KB6000III Modbus Protocol Instruction

1. Key figures:

 Bud rate: 4800 (optional of 9600 and 19200).

 8 digits of figure and 1 digit of stop. No verification digit (verification of odd

number and even number can be set)

 Device address ID is adjustable and the initial ID is 99.

2. Command code of reading the device information is 03. No other code is not

available now.

3. Below offsets can store different information. Some information (like the

quantity of the connected detectors) will only be stable after powering on for some

time. After power on, the device will automatically search for the detectors being

connected and this time will last for 2 minutes.

 offset 0: Quantity of the detectors

 offset 1: second

 offset 2: minute

 offset 3: hour

 offset 4: day

 offset 5: week

 offset 6: month
 offset 7: year

 Offset 500: to start save the structural morphology of each detector in turns. The

length of each morphology is 11 and total length is 11 * detector quantity.

Syllable Meaning

0 number; Serial number enumeration

1 name; Gas name enumeration

2 deepness; concentration signed number

3 unit; Unit enumeration

4 point; Scaling position exponent arithmetic of 10 signed number

5 state; status enumeration

6 preserve0 preserved

7 preserve1 preserved

8 preserve2 preserved

9 preserve3 preserved

10 preserve4 preserved

Final gas level = deepness * 10^(-point)

All the detectors will be displayed in turns automatically.


/*---- Status definition-------------------------------------------------*/

NODE_STATE_WARM_UP 0x00 Warm-up

NODE_STATE_NORMAL 0x01 Normal

NODE_STATE_DATA_ERROR 0x02 Data default

NODE_STATE_SENSOR_FAULT 0x03 Sensor fault

NODE_STATE_EARLY_WARING 0x04 Pre-alarm

NODE_STATE_LOW_ALARM 0x05 Low alarm

NODE_STATE_HIGH_ALARM 0x06 High alarm

NODE_STATE_VISIT_FAULT 0x07 Access failure

NODE_STATE_OUTRANGE 0x08 Over range

NODE_STATE_NEED_ADJUST 0x09 Need calibration

NODE_STATE_OUT_TIME 0x0A Overtime

NODE_STATE_ALARM_STEL 0x0B STEL alert

NODE_STATE_ALARM_TWA 0x0C TWA alert

NODE_STATE_COM_FAULT 0x0F Communications fault

NODE_STATE_1_SQUARE 0x80
NODE_STATE_2_SQUARE 0xA0

NODE_STATE_3_SQUARE 0xC0

/*----- Unit definition-------------------------------------------------------- */

/* Prefix P and it’s unit*/

UNIT_P_LEL 0x01 %lel

UNIT_P_VOL 0x02 %vol

UNIT_PPM 0x03 PPM

/*----- Gas type definition------------------------------------------------------*/

NAME_NEW_TYPE 0x00 New type

NAME_CH4 0x01 CH4

NAME_NH3 0x02 NH3

NAME_H2S 0x03 H2S

NAME_CO 0x04 CO

NAME_O2 0x05 O2

NAME_H2 0x06 H2
Working mode, KB6000III address ID, Bud rate and verification method can be set in

the menu of “factory setting”.

Working mode: mod 00 01 (00: rtu 01: ascii) (Initial is 00)

Address ID: addr 01-250 (Initial is 50)

Bud rate: buad 00 01 02 (00: 4800 01:9600 02:19200) (Initial is 4800)

Verification: pari 00 01 02 (00: none 01: odd 02: even) (Initial is none)

Note:

1. In working status, if modifying the setting, the device will not work normally. So

after setting, please reset the device, then the setting can be activated.

2. Technically speaking, the maximum frame length is 256. But if mass data is read

each time, transmission error rate is very a little big. So please reduce the reading

data and we suggest the frame length is within 60.