1 Description

QUINT POWER power supply with integrated decoupling Technical data (short form)
MOSFET, SFB Technology, and preventive function
Input voltage range 85 V AC ... 264 V AC
monitoring ensures superior system availability.
90 V DC … 350 V DC
Mains buffering typ. 36 ms (120 V AC)
Powerful
typ. 36 ms (230 V AC)
- SFB Technology: 6 times the nominal current for
Nominal output voltage (UN ) 24 V DC
15 ms
Setting range of the output voltage 24 V DC ... 28 V DC
- Power reserves:
(USet )
Static boost of up to 125% for a sustained period
Residual ripple < 30 mVPP
Dynamic boost of up to 200% for 5 s
Nominal output current (IN ) 20 A
Static Boost (IStat.Boost ) 25 A (up to 40°C)
Robust
Dynamic Boost (IDyn.Boost ) 30 A (5 s)
Selective Fuse Breaking (ISFB ) 120 A (15 ms)
- Mains buffering ≥ 20 ms
- High degree of electrical immunity, thanks to Output power (PN ) 480 W
integrated gas discharge tube Output power (PStat.Boost ) 600 W
- ATEX/IECEx approval with protective coating Output power (PDyn.Boost ) 720 W
Efficiency typ. 92.7 % (120 V AC)
Secure typ. 94.2 % (230 V AC)
MTBF (IEC 61709, SN 29500) > 524000 h (40°C)
- Safety integrity level 3 (SIL 3) for Overvoltage Ambient temperature (operation) -40 °C ... +75 °C
Protection > 60 °C Derating: 2,5 %/K
Dimensions W/H/D 70 mm / 130 mm / 125 mm
Preventive Weight 1.3 kg

- Comprehensive signaling:
Analog signal, digital signal, relay contact, LED bar
graph

Can be ordered pre-configured

- Perform configuration online and order 1 or more


units

All technical specifications are nominal values and refer to a room temperature of 25 °C and 70 % relative
i humidity at 100 m above sea level.
QUINT4-PS/1AC/24DC/20/+

2 Table of contents

1 Description………………………………………………………………………………………………………………………… .…………………………………………..... 1
2 Table of contents ..................................................................................................................................................................... 2
3 Ordering data .......................................................................................................................................................................... 3
4 Safety Manual ......................................................................................................................................................................... 4
4.1 Stand-alone application of QUINT4-PS/1AC/24DC/20/+ ................................................................................................. 5
4.2 Application of QUINT4-PS/1AC/24DC/20/+ in a 20 Amp redundant power system ........................................................ 6

Safety Manual PHOENIX CONTACT 2/7


QUINT4-PS/1AC/24DC/20/+

3 Ordering data

Description Type Order No. Pcs./Pkt.


Primary-switched QUINT POWER supply for DIN rail QUINT4-PS/1AC/24DC/20/+ 2904617 1
mounting, with selectable output characteristic curve and
SFB Technology (selective fuse breaking) , protective
coating and integrated decoupling MOSFET, input: 1-
phase, output: 24 V DC / 20 A
Preconfigured versions of the primary-switched QUINT QUINT4-PS/1AC/24DC/20/+/… 2908940 1
POWER supply for DIN rail mounting, with selectable output
characteristic curve and SFB Technology (selective fuse
breaking) , protective coating and integrated decoupling
MOSFET, input: 1-phase, output: 24 V DC / 20 A

Starting from quantities of one piece or more, you can order online configured versions of the primary-switched
i power supply QUINT POWER with SFB Technology (selective fuse breaking) using the following web code:
phoenixcontact.net/webcode/#0852.

Accessories Type Order No. Pcs./Pkt.


Universal wall adapter for securely mounting the power UWA 182/52 2938235 1
supply in the event of strong vibrations. The power supply is
screwed directly onto the mounting surface. The universal
wall adapter is attached at the top/bottom.
Assembly adapter for QUINT-PS... power supply on S7- QUINT-PS-ADAPTERS7/1 2938196 1
300 rail

Prior to startup, read the installations notes and check the device for damage.
i For additional information, please refer to the corresponding data sheet and package slip at
phoenixcontact.net/products.

Safety Manual PHOENIX CONTACT 3/7


QUINT4-PS/1AC/24DC/20/+

4 Safety Manual

The Phoenix Contact QUINT4-PS/1AC/24DC/20/+ power supply has been certified to the electrical safety in accordance to
IEC 60950-1 and IEC 61010-1 and multiple EMC standards including EN61000-6-7. The power supply guarantees superior
system availability with integrated decoupling MOSFET and an overvoltage protection circuitry with SIL 3, HFT = 1
certification in accordance with IEC 61508. With a protective coating and ATEX/IECEx approval in accordance with the
standards IEC 60079-0, IEC 60079-7, IEC 60079-11, and IEC 60079-15, it can also be mounted within potentially explosive
areas (zone 2).

The fourth generation of the high-performance QUINT POWER power supplies ensures superior system availability by
means of new functions. Signaling thresholds and characteristic curves can be individually adjusted via the NFC interface.
The unique SFB technology and preventive function monitoring of the QUINT POWER power supply increase the availability
of your application.

The overvoltage protection circuitry build in Phoenix Contact QUINT4-PS/1AC/24DC/20/+ (2904617) can be used to set up
single or redundant bulk power system with proven Overvoltage Protection (OVP). The power supply can be used in
applications up to SIL 3 according to IEC 61508 and IEC 61511.

The following application show how to use the Phoenix Contact QUINT4-PS/1AC/24DC/20/+ power supply to set up a:

 Single power application for 20 Amp with OVP for SIL 3


 Redundant power application for 20 Amp with OVP for SIL 3

Safety Manual PHOENIX CONTACT 4/7


QUINT4-PS/1AC/24DC/20/+

4.1 Stand-alone application of QUINT4-PS/1AC/24DC/20/+

Safety Function and Failure behavior:

The overvoltage protection circuitry implemented in QUINT4-PS/1AC/24DC/20/+ power supply is considered to be


operating as a Type A component, having Hardware Fault Tolerance (HFT) = 1. The safety function is to limit the output
voltage to 30V and if higher to switch off within 20ms.

The safe state is no output voltage.

Failure rates of the electronic components are calculated according to Siemens SN 29500.

Safety parameter: Overvoltage protection circuitry implemented in Phoenix Contact QUINT4-PS/1AC/24DC/20/+ in a stand-
alone application.

Value Remark

Safety Integrity Level SIL 3 IEC 61508, IEC 61511

PFH [1/h] 9.1 E-10 corresponds to < 1% of SIL 3

Corresponds to 5.6 % of SIL 3;


PFDavg 5.58 E-05 this value is valid for the stated
Proof Test Interval T1

Proof Test Interval T1 15 a

SFF > 60%

HFT 1

The overvoltage protection circuitry implemented in QUINT4-PS/1AC/24DC/20/+ power supply fulfils the requirement up
to SIL 3 and can be used in applications up to SIL 3 according to IEC 61508 and IEC 61511.

Safety Manual PHOENIX CONTACT 5/7


QUINT4-PS/1AC/24DC/20/+

4.2 Application of QUINT4-PS/1AC/24DC/20/+ in a 20 Amp redundant power system

Safety Function and Failure behavior:

The 1+1 redundant power system build up with path 1 and path 2 provides a symmetrical load sharing operation and
increases the system availability. Use the same cable cross sections and the same cable lengths for wiring for the DC
convergence point to avoid unbalanced load sharing. In the absence of path 1, path 2 will take over the output power and
securely supply the load. In the absence of path 2, path 1 will take over the output power and securely supply the load. If
both paths are missing, the output will be switched off and the power system will have a safe state.

The overvoltage protection circuitry implemented in QUINT4-PS/1AC/24DC/20/+ power supply is considered to be


operating as Type A component, having Hardware Fault Tolerance (HFT) = 1. The safety function is to limit the output
voltage to 30V and if higher to switch off within 20ms.

The safe state is no output voltage.

Failure rates of the electronic components are calculated according to Siemens SN 29500.

Safety Manual PHOENIX CONTACT 6/7


QUINT4-PS/1AC/24DC/20/+

Safety parameter: Overvoltage protection circuitry implemented in QUINT4-PS/1AC/24DC/20/+ in a 20 Amp redundant


power application.

Value Remark

Safety Integrity Level SIL 3 IEC 61508, IEC 61511

PFH [1/h] 1.8 E-09 corresponds to < 2% of SIL 3

Corresponds to 11 % of SIL 3;
PFDavg 1.1 E-04 this value is valid for the stated
Proof Test Interval T1

Proof Test Interval T1 15 a

SFF > 60%

HFT 1

The overvoltage protection circuitry implemented in QUINT4-PS/1AC/24DC/20/+ power supply fulfils the requirement up
to SIL 3 and can be used in redundant applications (1+1 and N+1) up to SIL 3 according to IEC 61508 and IEC 61511.