SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 1997

No.OC128
REVISED EDITION-A

TECHNICAL & SERVICE MANUAL


Outdoor unit
[model names] [Service Ref.]
PUH-1.6VKA PUH-1.6VKA2
PUH-2VKA PUH-2VKA2
PUH-2.5VKA PUH-2.5VKA2
PUH-3VKA PUH-3VKA2
PUH-3YKA PUH-3YKA2
PUH-4YKSA PUH-4YKSA3
PUH-5YKSA PUH-5YKSA3
PUH-6YKSA PUH-6YKSA2
PUH-5TKSA PUH-5TKSA
PUH-6TKSA PUH-6TKSA

CONTENTS
1. COMBINATION OF INDOOR AND OUTDOOR UNITS ·····3
2. PART NAMES AND FUNCTIONS·····················4
3. DATA··································································5
4. OUTLINES AND DIMENSIONS ························6
5. WIRING DIAGRAM ·········································10
6. REFRIGERANT SYSTEM DIAGRAM················18
7. DISASSEMBLY PROCEDURE ·······················20
8. PARTS LIST ····················································22
9. OPTIONAL PARTS ··························Back cover
OUTDOOR UNIT
PUH-3K

Revision
• PUH-5TKSA, 6TKSA are added.
• Please destroy OC128. The Slim Line.
From Mitsubishi Electric.
1 COMBINATION OF INDOOR AND OUTDOOR UNITS
Indoor unit Outdoor unit
Service 1.6 2 2.5 3 4 5 6 5 6
Service Ref.
Manual No. VKA2 VKA2 VKA2 VKA2 YKA2 YKSA3 YKSA3 YKSA3 TKSA TKSA
PLH-GKH(S)B1 OC139 — — —
PLH-KKHC OC123 — — — — — — —
PCH-GKH(S)A1 OC135 —
PEH-EKH(S)A2.TH OC153 — — — —
PKH-FKH(S)A3 OC130 — — — —
PSH-GJH(S)(1) OC144 — — —

3
2 PART NAMES AND FUNCTIONS
123456789
Air outlet Air outlet
(Expels warm air during cooling)

Air intake
Air intake

PUH-2.5VKA2
PUH-1.6VKA2 PUH-3YKA2
PUH-2VKA2 PUH-3VKA2

Air outlet
Air outlet
Air intake

Air intake

PUH-5YKSA3
PUH-4YKSA3
PUH-6YKSA2
PUH-5TKSA
PUH-6TKSA

CHARGELESS SYSTEM
PRE-CHARGED REFRIGERANT IS SUPPLIED FOR MAXIMUM PIPING LENGTH AT SHIPMENT.
The unique refrigerant circuit and a large accumulator always control the optimal refrigerant level regardless of the length
(30m max. and 5m min.) of piping. The additional refrigerant charging work during installation often causes problems.
Heretofore it is completely eliminated. This unique system improves the quality and reliability of the work done. It also helps
to speed up the installation time.

4
3 DATA
1. REFILLING REFRIGERANT CHARGE (R-22 : kg)
Refrigerant piping length (one way)
Service Ref.
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
PUH-1.6VKA2 1.5 1.7 1.8 1.9 2.1 2.2 2.3 2.4 — —
PUH-2VKA2 1.5 1.7 1.8 1.9 2.1 2.2 2.3 2.4 — —
PUH-2.5VKA2 2.1 2.3 2.4 2.5 2.7 2.8 2.9 3.0 3.1 3.3
PUH-3VKA2 2.5 2.7 2.8 2.9 3.1 3.2 3.3 3.4 3.6 3.7
PUH-3YKA2 2.5 2.7 2.8 2.9 3.1 3.2 3.3 3.4 3.6 3.7
PUH-4YKSA3 3.5 3.6 3.8 3.9 4.1 4.2 4.4 4.5 4.6 4.8
PUH-5YKSA3 4.7 4.8 5.0 5.1 5.3 5.4 5.6 5.7 5.9 6.0
PUH-6YKSA2 4.3 4.4 4.6 4.7 4.9 5.0 5.2 5.3 5.5 5.6
PUH-5TKSA 4.7 4.8 5.0 5.1 5.3 5.4 5.6 5.7 5.9 6.0
PUH-6TKSA 4.3 4.4 4.6 4.7 4.9 5.0 5.2 5.3 5.5 5.6

2. COMPRESSOR TECHNICAL DATA at 20˚C

Compressor Model RH247VFC NH38VMD NH41VMD NH52VND NH52YDA NH56YDA


U-V 2.00 1.05 1.03 0.83 3.60 3.50
Winding (R-C)
U-W
Resistance (S-C) 4.55 2.23 2.22 2.03 3.60 3.50
(Ω )
W-V — — — — 3.60 3.50

at 25˚C
Compressor Model ZR61K3TFD ZR68KCTFD ZR61KCTF5 ZR68KCTF5

T1-T2 2.53-2.91 2.31 0.63-0.72 0.48-0.55


Winding
Resistance T2-T3 2.53-2.91 2.31 0.63-0.72 0.48-0.55
(Ω )
T3-T1 2.53-2.91 2.31 0.63-0.72 0.48-0.55

5
6
Outdoor Unit-Necessary surrounding clearance
4

200
Outdoor Unit-Necessary surrounding clearance 185 185
(Concentrated installation) The upper side must be open. (7-9/32) 500(19-11/16) (7-9/32) Note:Allow adequate
upper clearance

17
Air intake 10 10
Front opening

Air intake

330(13)
150

200
39.5 27.5
362(14-1/4)
500
100 10
PUH-1.6VKA2/PUH-2VKA2

10
Air outlet Service space

15
For 10 units or less 1000
500

Terminal block for indoor and outdoor unit connection

Terminal block for power line

Handle
870(34-1/4) Ground terminal
for moving
7 295(11-5/8) 24(1) 302
Outlet guide Handle for moving
installation hole
Rear fresh Service panel
air intake
Handle for moving Refrigerant-pipe flared
Side air intake connection

524
[15.88 3/8F
650 (25-5/8)
444

Refrigerant-pipe flared
OUTLINES AND DIMENSIONS

45

339
282
connection
297

[9.52 3/8F

138
77
53

Knock out hole

23
33
95 40 524 60 60
Rear piping hole for front piping Knock out holes for
(refrigerant,drainage 120 power line 2-[27
and wiring)
2-12✕23 Oval holes 104
(standard bolt M10) Knock out hole
42
45

33 for right piping


(refrigerant,drainage
0

Drain hole
and wiring)
R2

R2
0
Bottom
piping hole
80
25 max.

2-U-shaped R6
Drain hole notched Standard bolt length
holes 65
17

Front right piping holes-


12
detail figures
Unit : mm (inch)
Outdoor Unit-Necessary surrounding clearance

200
185 185
PUH-2.5VKA2

(7-9/32) 500(19-11/16) (7-9/32)


Outdoor Unit-Necessary surrounding clearance

17
(Concentrated installation) Air intake Note:Allow adequate
The upper side must be open.
10 10 upper clearance
Front opening

Air intake

330(13)
39.5 27.5
PUH-3VKA2/PUH-3YKA2

362(14-1/4)
150

200
500
100 10 Air outlet

15
10
Service space
For 10 units or less 1000 500

Terminal block for indoor and outdoor unit connection


870(34-1/4)
7 295(11-5/8) 24(1) 302 Terminal block for power line
Handle
Outlet guide Ground
for moving
installation hole terminal
Side air intake
Handle for moving
Rear fresh Service panel
air intake Handle for moving

524
553

Refrigerant-pipe flared
850(33-7/16)

connection [15.88 5/8F


403

441
337
45

Refrigerant-pipe flared
352

connection [9.52 3/8F

179

138
53

Knock out hole

23
33
95 40 524 60 60
Rear piping hole for front piping Knock out holes for
(refrigerant,drainage 120 power line 2-[27
and wiring)
2-12✕23 Oval holes 104
(standard bolt M10) Knock out hole
42
45

33 for right piping


(refrigerant,drainage
0

Drain hole
and wiring)
R2

R2
0
Bottom
piping hole
80
25 max.

2-U-shaped R6
Drain hole notched Standard bolt length
holes 65
17

Front right piping holes-


12
detail figures

7
Unit : mm (inch)
8
Outdoor Unit-Necessary surrounding clearance Outdoor Unit-Necessary surrounding clearance
(Concentrated installation)

300
The upper side must be open.
PUH-4YKSA3
185 185 Note:Allow adequate
(7-9/32) 500(19-11/16) (7-9/32)
10 10 upper clearance

17
Air intake
Front opening

300
150 10
Air intake 100

330(13)
39.5 27.5
500
For 10 units or less 1000

362(14-1/4)
Terminal block for 10
indoor and outdoor
Air outlet unit connection Service space
500

15
870(34-1/4)
7 295(11-5/8) 24(1) Terminal block for power line
302
Outlet guide
installation hole

Service panel
Side air intake

Ground
Handle

524
terminal
for moving
Handle
for moving

585
61
Rear fresh
air intake Handle for moving
1258(49-1/2)
959

Refrigerant-pipe flared

524
connection [19.05 3/4F

345
382
45

Refrigerant-pipe flared
403

connection [9.52 3/8F

138
83
53

Knock out hole

23
33
95 40 524 60 60
Rear piping hole for front piping Knock out holes for
(refrigerant,drainage 120 power line 2-[27
2-12✕23 Oval holes 104
(standard bolt M10) and wiring)
52
57

39
Knock out hole
for right piping
0

Drain hole
R2

R2
(refrigerant, 0
Bottom
drainage and wiring)
piping hole
80
25 max.

2-U-shaped R6
Drain hole notched Standard bolt length
holes 65
17

12 Front right piping holes-


detail figures
Unit : mm (inch)
Outdoor Unit-Necessary surrounding clearance Outdoor Unit-Necessary surrounding clearance
(Concentrated installation)

300
The upper side must be open.
185 185 Note:Allow adequate
(7-9/32) 600(23-5/8) (7-9/32)
10 10 upper clearance

17
Air intake
Front opening

300
150 10
150

Air intake
PUH-5TKSA/PUH-6TKSA

39.5 27.5
500

For 10 units or less 1000

412(16-1/4)
380(14-31/32)
PUH-5YKSA3 /PUH-6YKSA2

Terminal block for 10


indoor and outdoor
Air outlet unit connection Service space
500

15
970(38-3/16)
7 345(13-9/16) 24(1) Terminal block for power line
352
Outlet guide
installation hole

Service panel
Side air intake

Ground
Handle

524
terminal
for moving
Handle
for moving

585
61
Rear fresh
air intake Handle for moving
1258(49-1/2)
959

Refrigerant-pipe flared

524
connection [19.05 3/4F

345
382
45

Refrigerant-pipe flared
403

connection [9.52 3/8F

138
83
53

Knock out hole

23
33
95 90 524 60 60
Rear piping hole for front piping Knock out holes for
(refrigerant,drainage 120 power line 2-[27
2-12✕23 Oval holes 104
(standard bolt M10) and wiring)
52
57

39
Knock out hole
for right piping
0

Drain hole
R2

R2
(refrigerant, 0
Bottom
drainage and wiring)
piping hole
80
25 max.

2-U-shaped R6
Drain hole notched Standard bolt length
holes 65
17

12 Front right piping holes-


detail figures

9
Unit : mm (inch)
5 WIRING DIAGRAM
PUH-1.6VKA2
SYMBOL NAME SYMBOL NAME SYMBOL NAME
HC CRANKCASE HEATER MC COMPRESSOR (INNER THERMOSTAT) X12<O.B> COMPRESSOR RELAY
C1 OUTDOOR FAN CAPACITOR MF OUTDOOR FAN MOTOR (INNER THERMOSTAT) X13<O.B> 21S4 RELAY
C2 COMPRESSOR CAPACITOR O.B OUTDOOR CONTROLLER BOARD X14<O.B> 21R RELAY
FC<O.B> FAN CONTROLLER SW1·2·3<O.B> CHECK,SERVICE SELECTOR ZNR<O.B> VARISTER
F<O.B> FUSE(6A) T TRANSFORMER 52C CONTACTOR
21S4 R.V.COIL TB1,3 TERMINAL BLOCK 63H1 HIGH PRESSURE SWITCH
OUTDOOR COIL THERMISTOR
21R B.V.COIL RT (0˚C/15kΩ,25˚C/5.4kΩ )

LD1~LD8 CHECK,SERVICE LED X11<O.B> HC RELAY

LED
1 YLW
FROOM INDOOR UNIT RT
2 ORN
CONNECTING WIRES
12V DC (polar) 3 BRN
O.B
TB3
SW1 4 3 2 1
CN2 ✕14 ✕13 ✕12 ✕11 FC
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8

SW2 CN4
S
SW2
OFF 26C
63H1
2 1 ON ✕14 ✕13 ✕12 ✕11 MF2
3
2 CN3 63H2
MF1
1
CN4T F 51CM
4 3 2 1 4
SV TRF 21S4 52C CH ZNR R/1 S/2 T/3
WHT
WHT

WHT
WHT

WHT
RED
RED

RED
RED

GRY
GRY

BLU
BRN
BRN
YLW
YLW
YLW
YLW

BLU
S BLU BLU
GRY

A 63H1
GRY

21R 21 52C HC BLU 4


RED
BRN 12.3V AC S4 WHT
220V
ORN B MF RED 3 RED
RED 12.3V AC YLW 230V ORN 2 C1
1 ORN
T 240V
RED
BLK
TB1 52C
L RED R U BLU R
POWER SUPPLY
N BLK WHT C
~/N(1phase) MC
T W BLU RED
220-240V 50Hz S
GRY/YLW C2

Main functions of LED (when both Nos. 1 and 2 of SW3 are ”OFF”)

LED No. Output display (light) Check display (flash)


LD1 Compressor ON command from indoor —
LD2 Heating indoor command —
LD3 63H1 ON RT short/open
LD4 Compressor ON —
LD5 Outdoor fan ON —
LD6 4-way valve ON 26C functions
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input
NOTE : If the operation stops and the protection device is functioning, the check display will flash. fig. 2 ❈When power supply is 220V
How to use SW1 and 2
●Pressing SW1 erases the past check contents loaded on the microcomputer.
RED 220V WHITE
●The output display (light) remains lit during operation, but pressing SW2 displays the past check contents by a flashing mode. ORANGE 230V
Pressing the switch again returns it to output display (light).
CAUTION FOR SERVICING YELLOW 240V
fig. 1 White connector
●The connector marked s turns the compressor ON and OFF during servicing.
The compressor stops when the white connector is disconnected. See fig.1.
CAUTIONS FOR POWER SUPPLY WIRING
●Since LD8 lights when normal power is turned ”ON”, check the power supply with the ON or OFF LD8.
❈Since the indoor transformer (T) is connected with 240V power, using 220V or 230V power will require a wiring connection change. See fig.2.
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●Since the indoor and outdoor connecting wires have polarity, be sure to connect the same terminal numbers (1,2,3) for the indoor and outdoor units.
10
PUH-2VKA2/PUH-2.5VKA2
SYMBOL NAME SYMBOL NAME SYMBOL NAME
CN3(O.B) CONNECTING WIRES MC COMPRESSOR (INNER THERMOSTAT) X12(O.B) MC RELAY
INDOOR/OUTDOOR CONNECTOR MF OUTDOOR FAN MOTOR (INNER THERMOSTAT) X13(O.B) 21S4 RELAY
CN4T(O.B) TRANSFORMER CONNECTOR O.B OUTDOOR CONTROLLER BOARD X14(O.B) 21R RELAY
HC CRANKCASE HEATER 21R BYPASS VALVE SOLENOID COIL ZNR(O.B) SURGE ABSORBER
C1 OUTDOOR FAN CAPACITOR SW1·2·3(O.B) CHECK,SERVICE SELECT SWITCH 21S4 4-WAY VALVE SOLENOID COIL
C2 COMPRESSOR CAPACITOR T TRANSFORMER 52C CONTACTOR
FC(O.B) FAN CONTROLLER TB1,3 TERMINAL BLOCK 63H1 HIGH PRESSURE SWITCH
F(O.B) FUSE(6,3A) RT OUTDOOR COIL THERMISTOR
LD1-LD8 CHECK,SERVICE LED X11(O.B) HC RELAY

1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8

CN4
SW3 ✕14 ✕13 ✕12 ✕11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 ✕14 ✕13 ✕12 ✕11
MF2
CN4T 63H1 51CM
MF1
4321
4
SV TRF 21S4 52C CH ZNR FR S T S
RED
GRY
GRY
RED
RED

RED
RED

BRN
BRN
YLW
YLW
YLW
YLW
WHT
WHT

BLU

BLU

WHT
RED
BRN BLUBLU
BRN A1 WHT
63H1 3
AC 21R 21 52C HC BLU
RED S4 4
12.3V 220V RED RED MF
ORN A2 2
230V WHT C1 ORN
AC12.3V YLW WHT ORN 1
T 240V
RED
POWER SUPPLY
~/N BLU
220-240V 50Hz
TB1
L RED L1/1 T1/2 BLU R
N BLU WHT C
MC
L3/5 BLU RED
52C T3/6 S
C2
GRN/YLW

CAUTIONS FOR POWER SUPPLY WIRING ❈When power supply is 220V

●Since LD8 lights when normal power is turned “ON”, check the power supply with the ON or OFF LD8. RED 220V WHITE
❈Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the ORANGE 230V
wiring connection in the following procedure
YELLOW 240V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
Main functions of LED
(when both Nos.1 and 2 of SW3 are “OFF”)
LED No. Output display (light) Check display (flash)
LD1 Compressor indoor command —
LD2 Heating indoor command —
LD3 63H1 ON Outdoor coil thermistor short/open
LD4 Compressor ON —
LD5 Outdoor fan ON —
LD6 4-way valve ON 26C functions
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input
NOTE :
If the operation stops to function of the protection device, the check
display flashes.

How to use SW1 and 2


●Pressing SW1 erases the past check contents loaded on the microcomputer.
●The output display (light) remains during operation but pressing SW2 displays the
past check contents in flushing mode.
Pressing the switch again returns to output display (light).
11
PUH-3VKA2
SYMBOL NAME SYMBOL NAME SYMBOL NAME
CN3(O.B) CONNECTING WIRES MC COMPRESSOR (INNER THERMOSTAT) X12(O.B) MC RELAY
INDOOR/OUTDOOR CONNECTOR MF OUTDOOR FAN MOTOR (INNER THERMOSTAT) X13(O.B) 21S4 RELAY
CN4T(O.B) TRANSFORMER CONNECTOR O.B OUTDOOR CONTROLLER BOARD X14(O.B) 21R RELAY
HC CRANKCASE HEATER 21R BYPASS VALVE SOLENOID COIL ZNR(O.B) SURGE ABSORBER
C1 OUTDOOR FAN CAPACITOR SW1·2·3(O.B) CHECK,SERVICE SELECT SWITCH 21S4 4-WAY VALVE SOLENOID COIL
C2 COMPRESSOR CAPACITOR T TRANSFORMER 52C CONTACTOR
FC(O.B) FAN CONTROLLER TB1,3 TERMINAL BLOCK 63H1 HIGH PRESSURE SWITCH
F(O.B) FUSE(6,3A) RT OUTDOOR COIL THERMISTOR
LD1-LD8 CHECK,SERVICE LED X11(O.B) HC RELAY

1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8

CN4
SW3 ✕14 ✕13 ✕12 ✕11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 ✕14 ✕13 ✕12 ✕11
MF2
CN4T 63H1 51CM
MF1
4321
4
SV TRF 21S4 52C CH ZNR FR S T S
RED
GRY
GRY
RED
RED

RED
RED

BRN
BRN
YLW
YLW
YLW
YLW
WHT
WHT

BLU

BLU

WHT
RED
BRN BLUBLU
BRN A1 WHT
63H1 3
AC 21R 21 52C HC BLU
RED S4 4
12.3V 220V RED RED MF
ORN A2 2
230V WHT C1 ORN
AC12.3V YLW WHT ORN 1
T 240V
RED
POWER SUPPLY
~/N BLU
220-240V 50Hz
TB1
L RED L1/1 T1/2 BLU R
N BLU WHT C
MC
L3/5 BLU RED
52C T3/6 S
C2
GRN/YLW

Main functions of LED (when both Nos.1 and 2 of SW3 are ”OFF”) How to use SW1 and 2
●Pressing SW1 erases the past check contents loaded on the
LED No. Output display (light) Check display (flash) microcomputer.
LD1 Compressor indoor command — ●The output display (light) remains lit during operation but
LD2 Heating indoor command — pressing SW2 displays the past check contents in flashing
LD3 63H1 ON Outdoor coil thermistor short/open mode. Pressing the switch again returns to output display
LD4 Compressor ON — (light).
LD5 Outdoor fan ON —
LD6 4-way valve ON —
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input
NOTE : If the operation stops to function of the protection device, the check display flashes.

CAUTIONS FOR POWER SUPPLY WIRING ❈When power supply is 220V

●SinceLD8 lights when normal power is furned ”ON”, check the power supply with the ON or OFF LD8. RED 220V WHITE
❈Sincethe transformer (T) is connected with 240V power, if 220V or 230V power is used, ORANGE 230V
change the wiring connection in the following procedure.
YELLOW 240V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
12
PUH-3YKA2
SYMBOL NAME SYMBOL NAME SYMBOL NAME
CN3<O.B> CONNECTING WIRES MF OUTDOOR FAN MOTOR (INNER THERMOSTAT) X14<O.B> SOLENOID COIL RELAY
INDOOR/OUTDOOR CONNECTOR O.B OUTDOOR CONTROLLER BOARD ZNR<O.B> SURGE ABSORBER
CN4T<O.B> TRANSFORMER CONNECTOR SW1·2·3<O.B> CHECK,SERVICE SELECT SWITCH 21R BYPASS VALVE SOLENOID COIL
C FAN MOTOR CAPACITOR T TRANSFORMER 21S4 4-WAY VALVE SOLENOID COIL
FC<O.B> FAN CONTROLLER TB1,3 TERMINAL BLOCK 26C THERMAL SWITCH
F<O.B> FUSE(6.3A) RT OUTDOOR COIL THERMISTOR 51C THERMAL RELAY
HC CRANKCASE HEATER X11<O.B> CRANKCASE HEATER RELAY 52C CONTACTOR
LD1-LD8 CHECK,SERVICE LED X12<O.B> COMPRESSOR RELAY 63H1 HIGH PRESSURE SWITCH
MC COMPRESSOR X13<O.B> SOLENOID COIL RELAY

1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8

CN4
SW3 ✕14 ✕13 ✕12 ✕11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 ✕14 ✕13 ✕12 ✕11
MF2
CN4T 63H1 51C
MF1
4321
4
SV TRF 21S4 52C CH ZNR FR S T 5
RED

ORN
ORN
GRY
GRY
RED
RED

RED
RED

BRN
BRN

YLW
YLW
WHT
WHT

RED
BRN
BRN A1 96 WHT WHT
63H1 51C 26C 3
AC 21R 21 52C HC BLU BLU
RED S4 95 4
12.3V 220V RED RED MF
ORN A2 2
230V WHT C1 ORN
AC12.3V YLW WHT ORN 1
240V
POWER SUPPLY T
RED
3N~ WHT
380/220-415/240V 50Hz BLK
BLU
TB1
L1 RED L1/1 L1/1 T1/2 BLU U
L2 WHT L2/3 T2/4 WHT V
MC
L3 BLK L3/5 T3/6 BLU
N W
L3/5
52C 51C
GRN/YLW

Main functions of LED (when both Nos.1 and 2 of SW3 are “OFF”) How to use SW1 and 2
●Pressing SW1 erases the past check contents loaded on the
LED No. Output display (light) Check display (flash) microcomputer.
LD1 Compressor indoor command Auti-phase detect ●The output display (light) remains lit during operation but
LD2 Heating indoor command Missing-phase detect pressing SW2 displays the past check contents in flashing
LD3 63H1 ON Pipe sensor short/open mode. Pressing the switch again returns to output display
LD4 Compressor ON — (light).
LD5 Outdoor fan ON 51C functions Power line reconnection procedure
LD6 4-way valve ON 26C functions In case of reverse rotation
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input Unit side Outdoor unit
NOTE : If the operation stops to function of the protection device, the check display flashes. wiring L1 L2 L3 terminal

charge 2 out of 1.
2 and 3.
Field wiring (This example shows
reconnection of 1
CAUTIONS FOR POWER SUPPLY WIRING Change thie side and 2.)
1 2 3
●Making wiring connection in anti-phase or missing phase “L2” or “L3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor oper-
❈When power supply is 220V
ation. If phase “L1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power is
turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side) RED 220V WHITE
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
❈Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection ORANGE 230V
in the following procedure. YELLOW 240V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
13
PUH-4YKSA3
SYMBOL NAME SYMBOL NAME SYMBOL NAME
CN3<O.B> CONNECTING WIRES MF1,2 OUTDOOR FAN MOTOR (INNER THERMOSTAT) X14(O.B) SOLENOID COIL RELAY
INDOOR/OUTDOOR CONNECTOR O.B OUTDOOR CONTROLLER BOARD ZNR(O.B) SURGE ABSORBER
CN4T<O.B> TRANSFORMER CONNECTOR SW1·2·3(O.B) CHECK,SERVICE SWITCH 21R BYPASS VALVE SOLENOID COIL
C1,2 FAN MOTOR CAPACITOR T TRANSFORMER 21S4 4-WAY VALVE SOLENOID COIL
FC<O.B> FAN CONTROLLER TB1,3 TERMINAL BLOCK 26C THERMAL SWITCH
F<O.B> FUSE(6,3A) RT OUTDOOR COIL THERMISTOR 51C THERMAL RELAY
HC CRANKCASE HEATER X11(O.B) CRANKCASE HEATER RELAY 52C CONTACTOR
LD1-LD8 CHECK,SERVICE LED X12(O.B) COMPRESSOR RELAY 63H1 HIGH PRESSURE SWITCH
MC COMPRESSOR X13(O.B) SOLENOID COIL RELAY

1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8

CN4
SW3 ✕14 ✕13 ✕12 ✕11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 ✕14 ✕13 ✕12 ✕11
MF2
CN4T 63H1 51C
MF1
4321
4
SV TRF 21S4 52C CH ZNR FR S T 5
RED

ORN
ORN
GRY
GRY
RED
RED

RED
RED

BRN
BRN

YLW
YLW
WHT
WHT

RED
BRN
BRN A1 96 WHT WHT
63H1 51C 26C 3
AC 21R 21 52C HC BLU BLU
RED S4 95 4
12.3V 220V RED RED MF1
ORN A2 2
230V WHT C1 ORN
AC12.3V YLW WHT ORN 1
240V WHT WHT
POWER SUPPLY T 3
RED BLU BLU
3N~ WHT 4
ORN ORN MF2
380/220-415/240V 50Hz 1
BLK C2 RED
BLU RED 2
TB1
L1 RED L1/1 T1/2 RED U
L2 WHT L2/3 T2/4 WHT V
MC
L3 BLK L3/5 T3/6 BLU
N W
52C 51C
GRN/YLW

Main functions of LED (when both Nos.1 and 2 of SW3 are “OFF”) How to use SW1 and 2
●Pressing SW1 erases the past check contents loaded on the
LED No. Output display (light) Check display (flash) microcomputer.
LD1 Compressor indoor command Auti-phase detect ●The output display (light) remains during operation but press-
LD2 Heating indoor command Missing-phase detect ing SW2 displays the past check contents in flashing mode.
LD3 63H1 ON Pipe sensor short/open Pressing the switch again returns to output display (light).
LD4 Compressor ON —
LD5 Outdoor fan ON 51C functions Power line reconnection procedure
LD6 4-way valve ON 26C functions In case of reverse rotation
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input Unit side Outdoor unit
NOTE : If the operation stops to function of the protection device, the check display flashes. wiring L1 L2 L3 terminal

charge 2 out of 1.
2 and 3.
Field wiring (This example shows
reconnection of 1
CAUTIONS FOR POWER SUPPLY WIRING Change thie side and 2.)
1 2 3
●Making wiring connection in anti-phase or missing phase “L2” or “L3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor oper-
❈When power supply is 220V
ation. If phase “L1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power is
turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side) RED 220V WHITE
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
❈Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection ORANGE 230V
in the following procedure. YELLOW 240V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.

14
PUH-5YKSA3
SYMBOL NAME SYMBOL NAME SYMBOL NAME
MC COMPRESSOR T TRANSFORMER X12(O.B) COMPRESSOR RELAY
MF1,2 OUTDOOR FAN MOTOR (INNER THERMOSTAT) TB1,3 TERMINAL BLOCK X13(O.B) SOLENOID COIL RELAY
C1,2 FAN MOTOR CAPACITOR 63H1 HIGH PRESSURE SWITCH X14(O.B) SOLENOID COIL RELEY
RT OUTDOOR COIL THERMISTOR 26C DIS.CHARGE THERMAL SWITCH CN3(O.B) CONNECTOR(CONNECTING
HC CRANKCASE HEATER O.B OUTDOOR CONTROLLER BOARD WIRES INDOOR/OUTDOOR)
49C INTERNAL THERMOSTAT FOR MC ZNR(O.B) SURGE ABSORBER CN4T(O.B) TRANSFORMER CONNECTOR
52C CONTACTOR F(O.B) FUSE(6.3A) SW1,2,3(O.B) CHECK,SERVICE SELECT SWITCH
21S4 4-WAY VALVE SOLENOID COIL FC(O.B) FAN CONTROLLER LD1-LD8(O.B) CHECK,SERVICE LED
21R BYPASS VALVE SOLENOID COIL X11(O.B) CRANKCASE HEATER RELAY 51CM(O.B) JUMPER CONNECTOR

1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8

CN4
SW3 ✕14 ✕13 ✕12 ✕11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 ✕14 ✕13 ✕12 ✕11
MF2
63H2
CN4T 63H1 MF1
4321 51CM
4
SV TRF 21S4 52C CH ZNR FR S T 5
RED
GRY
GRY
RED
RED

BRN
BRN
BLU
BLU

BLK
BLK
BLK
BLK

RED
BRN
BRN 13 A1 WHT WHT
63H1 26C 3
AC 52C 21R 21 52C HC BLU BLU
RED 14 S4 4
12.3V 220V RED RED MF1
2
RED

ORN A2
230V WHT C1 ORN ORN
YLW 1
AC12.3V WHT
240V WHT WHT
POWER SUPPLY T 3
RED BLU BLU
3N~ 4
ORN MF2
WHT
1 ORN
380/220-415/240V 50Hz BLK MC C2 RED RED
2
TB1 BLU
L1 RED L1/1 T1/2 RED T1 49C
L2 WHT L2/3 T2/4 WHT T2
L3 BLK L3/5 T3/6 BLU T3
N
52C
GRN/YLW

Main functions of LED (when both Nos.1 and 2 of SW3 are “OFF”) How to use SW1 and 2
●Pressing SW1 erases the past check contents loaded on the
LED No. Output display (light) Check display (flash) microcomputer.
LD1 Compressor indoor command Auti-phase detect ●The output display (light) remains lit during operation but
LD2 Heating indoor command Missing-phase detect pressing SW2 displays the past check contents in flashing
LD3 63H1 ON Pipe sensor short/open mode. Pressing the switch again returns to output display
LD4 Compressor ON 63H2 functions (light).
LD5 Outdoor fan ON 51C functions Power line reconnection procedure
LD6 4-way valve ON 26C functions In case of reverse rotation
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input Unit side Outdoor unit
NOTE : If the operation stops to function of the protection device, the check display flashes. wiring L1 L2 L3 terminal

CAUTION FOR SERVICING charge 2 out of 1.


2 and 3.
●Connect the lead wires accordling to the color indication of sticker on the compressor terminal. Field wiring (This example shows
reconnection of 1
CAUTIONS FOR POWER SUPPLY WIRING Change thie side and 2.)
1 2 3
●Making wiring connection in anti-phase or missing phase “L2” or “L3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor oper-
❈When power supply is 220V
ation. If phase “L1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power is
turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side) RED 220V WHITE
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
❈Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection
ORANGE 230V
in the following procedure. YELLOW 240V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
15
PUH-6YKSA2
SYMBOL NAME SYMBOL NAME SYMBOL NAME
MC COMPRESSOR TB1,3 TERMINAL BLOCK X12<O.B> COMPRESSOR RELAY
MF1,2 OUTDOOR FAN MOTOR (INNER THERMOSTAT) 63H1 HIGH PRESSURE SWITCH X13<O.B> SOLENOID COIL RELAY
C1,2 FAN MOTOR CAPACITOR 26C DIS.CHARGE THERMAL SWITCH X14<O.B> SOLENOID COIL RELEY
RT OUTDOOR COIL THERMISTOR X15 BYPASS VALVE RELAY CN3<O.B> CONNECTING WIRES
HC CRANKCASE HEATER O.B OUTDOOR CONTROLLER BOARD INDOOR/OUTDOOR CONNECTOR
49C INTERNAL THERMOSTAT FOR MC ZNR<O.B> SURGE ABSORBER CN4T<O.B> TRANSFORMER CONNECTOR
52C CONTACTOR F<O.B> FUSE(6.3A) SW1,2,3<O.B> CHECK,SERVICE SELECT SWITCH
21S4 4-WAY VALVE SOLENOID COIL FC<O.B> FAN CONTROLLER LD1-LD6<O.B> CHECK,SERVICE LED
21R BYPASS VALVE SOLENOID COIL X11<O.B> CRANKCASE HEATER RELAY 51CM<O.B> JUMPER CONNECTOR
T TRANSFORMER

1 YLW LED RT
TO INDOOR UNIT
CONNECTING WIRES 2 ORN O.B.
DC 12V 3 BRN SW1
TB3 SW2 4 3 2 1
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8

CN4
SW3 ✕14 ✕13 ✕12 ✕11
OFF CN2
ON
21
3
2 CN3 26C F.C.
1 ✕14 ✕13 ✕12 ✕11
MF2
63H2
CN4T 63H1 MF1
4321 51CM
4
SV TRF 21S4 52C CH ZNR FR S T 5
RED
GRY
GRY
RED
RED

BRN
BRN
BLK
BLK

BLK
BLK
BLK
BLK

RED
BRN BLK
BRN 13 A1 WHT WHT
7
21 63H1 26C 3
AC 52C 21R ✕15 S4 52C BLU BLU
RED 14 HC 4
12.3V 220V 8 RED RED MF1
2
RED

RED

ORN A2
230V 3 ✕15 5 BLK C1 ORN ORN
YLW 1
AC12.3V WHT
240V WHT WHT WHT
POWER SUPPLY T 3
RED BLU BLU
3N~ 4
ORN MF2
WHT
1 ORN
380/220-415/240V 50Hz BLK MC C2 RED RED
2
TB1 BLU
L1 RED L1/1 T1/2 RED T1 49C
L2 WHT L2/3 T2/4 WHT T2
L3 BLK L3/5 T3/6 BLU T3
N
52C
GRN/YLW

Main functions of LED (when both Nos.1 and 2 of SW3 are “OFF”) How to use SW1 and 2
●Pressing SW1 erases the past check contents loaded on the
LED No. Output display (light) Check display (flash) microcomputer.
LD1 Compressor indoor command Auti-phase detect ●The output display (light) remains lit during operation but
LD2 Heating indoor command Missing-phase detect pressing SW2 displays the past check contents in flashing
LD3 63H1 ON Pipe sensor short/open mode. Pressing the switch again returns to output display
LD4 Compressor ON 63H2 functions (light).
LD5 Outdoor fan ON 51C functions Power line reconnection procedure
LD6 4-way valve ON 26C functions In case of reverse rotation
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input Unit side Outdoor unit
NOTE : If the operation stops to function of the protection device, the check display flashes. wiring L1 L2 L3 terminal

CAUTION FOR SERVICING charge 2 out of 1.


2 and 3.
●Connect the lead wires accordling to the color indication of sticker on the compressor terminal. Field wiring (This example shows
reconnection of 1
CAUTIONS FOR POWER SUPPLY WIRING Change thie side and 2.)
1 2 3
●Making wiring connection in anti-phase or missing phase “L2” or “L3” causes the protection device incorporated in the
microcomputer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor oper-
❈When power supply is 220V
ation. If phase “L1” or “N” is missing it causes all displays to go out. Under normal condition LD8 light when power is
turned “ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side) RED 220V WHITE
contained in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.
❈Since the transformer (T) is connected with 240V power, if 220V or 230V power is used, change the wiring connection
ORANGE 230V
in the following procedure. YELLOW 240V
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
●Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
16
PUH-5TKSA/PUH-6TKSA
SYMBOL NAME SYMBOL NAME SYMBOL NAME
MC COMPRESSOR TB1,3 TERMINAL BLOCK X12<O.B> COMPRESSOR RELAY
MF1,2 OUTDOOR FAN MOTOR (INNER THERMOSTAT) 63H1 HIGH PRESSURE SWITCH X13<O.B> SOLENOID COIL RELAY
C1,2 FAN MOTOR CAPACITOR 26C DIS.CHARGE THERMAL SWITCH X14<O.B> SOLENOID COIL RELEY
RT PIPE TEMP THERMISTOR O.B OUTDOOR CONTROLLER BOARD CN3<O.B> CONNECTING WIRES
HC CRANKCASE HEATER ZNR<O.B> SURGE ABSORBER INDOOR/OUTDOOR CONNECTOR
49C INTERNAL THERMOSTAT FOR MC F<O.B> FUSE(6.3A) CN4T<O.B> TRANSFORMER CONNECTOR
52C CONTACTOR FC<O.B> FAN CONTROLLER SW1,2,3<O.B> CHECK,SERVICE SELECT SWITCH
21S4 4-WAY VALVE SOLENOID COIL X11<O.B> CRANKCASE HEATER RELAY LD1-LD8<O.B> CHECK,SERVICE LED
21R BYPASS VALVE SOLENOID COIL T TRANSFORMER 51CM<O.B> JUMPER CONNECTOR

1 YLW LED
TO INDOOR UNIT
CONNECTING WIRES 2 ORN RT
DC 12V (polar) 3 BRN
O.B
TB3
SW1 4 3 2 1
X14 X13 X12 X11 CN4
LD2
LD3
LD4
LD5
LD6
LD7
LD8
LD1

SW2 CN2
SW3
OFF 26C
ON F.C.
X14 X13 X12 X11
21
63H1
3 MF2
2 CN3 51CM
1
F MF1
CN4T
4 3 2 1 4
SV TRF 21S4 52C CH ZNR R S T 5
WHT
WHT

WHT
WHT

BRN
BRN
GRY
GRY
RED
RED

BLK
BLK
BLK
BLK

BRN AC12.3V RED 220V 13 A1


ORN 230V 52C 21R 21 52C HC
S4 WHT WHT
RED AC12.3V YLW 240V 14 63H1 26C 3
A2 BLU BLU
4
RED RED RED MF1
T ORN
2
ORN
BLK 1
BLK

C1
POWER SUPPLY RED
WHT WHT
3
WHT BLU BLU
3~(3PHASES) MC RED
4
RED MF2
1
220V 60Hz TB1 C2 ORN
2
ORN

L1 49C
RED L1/1 T1/2 RED T1
L2 WHT L2/3 T2/4 WHT T2
L3 BLK L3/5 T3/6 BLK T3
GRN/YLW 52C

Main functions of LED (when both Nos.1 and 2 of SW3 are “OFF”) How to use SW1 and 2
●Pressing SW1 erases the past check contents loaded on the
LED No. Output display (light) Check display (flash) microcomputer.
LD1 Compressor indoor command Auti-phase detect ●The output display (light) remains lit during operation but
LD2 Heating indoor command Missing-phase detect pressing SW2 displays the past check contents in flashing
LD3 63H1 ON Pipe sensor short/open mode. Pressing the switch again returns to output display
LD4 Compressor ON – (light).
LD5 Outdoor fan ON 51C functions Power line reconnection procedure
LD6 4-way valve ON 26C functions In case of reverse rotation
LD7 Bypass valve ON RT overheat protection
LD8 Crankcase heater ON Defective input Unit side Outdoor unit
NOTE : If the operation stops to function of the protection device, the check display flashes. wiring L1 L2 L3 terminal

CAUTION FOR SERVICING charge 2 out of 1.


2 and 3.
●Connect the lead wires accordling to the color indication of sticker on the compressor terminal. Field wiring (This example shows
reconnection of 1
CAUTIONS FOR POWER SUPPLY WIRING Change thie side and 2.)
1 2 3
●Making wiring connection in anti-phase or missing phase “L2” causes the protection device incorporated in the micro-
computer to function resulting in LD1 or LD2 shown in the table above to flash and prevents the compressor operation.
If phase “L1” or “L3” is missing it causes all displays to go out. Under normal condition LD8 light when power is turned
“ON”. If anti-phase connection is to be used, change connections of 2 out of 3 power lines (field wiring side) contained
in the power supply terminal block (TB1) of the outdoor unit as shown at the right upper.

CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES


●Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.

17
6 REFRIGERANT SYSTEM DIAGRAM
PUH-1.6VKA2 /PUH-2VKA2 /PUH-2.5VKA2
PUH-3VKA2 /PUH-3YKA2
High pressure
control switch
Refrigerant pipe Oil separator
(option) Service Outdoor unit
Indoor unit 4-way valve
15.88A({5/8") Ball valve port Outdoor heat exchanger
(with heat insulator) Strainer
Flexible tube
Indoor Service Outdoor coil
heat port thermistor
exchanger (RT)
Strainer Flared Bypass
connection valve
Accumulator Restrictor Capillary
Indoor coil valve tube
Restrictor
thermistor valve Compressor PUH-1.6 (O.D.3.2✕I.D.1.8-R600)
(TH2) PUH-2 (O.D.4.0✕I.D.2.0-R430)
Distributor PUH-1.6 (O.D.4.0✕I.D.2.4-R1550)
Refrigerant pipe Ball valve Strainer
with PUH-3 (O.D.4.0✕I.D.2.4-R1070)
(option) (with service port)
strainer Capillary 9.52A({3/8")
tube (with heat insulator)

PUH-4YKSA3
High pressure
control switch Outdoor unit
Refrigerant pipe Oil separator
(option) Service Outdoor heat exchanger
4-way valve
Indoor unit 19.05A({3/4") Ball valve port
(with heat insulator) Strainer

Flexible tube Outdoor coil


Indoor Service thermistor
heat port (RT)
exchanger (check) Restrictor
Strainer Flared Bypass valve
connection valve Capillary
tube
Indoor coil Restrictor (O.D.3.2✕I.D.2.0-R820)✕2pcs
thermistor valve Accumulator Compressor
(TH2)
Distributor
with Refrigerant pipe Ball valve Strainer
strainer (option) (with service port)
Capillary
tube 9.52A({3/8")
(with heat insulator)
R.V.coil
Refrigerant flow in cooling Heating:ON
Refrigerant flow in heating Cooling:OFF

PUH-5YKSA3
PUH-6YKSA2
Oil High pressure
Refrigerant pipe separator control switch
Outdoor unit
(option) Outdoor heat exchanger
4-way valve Service
Indoor unit 19.05A({3/4") Ball valve THERMAL
(with heat insulator) Strainer port SWITCH

Indoor Flexible tube Thermistor


Service RT
heat port
exchanger
Restrictor
Strainer Flared Bypass valve
connection valve
Capillary tube
Thermistor PUH-5....(O.D.4.0✕I.D.2.4-R840)✕2
TH2
Accumulator Compressor Capillary tube PUH-6....(O.D.4.0✕I.D.2.4-R1200)✕2
Restrictor valve
Distributor
with Refrigerant pipe Ball valve Strainer
strainer (option) (with service port)
Capillary
tube 9.52A({3/8")
(with heat insulator)

18
PUH-5TKSA
PUH-6TKSA

Oil High pressure


Refrigerant pipe separator control switch
Outdoor unit
(option) Outdoor heat exchanger
4-way valve Service
Indoor unit 19.05A({3/4") Ball valve THERMAL
(with heat insulator) Strainer port SWITCH

Indoor Flexible tube Thermistor


Service RT
heat port
exchanger
Restrictor
Strainer Flared Bypass valve
connection valve
Capillary tube
Thermistor PUH-5....(O.D.4.0✕I.D.2.4-R840)
TH2
Accumulator Compressor Capillary tube PUH-6....(O.D.4.0✕I.D.2.4-R740)
Restrictor valve
Distributor
with Refrigerant pipe Ball valve Strainer
strainer (option) (with service port) DPR
Capillary
tube 9.52A({3/8")
(with heat insulator)

19
7 DISASSEMBLY PROCEDURE
PUH-2.5VKA2 /PUH-3VKA2 /PUH-3YKA2
OPERATING PROCEDURE PHOTOS

1. Removing the electrical parts Photo 1


(1) Remove the 5 screws and the top panel. (3 screws in
front and 2 screws in rear) Screws
(2) Remove the screw of the cover panel. To remove the Top panel
cover panel, pull it toward you and unhook the catch-
es from the side panel.
(3) Remove the screw of the service panel. To remove the
service panel, pull it down toward you and unhook the
catches on the both sides.

Service panel

Panel cover
Front panel

Photo 2

Transformer Capacitor
Outdoor controller
board
Contactor

Overcurrent
relay

Screws Terminal block

2. Removing the fan motor Photo 3


(1) Remove the 3 screws of the front panel. Open the
front panel to a 45-degree angle. Then lift it and Motor support Separator support plate
unhook the 3 catches to remove.
(2) Remove the propeller nut and the propeller. High-pressure control
(3) Remove the 3 screws and the fan motor. switch
Propeller
Disconnect the lead connectors. Lead
connectors

Valve bed

Propeller nut Crankcase heater

20
OPERATING PROCEDURE PHOTOS

3. Removing the heat exchanger and the compressor Photo 4


(1) Remove the rear panel (2 screws in front, 1 screw on
the side, 3 screws in the rear). Remove the valve bed, Screws
and open the rear panel to the rear to remove.
NOTE :
All panels are fixed by catches, and must be removed by
shifting up and down.
(2) Remove the 4 screws of the right side panel and
remove it.
(3) Remove the 3 screws of the rear guard and remove it.
(4) Remove the 4 screws of the separator support plate
and remove it.
(5) Remove the 2 screws of the motor support and
remove it. Screws
(6) Remove the 5 screws of the valve bed.
The valve bed is fixed by the catches on the right and
left sides.
Lift it to remove.
(7) Remove the electrical parts box.
Disconnect the connectors from the high pressure
switch, crank case heater, shell thermo, and fan motor
lead.
(8) Remove the 2 screws of the separator and remove it. Photo 5
(9) Remove the 2 screws of the heat exchanger and
Heat exchanger
remove it.
Detach the welded point of pipe.
(10) Remove the 3 nuts of the compressor and remove it.
Detach the welded points of the compressor suction
pipe and discharge pipe.
Accumulator

Photo 6

Charge plug

Ball valve

Compressor

21
8 PARTS LIST
STRUCTURAL PARTS
PUH-1.6VKA
PUH-1.6VKA1
PUH-1.6VKA2

1 11 8 5 9

5
3

12 13 14 6 10

,
Q ty/set
PUH-1.6 Remarks Wining Recom- Price
No. Part No. Part Name Specification VKA
Diagram mended
,
(Drawing No.) Symbol Q ty
VKA1 Unit Amount
VKA2
1 R01 A00 641 TOP PANEL 1
2 — F.ST SCREW (5✕10) 13 (ZOO4M203H10)
3 R01 A00 668 FRONT PANEL 1
4 R01 A00 675 FAN GUARD 1
5 R01 A00 655 PANEL HANDLE 3
6 R01 A00 661 SERVICE PANEL 1
7 R01 A00 662 SIDE PANEL 1
8 — LABEL (MITSUBISHI) 1 (DG79R130H01)
9 R01 A00 682 REAR PANEL 1
10 R01 A00 658 PANEL COVER 1
11 R01 A00 698 REAR GUARD 1
12 — MOTOR SUPPORT 1 (BG00B020G55)
13 R01 A00 686 BASE 1
14 — LABEL (BRAND) 1 (BC79G510H01)

22
STRUCTURAL PARTS
PUH-2VKA
PUH-2VKA1
PUH-2VKA2

1 11 8 5 9

5
3

12 13 14 6 10

, Price
Q ty/set Wining Recom-
Remarks
No. Part No. Part Name Specification PUH-2 Diagram mended
,
(Drawing No.) Symbol Q ty Unit Amount
VKA,VKA1,VKA2
1 R01 A00 641 TOP PANEL 1
2 — F.ST SCREW (5✕10) 13 (ZOO4M203H10)
3 R01 A00 668 FRONT PANEL 1
4 R01 A00 675 FAN GUARD 1
5 R01 A00 655 PANEL HANDLE 3
6 R01 A00 661 SERVICE PANEL 1
7 R01 A00 662 SIDE PANEL 1
8 — LABEL (MITSUBISHI) 1 (DG79R130H01)
9 R01 A00 682 REAR PANEL 1
10 R01 A00 658 PANEL COVER 1
11 R01 A00 698 REAR GUARD 1
12 — MOTOR SUPPORT 1 (BG00B020G55)
13 R01 A04 686 BASE 1
14 — LABEL(BRAND) 1 (BC79G510H01)

23
STRUCTURAL PARTS
PUH-2.5VKA,PUH-2.5VKA1,PUH-2.5VKA2
PUH-3VKA,PUH-3VKA1,PUH-3VKA2
PUH-3YKA,PUH-3YKA1,PUH-3YKA2

2 1 11 8 5

9
3

14

4 13 12 6 10
,
Q ty/set
Price
PUH-2.5/3 PUH-3 Remarks Wining Recom-
No. Part No. Part Name Specification VKA1 Diagram mended
,
VKA VKA2 (Drawing No.) Symbol Q ty Unit Amount
YKA YKA1
YKA2
1 R01 A00 641 TOP PANEL 1 1
2 — F.ST SCREW (5✕10) 13 13 (ZOO4M203H10)
3 R01 A08 668 FRONT PANEL 1 1
4 R01 A00 675 FAN GUARD 1 1
5 R01 A00 655 PANEL HANDLE 1 1
6 R01 A08 661 SERVICE PANEL 3 3
7 R01 A08 662 SIDE PANEL 1 1
8 — LABEL (MITSUBISHI) 1 1 (DG79R130H01)
9 R01 A08 682 REAR PANEL 1 1
10 R01 A00 658 PANEL COVER 1 1
11 R01 A08 698 REAR GUARD 1 1
12 — MOTOR SUPPORT 1 1 (BG00B020G56)
R01 A04 686 BASE 1
13
R01 A10 686 BASE 1
14 — LABEL(BRAND) 1 1 (BC79G510H01)

24
STRUCTURAL PARTS
PUH-4YKSA,PUH-4YKSA1,PUH-4YKSA3

7 2 12 13 1 11 8 9

15
3

4
5

14 6 10
,
Q ty/set Price
PUH-4 Wining Recom-
Remarks
No. Part No. Part Name Specification Diagram mended
(Drawing No.) Symbol Q,ty
YKSA YKSA1 YKSA3 Unit Amount

1 R01 A00 641 TOP PANEL 1 1 1


2 — F.ST SCREW (5✕10) 13 13 13 (ZOO4M203H10)
3 R01 A11 668 FRONT PANEL 1 1 1
R01 A00 675 FAN GUARD 2
4 T7W 001 675 FAN GUARD 2
T7W A00 675 FAN GUARD 2
5 R01 A00 655 PANEL HANDLE 3 3 3
6 R01 A11 661 SERVICE PANEL 1 1 1
7 R01 A11 662 SIDE PANEL 1 1 1
8 — LABEL (MITSUBISHI) 1 1 1 (DG79R130H01)
9 R01 A11 682 REAR PANEL 1 1 1
10 R01 A00 658 PANEL COVER 1 1 1
11 R01 A11 698 REAR GUARD 1 1 1
12 — MOTOR SUPPORT 1 1 1 (BG00B020G46)
13 — MOTOR PLATE 1 1 1 (BG02C075H03)
14 R01 A10 686 BASE 1 1 1
15 — LABEL(BRAND) 1 1 1 (BC79G510H01)

25
STRUCTURAL PARTS
PUH-5YKSA,PUH-5YKSA1,PUH-5YKSA2,PUH-5YKSA3
PUH-6YKSA,PUH-6YKSA1,PUH-6YKSA2 13 12 1 11 8 9
3 2

4
15

10

14 5
,
Q ty/set Price
Wining Recom-
PUH-5 Remarks
No. Part No. Part Name Specification PUH-6 Diagram mended
,
(Drawing No.) Symbol Q ty
YKSA1
YKSA2

YKSA1
YKSA3

YKSA2

Unit Amount
YKSA
YKSA

1 R01 A14 641 TOP PANEL 1 1 1 1 1 1


2 — F.ST SCREW (5✕10) 13 13 13 13 13 13 (ZOO4M203H10)
3 R01 A14 668 FRONT PANEL 1 1 1 1 1 1
R01 A00 675 FAN GUARD 2 2
4
T7W 001 675 FAN GUARD 2 2 2 2
5 R01 A00 655 PANEL HANDLE 3 3 3 3 3 3
6 R01 A14 661 SERVICE PANEL 1 1 1 1 1 1
7 R01 A14 662 SIDE PANEL 1 1 1 1 1 1
8 — LABEL (MITSUBISHI) 1 1 1 1 1 1 (DG79R130H01)
9 R01 A14 682 REAR PANEL 1 1 1 1 1 1
10 R01 A14 658 PANEL COVER 1 1 1 1 1 1
11 R01 A14 698 REAR GUARD 1 1 1 1 1 1
R01 85H 130 MOTOR SUPPORT 1 1 1
12
T7W E00 130 MOTOR SUPPORT 1 1 1
13 — MOTOR PLATE 1 1 1 (BG02C075H03)
R01 A14 686 BASE 1 1 1 1
14
R01 AK6 686 BASE 1 1
15 — LABEL(BRAND) 1 1 1 1 1 1 (BC79G510H01)
26
STRUCTURAL PARTS
PUH-5TKSA
PUH-6TKSA
3 2 13 12 1 11 8 9

4
15

10

14 5
,
Q ty/set Price
Wining Recom-
Remarks
No. Part No. Part Name Specification PUH-5 PUH-6 Diagram mended
,
(Drawing No.) Symbol Q ty Unit Amount
TKSA TKSA

1 R01 A14 641 TOP PANEL 1 1


2 — F.ST SCREW (5✕10) 13 13 (ZOO4M203H10)

3 R01 A14 668 FRONT PANEL 1 1


4 R01 A00 675 FAN GUARD 2 2
5 R01 A00 655 PANEL HANDLE 3 3
6 R01 A14 661 SERVICE PANEL 1 1
7 R01 A14 662 SIDE PANEL 1 1
8 — LABEL (MITSUBISHI) 1 1 (DG79R130H01)

9 R01 A14 682 REAR PANEL 1 1


10 R01 A14 658 PANEL COVER 1 1
11 R01 A14 698 REAR GUARD 1 1
R01 85H 130 MOTOR SUPPORT 1
12
T7W E00 130 MOTOR SUPPORT 1
13 — MOTOR PLATE 1 (BG02C075H03)
14 R01 AK6 686 BASE 1
15 — LABEL(BRAND) 1 1

27
FUNCTIONAL PARTS
PUH-1.6VKA
PUH-1.6VKA1
PUH-1.6VKA2

4 3 9 8 7 10 14

17
27
15
11
16
19

18
5 22
2 6 13 20

28 19
1
26
12
21
22
24
23
25

28
Part numbers that are circled are not shown in the figure.
,
Q ty/set
Price
PUH-1.6 Wining Recom-
No. Part No. Part Name Specification Remarks Diagram mended
,
Symbol Q ty Unit Amount
VKA VKA1 VKA2

1 T7W 271 763 OUTDOOR FAN MOTOR PA6V85-UH(1.6VKA2) 1 1 1 MF


2 R01 A00 115 PROPELLER FAN 1 1 1
T7W 251 315 OUTDOOR CONTROLLER BOARD 1 O.B
3
T7W A01 315 OUTDOOR CONTROLLER BOARD 1 1 O.B
4 T7W 520 239 FUSE 250V 6.3A 1 1 1 F<O.B>
5 T7W 509 716 TERMINAL BLOCK 3P(L,N,;) 1 1 1 TB1
6 T7W 516 716 TERMINAL BLOCK 3P(1,2,3) 1 1 1 TB3
7 T7W 251 799 TRANSFORMER 1 1 1 T
8 R01 A00 255 OUTDOOR FAN CAPACITOR 2.5+ 440V 1 1 1 C1
9 T7W 737 723 COMPRESSOR CAPACITOR 35+ 420V 1 1 1 C2
10 T7W 249 708 CONTACTOR S-U12 230V 1 1 1 52C
2 2
11 R01 A00 208 HIGH PRESSURE SWITCH OFF26kg/cm ON21kg/cm 1 1 1 63H1
12 R01 272 428 SOLENOID VALVE 1 1 1
13 T7W 106 242 SOLENOID COIL 1 1 1 21R
14 R01 V39 490 OIL SEPARATOR 1 1 1
15 T7W 250 403 4-WAY VALVE 1 1 1
16 T7W 250 242 4-WAY COIL 4-WAY VALVE 1 1 1 21S4
R01 KL5 202 OUTDOOR COIL THERMISTOR 1 1 RT
17
R01 J07 202 OUTDOOR COIL THERMISTOR 1 RT
18 R01 L11 418 RESTRICTOR VALVE 1 1 1
R01 56H 450 STRAINER 1 1
19
R01 KL5 450 STRAINER 1
T7W 250 425 CAPILLARY TUBE {3.2✕{1.8✕600mm 1 1
20
T7W A00 425 CAPILLARY TUBE 1
21 R01 A00 440 ACCUMULLAOR 1 1 1
22 R01 943 411 BALL VALVE 5/8˝ 1 1 1
23 R01 943 410 BALL VALVE 3/8˝ 1 1 1
24 T92 547 452 COMPRESSOR RH247VFC 1 1 1 MC
25 T7W 249 236 CRANKCASE HEATER 240V 30W 1 1 1 HC
R01 02L 413 CHARGE PLUG 2 2
26
R01 943 413 CHARGE PLUG 2
27 R01 A04 408 HEAT EXCHANGER 1 1 1
28 R01 KL5 451 STRAINER 1 1 1

29
FUNCTIONAL PARTS
PUH-2VKA
PUH-2VKA1
PUH-2VKA2

3 9 8 7 28 10 13 12

27 16

1
14

15
17
18
2 19
20

(M8) 26
25

21

6 5 11 23 24 22

30
,
Q ty/set
Price
PUH-2 Wining Recom-
No. Part No. Part Name Specification Remarks Diagram mended
,
VKA1 Symbol Q ty Unit Amount
VKA VKA2

1 T7W 271 763 OUTDOOR FAN MOTOR PA6V85-UH(2VKA2) 1 1 MF


2 R01 A00 115 PROPELLER FAN 1 1
T7W 251 315 OUTDOOR CONTROLLER BOARD 1
3
T7W A01 315 OUTDOOR CONTROLLER BOARD 1 O.B
4 T7W 520 239 FUSE 250V 6.3A 1 1 F<O.B>
5 T7W 509 716 TERMINAL BLOCK 3P(L,N,;) 1 1 TB1
6 T7W 516 716 TERMINAL BLOCK 3P(1,2,3) 1 1 TB3
7 T7W 251 799 TRANSFORMER 1 1 T
8 R01 A00 255 OUTDOOR FAN CAPACITOR 2.5+ 440V 1 1 C1
9 T7W 100 723 COMPRESSOR CAPACITOR 50+ 400V 1 1 C2
10 R01 A00 208 HIGH PRESSURE SWITCH OFF25.5kg/cm ON21kg/cm
2 2
1 1 63H1
11 R01 272 428 SOLENOID VALVE 1 1
12 T7W 106 242 SOLENOID COIL 1 1 21R
13 T7W 250 490 OIL SEPARATOR 1 1
14 T7W 250 403 4-WAY VALVE 1 1
15 T7W 250 242 4-WAY COIL 1 1 21S4
R01 J07 202 OUTDOOR COIL THERMISTOR 1
16
R01 KL5 202 OUTDOOR COIL THERMISTOR 1 RT
R01 KN2 425 CAPILLARY TUBE 1
17
T7W A03 425 CAPILLARY TUBE {4.0✕{2.0✕430mm 1
18 R01 L11 418 RESTRICTOR VALVE 1 1
19 R01 A04 450 STRAINER 1 1
20 R01 A00 440 ACCUMLATOR 1 1
21 R01 943 411 BALL VALVE 5/8˝ 1 1
22 R01 943 410 BALL VALVE 3/8˝ 1 1
23 T92 612 362 COMPRESSOR NH-38VMD 1 1 MC
T7W 003 236 CRANKCASE HEATER 1 HC
24
T7W A00 236 CRANKCASE HEATER 240V 38W 1 HC
R01 943 413 CHARGE PLUG 1
25
R01 02L 413 CHARGE PLUG 1
26 R01 590 413 CHARGE PLUG 1 1
27 R01 A04 408 HEAT EXCHANGER 1 1
T7W 330 708 CONTACTOR S-K18 230V 1 52C
28
T7W 330 708 CONTACTOR S-K18(S-N18)230V 1 52C

31
FUNCTIONAL PARTS
PUH-2.5VKA
PUH-2.5VKA1
PUH-2.5VKA2

4 3 28 8 7 9 22 11 15

29
16

17
2 13
12
14

10

18
21

6 27 5 19 25 26 24 23 20

32
Part numbers that are circled are not shown in the figure.
, Price
Q ty/set
Wining Recom-
No. Part No. Part Name Specification PUH-2.5 Remarks Diagram mended
,
VKA1 Symbol Q ty
Unit Amount
VKA VKA2

T7W 270 763 OUTDOOR FAN MOTOR PA6V85-UF 1 MF


1
T7W 271 763 OUTDOOR FAN MOTOR PA6V85-UH 1 MF
2 R01 A00 115 PROPELLER FAN 1 1
T7W 251 315 OUTDOOR CONTROLLER BOARD 1 O.B
3
T7W A01 315 OUTDOOR CONTROLLER BOARD 1 O.B
4 T7W 520 239 FUSE 250V 6.3A 1 1 F(O.B)
5 T7W 509 716 TERMINAL BLOCK 3P(L,N,;) 1 1 TB1
6 T7W 516 716 TERMINAL BLOCK 3P(1,2,3) 1 1 TB3
7 T7W 251 799 TRANSFORMER 1 1 T
8 R01 576 255 OUTDOOR FAN CAPACITOR 3+ 440V 1 1 C1
9 T7W 330 708 CONTACTOR S-K18(S-N18)230V 1 1 52C
10 R01 272 428 SOLENOID VALVE 1 1
11 T7W 106 242 SOLENOID COIL 1 1 21R
12 R01 Z32 425 CAPILLARY TUBE {4.0✕{2.4✕1550mm 1 1
13 R01 L11 418 RESTRICTOR VALVE 1 1
14 R01 A04 450 STRAINER 1 1
15 T7W 250 403 4-WAY VALVE 1 1
16 T7W 250 242 4-WAY COIL 4-WAY VALVE 1 1 21S4
R01 J07 202 OUTDOOR COIL THERMISTOR 1 RT
17
R01 KL5 202 OUTDOOR COIL THERMISTOR 1 RT
18 R01 A08 451 STRAINER 1 1
R01 590 413 CHARGE PLUG 1
19
R01 42L 413 CHARGE PLUG 1
R01 943 413 CHARGE PLUG 1
20
R01 02L 413 CHARGE PLUG 1
21 R01 A08 440 ACCUMULATOR 1 1
22 R01 V39 490 OIL SEPARATOR 1 1
23 R01 951 411 BALL VALVE 5/8˝ 1 1
24 R01 943 410 BALL VALVE 3/8˝ 1 1
25 T97 525 300 COMPRESSOR NH-41VMD 1 1 MC
T7W 003 236 CRANKCASE HEATER 240V 38W 1 HC
26
T7W A00 236 CRANKCASE HEATER 240V 38W 1 HC
27 R01 A00 208 HIGH PRESSURE SWITCH OFF25.5kg/cm ON21kg/cm
2 2
1 1 63H1
28 T7W 105 723 COMPRESSOR CAPACITOR 45+ 440V 1 1 C2
29 R01 A08 408 HEAT EXCHANGER 1 1
30 R01 A00 425 CAPILLARY TUBE {2.5✕{0.6✕1000mm 1

33
FUNCTIONAL PARTS
PUH-3VKA / PUH-3YKA
PUH-3VKA1 / PUH-3YKA1
PUH-3VKA2 / PUH-3YKA2

5 3 28 4 7 8 9 22 11 16 15
6

29

12

17
13
2 PUH-3YKA
PUH-3YKA1
PUH-3YKA2
10
14
3 4 7 8 9
21

18

30

27 19 25 26 24 23 20
6 5
,
Q ty/set Price
PUH-3 Wining Recom-
No. Part No. Part Name Specification Remarks Diagram mended
,
VKA1
VKA2

YKA1

YKA2
YKA

Symbol Q ty
VKA

Unit Amount

PA6V85-UF(VKA,YKA)
1 T7W 271 763 OUTDOOR FAN MOTOR PA6V85-UH(VKA1,YKA1) 1 1 1 1 1 MF
2 R01 A00 115 PROPELLER FAN 1 1 1 1 1
T7W 251 315 OUTDOOR CONTROLLER BOARD 1 O.B
T7W A01 315 OUTDOOR CONTROLLER BOARD 1 O.B
3 T7W 256 315 OUTDOOR CONTROLLER BOARD 1 O.B
T7W A03 315 OUTDOOR CONTROLLER BOARD 1 1 O.B
4 T7W 520 239 FUSE 250V 6.3A 1 1 1 1 1 F(O.B)
T7W 509 716 TERMINAL BLOCK 3P(L,N,;) 1 1 TB1
5
T7W 511 716 TERMINAL BLOCK 5P(L1,L2,L3,N,;) 1 1 1 TB1
6 T7W 516 716 TERMINAL BLOCK 3P(1,2,3) 1 1 1 1 1 TB3

34
Part numbers that are circled are not shown in the figure.
,
Q ty/set Price
PUH-3 Wining Recom-
No. Part No. Part Name Specification Remarks Diagram mended
,

VKA1
VKA2

YKA1
YKA2
YKA
Symbol Q ty

VKA
Unit Amount

7 T7W 251 799 TRANSFORMER 1 1 1 1 1 T


8 R01 576 255 OUTDOOR FAN CAPACITOR 3+ 440V 1 1 1 1 1 C1
T7W 616 709 CONTACTOR S-K25 230V 1 52C
T7W 616 709 CONTACTOR S-K25(S-N25)230V 1 52C
9
T7W 301 708 CONTACTOR MSO-N11 1 1 52C
T7W A08 708 CONTACTOR MSO-NIIKF 1 52
10 R01 272 428 SOLENOID VALVE 1 1 1 1 1
11 T7W 106 242 SOLENOID COIL 1 1 1 1 1 21R
12 T7W Z25 425 CAPILLARY TUBE {4.0✕{2.4✕1070mm 1 1 1 1 1
13 R01 L11 418 RESTRICTOR VALVE 1 1 1 1 1
14 R01 A04 450 STRAINER 1 1 1 1 1
15 T7W 250 403 4-WAY VALVE 1 1 1 1 1
T7W 250 413 4-WAY COIL 1 1 21S4
16
T7W 106 242 4-WAY COIL 1 1 1 21S4
R01 J07 202 OUTDOOR COIL THERMISTOR 1 1 RT
17
R01 KL5 202 OUTDOOR COIL THERMISTOR 1 1 1 RT
18 R01 A08 451 STRAINER 1 1 1 1 1
R01 590 413 CHARGE PLUG 1 1
19
R01 42L 413 CHARGE PLUG 1 1 1
R01 943 413 CHARGE PLUG 1 1
20
R01 02L 413 CHARGE PLUG 1 1 1
21 R01 A08 440 ACCUMULATOR 1 1 1 1 1
22 R01 V39 490 OIL SEPARATOR 1 1 1 1 1
23 R01 951 411 BALL VALVE 5/8˝ 1 1 1 1 1
24 R01 943 410 BALL VALVE 3/8˝ 1 1 1 1 1
T97 600 300 COMPRESSOR NH-52VND 1 1 MC
25
T97 613 300 COMPRESSOR NH-52YDA 1 1 1 MC
T7W 003 236 CRANKCASE HEATER 240V 38W 1 1 HC
26
T7W A00 236 CRANKCASE HEATER 240V 38W 1 1 1 HC
27 R01 A00 208 HIGH PRESSURE SWITCH OFF25.5kg/cm2 ON21kg/cm2 1 1 1 1 1 63H1
28 T7W 101 723 COMPRESSOR CAPACITOR 60+ 400V 1 1 C2
29 R01 A10 408 HEAT EXCHANGER 1 1 1 1 1
30 R01 652 238 THERMAL SWITCH CUT125˚C IN90˚C 1 1 1 26C
31 R01 A00 425 CAPILLARY TUBE {2.5✕{0.6✕1000mm 1 1 1

35
FUNCTIONAL PARTS
PUH-4YKSA
PUH-4YKSA1
PUH-4YKSA3

6 5 3 4 79 8

27
21

22

(M8) 19

12
13
2 14
15
16

(M8) 19

27 18
20

1 25 11 17 10 26 23 24

36
Part numbers that are circled are not shown in the figure.
,
Q ty/set
Price
PUH-4
Wining Recom-
No. Part No. Part Name Specification Remarks Diagram mended
,
YKSA YKSA1 YKSA3 Symbol Q ty Unit Amount

1 T7W 554 763 OUTDOOR FAN MOTOR PS6V60-UA 2 2 2 MF1,2


2 R01 A00 115 PROPELLER FAN 2 2 2
T7W 256 315 OUTDOOR CONTROLLER BOARD 1 O.B
3
T7W A03 315 OUTDOOR CONTROLLER BOARD 1 1 O.B
4 T7W 520 239 FUSE 250V 6.3A 1 1 1 F(O.B)
5 T7W 511 716 TERMINAL BLOCK 5P(L1,L2,L3,N,;) 1 1 1 TB1
6 T7W 516 716 TERMINAL BLOCK 3P(1,2,3) 1 1 1 TB3
7 T7W 251 799 TRANSFORMER 1 1 1 T
8 R01 653 255 OUTDOOR FAN CAPACITOR 4+ 440V 2 2 2 C1,2
T7W 106 708 CONTACTOR MSO-N20KF 1 1 52C
9
T7W A06 708 CONTACTOR MSO-N20KF 1 52C
10 R01 272 428 SOLENOID VALVE 1 1 1
11 T7W 106 242 SOLENOID COIL 1 1 1 21R
12 R01 Z25 425 CAPILLARY TUBE {3.2✕{2.0✕820mm 2 2 2
13 R01 993 418 RESTRICTOR VALVE 2 2 2
R01 A11 450 STRAINER 1
14
R01 42L 450 STRAINER 1 1
15 T7W 260 403 4-WAY VALVE 1 1 1
16 R01 260 242 4-WAY COIL 1 1 1 21S4
R01 943 413 CHARGE PLUG 2 1 1
17
R01 A01 413 CHARGE PLUG 1 1
18 R01 670 411 BALL VALVE 3/4˝ 1 1 1
19 R01 943 410 BALL VALVE 3/8˝ 1 1 1
20 R01 A14 490 OIL SEPARATOR 1 1 1
21 R01 A12 440 ACCUMULATOR 1 1 1
R01 J01 202 OUTDOOR COIL THERMISTOR 1 RT
22
R01 KN7 202 OUTDOOR COIL THERMISTOR 1 1 RT
23 T97 614 300 COMPRESSOR NH-56YDA 1 1 1 MC
T7W 003 236 CRANKCASE HEATER 240V 38W 1 HC
24
T7W A02 236 CRANKCASE HEATER 240V 38W 1 1 HC
25 R01 A00 208 HIGH PRESSURE SWITCH OFF25.5kg/cm ON21kg/cm
2 2
1 1 1 63H1
26 R01 652 238 THERMAL SWITCH CUT125˚C IN90˚C 1 1 1 26C
27 R01 A12 408 HEAT EXCHANGER 2 2 2
28 R01 A00 425 CAPILLARY TUBE {2.5✕{0.6✕1000mm 1 1

37
FUNCTIONAL PARTS 1 6 5 3 4 7 8 9 19
PUH-5YKSA
PUH-5YKSA1 18
PUH-5YKSA3
PUH-6YKSA
PUH-6YKSA1
PUH-6YKSA2
27

17

1
13
12
14
27 15
16
18
11
2 10
20

21

26 24 23 25 22
Part numbers that are circled are not shown in the figure.
,
Q ty/set Price
PUH-5 PUH-6 Wining Recom-
No. Part No. Part Name Specification Remarks Diagram mended
,
YKSA1

YKSA3

YKSA1

YKSA2
YKSA

YKSA

Symbol Q ty
Unit Amount

T7W 276 763 OUTDOOR FAN MOTOR PA6V85-UE 2 MF1,2


1 T7W 256 763 OUTDOOR FAN MOTOR PA6V85-UE 2 2 MF1,2
PA6V100-UG(6YKSA)
T7W 277 763 OUTDOOR FAN MOTOR PA6V100-UH(6YKSA1) 2 2 2 MF1,2
2 R01 A00 115 PROPELLER FAN 2 2 2 2 2 2
T7W 256 315 OUTDOOR CONTROLLER BOARD 1 1 O.B
3
T7W A03 315 OUTDOOR CONTROLLER BOARD 1 1 1 1 O.B
4 R01 520 239 FUSE 250V6.3A 1 1 1 1 1 1 F<O.B>
5 T7W 511 716 TERMINAL BLOCK 5P(1L,L2,L3,N,;) 1 1 1 1 1 1 TB1
6 T7W 516 716 TERMINAL BLOCK 3P(1,2,3) 1 1 1 1 1 1 TB3
38
Part numbers that are circled are not shown in the figure.
,
Q ty/set Price
PUH-5 PUH-6 Wining Recom-
No. Part No. Part Name Specification Remarks Diagram mended
,

YKSA3

YKSA1
YKSA1

YKSA2
YKSA

YKSA
Symbol Q ty Unit Amount

7 T7W 251 799 TRANSFORMER 1 1 1 1 1 1 T


R01 576 255 FAN MOTOR CAPACITOR 3+ 440V 2 2 2 C1,2
8
R01 653 255 FAN MOTOR CAPACITOR 4+ 440V 2 2 2 C1,2
9 T7W 517 708 CONTACTOR S-K20(S-N20)230V 1 1 1 1 1 1 52C
10 R01 A14 428 SOLENOID VALVE 1 1 1 1 1 1
11 T7W 106 242 SOLENOID COIL 1 1 1 1 1 1 21R
R01 KP2 425 CAPILLARY TUBE {4.0✕{2.4✕840mm 2
R01 62L 425 CAPILLARY TUBE {4.0✕{2.4✕840mm 2 2
12
T7W 111 425 CAPILLARY TUBE {4.0✕{2.4✕1200mm 2
T7W A09 425 CAPILLARY TUBE {4.0✕{2.4✕1200mm 2 2
13 R01 993 418 RESTRICTOR VALVE 2 2 2 2 2 2
R01 A14 450 STRAINER 1 1
14 R01 421 450 STRAINER 1 1
R01 42L 450 STRAINER 1 1
T7W 261 403 4-WAY VALVE 1 1
15 R01 V29 403 4-WAY VALVE 1 1 1
T7W 258 403 4-WAY VALVE 1
T7W 260 242 4-WAY COIL 1 1 21S4
16 T7W 258 242 4-WAY COIL 1 1 1 21S4
T7W A01 242 SOLENOID COIL 1 21S4
R01 J01 202 OUTDOOR COIL THERMISTOR 1 1 RT
17
R01 KN7 202 OUTDOOR COIL THERMISTOR 1 1 1 1 RT
R01 943 413 CHARGE PLUG 2 1 1 2 1 1
18
T7W A02 413 CHARGE PLUG 1 1 1 1
19 R01 A14 440 ACCUMULATOR 1 1 1 1 1 1
20 R01 A14 490 OIL SEPARATOR 1 1 1 1 1 1
21 R01 670 411 BALL VALVE 3/4˝ 1 1 1 1 1 1
22 R01 943 410 BALL VALVE 3/8˝ 1 1 1 1 1 1
T97 500 500 COMPRESSOR ZR61K3TFD 1 1 1 MC
23
T97 500 501 COMPRESSOR ZR68KCTFD 1 1 1 MC
24 R01 86H 201 THERMOSTAT CUT125˚C IN90˚C 1 1 1 1 1 1 26C
25 T7W 010 236 CRANKCASE HEATER 240V 38W 1 1 1 1 1 1 HC
26 R01 A00 208 HIGH PRESSURE SWITCH OFF25.5kg/cm2 ON21kg/cm2 1 1 1 1 1 1 63H1
T7W 555 408 HEAT EXCHANGER 2 2 2
27
T7W 556 408 HEAT EXCHANGER 2 2 2
T2W 813 342 RELAY LY2F 240V 10A 1 X15
28
T7W 737 215 RELAY LY2F 240V 10A 1 1 X15
29 R01 597 425 CAPILLARY TUBE {4.0✕{3.0✕2.0mm 1 1 1 1
30 R01 A00 425 CAPILLARY TUBE {2.5✕{0.6✕1000mm 1 1 1 1

39
FUNCTIONAL PARTS 1 6 5 3 4 7 8 9 19
PUH-5TKSA
PUH-6TKSA 18

27

17

1
13
12
14
27 15
16
18
11
2 10
20

21

Part numbers that are circled are not shown in the figure. 26 24 23 25 22
,
Q ty/set Price
Wining Recom-
PUH-5 PUH-6 Remarks Diagram mended
No. Part No. Part Name Specification ,
Symbol Q ty
TKSA TKSA
Unit Amount

1 T7W A04 763 OUTDOOR FAN MOTOR PA6N100-UE 2 2 MF1,2


2 R01 A00 115 PROPELLER FAN 2 2
3 T7W A02 315 OUTDOOR CONTROLLER BOARD 1 1 O.B
4 T7W 520 239 FUSE 250V6.3A 1 1 F<O.B>
5 T7W 513 716 TERMINAL BLOCK 3P(1L,L2,;) 1 1
6 T7W 516 716 TERMINAL BLOCK 3P(1,2,3) 1 1 TB3

40
Part numbers that are circled are not shown in the figure.
,
Q ty/set Wining Recom- Price
No. Part No. Part Name Specification PUH-5 PUH-6 Remarks Diagram mended
,
Symbol Q ty Unit Amount
TKSA TKSA
7 T7W E00 799 TRANSFORMER 1 1 T
8 R01 653 255 FAN MOTOR CAPACITOR 4+ 440V 2 2 C1,2
9 T7W A15 708 CONTACTOR S-N25EX 1 1 52C
10 R01 A14 428 SOLENOID VALVE 1
11 T7W 106 242 SOLENOID COIL 1 1 21R
T7W E00 425 CAPILLARY TUBE {4.0✕{2.4✕840mm 2
12
R01 62L 425 CAPILLARY TUBE {4.0✕{2.4✕840mm 2
13 R01 993 418 RESTRICTOR VALVE 2 2
14 R01 42L 450 STRAINER 1 1
R01 V29 403 4-WAY VALVE 1
15
T7W 258 403 4-WAY VALVE 1
T7W 258 242 4-WAY COIL 1 21S4
16
T7W A01 242 SOLENOID COIL 1 21S4
17 R01 KN7 202 OUTDOOR COIL THERMISTOR 1 1 RT
R01 943 413 CHARGE PLUG 1 1
18
T7W A02 413 CHARGE PLUG 1 1
19 R01 A14 440 ACCUMULATOR 1 1
20 R01 A14 490 OIL SEPARATOR 1 1
21 R01 670 411 BALL VALVE 3/4˝ 1 1
22 R01 943 410 BALL VALVE 3/8˝ 1 1
T97 512 500 COMPRESSOR ZR61KCTF5 1 MC
23
T97 521 501 COMPRESSOR ZR68KCTF5 1 MC
24 R01 86H 201 THERMOSTAT CUT125˚C IN90˚C 1 1 26C
25 T7W E00 236 CRANKCASE HEATER 220V 38W 1 1 HC
26 R01 A00 208 HIGH PRESSURE SWITCH 2
OFF25.5kg/cm ON21kg/cm2
1 1 63H1
T7W 555 408 HEAT EXCHANGER 2
27
T7W 556 408 HEAT EXCHANGER 2
28 T7W A10 425 CAPILLARY TUBE {4.0✕{3.0✕2.0mm 1 1
29 T7W A00 401 DIS.PRES.REGULATOR 1 1

41
9 OPTIONAL PARTS
AIR OUTLET GUIDE
This guide is for changing the outdoor unit air discharge direction. For PUH-4/5/6 type, 2 sets of PAC-292SG are needed.
Part No. PAC-292SG (1 pc/set)
Applied model PUH-1~6K type

538
4 holes
7 524 7 {6

537 7

524

72
7

42
HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100 TELEX J24532 CABLE MELCO TOKYO

cCopyright 1997 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.


Issued in Jun.1997 No.OC128 790 New publication, effective Dec.1997
Issued in Dec.1997 No.OC128 REVISED EDITION-A 1285 Specifications subject to change without notice.
Printed in Japan.