4 Set Up 4.

4 CT Configuration
The CT options set the Secondary Current (CT2 5A or 1A) of the
To enter set up mode, hold the button for 3 seconds, until the Current Transformer (CT) that are used with the meter.
Phase to neutral voltages. password screen appears.

The set up is password- Use the and

User Manual protected so you must buttons to select the menu


enter the correct password option. The screen will
2019 v2.0 (default ‘1000’) before show the current setting.
Current on each phase. processing.

SDM630MCT-E Secondary CT Setting:


DIN Rail Smart Energy Meter for Single and Three If an incorrect password
Hold the button to
Phase Electrical Systems is entered, the display will
set the CT secondary
option: 5A (default) or 1A.
show:
Phase to neutral voltage
1 Introduction THD%. PASS Err (Error)
Set the CT Ratio Value:
This document provides operating, maintenance and installation Hold the button to
instructions. This unit measures and displays the characteristics To exit the set up menu, hold the for 3 seconds, the enter the CT Ratio setting
of Single Phase Two Wire (1P2W), Three Phase Three Wire (3P3W) measurement screen will display. screen. The range is from
and Three Phase Four Wire (3P4W) networks. The measuring 0001 to 9999.
parameters include Voltage (V), Current (A), Frequency (Hz), Power Current THD% for each
(kW/KVA/KVAr), Power Factor (PF), Imported, Exported and Total phase. 4.1 Set up Entry Methods
Energy (kWh/kVArh). The unit also measures Maximum Demand The CT Rate is the CT Primary divided by the CT Secondary. For
Current and Power, this is measured over preset periods of up to Some menu items, such as Password and CT, require a four- Example: 200/5A Current Transformers - 200÷5=40, so the CT Rate
60 minutes. digit number entry while others, such as supply system, require would be 0040 and the CT2 would be 5.
selection from a number of menu options.
On the MID Version, you can only program the
This particular model accommodates 1A or 5A Current 3.2 Frequency and Power Factor and Demand
Transformers and can be configured to work with a wide range of CT Rate ONCE.
CTs. It also comes with a complete comms capability with built in Each successive press of the button selects a new range: 4.1.1 Menu Option Selection
Pulse and RS485 Modbus RTU outputs, configuration is password 4.5 CT Reversal
protected. 1. Use the and buttons to scroll through the different If the CT connections are incorrectly wired, they can be reversed
options of the set up menu. through the “Set System Continued” menu:
This unit can be powered from a separate auxiliary supply (AC or Frequency and Power
DC). Alternatively, it can be powered from the monitored supply by 2. Hold the button for 3 seconds to confirm your selection.
Factor (total).
linking the voltage reference and neutral reference in to terminals 5 Use the and
3. If an item flashes, then it can be adjusted by the and
& 6 (Please refer to wiring diagram). buttons to select the
buttons.
menu option. Hold the
4. Having selected an option from the current layer, hold the button to view the
1.1 Unit Characteristics button for 3 seconds to confirm your selection. sub-menu.
Power Factor of each
The SDM630MCT-E can measure and display: 5. Having completed a parameter setting, hold the button for
phase.
• Phase to Neutral Voltage and THD% (Total Harmonic Distortion) 3 seconds to return to a higher menu level. This screen will display,
of all Phases you can change “Forward”
6. On completion of all setting-up, hold the button for 3
• Line Frequency seconds, the measurement screen will then be restored. to “Reverse” on each
individual CT connection.
• Current, Maximum Demand Current and Current THD% of all
Phases
• Power, Maximum Power Demand and Power Factor Maximum Power Demand. 4.1.2 Number Entry Procedure
• Imported, Exported & Total Active Energy Hold the button to
When setting up the unit, some screens require the entering confirm your adjustment.
• Imported, Exported & Total Reactive Energy of a number. In particular, on entry to the setting up section, a You can then move on to
password must be entered. Digits are set individually, from left to IB or IC using the and
The unit has a Password-Protected set up menu for: right. The procedure is as follows: buttons.
• Changing the Password Maximum Current 1. The current digit to be set flashes and then can be adjusted using
• System Configuration - 1P2W, 3P3W, 3P4W. Demand. the and buttons. Hold the button for 3 seconds to exit the set up menu.
• Demand Interval Time 2. Press the button to more right to the next digit. 4.6 PT
• Reset for Demand Measurements
3. After setting the last digit, hold the button for 3 seconds to The PT option sets the Secondary Voltage (PT2 100-500V) of the
• Pulsed Output Duration save your selection. Voltage Transformer (PT) that may be connected to the meter.
3.3 Power
1.2 Current Transformer Primary Current Each successive press of the button select a new range:
Use the and
4.2 Change Password buttons to select the menu
This unit requires configuring to operate with the appropriate
option. The screen will
curren transformer(s), the optional secondary currents are 1A or 5A.
show the current setting.
It is programmed by inputting the ratio (CT Primary divided by the Instantaneous Active The default value is 400V.
CT Secondary). It can be used on primary currents up to 6000A. Power in kW.
Use the and
to choose the change
On the MID Version, you can only program the password option. Secondary PT Setting:
CT Rate ONCE. Hold the button to
set the PT secondary
option: 100-500V.
Instantaneous Reactive
1.3 RS485 Serial – Modbus RTU Power in kVAr.
Hold the button to
This unit is compatible with remote monitoring through RS485 enter the set up menu. The
Modbus RTU. Set-up screens are provided for configuring the first digit will start flashing. Set the PT Ratio Value:
RS485 port. Refers to section 4.8. Hold the button to
enter the PT Ratio setting
screen. The range is from
Instantaneous Volt-Amps 0001 to 9999.
1.4 Pulsed Outputs in KVA. Use and to set
The SDM630MCT-E has Two Pulsed Outputs that can be set for the first digit and press
to move right. The The PT Rate is the PT Primary divided by the PT Secondary. For
active (kWh) or reactive (kVArh) energy. Terminals 9 & 10 (Pulse 1)
next digit will flash. Example: Voltage Transformer - 11000÷110=100, so the PT Rate
are configurable within the setup menu.
Terminals 11 & 10 (Pulse 2) have a fixed output of 3200imp/kWh. would be 0100 and the PT2 would be 110.

4.7 Pulsed Output


Total kW, kVArh, kVA.
2 Start Up Screens Repeat the procedure for
Use this section to configure the Pulsed Output Type.
Units: kVArh (default); kWh.
the remaining three digits.

The first screen lights Use the and


up all display segments 3.4 Energy Measurements buttons to select the menu
and can be used as a option. The screen will
display check. Each successive press of the button selects a new range: After setting the last digit, show the current setting.
Hold the button to
save your selection.

The second screen Imported active energy


in kWh. Hold the button to
indicates the firmware Hold the button for 3 seconds to exit the set up menu. enter the menu option, the
installed in the unit and
current selection will flash.
its build number.

4.3 Supply System


Exported active energy The unit has a default setting of 3 Phase 4 Wire (3P4W). Use the and
The interface performs a in kWh. Use this section to set the type of electrical system. buttons to select the
self-test and indicates the required option. Hold the
result if the test passes. button to confirm the
Use the and selection.
buttons to select the menu
*After a short delay, the screen will display active option. The screen will Hold the button for 3 seconds to exit the set up menu.
Imported reactive energy show the current setting.
energy measurements.
in kVArh.

3 Measurements
Hold the button to
The buttons operate as follows: enter the menu option, the
Exported reactive energy current selection will flash.
Selects the Voltage and Current display in kVArh.
screens. In Set-up Mode, this is the
“Left” (press) or “Escape” (hold 3sec)
button.
Use the and
buttons to select the
Select the Frequency and Power factor required option.
display screens. In Set-up Mode, this is Total active energy in kWh.
the “Up” (press) button.
Hold the button to confirm your adjustment. Hold the
Select the Power display screens. button for 3 seconds to exit the set up menu.
In Set-up Mode, this is the
“Down” (press) button.
Total reactive energy in
kVArh.
Select the Energy display screens.
In Set-up mode, this is the
“Right” (press) or “Enter” (hold 3sec)
button.
Please note the register is 9999999.9 display over two lines.
3.1 Voltage and Current
Each successive press of the button selects a new parameter:
4.7.1 Pulse Rate 4.8.3 Parity 5.5 Interfaces for External Monitoring 7 Installation
You can configure the number of pulses to relate to a defined Three interfaces are provided:
amount of Total Energy.
• RS485 communication channel that can be programmed
Use the and for Modbus RTU protocol
7.1 Single phase two wires
Please note there are limitations that need to be factored in
when setting the pulsed output. This is based upon the relay buttons to select the menu • Relay output indicating real-time measured energy.
output only being able to pulse 2 times per second. option. The screen will (configurable)
show the current setting.
• Pulse output 3200IMP/kWh (not configurable)
For example, If the CT is set to 500/5A on a Single Phase
network this would generate (500Ax230V=115,000 / 1000) The Modbus configuration (baud rate etc.) and the pulse
115kWh which is 31W per second. A setting of 10IMP/kWh relay output assignments (kW/kVArh) are configured through
(10 pulses per kWH) would generate 3 pulses per second. Hold the button to the set-up screens.
This will exceed the 2 pulse per second limitation. enter the menu option, the
current selection will flash.
Pulse settings: 1 Pulse per: 10W (0.01) / 100W (0.1) /
1000W/1kWh (1) / 10kWh (10) / 100kWh (100) /1000kWh
5.5.1 Pulse Output
(1000) Opto-coupler with potential free SPST-NO Contact
Use the and (Contact rating 5-27V DC / Max current input: Imin 2mA and
buttons to select the Imax 27mA DC). The pulse output can be set to generate
required option. pulses to represent kWh or kVArh.
Use the and Range: None (default), Odd
Rate can be set to generate 1 pulse per:
buttons to select the menu or Even.
0.01 = 10 Wh/VArh
option. The screen will
0.1 = 100 Wh/VArh
show the current setting.
On completion of the entry procedure, hold the button 1 = 1 kWh/kVArh
for 3 seconds until the selection stops flashing. 10 = 10 kWh/kVArh
100 = 100 kWh/kVArh
1 2 3 4 5 6 7 8
4.8.4 Stop bits Pulse width 200/100/60 mS.
Hold the button to L N L N
enter the menu option, the
current selection will flash.
5.5.2 RS485 Output for Modbus RTU
Use the and
For Modbus RTU, the following RS485 communication
Use the and buttons to choose the desired pulse
buttons to select the menu
parameters can be configured from the set-up menu: L1
option. The screen will
rate. To save the new setting, hold the button for 3
show the current setting. Baud rate: 2400, 4800, 9600
seconds until the selection stops flashing.
Parity: none (default) / odd / even N
4.7.2 Pulse Duration Stop bits: 1 or 2
Hold the button to
The energy monitored can be active or reactive and the pulse RS485 Network Address: 3 digit number - 001-247
enter the menu option, the
width can be selected as 200, 100 or 60mS. current selection will flash. Modbus™ Word order Hi/Lo byte order is set automatically to
normal or reverse. It cannot be configured from the 7.2 Three phase four wires
set-up menu.

Use the and


Use the and
buttons to select the menu
buttons to select the 5.6 Reference Conditions of Influence
option. The screen will
show the current setting. required option. Quantities
Range: 1 (default) or 2.
Influence Quantities are variables that affect measurement
errors to a minor degree. Accuracy is verified under nominal
On completion of the entry procedure, hold the button value (within the specified tolerance) of these conditions.
Hold the button to for 3 seconds until the selection stops flashing. 9 10 11 12 13 14 15 16 17 18 19 20 9 10 11 12 13 14 15 16 17 18 19 20
enter the menu option, the • Ambient temperature 23°C ±1°C
current selection will flash.
• Input waveform 50 or 60Hz ±2%
• Input waveform Sinusoidal (distortion
Use the and buttons to choose the desired pulse 5 Specifications factor < 0·005)
rate. To save the new setting, hold the button for 3 • Auxiliary supply voltage Nominal ±1%
seconds until the selection stops flashing.
5.1 Measured Parameters • Auxiliary supply frequency Nominal ±1%
• Auxiliary supply waveform (if AC) Sinusoidal (distortion
4.8 Communication The unit can monitor and display the following parameters factor < 0·05)
of a Single Phase Two Wire (1P2W), Three Phase Three Wire
The RS485 port can be used for communication using (3P3W) or Three Phase Four Wire (3P4W) system. • Magnetic field of external origin Terrestrial flux
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Modbus RTU Protocol. To configure the Modbus settings,
such as Address and Baud Rate, this is also done within the L N L N
L N L N L N L N
Password-protected set up menu. 5.1.1 Voltage and Current 5.7 Environment
• Phase to Neutral Voltages 100-289V AC • Operating temperature -25°C to +55°C*
4.8.1 RS485 Address (not for 3P3W supplies).
• Storage temperature -40°C to +70°C*
L1 L1 L1
• Phase to Phase Voltages 173-500V AC
• Relative humidity L2 0 to 95%, L2
(3 Phase supplies only).
non-condensing L3
• Current Phase L3
Use the and • Altitude Up to 3000m N
buttons to select the menu N
option. The screen will • Warm up time 1 minute
show the current setting. 5.1.2 Power factor and Frequency and • Vibration 10Hz to 50Hz, IEC
Max. Demand 60068-2-6, 2g

• Frequency in Hz • Shock 30g in 3 planes

Hold the button to • Instantaneous power: *Maximum operating and storage temperatures are in the
set the meter Address. • Power 0-3600 MW context of typical daily and seasonal variation.
Range: 001(default) to 247.
• Reactive power 0-3600 MVAr
• Volt-amps 0-3600 MVA 5.8 Mechanics
• Power factor
• DIN rail dimensions 72 x 94.5 mm (WxH)
Hold the button to 5.1.3 Energy Measurements per DIN 43880
confirm the selection.
• Mounting DIN rail (DIN 43880)
• Imported/Exported active energy 0 to 9999999.9 kWh
• Sealing IP51 indoor
• Imported/Exported reactive energy 0 to 9999999.9 kVArh
• Material Self-extinguishing UL
Use the and buttons to choose the necessary • Total active energy 0 to 9999999.9 kWh
94 V-0
number, then press the button to move along to the next
• Total reactive energy 0 to 9999999.9 kVArh
number. To save the new setting, hold the button for 3
seconds until the selection stops flashing. 5.9 Declaration of Conformity
5.2 Measured Inputs We, Eastron (Metering) Europe Limited, declare under our
4.8.2 Baud Rate Voltage inputs through 4-way fixed connector with 2.5mm²
sole responsibility as the manufacturer that the poly phase
multifunction electrical energy meter “SDM630MCT-E” correspond
stranded wire capacity. Single Phase Two Wire (1P2W), Three
to the production model described in the EC-type examination
Phase Three Wire (3P3W) or Three Phase Four Wire (3P4W)
certificate and to the requirements of the Directive 2004/22/EC EC
unbalanced. Line frequency measured from L1 Voltage
Use the and type examination certificate number 0120/SGS0142. Identifcation
or L3 Voltage. Three current inputs (six physical terminals) with
buttons to select the menu 2.5mm² stranded wire capacity for connection of external CTs.
option. The screen will number of the NB 0120.
Nominal rated input current 5A or 1A AC RMS.
show the current setting.

Hold the button to


enter the menu option, the 5.3 Accuracy
current selection will flash.
• Voltage 0·5% of range maximum
• Current 0·5% of nominal
• Frequency 0·2% of mid-frequency
6 Dimensions
Use the and • Power factor 1% of unity (0.01)
buttons to select the • Active power (W) ±1% of range maximum
required option.
• Reactive power (VAr) ±1% of range maximum
• Apparent power (VA) ±1% of range maximum
On completion of the entry procedure, hold the button to • Active energy (Wh) Class 1 IEC 62053-21
confirm the setting.
• Reactive energy (VARh) ±1% of range maximum
• Response time to step input 1s, typical, to >99% of
final reading, at 50 Hz.

5.4 Auxiliary Supply

Two-way fixed connector with 2.5mm² stranded wire


capacity. 85-275V AC 50/60Hz ±10% or 120-380V DC ±20%.
Consumption <2W 10VA.

Eastron Europe Limited


0203 758 3494| www.eastroneurope.com | Specifications are subject to change without notice