake connection
524
[15.88 3/8F
650 (25-5/8)
444
Refrigerant-pipe flared
OUTLINES AND DIMENSIONS
45
339
282
connection
297
[9.52 3/8F
138
77
53
23
33
95 40 524 60 60
Rear piping hole for front piping Knock out holes for
(refrigerant,drainage 120 power line 2-[27
and wiring)
2-12✕23 Oval holes 104
(standard bolt M10) Knock out hole
42
45
Drain hole
and wiring)
R2
R2
0
Bottom
piping hole
80
25 max.
2-U-shaped R6
Drain hole notched Standard bolt length
holes 65
17
200
185 185
PUH-2.5VKA2
17
(Concentrated installation) Air intake Note:Allow adequate
The upper side must be open.
10 10 upper clearance
Front opening
Air intake
330(13)
39.5 27.5
PUH-3VKA2/PUH-3YKA2
362(14-1/4)
150
200
500
100 10 Air outlet
15
10
Service space
For 10 units or less 1000 500
524
553
Refrigerant-pipe flared
850(33-7/16)
441
337
45
Refrigerant-pipe flared
352
179
138
53
23
33
95 40 524 60 60
Rear piping hole for front piping Knock out holes for
(refrigerant,drainage 120 power line 2-[27
and wiring)
2-12✕23 Oval holes 104
(standard bolt M10) Knock out hole
42
45
Drain hole
and wiring)
R2
R2
0
Bottom
piping hole
80
25 max.
2-U-shaped R6
Drain hole notched Standard bolt length
holes 65
17
7
Unit : mm (inch)
8
Outdoor Unit-Necessary surrounding clearance Outdoor Unit-Necessary surrounding clearance
(Concentrated installation)
300
The upper side must be open.
PUH-4YKSA3
185 185 Note:Allow adequate
(7-9/32) 500(19-11/16) (7-9/32)
10 10 upper clearance
17
Air intake
Front opening
300
150 10
Air intake 100
330(13)
39.5 27.5
500
For 10 units or less 1000
362(14-1/4)
Terminal block for 10
indoor and outdoor
Air outlet unit connection Service space
500
15
870(34-1/4)
7 295(11-5/8) 24(1) Terminal block for power line
302
Outlet guide
installation hole
Service panel
Side air intake
Ground
Handle
524
terminal
for moving
Handle
for moving
585
61
Rear fresh
air intake Handle for moving
1258(49-1/2)
959
Refrigerant-pipe flared
524
connection [19.05 3/4F
345
382
45
Refrigerant-pipe flared
403
138
83
53
23
33
95 40 524 60 60
Rear piping hole for front piping Knock out holes for
(refrigerant,drainage 120 power line 2-[27
2-12✕23 Oval holes 104
(standard bolt M10) and wiring)
52
57
39
Knock out hole
for right piping
0
Drain hole
R2
R2
(refrigerant, 0
Bottom
drainage and wiring)
piping hole
80
25 max.
2-U-shaped R6
Drain hole notched Standard bolt length
holes 65
17
300
The upper side must be open.
185 185 Note:Allow adequate
(7-9/32) 600(23-5/8) (7-9/32)
10 10 upper clearance
17
Air intake
Front opening
300
150 10
150
Air intake
PUH-5TKSA/PUH-6TKSA
39.5 27.5
500
412(16-1/4)
380(14-31/32)
PUH-5YKSA3 /PUH-6YKSA2
15
970(38-3/16)
7 345(13-9/16) 24(1) Terminal block for power line
352
Outlet guide
installation hole
Service panel
Side air intake
Ground
Handle
524
terminal
for moving
Handle
for moving
585
61
Rear fresh
air intake Handle for moving
1258(49-1/2)
959
Refrigerant-pipe flared
524
connection [19.05 3/4F
345
382
45
Refrigerant-pipe flared
403
138
83
53
23
33
95 90 524 60 60
Rear piping hole for front piping Knock out holes for
(refrigerant,drainage 120 power line 2-[27
2-12✕23 Oval holes 104
(standard bolt M10) and wiring)
52
57
39
Knock out hole
for right piping
0
Drain hole
R2
R2
(refrigerant, 0
Bottom
drainage and wiring)
piping hole
80
25 max.
2-U-shaped R6
Drain hole notched Standard bolt length
holes 65
17
9
Unit : mm (inch)
5 WIRING DIAGRAM
PUH-1.6VKA2
SYMBOL NAME SYMBOL NAME SYMBOL NAME
HC CRANKCASE HEATER MC COMPRESSOR (INNER THERMOSTAT) X12<O.B> COMPRESSOR RELAY
C1 OUTDOOR FAN CAPACITOR MF OUTDOOR FAN MOTOR (INNER THERMOSTAT) X13<O.B> 21S4 RELAY
C2 COMPRESSOR CAPACITOR O.B OUTDOOR CONTROLLER BOARD X14<O.B> 21R RELAY
FC<O.B> FAN CONTROLLER SW1·2·3<O.B> CHECK,SERVICE SELECTOR ZNR<O.B> VARISTER
F<O.B> FUSE(6A) T TRANSFORMER 52C CONTACTOR
21S4 R.V.COIL TB1,3 TERMINAL BLOCK 63H1 HIGH PRESSURE SWITCH
OUTDOOR COIL THERMISTOR
21R B.V.COIL RT (0˚C/15kΩ,25˚C/5.4kΩ )
LED
1 YLW
FROOM INDOOR UNIT RT
2 ORN
CONNECTING WIRES
12V DC (polar) 3 BRN
O.B
TB3
SW1 4 3 2 1
CN2 ✕14 ✕13 ✕12 ✕11 FC
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
SW2 CN4
S
SW2
OFF 26C
63H1
2 1 ON ✕14 ✕13 ✕12 ✕11 MF2
3
2 CN3 63H2
MF1
1
CN4T F 51CM
4 3 2 1 4
SV TRF 21S4 52C CH ZNR R/1 S/2 T/3
WHT
WHT
WHT
WHT
WHT
RED
RED
RED
RED
GRY
GRY
BLU
BRN
BRN
YLW
YLW
YLW
YLW
BLU
S BLU BLU
GRY
A 63H1
GRY
Main functions of LED (when both Nos. 1 and 2 of SW3 are ”OFF”)
1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
CN4
SW3 ✕14 ✕13 ✕12 ✕11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 ✕14 ✕13 ✕12 ✕11
MF2
CN4T 63H1 51CM
MF1
4321
4
SV TRF 21S4 52C CH ZNR FR S T S
RED
GRY
GRY
RED
RED
RED
RED
BRN
BRN
YLW
YLW
YLW
YLW
WHT
WHT
BLU
BLU
WHT
RED
BRN BLUBLU
BRN A1 WHT
63H1 3
AC 21R 21 52C HC BLU
RED S4 4
12.3V 220V RED RED MF
ORN A2 2
230V WHT C1 ORN
AC12.3V YLW WHT ORN 1
T 240V
RED
POWER SUPPLY
~/N BLU
220-240V 50Hz
TB1
L RED L1/1 T1/2 BLU R
N BLU WHT C
MC
L3/5 BLU RED
52C T3/6 S
C2
GRN/YLW
●Since LD8 lights when normal power is turned “ON”, check the power supply with the ON or OFF LD8. RED 220V WHITE
❈Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the ORANGE 230V
wiring connection in the following procedure
YELLOW 240V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
Main functions of LED
(when both Nos.1 and 2 of SW3 are “OFF”)
LED No. Output display (light) Check display (flash)
LD1 Compressor indoor command —
LD2 Heating indoor command —
LD3 63H1 ON Outdoor coil thermistor short/open
LD4 Compressor ON —
LD5 Outdoor fan ON —
LD6 4-way valve ON 26C functions
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input
NOTE :
If the operation stops to function of the protection device, the check
display flashes.
1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
CN4
SW3 ✕14 ✕13 ✕12 ✕11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 ✕14 ✕13 ✕12 ✕11
MF2
CN4T 63H1 51CM
MF1
4321
4
SV TRF 21S4 52C CH ZNR FR S T S
RED
GRY
GRY
RED
RED
RED
RED
BRN
BRN
YLW
YLW
YLW
YLW
WHT
WHT
BLU
BLU
WHT
RED
BRN BLUBLU
BRN A1 WHT
63H1 3
AC 21R 21 52C HC BLU
RED S4 4
12.3V 220V RED RED MF
ORN A2 2
230V WHT C1 ORN
AC12.3V YLW WHT ORN 1
T 240V
RED
POWER SUPPLY
~/N BLU
220-240V 50Hz
TB1
L RED L1/1 T1/2 BLU R
N BLU WHT C
MC
L3/5 BLU RED
52C T3/6 S
C2
GRN/YLW
Main functions of LED (when both Nos.1 and 2 of SW3 are ”OFF”) How to use SW1 and 2
●Pressing SW1 erases the past check contents loaded on the
LED No. Output display (light) Check display (flash) microcomputer.
LD1 Compressor indoor command — ●The output display (light) remains lit during operation but
LD2 Heating indoor command — pressing SW2 displays the past check contents in flashing
LD3 63H1 ON Outdoor coil thermistor short/open mode. Pressing the switch again returns to output display
LD4 Compressor ON — (light).
LD5 Outdoor fan ON —
LD6 4-way valve ON —
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input
NOTE : If the operation stops to function of the protection device, the check display flashes.
●SinceLD8 lights when normal power is furned ”ON”, check the power supply with the ON or OFF LD8. RED 220V WHITE
❈Sincethe transformer (T) is connected with 240V power, if 220V or 230V power is used, ORANGE 230V
change the wiring connection in the following procedure.
YELLOW 240V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
12
PUH-3YKA2
SYMBOL NAME SYMBOL NAME SYMBOL NAME
CN3<O.B> CONNECTING WIRES MF OUTDOOR FAN MOTOR (INNER THERMOSTAT) X14<O.B> SOLENOID COIL RELAY
INDOOR/OUTDOOR CONNECTOR O.B OUTDOOR CONTROLLER BOARD ZNR<O.B> SURGE ABSORBER
CN4T<O.B> TRANSFORMER CONNECTOR SW1·2·3<O.B> CHECK,SERVICE SELECT SWITCH 21R BYPASS VALVE SOLENOID COIL
C FAN MOTOR CAPACITOR T TRANSFORMER 21S4 4-WAY VALVE SOLENOID COIL
FC<O.B> FAN CONTROLLER TB1,3 TERMINAL BLOCK 26C THERMAL SWITCH
F<O.B> FUSE(6.3A) RT OUTDOOR COIL THERMISTOR 51C THERMAL RELAY
HC CRANKCASE HEATER X11<O.B> CRANKCASE HEATER RELAY 52C CONTACTOR
LD1-LD8 CHECK,SERVICE LED X12<O.B> COMPRESSOR RELAY 63H1 HIGH PRESSURE SWITCH
MC COMPRESSOR X13<O.B> SOLENOID COIL RELAY
1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
CN4
SW3 ✕14 ✕13 ✕12 ✕11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 ✕14 ✕13 ✕12 ✕11
MF2
CN4T 63H1 51C
MF1
4321
4
SV TRF 21S4 52C CH ZNR FR S T 5
RED
ORN
ORN
GRY
GRY
RED
RED
RED
RED
BRN
BRN
YLW
YLW
WHT
WHT
RED
BRN
BRN A1 96 WHT WHT
63H1 51C 26C 3
AC 21R 21 52C HC BLU BLU
RED S4 95 4
12.3V 220V RED RED MF
ORN A2 2
230V WHT C1 ORN
AC12.3V YLW WHT ORN 1
240V
POWER SUPPLY T
RED
3N~ WHT
380/220-415/240V 50Hz BLK
BLU
TB1
L1 RED L1/1 L1/1 T1/2 BLU U
L2 WHT L2/3 T2/4 WHT V
MC
L3 BLK L3/5 T3/6 BLU
N W
L3/5
52C 51C
GRN/YLW
Main functions of LED (when both Nos.1 and 2 of SW3 are “OFF”) How to use SW1 and 2
●Pressing SW1 erases the past check contents loaded on the
LED No. Output display (light) Check display (flash) microcomputer.
LD1 Compressor indoor command Auti-phase detect ●The output display (light) remains lit during operation but
LD2 Heating indoor command Missing-phase detect pressing SW2 displays the past check contents in flashing
LD3 63H1 ON Pipe sensor short/open mode. Pressing the switch again returns to output display
LD4 Compressor ON — (light).
LD5 Outdoor fan ON 51C functions Power line reconnection procedure
LD6 4-way valve ON 26C functions In case of reverse rotation
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input Unit side Outdoor unit
NOTE : If the operation stops to function of the protection device, the check display flashes. wiring L1 L2 L3 terminal
charge 2 out of 1.
2 and 3.
Field wiring (This example shows
reconnection of 1
CAUTIONS FOR POWER SUPPLY WIRING Change thie side and 2.)
1 2 3
●Making wiring connection in anti-phase or missing phase “L2” or “L3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor oper-
❈When power supply is 220V
ation. If phase “L1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power is
turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side) RED 220V WHITE
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
❈Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection ORANGE 230V
in the following procedure. YELLOW 240V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
13
PUH-4YKSA3
SYMBOL NAME SYMBOL NAME SYMBOL NAME
CN3<O.B> CONNECTING WIRES MF1,2 OUTDOOR FAN MOTOR (INNER THERMOSTAT) X14(O.B) SOLENOID COIL RELAY
INDOOR/OUTDOOR CONNECTOR O.B OUTDOOR CONTROLLER BOARD ZNR(O.B) SURGE ABSORBER
CN4T<O.B> TRANSFORMER CONNECTOR SW1·2·3(O.B) CHECK,SERVICE SWITCH 21R BYPASS VALVE SOLENOID COIL
C1,2 FAN MOTOR CAPACITOR T TRANSFORMER 21S4 4-WAY VALVE SOLENOID COIL
FC<O.B> FAN CONTROLLER TB1,3 TERMINAL BLOCK 26C THERMAL SWITCH
F<O.B> FUSE(6,3A) RT OUTDOOR COIL THERMISTOR 51C THERMAL RELAY
HC CRANKCASE HEATER X11(O.B) CRANKCASE HEATER RELAY 52C CONTACTOR
LD1-LD8 CHECK,SERVICE LED X12(O.B) COMPRESSOR RELAY 63H1 HIGH PRESSURE SWITCH
MC COMPRESSOR X13(O.B) SOLENOID COIL RELAY
1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
CN4
SW3 ✕14 ✕13 ✕12 ✕11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 ✕14 ✕13 ✕12 ✕11
MF2
CN4T 63H1 51C
MF1
4321
4
SV TRF 21S4 52C CH ZNR FR S T 5
RED
ORN
ORN
GRY
GRY
RED
RED
RED
RED
BRN
BRN
YLW
YLW
WHT
WHT
RED
BRN
BRN A1 96 WHT WHT
63H1 51C 26C 3
AC 21R 21 52C HC BLU BLU
RED S4 95 4
12.3V 220V RED RED MF1
ORN A2 2
230V WHT C1 ORN
AC12.3V YLW WHT ORN 1
240V WHT WHT
POWER SUPPLY T 3
RED BLU BLU
3N~ WHT 4
ORN ORN MF2
380/220-415/240V 50Hz 1
BLK C2 RED
BLU RED 2
TB1
L1 RED L1/1 T1/2 RED U
L2 WHT L2/3 T2/4 WHT V
MC
L3 BLK L3/5 T3/6 BLU
N W
52C 51C
GRN/YLW
Main functions of LED (when both Nos.1 and 2 of SW3 are “OFF”) How to use SW1 and 2
●Pressing SW1 erases the past check contents loaded on the
LED No. Output display (light) Check display (flash) microcomputer.
LD1 Compressor indoor command Auti-phase detect ●The output display (light) remains during operation but press-
LD2 Heating indoor command Missing-phase detect ing SW2 displays the past check contents in flashing mode.
LD3 63H1 ON Pipe sensor short/open Pressing the switch again returns to output display (light).
LD4 Compressor ON —
LD5 Outdoor fan ON 51C functions Power line reconnection procedure
LD6 4-way valve ON 26C functions In case of reverse rotation
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input Unit side Outdoor unit
NOTE : If the operation stops to function of the protection device, the check display flashes. wiring L1 L2 L3 terminal
charge 2 out of 1.
2 and 3.
Field wiring (This example shows
reconnection of 1
CAUTIONS FOR POWER SUPPLY WIRING Change thie side and 2.)
1 2 3
●Making wiring connection in anti-phase or missing phase “L2” or “L3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor oper-
❈When power supply is 220V
ation. If phase “L1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power is
turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side) RED 220V WHITE
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
❈Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection ORANGE 230V
in the following procedure. YELLOW 240V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
14
PUH-5YKSA3
SYMBOL NAME SYMBOL NAME SYMBOL NAME
MC COMPRESSOR T TRANSFORMER X12(O.B) COMPRESSOR RELAY
MF1,2 OUTDOOR FAN MOTOR (INNER THERMOSTAT) TB1,3 TERMINAL BLOCK X13(O.B) SOLENOID COIL RELAY
C1,2 FAN MOTOR CAPACITOR 63H1 HIGH PRESSURE SWITCH X14(O.B) SOLENOID COIL RELEY
RT OUTDOOR COIL THERMISTOR 26C DIS.CHARGE THERMAL SWITCH CN3(O.B) CONNECTOR(CONNECTING
HC CRANKCASE HEATER O.B OUTDOOR CONTROLLER BOARD WIRES INDOOR/OUTDOOR)
49C INTERNAL THERMOSTAT FOR MC ZNR(O.B) SURGE ABSORBER CN4T(O.B) TRANSFORMER CONNECTOR
52C CONTACTOR F(O.B) FUSE(6.3A) SW1,2,3(O.B) CHECK,SERVICE SELECT SWITCH
21S4 4-WAY VALVE SOLENOID COIL FC(O.B) FAN CONTROLLER LD1-LD8(O.B) CHECK,SERVICE LED
21R BYPASS VALVE SOLENOID COIL X11(O.B) CRANKCASE HEATER RELAY 51CM(O.B) JUMPER CONNECTOR
1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
CN4
SW3 ✕14 ✕13 ✕12 ✕11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 ✕14 ✕13 ✕12 ✕11
MF2
63H2
CN4T 63H1 MF1
4321 51CM
4
SV TRF 21S4 52C CH ZNR FR S T 5
RED
GRY
GRY
RED
RED
BRN
BRN
BLU
BLU
BLK
BLK
BLK
BLK
RED
BRN
BRN 13 A1 WHT WHT
63H1 26C 3
AC 52C 21R 21 52C HC BLU BLU
RED 14 S4 4
12.3V 220V RED RED MF1
2
RED
ORN A2
230V WHT C1 ORN ORN
YLW 1
AC12.3V WHT
240V WHT WHT
POWER SUPPLY T 3
RED BLU BLU
3N~ 4
ORN MF2
WHT
1 ORN
380/220-415/240V 50Hz BLK MC C2 RED RED
2
TB1 BLU
L1 RED L1/1 T1/2 RED T1 49C
L2 WHT L2/3 T2/4 WHT T2
L3 BLK L3/5 T3/6 BLU T3
N
52C
GRN/YLW
Main functions of LED (when both Nos.1 and 2 of SW3 are “OFF”) How to use SW1 and 2
●Pressing SW1 erases the past check contents loaded on the
LED No. Output display (light) Check display (flash) microcomputer.
LD1 Compressor indoor command Auti-phase detect ●The output display (light) remains lit during operation but
LD2 Heating indoor command Missing-phase detect pressing SW2 displays the past check contents in flashing
LD3 63H1 ON Pipe sensor short/open mode. Pressing the switch again returns to output display
LD4 Compressor ON 63H2 functions (light).
LD5 Outdoor fan ON 51C functions Power line reconnection procedure
LD6 4-way valve ON 26C functions In case of reverse rotation
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input Unit side Outdoor unit
NOTE : If the operation stops to function of the protection device, the check display flashes. wiring L1 L2 L3 terminal
1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
CN4
SW3 ✕14 ✕13 ✕12 ✕11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 ✕14 ✕13 ✕12 ✕11
MF2
63H2
CN4T 63H1 MF1
4321 51CM
4
SV TRF 21S4 52C CH ZNR FR S T 5
RED
GRY
GRY
RED
RED
BRN
BRN
BLK
BLK
BLK
BLK
BLK
BLK
RED
BRN BLK
BRN 13 A1 WHT WHT
7
21 63H1 26C 3
AC 52C 21R ✕15 S4 52C BLU BLU
RED 14 HC 4
12.3V 220V 8 RED RED MF1
2
RED
RED
ORN A2
230V 3 ✕15 5 BLK C1 ORN ORN
YLW 1
AC12.3V WHT
240V WHT WHT WHT
POWER SUPPLY T 3
RED BLU BLU
3N~ 4
ORN MF2
WHT
1 ORN
380/220-415/240V 50Hz BLK MC C2 RED RED
2
TB1 BLU
L1 RED L1/1 T1/2 RED T1 49C
L2 WHT L2/3 T2/4 WHT T2
L3 BLK L3/5 T3/6 BLU T3
N
52C
GRN/YLW
Main functions of LED (when both Nos.1 and 2 of SW3 are “OFF”) How to use SW1 and 2
●Pressing SW1 erases the past check contents loaded on the
LED No. Output display (light) Check display (flash) microcomputer.
LD1 Compressor indoor command Auti-phase detect ●The output display (light) remains lit during operation but
LD2 Heating indoor command Missing-phase detect pressing SW2 displays the past check contents in flashing
LD3 63H1 ON Pipe sensor short/open mode. Pressing the switch again returns to output display
LD4 Compressor ON 63H2 functions (light).
LD5 Outdoor fan ON 51C functions Power line reconnection procedure
LD6 4-way valve ON 26C functions In case of reverse rotation
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input Unit side Outdoor unit
NOTE : If the operation stops to function of the protection device, the check display flashes. wiring L1 L2 L3 terminal
1 YLW LED
TO INDOOR UNIT
CONNECTING WIRES 2 ORN RT
DC 12V (polar) 3 BRN
O.B
TB3
SW1 4 3 2 1
X14 X13 X12 X11 CN4
LD2
LD3
LD4
LD5
LD6
LD7
LD8
LD1
SW2 CN2
SW3
OFF 26C
ON F.C.
X14 X13 X12 X11
21
63H1
3 MF2
2 CN3 51CM
1
F MF1
CN4T
4 3 2 1 4
SV TRF 21S4 52C CH ZNR R S T 5
WHT
WHT
WHT
WHT
BRN
BRN
GRY
GRY
RED
RED
BLK
BLK
BLK
BLK
C1
POWER SUPPLY RED
WHT WHT
3
WHT BLU BLU
3~(3PHASES) MC RED
4
RED MF2
1
220V 60Hz TB1 C2 ORN
2
ORN
L1 49C
RED L1/1 T1/2 RED T1
L2 WHT L2/3 T2/4 WHT T2
L3 BLK L3/5 T3/6 BLK T3
GRN/YLW 52C
Main functions of LED (when both Nos.1 and 2 of SW3 are “OFF”) How to use SW1 and 2
●Pressing SW1 erases the past check contents loaded on the
LED No. Output display (light) Check display (flash) microcomputer.
LD1 Compressor indoor command Auti-phase detect ●The output display (light) remains lit during operation but
LD2 Heating indoor command Missing-phase detect pressing SW2 displays the past check contents in flashing
LD3 63H1 ON Pipe sensor short/open mode. Pressing the switch again returns to output display
LD4 Compressor ON – (light).
LD5 Outdoor fan ON 51C functions Power line reconnection procedure
LD6 4-way valve ON 26C functions In case of reverse rotation
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input Unit side Outdoor unit
NOTE : If the operation stops to function of the protection device, the check display flashes. wiring L1 L2 L3 terminal
17
6 REFRIGERANT SYSTEM DIAGRAM
PUH-1.6VKA2 /PUH-2VKA2 /PUH-2.5VKA2
PUH-3VKA2 /PUH-3YKA2
High pressure
control switch
Refrigerant pipe Oil separator
(option) Service Outdoor unit
Indoor unit 4-way valve
15.88A({5/8") Ball valve port Outdoor heat exchanger
(with heat insulator) Strainer
Flexible tube
Indoor Service Outdoor coil
heat port thermistor
exchanger (RT)
Strainer Flared Bypass
connection valve
Accumulator Restrictor Capillary
Indoor coil valve tube
Restrictor
thermistor valve Compressor PUH-1.6 (O.D.3.2✕I.D.1.8-R600)
(TH2) PUH-2 (O.D.4.0✕I.D.2.0-R430)
Distributor PUH-1.6 (O.D.4.0✕I.D.2.4-R1550)
Refrigerant pipe Ball valve Strainer
with PUH-3 (O.D.4.0✕I.D.2.4-R1070)
(option) (with service port)
strainer Capillary 9.52A({3/8")
tube (with heat insulator)
PUH-4YKSA3
High pressure
control switch Outdoor unit
Refrigerant pipe Oil separator
(option) Service Outdoor heat exchanger
4-way valve
Indoor unit 19.05A({3/4") Ball valve port
(with heat insulator) Strainer
PUH-5YKSA3
PUH-6YKSA2
Oil High pressure
Refrigerant pipe separator control switch
Outdoor unit
(option) Outdoor heat exchanger
4-way valve Service
Indoor unit 19.05A({3/4") Ball valve THERMAL
(with heat insulator) Strainer port SWITCH
18
PUH-5TKSA
PUH-6TKSA
19
7 DISASSEMBLY PROCEDURE
PUH-2.5VKA2 /PUH-3VKA2 /PUH-3YKA2
OPERATING PROCEDURE PHOTOS
Service panel
Panel cover
Front panel
Photo 2
Transformer Capacitor
Outdoor controller
board
Contactor
Overcurrent
relay
Valve bed
20
OPERATING PROCEDURE PHOTOS
Photo 6
Charge plug
Ball valve
Compressor
21
8 PARTS LIST
STRUCTURAL PARTS
PUH-1.6VKA
PUH-1.6VKA1
PUH-1.6VKA2
1 11 8 5 9
5
3
12 13 14 6 10
,
Q ty/set
PUH-1.6 Remarks Wining Recom- Price
No. Part No. Part Name Specification VKA
Diagram mended
,
(Drawing No.) Symbol Q ty
VKA1 Unit Amount
VKA2
1 R01 A00 641 TOP PANEL 1
2 — F.ST SCREW (5✕10) 13 (ZOO4M203H10)
3 R01 A00 668 FRONT PANEL 1
4 R01 A00 675 FAN GUARD 1
5 R01 A00 655 PANEL HANDLE 3
6 R01 A00 661 SERVICE PANEL 1
7 R01 A00 662 SIDE PANEL 1
8 — LABEL (MITSUBISHI) 1 (DG79R130H01)
9 R01 A00 682 REAR PANEL 1
10 R01 A00 658 PANEL COVER 1
11 R01 A00 698 REAR GUARD 1
12 — MOTOR SUPPORT 1 (BG00B020G55)
13 R01 A00 686 BASE 1
14 — LABEL (BRAND) 1 (BC79G510H01)
22
STRUCTURAL PARTS
PUH-2VKA
PUH-2VKA1
PUH-2VKA2
1 11 8 5 9
5
3
12 13 14 6 10
, Price
Q ty/set Wining Recom-
Remarks
No. Part No. Part Name Specification PUH-2 Diagram mended
,
(Drawing No.) Symbol Q ty Unit Amount
VKA,VKA1,VKA2
1 R01 A00 641 TOP PANEL 1
2 — F.ST SCREW (5✕10) 13 (ZOO4M203H10)
3 R01 A00 668 FRONT PANEL 1
4 R01 A00 675 FAN GUARD 1
5 R01 A00 655 PANEL HANDLE 3
6 R01 A00 661 SERVICE PANEL 1
7 R01 A00 662 SIDE PANEL 1
8 — LABEL (MITSUBISHI) 1 (DG79R130H01)
9 R01 A00 682 REAR PANEL 1
10 R01 A00 658 PANEL COVER 1
11 R01 A00 698 REAR GUARD 1
12 — MOTOR SUPPORT 1 (BG00B020G55)
13 R01 A04 686 BASE 1
14 — LABEL(BRAND) 1 (BC79G510H01)
23
STRUCTURAL PARTS
PUH-2.5VKA,PUH-2.5VKA1,PUH-2.5VKA2
PUH-3VKA,PUH-3VKA1,PUH-3VKA2
PUH-3YKA,PUH-3YKA1,PUH-3YKA2
2 1 11 8 5
9
3
14
4 13 12 6 10
,
Q ty/set
Price
PUH-2.5/3 PUH-3 Remarks Wining Recom-
No. Part No. Part Name Specification VKA1 Diagram mended
,
VKA VKA2 (Drawing No.) Symbol Q ty Unit Amount
YKA YKA1
YKA2
1 R01 A00 641 TOP PANEL 1 1
2 — F.ST SCREW (5✕10) 13 13 (ZOO4M203H10)
3 R01 A08 668 FRONT PANEL 1 1
4 R01 A00 675 FAN GUARD 1 1
5 R01 A00 655 PANEL HANDLE 1 1
6 R01 A08 661 SERVICE PANEL 3 3
7 R01 A08 662 SIDE PANEL 1 1
8 — LABEL (MITSUBISHI) 1 1 (DG79R130H01)
9 R01 A08 682 REAR PANEL 1 1
10 R01 A00 658 PANEL COVER 1 1
11 R01 A08 698 REAR GUARD 1 1
12 — MOTOR SUPPORT 1 1 (BG00B020G56)
R01 A04 686 BASE 1
13
R01 A10 686 BASE 1
14 — LABEL(BRAND) 1 1 (BC79G510H01)
24
STRUCTURAL PARTS
PUH-4YKSA,PUH-4YKSA1,PUH-4YKSA3
7 2 12 13 1 11 8 9
15
3
4
5
14 6 10
,
Q ty/set Price
PUH-4 Wining Recom-
Remarks
No. Part No. Part Name Specification Diagram mended
(Drawing No.) Symbol Q,ty
YKSA YKSA1 YKSA3 Unit Amount
25
STRUCTURAL PARTS
PUH-5YKSA,PUH-5YKSA1,PUH-5YKSA2,PUH-5YKSA3
PUH-6YKSA,PUH-6YKSA1,PUH-6YKSA2 13 12 1 11 8 9
3 2
4
15
10
14 5
,
Q ty/set Price
Wining Recom-
PUH-5 Remarks
No. Part No. Part Name Specification PUH-6 Diagram mended
,
(Drawing No.) Symbol Q ty
YKSA1
YKSA2
YKSA1
YKSA3
YKSA2
Unit Amount
YKSA
YKSA
4
15
10
14 5
,
Q ty/set Price
Wining Recom-
Remarks
No. Part No. Part Name Specification PUH-5 PUH-6 Diagram mended
,
(Drawing No.) Symbol Q ty Unit Amount
TKSA TKSA
27
FUNCTIONAL PARTS
PUH-1.6VKA
PUH-1.6VKA1
PUH-1.6VKA2
4 3 9 8 7 10 14
17
27
15
11
16
19
18
5 22
2 6 13 20
28 19
1
26
12
21
22
24
23
25
28
Part numbers that are circled are not shown in the figure.
,
Q ty/set
Price
PUH-1.6 Wining Recom-
No. Part No. Part Name Specification Remarks Diagram mended
,
Symbol Q ty Unit Amount
VKA VKA1 VKA2
29
FUNCTIONAL PARTS
PUH-2VKA
PUH-2VKA1
PUH-2VKA2
3 9 8 7 28 10 13 12
27 16
1
14
15
17
18
2 19
20
(M8) 26
25
21
6 5 11 23 24 22
30
,
Q ty/set
Price
PUH-2 Wining Recom-
No. Part No. Part Name Specification Remarks Diagram mended
,
VKA1 Symbol Q ty Unit Amount
VKA VKA2
31
FUNCTIONAL PARTS
PUH-2.5VKA
PUH-2.5VKA1
PUH-2.5VKA2
4 3 28 8 7 9 22 11 15
29
16
17
2 13
12
14
10
18
21
6 27 5 19 25 26 24 23 20
32
Part numbers that are circled are not shown in the figure.
, Price
Q ty/set
Wining Recom-
No. Part No. Part Name Specification PUH-2.5 Remarks Diagram mended
,
VKA1 Symbol Q ty
Unit Amount
VKA VKA2
33
FUNCTIONAL PARTS
PUH-3VKA / PUH-3YKA
PUH-3VKA1 / PUH-3YKA1
PUH-3VKA2 / PUH-3YKA2
5 3 28 4 7 8 9 22 11 16 15
6
29
12
17
13
2 PUH-3YKA
PUH-3YKA1
PUH-3YKA2
10
14
3 4 7 8 9
21
18
30
27 19 25 26 24 23 20
6 5
,
Q ty/set Price
PUH-3 Wining Recom-
No. Part No. Part Name Specification Remarks Diagram mended
,
VKA1
VKA2
YKA1
YKA2
YKA
Symbol Q ty
VKA
Unit Amount
PA6V85-UF(VKA,YKA)
1 T7W 271 763 OUTDOOR FAN MOTOR PA6V85-UH(VKA1,YKA1) 1 1 1 1 1 MF
2 R01 A00 115 PROPELLER FAN 1 1 1 1 1
T7W 251 315 OUTDOOR CONTROLLER BOARD 1 O.B
T7W A01 315 OUTDOOR CONTROLLER BOARD 1 O.B
3 T7W 256 315 OUTDOOR CONTROLLER BOARD 1 O.B
T7W A03 315 OUTDOOR CONTROLLER BOARD 1 1 O.B
4 T7W 520 239 FUSE 250V 6.3A 1 1 1 1 1 F(O.B)
T7W 509 716 TERMINAL BLOCK 3P(L,N,;) 1 1 TB1
5
T7W 511 716 TERMINAL BLOCK 5P(L1,L2,L3,N,;) 1 1 1 TB1
6 T7W 516 716 TERMINAL BLOCK 3P(1,2,3) 1 1 1 1 1 TB3
34
Part numbers that are circled are not shown in the figure.
,
Q ty/set Price
PUH-3 Wining Recom-
No. Part No. Part Name Specification Remarks Diagram mended
,
VKA1
VKA2
YKA1
YKA2
YKA
Symbol Q ty
VKA
Unit Amount
35
FUNCTIONAL PARTS
PUH-4YKSA
PUH-4YKSA1
PUH-4YKSA3
6 5 3 4 79 8
27
21
22
(M8) 19
12
13
2 14
15
16
(M8) 19
27 18
20
1 25 11 17 10 26 23 24
36
Part numbers that are circled are not shown in the figure.
,
Q ty/set
Price
PUH-4
Wining Recom-
No. Part No. Part Name Specification Remarks Diagram mended
,
YKSA YKSA1 YKSA3 Symbol Q ty Unit Amount
37
FUNCTIONAL PARTS 1 6 5 3 4 7 8 9 19
PUH-5YKSA
PUH-5YKSA1 18
PUH-5YKSA3
PUH-6YKSA
PUH-6YKSA1
PUH-6YKSA2
27
17
1
13
12
14
27 15
16
18
11
2 10
20
21
26 24 23 25 22
Part numbers that are circled are not shown in the figure.
,
Q ty/set Price
PUH-5 PUH-6 Wining Recom-
No. Part No. Part Name Specification Remarks Diagram mended
,
YKSA1
YKSA3
YKSA1
YKSA2
YKSA
YKSA
Symbol Q ty
Unit Amount
YKSA3
YKSA1
YKSA1
YKSA2
YKSA
YKSA
Symbol Q ty Unit Amount
39
FUNCTIONAL PARTS 1 6 5 3 4 7 8 9 19
PUH-5TKSA
PUH-6TKSA 18
27
17
1
13
12
14
27 15
16
18
11
2 10
20
21
Part numbers that are circled are not shown in the figure. 26 24 23 25 22
,
Q ty/set Price
Wining Recom-
PUH-5 PUH-6 Remarks Diagram mended
No. Part No. Part Name Specification ,
Symbol Q ty
TKSA TKSA
Unit Amount
40
Part numbers that are circled are not shown in the figure.
,
Q ty/set Wining Recom- Price
No. Part No. Part Name Specification PUH-5 PUH-6 Remarks Diagram mended
,
Symbol Q ty Unit Amount
TKSA TKSA
7 T7W E00 799 TRANSFORMER 1 1 T
8 R01 653 255 FAN MOTOR CAPACITOR 4+ 440V 2 2 C1,2
9 T7W A15 708 CONTACTOR S-N25EX 1 1 52C
10 R01 A14 428 SOLENOID VALVE 1
11 T7W 106 242 SOLENOID COIL 1 1 21R
T7W E00 425 CAPILLARY TUBE {4.0✕{2.4✕840mm 2
12
R01 62L 425 CAPILLARY TUBE {4.0✕{2.4✕840mm 2
13 R01 993 418 RESTRICTOR VALVE 2 2
14 R01 42L 450 STRAINER 1 1
R01 V29 403 4-WAY VALVE 1
15
T7W 258 403 4-WAY VALVE 1
T7W 258 242 4-WAY COIL 1 21S4
16
T7W A01 242 SOLENOID COIL 1 21S4
17 R01 KN7 202 OUTDOOR COIL THERMISTOR 1 1 RT
R01 943 413 CHARGE PLUG 1 1
18
T7W A02 413 CHARGE PLUG 1 1
19 R01 A14 440 ACCUMULATOR 1 1
20 R01 A14 490 OIL SEPARATOR 1 1
21 R01 670 411 BALL VALVE 3/4˝ 1 1
22 R01 943 410 BALL VALVE 3/8˝ 1 1
T97 512 500 COMPRESSOR ZR61KCTF5 1 MC
23
T97 521 501 COMPRESSOR ZR68KCTF5 1 MC
24 R01 86H 201 THERMOSTAT CUT125˚C IN90˚C 1 1 26C
25 T7W E00 236 CRANKCASE HEATER 220V 38W 1 1 HC
26 R01 A00 208 HIGH PRESSURE SWITCH 2
OFF25.5kg/cm ON21kg/cm2
1 1 63H1
T7W 555 408 HEAT EXCHANGER 2
27
T7W 556 408 HEAT EXCHANGER 2
28 T7W A10 425 CAPILLARY TUBE {4.0✕{3.0✕2.0mm 1 1
29 T7W A00 401 DIS.PRES.REGULATOR 1 1
41
9 OPTIONAL PARTS