ISH2009 Paper
ISH2009 Paper
ISH2009 Paper
Abstract: The dielectric strength of air is influenced by air density (temperature and pressure) and
humidity. Such effects need to be taken into account when external insulation is designed and
tested. Since the conditions of application and the conditions of the laboratory tests may be
different, it is often necessary to make corrections between different atmospheric conditions. For
engineers at manufacturers, utilities or high-voltage laboratories, they follow the relevant IEC
standards. However, atmospheric conditions influence the dielectric strength of air in a
complicated way. Simplified and generalized solutions may cause vacillations especially when
different recommendations are given in different standards without sufficient clarifications. It is
the intension of this paper to give an outline of such issues that may lead to uncertainties in the
application of various IEC standards regarding the atmospheric correction. Some proposals are
also given for discussion.
3. RECOMMENDATIONS IN IEC
STANDARDS
Theoretically, for the design and test of external • For gaps of lengths shorter than 2 meters, m=1
insulation, atmospheric corrections should be applied
between the specific site conditions, laboratory test • For gaps of lengths longer than 2 meters, use
conditions and the standard reference conditions. the same m value as that for SI obtained in
However, for most equipment, there are normal service Figure 2
conditions specified in the relevant IEC standards. For
Note that peak AC voltage should be used as SI in
economical reasons and industrial practice, equipments
Figure 2.
have to be designed to withstand the required withstand
voltage within the range of normal service conditions.
No correction for DC was included in most of these
The differences between the standard reference
standards. In Cigré report a linear relation between the
conditions and the normal service conditions have been
short duration DC breakdown voltage and the length of
included in the design. This means that for equipment
rod-plane gap has been reported up to 1000 kV with
used at a location with altitude not exceeding 1000
mean breakdown field in the level of 500 kV/m [2].
meters; no altitude correction will be necessary. This
Since the gap length is short, m=1 would be used.
industrial practice has been supported by vast
However, other literature has reported slightly non-
operational experience and adopted by many IEC
linearity from 2 to 4 meters of gap lengths [11]. The
standards. This is especially true for the cases when
mean breakdown field is in the level of 400 kV/m. This
deterministic method is used for insulation
will result in: G=0.8 and m=0.6. More laboratory
coordination, e.g. for HVDC systems (IEC60071-5,
studies are needed for longer gaps. However, with the
under revision). The effect of the air density in this
limited results today, the recommendations would be:
range, where H 1000 meters, has already been
included in the margins commonly adopted for
insulation design. • For gaps of lengths shorter 2 meters, m=1
• For gaps of lengths longer than 2 meters,
For equipment that will be used at the specific site m=0.6.
conditions more severe than the normal service
The recommendation of use m=0.75 for all SI level is a 2. The correction method recommendation in
conservative approach. This value may be justified for IEC 60071-2 is convenient to use for purpose
EHV systems. For UHV system, relations in Figure 2 of insulation co-ordination and the
should be followed. determination of withstand test voltages. It
can be applied for altitude correction for
4.4. Altitude correction for creepage altitudes up to 4000 m, as being recommended
by several other IEC standards, before any
Along hydrophilic surfaces, when pollution has been research results prove otherwise. It is a
wetted, dry-band related discharge activities may take
conservative approximation of G factor
place. This is a short gap with streamer breakdown.
method.
The dry-band can become wetted again after the
current flow though the arc in air. Such activities can
3. For equipment with a specified normal service
occur several times and a full flashover of the insulator
conditions including altitudes not exceeding
may take place. In this process, the change of air
1000 m, altitude correction should only be
density will change the dielectric strength of the air. If
applied to correct the altitude exceeding 1000
it was pure air breakdown in the form of streamer, then
m as that given in formula (5):
the correction would be kt=δm with m=1. However, the
conditions of both surfaces in series and parallel to the H −1000
dry-bend activity contribute to the effects. For real m