0% found this document useful (0 votes)
12 views7 pages

Topic 4 Elective Topic - Power Electronics - Term 3 2021

Uploaded by

engrkam257
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
12 views7 pages

Topic 4 Elective Topic - Power Electronics - Term 3 2021

Uploaded by

engrkam257
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

ELEC4123: Electrical Design Proficiency Term 3 2021

Topic 4: Elective Topics


Power Electronics – Distribution Grid Networks
Context and Objectives
Microgrids can be defined as a subsystem of a larger power system. This subsystem may include a set of
local generation sources and associated loads. Microgrids can be operated in grid-connected mode (GCM)
when connected to a larger network or islanded mode (IM) when disconnected from the grid. In islanded
mode, the microgrid can autonomously manage the local generation and demand offering a great potential to
improve local energy reliability.
In this elective task, you will design a three-phase (3-ph) microgrid with two inverters as shown in Figure 1.
Inverter 1 will be designed to operate as a grid-feeding inverter during the GCM operation of the microgrid and
grid-forming inverter during the IM operation of the microgrid. Inverter 2 will be designed to operate as a grid
feeding inverter in either GCM or IM mode. Inverter 1 should also have some form of islanding detection, to
detect disconnection from the grid, which should prompt the change from grid-feeding to grid-forming.

3-ph Grid (AC Source)

Grid-Feeding during GCM and Grid-forming during IM

Ideal DC 3-ph 3-ph


Voltage Inverter1 Output Load
Source 1 Filter 1

Grid-Feeding during all cases

Ideal DC 3-ph
Voltage Inverter2 Output
Source 2 Filter 2

Figure 1. Overall combined tasks overview.

Detailed Description
There are 4 deliverables or levels for this task: Basic, Satisfactory, High, and Outstanding levels, with higher
difficulty in later levels. The overall requirement mark that you can receive for this elective topic is based on
how many levels you can complete successfully (total 10% of your assessment for the course). For instance,
you have the choice to complete only one level, and if successful, a Basic mark is awarded. The more levels
you complete, the higher your final requirements mark will be. But you may want to strategies for balancing
your workload and not necessarily try to push your group to complete all tasks but rather focusing on the first
and the second levels and do a good job on them so you can guarantee a minimum Satisfactory mark for this
topic.

Original version created by Dr Matthew Priestley. Revised in Term 3, 2021 Page 1 of 7


Power Electronics – Distribution Grid Networks

Basic Level: Phase Lock Loop (PLL)


One popular technique that is used to synchronize a generator output voltage to the grid voltage is to use a
phase lock loop (PLL) to measure the amplitude, frequency, and phase angle of the three phase grid voltages.
Many generation sources use an inverter to synchronize to an AC grid and these inverters typically use a PLL
to perform this grid voltage synchronization. A PLL must accurately estimate the amplitude, frequency and
phase angle of the fundamental component of the grid voltages during steady-state conditions. It must also
quickly respond to any changes in the grid voltage amplitude, frequency or phase angle. These changes in
the grid voltage are often caused by grid voltage disturbances.
Grid Voltage Disturbances
Two common types of grid voltage disturbance are a phase angle jump and a voltage sag. A phase angle
jump is where the grid voltage phase angle suddenly jumps by a specific amount. For example, the grid voltage
phase angle might suddenly jump from 40° to 65° due to fault somewhere in the network. After a phase jump
occurs, the PLL must synchronize to the new phase angle value within a specific time or the generation source
must be disconnected from the grid, which is undesired.
Another grid voltage disturbance is a sudden reduction of the rms voltage which is called an undervoltage or
voltage sag. These sags are typically caused by an electrical short circuit occurring at some point in the
electricity supply system. The high short-circuit current yields large voltage drops in the impedances of the
supply system, which lower the rms voltage of the network. Practically, a sag will typically only occur in a
distribution network for a short duration of time until a protection device isolates the source of short-circuit
current. Yet again during this fault type, the PLL must stay synchronized to avoid needing to take an energy
generation source offline.

The minimum design constraints for this system are as follows:


• You are provided with a basic template in Simulink as shown in Figure 2 to help saving time and build
your system. The solver and the fundamental step size are already configured in this template for your
convenience.
• No Simulink integrated blocks are allowed to be used, including built-in PLL block, DQ transform.
• No discrete transfer function blocks are allowed to be used to implement your controller, only basic
Simulink blocks like unit delay, gain and summing junction are allowed to be used to implement the
controller.

Basic Level Deliverable:


The 3-phase PLL must accurately track a set of perfectly sinusoidal three-phase voltage signals with an
amplitude of 𝟐𝟑𝟎√𝟐𝐕 (nominal value) and any grid frequency in between 48-52 Hz during steady-state
conditions, during a voltage sag and during a phase jump.
To do this:
1. The PLL must track the frequency with a peak-to-peak ripple of < ±0.0001 Hz during steady-state
conditions with zero average steady-state error.
2. The PLL must track the signal amplitude with a peak-to-peak ripple of < ±1 mV during steady-state
conditions with zero average steady-state error.
3. The difference between the actual phase angle and PLL phase angle estimate must not exceed ±0.1°
during steady-state conditions.
4. During a phase jump of 15°, the frequency and amplitude responses must have a settling time (< 0.05%
final value) < 150 ms and a percentage overshoot of < 10%.
5. During a voltage sag of 0.2 p.u, the frequency and amplitude responses must have a settling time < 50
ms and a percentage overshoot of < 2%.

Page 2 of 7
ELEC4123: Electrical Design Proficiency

Figure 2. Basic Simulink template.

Satisfactory Level: Grid-Forming Inverters


A grid-forming inverter will convert the dc bus voltage from the output of a renewable energy source (RES) to
an AC grid voltage with a voltage frequency and amplitude input reference. In Australia, standards dictate that
the nominal three-phase AC grid voltage and frequency is 400 Vrms,l-l and 50 Hz respectively, so these values
should be used as the input references for a grid-forming inverter in Australia. Standards also require that
inverters use an output low-pass filter to remove any high frequency switching current harmonics to ensure
that the inverter output current is sinusoidal when interfacing to the grid. Ideally, a filter with a low cut-off
frequency and high attenuation at the high switching frequency is desirable to better eliminate switching
current ripple.
Inverter Output Filters
Typically, an L, LC or LCL circuit is used to perform the inverter output filtering. The L-filter is popular and
simple to use but has a low attenuation and high required inductance value, which makes the filter size large.
The LCL-filter produces the best attenuation at the inverter switching frequency and can provide the best
decoupling between the filter and the grid impedance out of these three filter topologies. However, the three-
order nature of the LCL-filter circuit means that it is difficult to design as there are many important design
considerations. The LC-filter is a trade-off for simple design and better attenuation to the switching frequency.
A high-level block diagram of grid-forming system is shown in Figure 3.

Additional minimum design constraints for this system are as follows:


• The inverter must be three-phase and must have the conventional six-switch configuration.
• The inverter must use individual IGBT semiconductor switching components from the electrical
Simscape library. Note that you cannot simply use a universal bridge or inverter block.
• The dc bus voltage must be chosen to be large enough to supply the required grid voltages but not be
unnecessarily oversized.
• The inverter must have an inner current control loop (using PI or PR controllers).
• The inverter must have an output filter which has practical component values.
• A three-phase wye-connected 10 kW RL load with a lagging power factor of 0.95 @ 50 Hz must be
used as the load.
• The inverter must have deadtime included in the switching PWM algorithm to avoid short circuiting the
dc bus voltage source during a switching event.

Page 3 of 7
Power Electronics – Distribution Grid Networks

Figure 3. Grid-forming block diagram.

Satisfactory Level Deliverable:


1. An LC-filter has been used with practical values. The filter values must be chosen to give:
• An inverter output current with maximum peak-to-peak ripple, Δ𝑖𝑖𝑛𝑣 < 1𝐴, at the rated load current to
avoid necessarily high practical IGBT current ratings.
• A reactive power drop across the capacitor which is < 5% of the rated power, to avoid high reactive
power consumption in the capacitor.
2
𝑉𝑟𝑎𝑡𝑒𝑑
< 5% × 𝑆𝑟𝑎𝑡𝑒𝑑
𝑋𝑐
• The total impedance of the inductors is < 10% of the base impedance to avoid large voltage drops
across the inductors.
2
𝑉𝑟𝑎𝑡𝑒𝑑
𝑋𝐿 < 10% ×
𝑆𝑟𝑎𝑡𝑒𝑑
2. The inner current control loop has been tuned appropriately for the LC-filter and RL load. The inverter
current controller can accurately track a step change in the amplitude of the load current from zero to the
rated value and obtain a settling time < 120𝑚𝑠, percentage overshoot < 20% and steady state error <
0.5%.
You must provide a setting to switch between voltage and current control. An outer voltage control loop has
been tuned appropriately to provide an AC grid voltage with fundamental component amplitude of 400 𝑉𝑟𝑚𝑠,𝑙−𝑙
(±2% error allowed) and a frequency of 50𝐻𝑧 (±2% error allowed) during steady state conditions. The voltage
controller can also achieve a setting time < 800𝑚𝑠 and percentage overshoot < 5%, when the load power
demand is stepped from 0kW to 10kW. Ensure THD is < 5% for the load voltage and currents.

High Level: Grid-Forming and Grid-Feeding Inverters


Typically, a grid-forming inverter contains an inner current control loop and an outer voltage control loop. The
outer voltage control loop possesses the desired grid voltage amplitude and frequency as input references.
This allows the grid-forming inverter to generate the desired ac voltages. A PLL is not required for a grid-
forming inverter as it is effectively setting the phase angle of the grid voltage. Whereas, a grid-feeding inverter
contains an inner current control loop, an outer power control loop and a PLL. The PLL locks onto the phase
and frequency of the grid voltage and ensures that the grid-feeding inverter is supplying voltages at the correct
grid frequency and phase angle. The outer power control loop possesses the desired real and reactive power
as input references. Note that these power references are often chosen by higher level control systems which
is beyond the scope of this course. Also, note that you cannot have a grid feeding inverter in an islanded
microgrid without the presence of a grid-forming inverter to set the ac grid voltage. A high-level block diagram
of grid-forming system is shown in Figure 4.

Additional minimum design constraints for this system are as follows:


⚫ The grid-feeding inverter must have an inner current control loop and must have real and reactive input
power references for the outer control loop.
⚫ The grid network bus must be represented by a set of sinusoidal voltage sources with an amplitude of
400 Vrms,l-l and a frequency of between 48-52 Hz.

Page 4 of 7
ELEC4123: Electrical Design Proficiency

Figure 4. Grid-forming and Grid-Feeding Inverters block diagram.

High Level Deliverable:


A LC-filter has been used with the inverter. The same filter specifications as shown in SF feature requirement
one.
1. The grid-feeding inverter can supply 5𝑘𝑊 ± 10% and 0𝑘𝑉𝐴𝑅 ± 1𝑘𝑉𝐴𝑅 at the filter output during steady-
state conditions.
2. The inverter can track a step change in the real power from 0 to 5kW with a settling time < 150𝑚𝑠 and a
percentage overshoot of 15%.

Outstanding Level: Grid-connected Mode and Islanded Mode Switch


Outstanding Level Deliverable:
1. The inverter one must have the ability to automatically switch between grid-connected and islanded mode
during live operation, when the grid-network bus is connected or disconnected to the microgrid. Note that
you should include a signal to detect the connection status of the grid-network bus to determine the
operating mode of the inverter. A high-level block diagram of for this task is shown in Figure 5.

Figure 5. Grid-connected Mode and Islanded Mode Switch block diagram.

Page 5 of 7
Power Electronics – Distribution Grid Networks

Simulink solver and Local Solver settings


Continuous Time vs Discrete Time States
When modelling a system, it is important to think about what which parts are continuous time, and which are
discrete time. Note that continuous time is where the signal/state is defined for all time t and contains no
sampling. Whereas discrete time is where there signal/state is sampled at a specific sampling frequency. It is
important to realize that MATLAB Simulink treats continuous states differently to discrete states and hence
solves them differently. Note that a digital processor should be modelled in discrete time to create an accurate
represent of a practical model. You will find that designing controller in the continuous time-domain is quite
simple. However, designing a practical controller in the discrete time-domain is much more difficult as stability
becomes as issue as your controller bandwidth approaches the controller sampling time.
Simulink Solver
You must carefully select your Simulink solver depending on the nature of the states of your system. For
example, a mostly continuous state system should use a variable-step auto solver as this has a fast-solving
time and yields enough accuracy for this assignment. However, a simulation with discrete states like a PWM
inverter should use a fixed-step discrete solver with a fixed step size.
Solver settings!!!
In this task, you need to use Fixed-step discrete (no continuous states) as your solver selection. And your
fixed-step size (fundamental sample time) is 𝑇𝑠 = 1𝑢𝑠 as shown in Figure 6.

Figure 6. Simulink Configuration Paramaters window.

Then, in your Simscape Solver Configuration, use local solver and set the sample time to be 𝑇𝑠 = 1𝑢𝑠 with
Solver type as Backward Euler, which means your circuits minimum time step is 1us as shown in Figure 7
(this is the F(x)=0 block in the Simulink template file).

Figure 7. Setting local solver in the Simulink templet file.

Page 6 of 7
ELEC4123: Electrical Design Proficiency

For your controller, the minimum time step should be set to 𝑇𝑐𝑠 = 100𝑢𝑠, which is 100 times larger than the
sample time, 𝑇𝑠 , so that the circuit can be regarded as a relatively continuous system.
You can refer to the basic level template Simulink file.

Project Report
Note that the design requirements are very open; there are many solutions to the problem, some good, some
not so good. The same can be said about the requirements to the report. It is left for the students to judge
what makes up a good design, good supporting simulations, and a convincing report, keeping the following in
mind: the report must answer all questions asked and implied in the project description, it must document the
work done, and it must show that the authors understand the material.
Note: The draft report must contain at least a close approximation to the final design. Informal notes can
provide any remaining details by the time of marking. The draft report must also identify the individual sections
written by (or that will be written by) each team member.
Furthermore, requirements to the report include:
• one report per group
• research section
• reasoning for design choices
• inclusion of complete schematic
• inclusion of relevant simulation plots
• calculation of performance measures: At the least, you need calculations for all of the circuit components.

Draft design plan: This serves as a milestone to make sure you are heading in the right direction. This review
is compulsory, and must be ticked off either Tue or Fri of Week 9. It should consist of a summary of your
current research, possible design choices, as well as a complete system block diagram (including power and
peripherals) with Inputs/Outputs labelled.
*It is not necessary to have a schematic or full design constructed*

--- End of Power Electronics Task ---

Page 7 of 7

You might also like