R02 - Cable Loss Calc - 30032023
R02 - Cable Loss Calc - 30032023
R02 - Cable Loss Calc - 30032023
2) CABLE REACTANCE -
3) CABLE CURRENT RATING -
INVERTER TO ACDB
Description Cable Clasification Input Values Electrical Charactersitics Voltage Drop Power Loss
S. No. Cable Size No. of Runs Power Full Load Current Per cable run Current Carrying Effective AC
From To (Sqmm) Type of Cable Cable Length (m) (Nos.) (P) in Watt at unity pf current (A) capacity(A) Derating Factor Rating(A) Resistance(Ω/Km AC Reactance
50 Hz
at Impedance MF @
UNITY PF Voltage Drop %Voltage Drop
P drop = No. of
Runs*3*I*I*R*L in Watt
%
P drop in Watt
) at 90 deg
1 INVERTER 1 ACDB 3.5C X 120 Al 20 1 125000 205 205 249 0.78 195.02 0.33 0.071 0.28 1.96 0.47 693.82 0.56
2 INVERTER 2 ACDB 3.5C X 25 Al 25 1 33000 54 54 93 0.78 72.84 1.54 0.081 1.31 3.06 0.74 286.42 0.87
AVG. VOL. DROP 0.60 0.71
1 ACDB CLIENT LT PANEL 3.5C X 240 Al 160 1 158000 259 259 392 0.89 348.88 0.161 0.072 0.14 9.81 2.363 4393.1 2.8
INVERTER TO ACDB
Description Cable Clasification Input Values Electrical Charactersitics Voltage Drop Power Loss
Full Load AC Impedance MF
S. No. Cable Size No. of Runs Power Per cable run Current Carrying Effective AC Reactance at @ UNITY PF P drop = No. of %
From To Type of Cable Cable Length (m) Current at unity Derating Factor Resistance(Ω/K Voltage Drop %Voltage Drop
(Sqmm) (Nos.) (P) in Watt current (A) capacity(A) Rating(A) 50 Hz Runs*3*I*I*R*L in Watt P drop in Watt
pf m) at 90 deg
1 INVERTER 1 ACDB 3.5C X 35 Al 15 1 50000 82 82 114 0.78 89.28 1.11 0.079 0.94 2.01 0.48 284.36 0.57
2 INVERTER 2 ACDB 3.5C X 25 Al 20 1 33000 54 54 95 0.78 74.40 1.54 0.081 1.31 2.45 0.59 229.13 0.69
AVG. VOL. DROP 0.54 0.63
1 ACDB CLIENT LT PANEL 3.5C X 120 Al 85 1 83000 136 136 249 0.89 221.61 0.330 0.071 0.28 5.61 1.35 1320.08 1.59
INVERTER TO ACDB
S. No. Description Cable Clasification Input Values Electrical Charactersitics Voltage Drop Power Loss
AC Impedance MF @
Cable Size Power Full Load Current Per cable run Current Carrying Effective Resistance(Ω/Km AC Reactance at UNITY PF P drop = No. of %
From To (Sqmm) Type of Cable Cable Length (m) No. of Runs (Nos.) (P) in Watt at unity pf current (A) capacity(A) Derating Factor Rating(A) 50 Hz Voltage Drop %Voltage Drop Runs*3*I*I*R*L in Watt P drop in Watt
) at 90 deg
1 INVERTER 1 ACDB 3.5C X 120 Al 15 1 125000 205 205 249 0.70 175.07 0.33 0.071 0.28 1.47 0.35 520.36 0.42
2 INVERTER 2 ACDB 3.5C X 120 Al 26 1 125000 205 205 249 0.70 175.07 0.33 0.071 0.28 2.55 0.61 901.96 0.72
3 INVERTER 3 ACDB 3.5C X 120 Al 33 1 125000 205 205 249 0.70 175.07 0.33 0.071 0.28 3.23 0.78 1144.79 0.92
4 INVERTER 4 ACDB 3.5C X 25 Al 59 1 33000 54 54 95 0.78 74.40 1.54 0.081 1.31 7.23 1.74 675.94 2.05
4 INVERTER 5 ACDB 3.5C X 25 Al 59 1 33000 54 54 95 0.78 74.40 1.54 0.081 1.31 7.23 1.74 675.94 2.05
AVG. VOL. DROP 1.05 1.23
Cable Size Power Full Load Current Per cable run Current Carrying Effective AC
From To (Sqmm) Type of Cable Cable Length (m) No. of Runs (Nos.) (P) in Watt at unity pf current (A) capacity(A) Derating Factor Rating(A) Resistance(Ω/Km AC Reactance
50 Hz
at Impedance MF
@ UNITY PF Voltage Drop %Voltage Drop
P drop = No. of
Runs*3*I*I*R*L in Watt
%
P drop in Watt
) at 90 deg
1 ACDB CLIENT LT PANEL 3.5C X 240 Al 85 3 408000 668 223 392 0.7031 275.6152 0.161 0.072 0.14 4.48 1.08 5187.5 1.27
TOTAL VOL. DROP 2.13 2.50
INVERTER TO ACDB
Description Cable Clasification Input Values Electrical Charactersitics Voltage Drop Power Loss
Impedance MF @
S. No. AC UNITY PF
From To Cable Size (Sqmm) Type of Cable Cable(m)
Length No. of Runs
(Nos.)
Power
(P) in Watt
Full Load Current at
unity pf
Per cable run current
(A)
Current Carrying
capacity(A) Derating Factor Effective Rating(A) Resistance(Ω/Km) AC Reactance
Hz
at 50 Voltage Drop %Voltage Drop P drop = No. of
Runs*3*I*I*R*L in Watt
%
P drop in Watt
at 90 deg
1 INVERTER 1 ACDB 3.5C X 120 Al 24 1 125000 205 205 249 0.89 221.61 0.33 0.071 0.28 2.35 0.57 832.58 0.67
AVG. VOL. DROP 0.57 0.67
1 ACDB CLIENT LT PANEL 3.5C X 120 Al 60 1 125000 205 205 249 0.89 221.61 0.33 0.071 0.28 5.87 1.42 2081.45 1.67
TOTAL VOL. DROP 1.98 2.33
INVERTER TO ACDB
Description Cable Clasification Input Values Electrical Charactersitics Voltage Drop Power Loss
Impedance MF @
S. No. AC UNITY PF
From To Cable Size (Sqmm) Type of Cable Cable(m)
Length No. of Runs
(Nos.)
Power
(P) in Watt
Full Load Current at
unity pf
Per cable run current
(A)
Current Carrying
capacity(A) Derating Factor Effective Rating(A) Resistance(Ω/Km) AC Reactance
Hz
at 50 Voltage Drop %Voltage Drop P drop = No. of
Runs*3*I*I*R*L in Watt
%
P drop in Watt
at 90 deg
1 INVERTER 1 ACDB 3.5C X 120 Al 24 1 125000 205 205 249 0.89 221.61 0.33 0.071 0.28 2.35 0.57 832.58 0.67
AVG. VOL. DROP 0.57 0.67
1 ACDB CLIENT LT PANEL 3.5C X 120 Al 60 1 125000 205 205 249 0.89 221.61 0.33 0.071 0.28 5.87 1.42 2081.45 1.67
TOTAL VOL. DROP 1.98 2.33
`
SITE NAME Main Store -1 ( RCC Roof)
DC CAPACITY 316.1 kWp
AC CAPACITY 241 KW
1 INVERTER 1 3.5C X 120 Al 40 1 125000 205 205 249 0.89 221.61 0.33 0.071 0.28 3.92 0.94 1387.63 1.11
ACDB-1
2 INVERTER 2 3.5C X 25 Al 10 1 33000 54 54 95 0.78 74.40 1.54 0.081 1.31 1.22 0.30 114.57 0.35
3 INVERTER 3 3.5C X 35 Al 40 1 50000 82 82 114 0.70 80.15 1.11 0.787 0.94 5.35 1.29 758.29 1.52
ACDB-2
4 INVERTER 4 3.5C X 25 Al 10 1 33000 54 54 95 0.78 74.40 1.54 0.081 1.31 1.22 0.30 114.57 0.35
AVG. VOL. DROP 0.71 0.83
Cable Size No. of Runs Power Full Load Current Per cable run current Current Carrying Effective AC Resistance(Ω/Km) at AC Reactance at Impedance MF P drop = No. of Runs*3*I*I*R*L in %
From To (Sqmm) Type of Cable Cable Length (m) (Nos.) (P) in Watt at unity pf (A) capacity(A) Derating Factor Rating(A) 90 deg 50 Hz @ UNITY PF Voltage Drop %Voltage Drop Watt P drop in Watt
1 ACDB-1 CLIENT LT PANEL 3.5C X 240 Al 160 2 158000 259 129 392 0.7031 275.6152 0.161 0.072 0.14 4.90 1.18 2196.5 1.39
2 ACDB-2 CLIENT LT PANEL 3.5C X 120 Al 45 1 83000 136 136 249 0.89 221.61 0.330 0.071 0.28 2.97 0.72 698.86 0.84
1 INVERTER 1 3.5C X 120 Al 45 1 125000 174 174 249 0.89 221.61 0.33 0.071 0.28 3.74 0.90 1127.88 0.90
ACDB-1
2 INVERTER 2 3.5C X 120 Al 126 1 125000 174 174 249 0.89 221.61 0.33 0.071 0.28 10.48 2.53 3158.07 2.53
AVG. VOL. DROP 1.71 1.71
1 ACDB CLIENT LT PANEL 3.5C X 240 Al 120 3 250000 409 136 392 0.7031 275.6152 0.161 0.072 0.14 3.88 0.93 2749.6 1.10
TOTAL VOL. DROP 2.65 2.81
1 INVERTER 1 3.5C X 120 Al 82 1 125000 205 205 249 0.89 221.61 0.33 0.071 0.28 8.03 1.93 2844.64 2.28
2 INVERTER 2 3.5C X 25 Al 25 1 33000 54 54 95 0.78 74.40 1.54 0.081 1.31 3.06 0.74 286.42 0.87
ACDB
3 INVERTER 3 3.5C X 120 Al 120 1 125000 205 205 249 0.89 221.61 0.33 0.071 0.28 11.75 2.83 4162.89 3.33
4 INVERTER 4 3.5C X 25 Al 90 1 33000 54 54 95 0.78 74.40 1.54 0.081 1.31 11.02 2.66 1031.10 3.12
AVG. VOL. DROP 2.04 2.40
1 ACDB CLIENT LT PANEL 3.5C X 240 Al 85 3 316000 517 172 392 0.7031 275.6152 0.161 0.072 0.14 3.47 0.84 3111.8 0.98
TOTAL VOL. DROP 2.88 3.38