ARLIETTE RESIDENCE - 12926 SW 266 TERRACE Calcs 10 08 24
ARLIETTE RESIDENCE - 12926 SW 266 TERRACE Calcs 10 08 24
ARLIETTE RESIDENCE - 12926 SW 266 TERRACE Calcs 10 08 24
CONSULTING ENGINEERS
CERTIFICATION OF AUTH. # 31618
14021 SW 143rd Court - Bay 1, Miami, Florida 33186 - Phone -Fax # (305) 253-9442
PROJECT:
ALUMINUM ROOFED STRUCTURE 40'-0"x13'-0"
GCpn1 = -0.60
- Fig. 30.9-1B - Using EA and hc/he
GCpn2 = 0.60
P design = qh * GCpn
W1 = -33.99 psf - CRITICAL UPLIFTING WIND PRESSURE
W2 = 33.99 psf - CRITICAL GRAVITY WIND PRESSURE
1.- CHECKING CRITICAL MAIN BEAM - SPAN = 12' - 2" - (1) ALUMINUM RT 2"X6"X1/8"
Afferent Width b= 6.00 ft
W = PASD1 x b = 272.35 Lb/ft
Critical Single Span, L = 12.17 ft
W x L2 = 5039 lbs-ft
M=
8
Then M = 60.47 Kip-in
CHECKING TO BENDING:
(UnWelded - See reference ADM 2020 - Table 2-19) - Elements in Flexural Compression
With : l=b/t= 33.1 < 46 < 77
Then Fb(UnWelding elements in flexure) = 40.5 - 0.262λ 28.45 Ksi - 6061T6 Alloy
Then Srqr'd = M = 2.13 in3
Fb
Then try with : (1) RT 2"x6"x1/8"
Sxx = 2.76 in3 > Srqr'd = 2.13 in3 O.K.
Ixx = 8.28 in4
CHECKING DEFLECTION:
5 * W * L4 = 0.51 in
384 * EAlum * Ixx
Then 0.51 in < 0.61 in (L/240) O.K.
(Critical Reaction) Rf1a = WxL/2 = 1657 Lbs By Critical Gravity Combination at ends
Rf1b = 525 Lbs By Critical Uplift Combination at ends
CONSIGN, LLC
CONSULTING ENGINEERS
CERTIFICATION OF AUTH. # 31618
14021 SW 143rd Court - Bay 1, Miami, Florida 33186 - Phone -Fax # (305) 253-9442
2.- CRITICAL COLUMN - LENGHT= 7'- 6" - (1) ALUMINUM SQ.T 6"X6"X1/8"
Try Using: (1) ALUMINUM SQ.T 6"X6"X1/8"
3.- CHECKING TYPICAL INSULATED ALUMINUM PANEL - (1) 3"x0.024"x2 SKIN BY ELITE ALUMINUM CORP.
WINDSPEED= 175 MPH - FBC 2023 - Figure 1609.3
EXPOSURE CATEGORY= "C" - FBC 2023 - 3105.4.2.2
CRITICAL PRESURE= 45.4 psf < 50 psf O.K. SEE DOC FL7561-R7 ATTACHED
CRITICAL SPAN= 12.00 ft < 13,76 ft (L/120) O.K. SEE DOC FL7561-R7 ATTACHED
Try using : (2) 1/2"ɸ S.S Wedge Bolt Anchor per Plate (Min. embed. 4 1/2") Into Concrete Wall
Spacing Between Bolts > 6 in 100% - For Tension
Edge Distance > 4 in 100% - For Tension
SHEAR CHECK
Ru = 1425 x 2 Anchors x 100%
2850 lbs > 1657 lbs O.K.
Then use : (2) 1/2"ɸ S.S Wedge Bolt Anchor per Plate (Min. embed. 4 1/2") Into Concrete Wall
CONSIGN, LLC
CONSULTING ENGINEERS
CERTIFICATION OF AUTH. # 31618
14021 SW 143rd Court - Bay 1, Miami, Florida 33186 - Phone -Fax # (305) 253-9442
7.- CHECKING ALUMINUM REAR CHANNEL TO EXISTING CONCRETE WALL CONNECTION - DETAIL B
Crit. Gravity Load = G = 136 lbs Per Connection
Try using : (1) 1/4"ɸ S.S Tapcon @ max 6" O.C (Min. embed. 1 3/4") Into Existing Concrete Tie Beam
Spacing Between Bolts > 2 in 100% - For Shear
Edge Distance > 2.5 in 100% - For Shear
SHEAR CHECKING
Ru = 297 x 1 Tapcon x 100%
297 lbs > 136 lbs O.K.
Then use : (1) 1/4"ɸ S.S Tapcon @ max 6" O.C (Min. embed. 1 3/4") Into Existing Concrete Tie Beam
2
Then use : (5) 5/8"Φ Reinf. Bar (1.53 in ) Both Ways - Bottom Reinforcement.
BCIS Home Log In User Registration Hot Topics Submit Surcharge Stats & Facts Publications Contact Us BC
Product Approval
USER: Public User
Product Approval Menu > Product or Application Search > Application List > Application Detail
FL # FL7561-R7
Application Type Revision
Code Version 2023
Application Status Approved
Comments
Archived
Category Roofing
Subcategory Products Introduced as a Result of New Technology
https://floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDqsqJkzX72BeuCecN82vc%2bRByiZtb8kp21A%3d 1/2
1/31/24, 11:24 AM Florida Building Code Online
Summary of Products
Back Next
The State of Florida is an AA/EEO employer. Copyright 2007-2013 State of Florida. :: Privacy Statement :: Accessibility Sta
Under Florida law, email addresses are public records. If you do not want your e-mail address released in response to a publi
electronic mail to this entity. Instead, contact the office by phone or by traditional mail. If you have any questions, please cont
Section 455.275(1), Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide th
address if they have one. The emails provided may be used for official communication with the licensee. However email addres
not wish to supply a personal address, please provide the Department with an email address which can be made available to
are a licensee under Chapter 455, F.S., please click here .
Product Approval Accepts:
https://floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDqsqJkzX72BeuCecN82vc%2bRByiZtb8kp21A%3d 2/2
Do Kim & Associates, LLC
Consulting Structural Engineers
Certificate of Independence
Do Kim and Associates, LLC and Do Kim, P.E. do not have nor will acquire financial interest in the
company manufacturing or distributing the product or in any other entity involved in the approval process
of the product named in the accompanying Florida Product Approval.
Digitally signed by Do Y
Do Y Kim Kim
Date: 2023.08.01
12:09:24 -04'00'
Do Kim, P.E.
FL #49497
Scope:
This product evaluation report issued by Do Kim and Associates, LLC and Do Kim, P.E. for Elite
Aluminum Corporation is based on Florida Department of Business and Professional Regulation Rule
61G20-3.005 (2) Method 2 (b) of the State of Florida Product Approval. Re-evaluation of this product
shall be required following pertinent Florida Building Code modifications or updates.
Do Kim and Associates, LLC and Do Kim, P.E. do not have nor will acquire financial interest in the
company manufacturing or distributing the product or in any other entity involved in the approval process
of the product named herein.
This product has been evaluated for use in locations adhering to the Florida Building Code, 8th Edition
(2023 FBC) and where pressure and deflection requirements, as determined by Chapter 16 of the Florida
Building Code, do not exceed the design pressures as shown on the approval.
Digitally signed by
Do Y Kim Do Y Kim
Date: 2023.08.20
19:01:43 -04'00'
Do Kim, P.E.
FL #49497
Supporting Documents
1. Code Compliance
a. The product assembly described herein has demonstrated compliance with the Florida
Building Code 8th Edition (FBC), Section 1708.2.
2. Drawings:
a. Drawing No. FL-1001 titled “EPS Foam Core Composite Panels”, Sheets 1 and 2
prepared by Do Kim and Associates, LLC., signed and sealed by Do Kim, P.E.
3. Testing
a. Testing per ASTM E72 as performed by Hurricane Engineering & Testing, Inc. (HETI),
and reported in test report numbers HETI-05-1988, HETI-06-2104, HETI-06-2066,
HETI-06-2105, HETI-06-2067, HETI-05-1002, HETI-06-2107, HETI-05-1987, HETI-
06-2069, HETI-06-2070, HETI-06-2071, HETI-05-1994, HETI-05-1991, HETI-06-2072,
HETI-06-2073, HETI-06-2074, HETI-05-1996, HETI-05-1989, HETI-05-1993, HETI-
05-1985, HETI-05-1995, HETI-05-1990, HETI-05-1997, HETI-05-2037, HETI-05-2029,
HETI-05-2039, HETI-05-2030, HETI-05-2041, HETI-05-2048, HETI-05-2036, HETI-
05-2031, HETI-05-2038, HETI-05-2065, HETI-05-2040, HETI-05-2042.
4. Calculations
a. Panel performance engineering analysis for tested loading conditions have been prepared
based on comparative and/or rational analysis, prepared, and submitted by Do Kim, P.E.
5. Other
a. Quality Assurance Agreement verified with Quality Auditing-Institute, LTD. (QAI
Laboratories, LTD.) (FBC Organization #QUA7628).
1. Code Compliance
a. The product assembly described herein has demonstrated compliance with the Florida
Building Code 8th Edition (FBC), Section 1708.2.
2. Large and small missile impact resistance has NOT been tested to or evaluated for in this
approval. In HVHZ, this product shall be used in structures “not to be considered living areas”
per Section 1616 unless impact resistance in accordance to the HVHZ requirements are met.
3. Each product listed above shall be installed in strict compliance with its respective Product
Evaluation Document and site-specific engineering along with all components noted herein.
4. Use of each product shall be in strict accordance with its Product Approval Evaluation and
Limitations of Use.
6. Composite panels shall be constructed using type 3003-H154 or 3105-H154 aluminum facings, 2 PCF
ASTM C-578 Kingspan Insulation LLC brand EPS foam insulation (NOA No. 22-0627.04) or Imperial
Foam & Insulation MFG. CO. adhered to aluminum facings with Ashland Chemical 2020D ISO grip.
Fabrication to be by Elite panel products only in accordance with approved fabrication methods.
7. Elite roof panels maintain a UL 1715 (int) class ‘B’ (ext) rating and are NER-501 approved.
8. This specification has been designed and shall be fabricated in accordance with the requirements
of the FBC, composite panels comply with Chapter 7 Section 720, Chapter 8 Section 803, Class
A interior finish, and Chapter 26 Section 2603. All local building code amendments shall be
adhered to as required.
9. The designer shall determine by accepted engineering practice the allowable loads for site
specific load conditions (including load combinations) using the data from the allowable load
tables and spans in this approval.
10. Deflection limits and allowable spans have been listed to meet FBC including the HVHZ (L/80
for spans < 12’-0” and L/180 for spans > 12’-0”).
11. All supporting host structures shall be designed to resist all superimposed loads.
12. All components which are permanently installed shall be protected against corrosion,
contamination, and other such damage.
13. Size and Span Limitations:
a. Composite panels shall be limited to those specific panels listed in the DWG. FL-1001.
b. Panel spans shall not exceed those listed in the tables of DWG. FL-1001.
14. ELITE ALUMINUM PANELS ARE LABELED WITH A FL7561 LABEL TO ENSURE
BUILDING INSPECTOR THAT THE INSULATED PANELS INSTALLED ARE APPROVED
FOR USE IN THE STATE OF FLORIDA.