ARLIETTE RESIDENCE - 12926 SW 266 TERRACE Calcs 10 08 24

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

CONSIGN, LLC

CONSULTING ENGINEERS
CERTIFICATION OF AUTH. # 31618
14021 SW 143rd Court - Bay 1, Miami, Florida 33186 - Phone -Fax # (305) 253-9442

PROJECT:
ALUMINUM ROOFED STRUCTURE 40'-0"x13'-0"

Work at: 12926 SW 266th Terrace


Homestead, FL 33032, EE. UU.

CUSTOMER: ARLIETTE RESIDENCE

DESIGNER: Adolfo Espino P.E.


STATE OF FLORIDA REG. # 98949

CODES AND SPECIFICATIONS:


F.B.C 2023 8TH EDITION
A.S.C.E. 7-22
ALUMINUM DESIGN MANUAL 2020
A.I.S.C 16TH EDITION
ACI 318-19
CONSIGN, LLC
CONSULTING ENGINEERS
CERTIFICATION OF AUTH. # 31618
14021 SW 143rd Court - Bay 1, Miami, Florida 33186 - Phone -Fax # (305) 253-9442
ALUMINUM ROOFED STRUCTURE 40'-0"x13'-0" - CALCULATIONS
DESIGN CRITERIA & APPLICABLE CODES
F.B.C 2023 8TH EDITION
A.S.C.E. 7-22
ALUMINUM DESIGN MANUAL 2020
A.I.S.C 16TH EDITION
ACI 318-19

WIND LOAD CALCULATIONS - Z < 60 ft


WIND CODE : ASCE 7-22
RISK CATEGORY : II
WINDSPEED : V= 175 MPH - FBC 2023 - Figure 1609.3

MEAN ROOF HEIGHT : Z= 8.50 ft < 60 ft


EXPOSURE CATEGORY : "C" - FBC 2023 - 3105.4.2.2
EFFECTIVE AREA, EA = 40.00 ft X 13.00 ft = 520.00 ft2
Kzt = 1 - Section 26.8-2 ASCE 7-22
Kd = 0.85 - Table 26.6-1 ASCE 7-22
Kz = 0.85 - Table 26.10-1 ASCE 7-22
qh = 0.00256 * Kz * Kzt Kd * V2 - Section 30.3-1
56.64 psf
And:
hc = 8.50 ft - Mean Canopy height
he = 15.0 ft - Mean Eave height
hc/he = 0.57

GCpn1 = -0.60
- Fig. 30.9-1B - Using EA and hc/he
GCpn2 = 0.60
P design = qh * GCpn
W1 = -33.99 psf - CRITICAL UPLIFTING WIND PRESSURE
W2 = 33.99 psf - CRITICAL GRAVITY WIND PRESSURE

CHECKING LOADS COMBINATIONS. - ASCE 7-22


Live Load - L = 20 psf - DESIGN LOADS PER ASCE 7-22
Dead Load - D = 10 psf - DESIGN LOADS PER ASCE 7-22
Wind Load - W1 = -33.99 psf - CRITICAL UPLIFTING WIND PRESSURE
Wind Load - W2 = 33.99 psf - CRITICAL GRAVITY WIND PRESSURE
1.- D 4.- D+0.6W
2.- D+L 5.- D+0.75L+0.6W
3.- D+0.75L 6.- 0.6D+0.6W

CRITICAL DESIGN LOADS:


LIVE LOAD, L = 20.0 #/SQF
DEAD LOAD, D = 10.0 #/SQF
AWAY WIND LOAD, W1 = -33.99 #/SQF
TOWARD WIND LOAD, W2 = 33.99 #/SQF
CRITICAL GRAVITY COMBINATION (D+0.75L+0.6W2) = 45.4 #/SQF PASD1
CRITICAL UPLIFT COMBINATION (0.6D+0.6W1) = -14.39 #/SQF PASD2

1.- CHECKING CRITICAL MAIN BEAM - SPAN = 12' - 2" - (1) ALUMINUM RT 2"X6"X1/8"
Afferent Width b= 6.00 ft
W = PASD1 x b = 272.35 Lb/ft
Critical Single Span, L = 12.17 ft

W x L2 = 5039 lbs-ft
M=
8
Then M = 60.47 Kip-in
CHECKING TO BENDING:
(UnWelded - See reference ADM 2020 - Table 2-19) - Elements in Flexural Compression
With : l=b/t= 33.1 < 46 < 77
Then Fb(UnWelding elements in flexure) = 40.5 - 0.262λ 28.45 Ksi - 6061T6 Alloy
Then Srqr'd = M = 2.13 in3
Fb
Then try with : (1) RT 2"x6"x1/8"
Sxx = 2.76 in3 > Srqr'd = 2.13 in3 O.K.
Ixx = 8.28 in4
CHECKING DEFLECTION:
5 * W * L4 = 0.51 in
384 * EAlum * Ixx
Then 0.51 in < 0.61 in (L/240) O.K.

THEN USE: (1) RT 2"x6"x1/8"

(Critical Reaction) Rf1a = WxL/2 = 1657 Lbs By Critical Gravity Combination at ends
Rf1b = 525 Lbs By Critical Uplift Combination at ends
CONSIGN, LLC
CONSULTING ENGINEERS
CERTIFICATION OF AUTH. # 31618
14021 SW 143rd Court - Bay 1, Miami, Florida 33186 - Phone -Fax # (305) 253-9442
2.- CRITICAL COLUMN - LENGHT= 7'- 6" - (1) ALUMINUM SQ.T 6"X6"X1/8"
Try Using: (1) ALUMINUM SQ.T 6"X6"X1/8"

COLUMN TENSION CHECK: 14.39 x 88.7


(CRITICAL UPLIFT) T = 1276 lbs
CHECKING TENSION(CRITICAL)
USING STRUCTURAL ALUMINUM T-6061 ALLOY - Fy=9.1Ksi (FROM ALUMINUM DESIGN MANUAL - TABLE 2-19W)

Type Uplift Load Heigth(FT)


1 1276 8.67
Nominal Size A(in2) rxx(in) L(in) K(Factor) KL(in) KL / r
(1) ALUMINUM SQ.T 6"X6"X1/8" 2.94 2.40 104 1.0 104 43
Then: A rq'd = 1276 / 9100 = 0.14 in2
And 0.14 < 2.94 O.K.
Kl/r = 43 < 240 O.K.

COLUMN COMPRESSION CHECK: 45.39 x 88.7


(CRITICAL GRAVITY LOAD) P = 4025 lbs
CHECKING COMPRESION (CRITICAL)
Type Load(lbs) Gravity Heigth(FT)
1 4025 8.67
Nominal Size A(in2) rxx(in) L(in) K(Factor) KL / r b/t Fa(ksi) - 2-19W
(1) ALUMINUM SQ.T 6"X6"X1/8" 2.94 2.40 104 1.0 43 28,2<46 <58 7.17
Then: Pa = Fa x A = 21062 lbs > 4025 lbs O.K.
Kl/r = 43 < 120 O.K.

Then use : (1) ALUMINUM SQ.T 6"X6"X1/8"

3.- CHECKING TYPICAL INSULATED ALUMINUM PANEL - (1) 3"x0.024"x2 SKIN BY ELITE ALUMINUM CORP.
WINDSPEED= 175 MPH - FBC 2023 - Figure 1609.3
EXPOSURE CATEGORY= "C" - FBC 2023 - 3105.4.2.2
CRITICAL PRESURE= 45.4 psf < 50 psf O.K. SEE DOC FL7561-R7 ATTACHED

CRITICAL SPAN= 12.00 ft < 13,76 ft (L/120) O.K. SEE DOC FL7561-R7 ATTACHED

4.- CHECKING INSULATED PANEL TO ALUMINUM PURLIN CONNECTION


Uplift Load=P ASD2 86 lbs Per Connector

PULL-OUT ON ALUMINUM PURLING


Try using : (1) 1/4"ΦX5" S.S Screw @ Max 12" O.C
Spacing Between Bolts > 1 in 100% - 100% FULL DESIGN
Edge Distance > 0.5 in 100% - 100% FULL DESIGN

PULL-OUT CHECKING Ru = 403 x 1 Screw x 100%


403 lbs > 86 lbs O.K.

Then use : (1) 1/4"ΦX5" S.S Screw @ Max 12" O.C

5.- CHECKING MAIN BEAM TO COLUMN CONNECTION - DETAIL A


V = Shear = Rf1b = 525 lbs Per Connection

Try using : (3) 1/4"ΦX2" S.S Screw O.C to Aluminum Column


Spacing Between Bolts > 1 in 100% - 100% FULL DESIGN
Edge Distance > 0.5 in 100% - 100% FULL DESIGN

PULL-OUT CHECKING Ru = 403 x 3 Screw x 100%


1209 lbs > 525 lbs O.K.

Then use : (3) 1/4"ΦX2" S.S Screw O.C to Aluminum Column

6.- CHECKING ALUMINUM BEAM TO CONCRETE WALL CONNECTION - DETAIL D


Crit. Gravity Load = Rf1a = 1657 lbs Per Connection

Try using : (2) 1/2"ɸ S.S Wedge Bolt Anchor per Plate (Min. embed. 4 1/2") Into Concrete Wall
Spacing Between Bolts > 6 in 100% - For Tension
Edge Distance > 4 in 100% - For Tension

SHEAR CHECK
Ru = 1425 x 2 Anchors x 100%
2850 lbs > 1657 lbs O.K.

Then use : (2) 1/2"ɸ S.S Wedge Bolt Anchor per Plate (Min. embed. 4 1/2") Into Concrete Wall
CONSIGN, LLC
CONSULTING ENGINEERS
CERTIFICATION OF AUTH. # 31618
14021 SW 143rd Court - Bay 1, Miami, Florida 33186 - Phone -Fax # (305) 253-9442

7.- CHECKING ALUMINUM REAR CHANNEL TO EXISTING CONCRETE WALL CONNECTION - DETAIL B
Crit. Gravity Load = G = 136 lbs Per Connection

Try using : (1) 1/4"ɸ S.S Tapcon @ max 6" O.C (Min. embed. 1 3/4") Into Existing Concrete Tie Beam
Spacing Between Bolts > 2 in 100% - For Shear
Edge Distance > 2.5 in 100% - For Shear

SHEAR CHECKING
Ru = 297 x 1 Tapcon x 100%
297 lbs > 136 lbs O.K.

Then use : (1) 1/4"ɸ S.S Tapcon @ max 6" O.C (Min. embed. 1 3/4") Into Existing Concrete Tie Beam

8.- DESIGN OF TYPICAL CONCRETE FOOTERS


8.1- DESIGN OF CONCRETE FOOTER TYPE 1
CHECKING FOOTER DIMENSIONS
T = Rf1b x 2 = 1051 lbs - CRITICAL UPLIFT LOAD
Try using = Concrete footer 2'-6" x 2'-6" x 2'-6"
gc = 150 pcf Volumetric Weigth for concrete
V= 15.63 ft3 Footer volume
P = gc x V 2344 lbs Self Weigth of the footer
Checking: T / 0.6 = 1751 < P O.K.

Then use : Concrete footer 2'-6" x 2'-6" x 2'-6"

CHECKING PRESSURES ON SOIL


P = Rf1a x 2 = 3314 lbs - CRITICAL GRAVITY LOAD
Footer dimensions
A= 2.50 ft Length of footer
B= 2.50 ft Width of footer
H= 2.50 ft Height of footer
Soil Properties
gc = 150 pcf Volumetric Weigth for concrete
sALLOW = 2000 psf Allowable Pressure for the foundation soil
Calculations
W SW = gc x H x A x B = 2344 lbs Self Weigth
P = 3314 lbs Load on Footer By Gravity Loads
Checking (W SW + P) / (A x B) = 905 psf < sALLOW O.K.

CHECKING CONCRETE FOOTER REINFORCEMENT DESIGN


smax = 1267 psf Maximun Mayored design pressure
Footer dimensions
A= 2.50 ft Length of footer
B= 2.50 ft Width of footer
H= 2.50 ft Height of footer
Structural Parameters
f'C = 3000 Psi Compression resistan at 28 days for simple concrete
fY = 60000 Psi Yield strength for the reinforcement steel
r= 3.0 in Bars reinforcement covering

Checking Main bending reinforcement


Mmax (-) = (smax X B)x(A/2) 2 = 2475 Lbs-ft
2
MDesign= 2475 Lbs-ft Design Moment force
r Design= 0.0018 Minimun Reinforcement
AS = 1.46 Req. Steel reinforcement area

2
Then use : (5) 5/8"Φ Reinf. Bar (1.53 in ) Both Ways - Bottom Reinforcement.

Checking concrete footer Shear


a= 12 in Base plate Width
d=H-r= 10 in Critical Height of footer
B0 = 4(a + d/4) = 58 in Critical Shear Perimeter
Vmax = smax X (BxA - a2) = 6653 Lbs
Vdesign = 6653 Lbs Design Shear force
Checking
ɸVC = 0.70x0.33xf'c 1/2xB0xd = 7338 Lbs
ɸVC > VDesign O.K.
Scanned with CamScanner
1/31/24, 11:24 AM Florida Building Code Online

BCIS Home Log In User Registration Hot Topics Submit Surcharge Stats & Facts Publications Contact Us BC

Product Approval
USER: Public User

Product Approval Menu > Product or Application Search > Application List > Application Detail

FL # FL7561-R7
Application Type Revision
Code Version 2023
Application Status Approved

Comments
Archived

Product Manufacturer Elite Aluminum Corporation


Address/Phone/Email 4650 Lyons Technology Parkway
Coconut Creek, FL 33073
(954) 949-3200
[email protected]

Authorized Signature Bruce Peacock


[email protected]

Technical Representative Bruce Peacock


Address/Phone/Email 4650 Lyons Technology Parkway
Coconut Creek, FL 33073
(954) 949-3200
[email protected]

Quality Assurance Representative


Address/Phone/Email

Category Roofing
Subcategory Products Introduced as a Result of New Technology

Compliance Method Evaluation Report from a Florida Registered Archite


Professional Engineer
Evaluation Report - Hardcopy Received

Florida Engineer or Architect Name who developed the Do Kim, P.E.


Evaluation Report
Florida License PE-49497
Quality Assurance Entity QAI Laboratories
Quality Assurance Contract Expiration Date 12/31/2026
Validated By James L. Buckner, P.E. @ CBUCK Engineering
Validation Checklist - Hardcopy Received

Certificate of Independence FL7561_R7_COI_certificate of independence.pdf

Referenced Standard and Year (of Standard)

https://floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDqsqJkzX72BeuCecN82vc%2bRByiZtb8kp21A%3d 1/2
1/31/24, 11:24 AM Florida Building Code Online

Equivalence of Product Standards


Certified By

Sections from the Code


1708.2

Product Approval Method Method 2 Option B

Date Submitted 08/16/2023


Date Validated 08/21/2023
Date Pending FBC Approval 08/25/2023
Date Approved 10/17/2023

Summary of Products

FL # Model, Number or Name Description


7561.1 Aluminum/Aluminum Composite 3"/4"/6"x0.024"x1lb EPS Composite Pa
Panels EPS Composite Panel, 3"/4"/6"x0.024"x
3"/4"/6"x0.030"x2lb EPS Composite Pa
Limits of Use Installation Instructions
Approved for use in HVHZ: Yes FL7561_R7_II_2023 FBC-Elite Aluminu
Approved for use outside HVHZ: Yes Verified By: Do Kim, P.E. PE 49497
Impact Resistant: No Created by Independent Third Party: Y
Design Pressure: +80/-80 Evaluation Reports
Other: In HVHZ, not to be used in structures considered living FL7561_R7_AE_FL 7561 Evaluation Re
areas per FBC Section 1616 unless impact protection is provided. Created by Independent Third Party: Y
See installation drawing for nominal allowable design pressures
and spans.

Back Next

Contact Us :: 2601 Blair Stone Road, Tallahassee FL 32399 Phone: 850-487-1824

The State of Florida is an AA/EEO employer. Copyright 2007-2013 State of Florida. :: Privacy Statement :: Accessibility Sta

Under Florida law, email addresses are public records. If you do not want your e-mail address released in response to a publi
electronic mail to this entity. Instead, contact the office by phone or by traditional mail. If you have any questions, please cont
Section 455.275(1), Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide th
address if they have one. The emails provided may be used for official communication with the licensee. However email addres
not wish to supply a personal address, please provide the Department with an email address which can be made available to
are a licensee under Chapter 455, F.S., please click here .
Product Approval Accepts:

https://floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDqsqJkzX72BeuCecN82vc%2bRByiZtb8kp21A%3d 2/2
Do Kim & Associates, LLC
Consulting Structural Engineers

Florida Board of Engineers Certificate of Authorization No. 26887

Certificate of Independence

Do Kim and Associates, LLC and Do Kim, P.E. do not have nor will acquire financial interest in the
company manufacturing or distributing the product or in any other entity involved in the approval process
of the product named in the accompanying Florida Product Approval.

Digitally signed by Do Y

Do Y Kim Kim
Date: 2023.08.01
12:09:24 -04'00'

Do Kim, P.E.
FL #49497

P.O. Box 10039 813.857.9955


Tampa, FL 33679 [email protected]
Do Y Digitally signed
by Do Y Kim
Date:
Kim 2023.08.16
15:30:52 -04'00'

This item has been digitally signed and sealed by Do Y. Kim


on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the
signature must be verified on any electronic copies.
This item has been digitally signed and sealed by Do Y. Kim
on the date adjacent to the seal. Printed copies of this
document are not considered signed and sealed and the
signature must be verified on any electronic copies.
Do Kim & Associates, LLC
Consulting Structural Engineers

Florida Board of Engineers Certificate of Authorization No. 26887

Product Evaluation Report

Date: August 15, 2023

Report No.: FL# 7561-R7

Product Category: Roofing

Product sub-category: Products Introduced as a Result of New Technology

Product Name: EPS Foam Core w/ Aluminum Skin Composite Panels

Manufacturer: Elite Aluminum Corporation


4650 Lyons Technology Parkway
Coconut Creek, FL 33073
Phone: 800-421-0682

Scope:

This product evaluation report issued by Do Kim and Associates, LLC and Do Kim, P.E. for Elite
Aluminum Corporation is based on Florida Department of Business and Professional Regulation Rule
61G20-3.005 (2) Method 2 (b) of the State of Florida Product Approval. Re-evaluation of this product
shall be required following pertinent Florida Building Code modifications or updates.

Do Kim and Associates, LLC and Do Kim, P.E. do not have nor will acquire financial interest in the
company manufacturing or distributing the product or in any other entity involved in the approval process
of the product named herein.

This product has been evaluated for use in locations adhering to the Florida Building Code, 8th Edition
(2023 FBC) and where pressure and deflection requirements, as determined by Chapter 16 of the Florida
Building Code, do not exceed the design pressures as shown on the approval.

Digitally signed by

Do Y Kim Do Y Kim
Date: 2023.08.20
19:01:43 -04'00'

Do Kim, P.E.
FL #49497

P.O. Box 10039 813.857-9955


Tampa, FL 33679 [email protected]
Sheet 1 of 3
Do Kim & Associates, LLC
Consulting Structural Engineers

Supporting Documents
1. Code Compliance
a. The product assembly described herein has demonstrated compliance with the Florida
Building Code 8th Edition (FBC), Section 1708.2.
2. Drawings:
a. Drawing No. FL-1001 titled “EPS Foam Core Composite Panels”, Sheets 1 and 2
prepared by Do Kim and Associates, LLC., signed and sealed by Do Kim, P.E.
3. Testing
a. Testing per ASTM E72 as performed by Hurricane Engineering & Testing, Inc. (HETI),
and reported in test report numbers HETI-05-1988, HETI-06-2104, HETI-06-2066,
HETI-06-2105, HETI-06-2067, HETI-05-1002, HETI-06-2107, HETI-05-1987, HETI-
06-2069, HETI-06-2070, HETI-06-2071, HETI-05-1994, HETI-05-1991, HETI-06-2072,
HETI-06-2073, HETI-06-2074, HETI-05-1996, HETI-05-1989, HETI-05-1993, HETI-
05-1985, HETI-05-1995, HETI-05-1990, HETI-05-1997, HETI-05-2037, HETI-05-2029,
HETI-05-2039, HETI-05-2030, HETI-05-2041, HETI-05-2048, HETI-05-2036, HETI-
05-2031, HETI-05-2038, HETI-05-2065, HETI-05-2040, HETI-05-2042.
4. Calculations
a. Panel performance engineering analysis for tested loading conditions have been prepared
based on comparative and/or rational analysis, prepared, and submitted by Do Kim, P.E.
5. Other
a. Quality Assurance Agreement verified with Quality Auditing-Institute, LTD. (QAI
Laboratories, LTD.) (FBC Organization #QUA7628).

P.O. Box 10039 813.857-9955


Tampa, FL 33679 [email protected]
Sheet 2 of 3
Do Kim & Associates, LLC
Consulting Structural Engineers

Limitations and Condition of Use

1. Code Compliance
a. The product assembly described herein has demonstrated compliance with the Florida
Building Code 8th Edition (FBC), Section 1708.2.
2. Large and small missile impact resistance has NOT been tested to or evaluated for in this
approval. In HVHZ, this product shall be used in structures “not to be considered living areas”
per Section 1616 unless impact resistance in accordance to the HVHZ requirements are met.
3. Each product listed above shall be installed in strict compliance with its respective Product
Evaluation Document and site-specific engineering along with all components noted herein.
4. Use of each product shall be in strict accordance with its Product Approval Evaluation and
Limitations of Use.
6. Composite panels shall be constructed using type 3003-H154 or 3105-H154 aluminum facings, 2 PCF
ASTM C-578 Kingspan Insulation LLC brand EPS foam insulation (NOA No. 22-0627.04) or Imperial
Foam & Insulation MFG. CO. adhered to aluminum facings with Ashland Chemical 2020D ISO grip.
Fabrication to be by Elite panel products only in accordance with approved fabrication methods.
7. Elite roof panels maintain a UL 1715 (int) class ‘B’ (ext) rating and are NER-501 approved.
8. This specification has been designed and shall be fabricated in accordance with the requirements
of the FBC, composite panels comply with Chapter 7 Section 720, Chapter 8 Section 803, Class
A interior finish, and Chapter 26 Section 2603. All local building code amendments shall be
adhered to as required.
9. The designer shall determine by accepted engineering practice the allowable loads for site
specific load conditions (including load combinations) using the data from the allowable load
tables and spans in this approval.
10. Deflection limits and allowable spans have been listed to meet FBC including the HVHZ (L/80
for spans < 12’-0” and L/180 for spans > 12’-0”).
11. All supporting host structures shall be designed to resist all superimposed loads.
12. All components which are permanently installed shall be protected against corrosion,
contamination, and other such damage.
13. Size and Span Limitations:
a. Composite panels shall be limited to those specific panels listed in the DWG. FL-1001.
b. Panel spans shall not exceed those listed in the tables of DWG. FL-1001.
14. ELITE ALUMINUM PANELS ARE LABELED WITH A FL7561 LABEL TO ENSURE
BUILDING INSPECTOR THAT THE INSULATED PANELS INSTALLED ARE APPROVED
FOR USE IN THE STATE OF FLORIDA.

P.O. Box 10039 813.857-9955


Tampa, FL 33679 [email protected]
Sheet 3 of 3

You might also like