Experiment 1 T: Experiment On Vapor Refigiration Commpression Cycle Without Load
Experiment 1 T: Experiment On Vapor Refigiration Commpression Cycle Without Load
Experiment 1 T: Experiment On Vapor Refigiration Commpression Cycle Without Load
Before starting the experiment, open the shut-off valve. All other capillary tubes remains
closed
Wait until the system reaches a steady state. This is the case if the temperature no longer
varying. The steady state is reached about 20 minutes.
Table1-analysis of experiment 1
Result
o First we need to calculate the compression ratio of the system:-
The compression ratio is the ratio of the outlet pressure of the compressor (p2) to the
pressure at the inlet of the compressor (p1)
𝑟 = 𝑃2/𝑃1
10𝑏𝑎𝑟
r=
1.9𝑏𝑎𝑟
𝑟 = 5.263
Next we can calculate the refrigeration capacity and condensation capacity:-
o The capacity of the condenser can be determined using the mass flow and the enthalpy
difference of the condenser and first let us calculate the mass flow rate of the system from
the volume flow rate:
𝑄𝑂 = 𝑚̇ . (ℎ5 − ℎ4)
𝑚̇ = 𝑉̇ . ⍴
𝜌 = 1.12𝑘𝑔/ 𝐿
= 0.003733333𝑘𝑔/𝑠
= 0.6
Heat of condensation can be calculated
= 0.612 𝑘𝐽/𝑠
𝑊̇ = 𝑄𝑐 − 𝑄0
= 0.012𝐾𝐽/𝑠
𝐶𝑜𝑝 = 50 𝑎𝑛𝑠𝑤𝑒𝑟
Experiment 2:- Steady state operation under load with 6m capillary tube.
The evaporator fan is turned on, to put a greater load on the system. Moreover, in
this experiment the collector is by passed. To do so require the shut-off highlighted in to
be open. The other valves remain closed.
Before starting the experiment, open the capillary tube 6m and All other shut-off
valve remains closed.
Wait until the system reaches a steady state. This is the case if the temperature no
longer varying. The steady state is reached about 20 minutes.
h2 in KJ/kg 432.8
h3 in KJ/kg 244.8
h4 in KJ/kg 244.8
h5 in KJ/kg 415.3
Result
First we need to calculate the compression ratio of the system:-
The compression ratio is the ratio of the outlet pressure of the compressor (p2) to the
pressure at the inlet of the compressor (p1).
𝑟 = 𝑃2 /𝑃1
= 7.9𝑏𝑎𝑟/2𝑏𝑎𝑟
= 3.95
The capacity of the condenser can be determined using the mass flow and the
enthalpy difference of the condenser and first let us calculate the mass flow rate of the
system from the volume flow rate:
𝑄𝑂 = 𝑚̇ . (ℎ5 − ℎ4)
𝑚̇ = 𝑉̇ . 𝜌
= 0.002333𝑘𝑔/𝑠
𝑄𝑂 = 𝑚̇ . (ℎ5 − ℎ4)
= 0.398𝑘𝐽/𝑠
𝑄 𝑐 = 𝑚̇ . (ℎ2 − ℎ3)
𝑊̇ = 𝑄𝑐 − 𝑄𝑂
= 0.439𝑘𝐽/𝑠 − 0.398𝑘𝐽/𝑠
Experiment 3:- Steady state operation under load with 3m capillary tube.
PR0CEDURES FOR MAKING EXPERMENT 3
Before starting the experiment, open the capillary tube 3m and all other shut-off
valve remains closed.
Wait until the system reaches a steady state. This is the case if the temperature no
longer varying. The steady state is reached about 20 minutes.
The measured values are tabulated as below.
Result
First we need to calculate the compression ratio of the system:-
The compression ratio is the ratio of the outlet pressure of the compressor (p2) to the
pressure at the inlet of the compressor (p1)-
𝑟 = 𝑃2 /𝑃1
= 10.2𝑏𝑎𝑟/2.4𝑏𝑎𝑟
= 4.25
The capacity of the condenser can be determined using the mass flow and the
enthalpy difference of the condenser and first let us calculate the mass flow rate of the
system from the volume flow rate:
𝑄𝑂 = 𝑚̇ . (ℎ5 − ℎ4)
𝑚̇ = 𝑉̇ . 𝜌
= 0.00218𝑘𝑔/𝑠
𝑄𝑂 = 𝑚̇. (ℎ5 − ℎ4 )
= 0.343 𝑘𝐽/𝑠
𝑄𝐶 = 𝑚̇ . (ℎ2 − ℎ3)
𝑊̇ = 𝑄𝐶 − 𝑄𝑂
= 0.078𝐾𝐽/𝑠
Experiment 4:- Steady state operation under load with 1.5m capillary tube.
PROCEDURES FOR MAKING EXPERMENT 4
Before starting the experiment, open the capillary tube 1.5m and all other shut-off
valve remains closed.
Wait until the system reaches a steady state. This is the case if the temperature no
longer varying. The steady state is reached about 20 minutes.
Result
First we need to calculate the compression ratio of the system:-
The compression ratio is the ratio of the outlet pressure of the compressor (p2) to the
pressure at the inlet of the compressor (p1)-
𝑟 = 𝑃2 /𝑃1
= 12.9𝑏𝑎𝑟/2.4𝑏𝑎𝑟
= 5.375
And then next we can calculate the refrigeration capacity and condensation capacity:-
The capacity of the condenser can be determined using the mass flow and the
enthalpy difference of the condenser and first let us calculate the mass flow rate of the
system from the volume flow rate:
𝑄𝑂 = 𝑚̇. (ℎ5 − ℎ4 )
𝑚̇ = 𝑉̇ . 𝜌𝐾
= 0.00373𝑘𝑔/𝑠
𝑄𝑂 = 𝑚̇. (ℎ5 − ℎ4 )
= 0.49 𝑘𝐽/𝑠
= 0.623𝑘𝐽/𝑠
𝑊̇ = 𝑄𝐶 − 𝑄𝑂
= 0.133𝐾𝐽/𝑠
2.8 Discussion
Based on the information from the experiment we got three different results which are heat of
condenser, heat of evaporator, work done of the system and Cop. thus results can be depend of
different parameters such as temperature ,enthalpy ,volume flow rate & length of the capillary
tube of the system.
1 5.263 50
2 3.95 9.71
3 4.25 4.4
4 5.375 3.68
Here from the above comparison we can say that as the length of the capillary tube increases
the cop also increase. Therefore in order to have efficient refrigeration system we need to
have higher length of capillary tube. And also the compression ratio increases as the
length of the capillary tube increases.
Conclusion
o From the above 4 different experiments calculated results we can conclude that the COP of
all the capillary tubes ( with 6m,3m,1.5m) are greater than the expansion valve.so it is better
to use the capillary tube instead of the expansion valve for better coefficient of performance.
o From the previously calculated results we can conclude that we have to use longer capillary
tube to have high refrigeration effect and low power consumption of the compressor (high
COP) and the experiment shows that the compression ratio increases as the length of the
capillary tube increases so using longer capillary tube we can achieve efficient compression
at the compressor.
o And also since the experiment shows that with increasing capillary tube length both
evaporation pressure and evaporation temperature fall. And also a longer capillary tube
causes the refrigerant mass flow in the system to decrease. This also reduces the refrigeration
capacity. As a result, less energy needs to be dissipated by the condenser. Our experiment
with 1.5m have a highest refrigeration capacity but have a small cop means it dissipate more
work done so we observe experiment 2 have high cop that wise the evaporator is used
sufficiently and the system works efficiently.
References
Refrigeration and Air Conditioning text book
Thermal lab report on VCRS manual
http://www.mechanicalengineeringblog.com
http://en.m.wikipedia.org
Principles of Refrigeration by R.J. Dossat, Pearson Education, Inc., 1997
Refrigeration and Air Conditioning by C.P.Arora, Tata-McGraw-Hill, 2003
www.google.com
You tube
A Practical Approach HEAT TRANSFER YUNUS A. CENGEL 2nd edition
Fundamentals of Heat and Mass Transfer - Incroperation
Lab manual of tubular forced convection Measured data’s during experiment conduction