Nonreinforced Concrete Sewer, Storm Drain, and Culvert Pipe: Standard Specification For
Nonreinforced Concrete Sewer, Storm Drain, and Culvert Pipe: Standard Specification For
Nonreinforced Concrete Sewer, Storm Drain, and Culvert Pipe: Standard Specification For
1. SCOPE
1.1. This specification covers nonreinforced concrete pipe intended to be used for the conveyance of
sewage, industrial wastes, storm water, and for the construction of culverts.
1.2. This specification is applicable for orders in either SI units (M 86M) or in inch-pound units
(M 86). SI units and inch-pound units are not necessarily equivalent. Inch-pound units are shown
in brackets in the text for clarity, but they are the applicable values when the material is ordered to
M 86.
Note 1—This specification is a manufacturing and purchasing specification only and does not
include requirements for bedding, backfill, or the relationship between field load conditions and
the strength classification of pipe. However, experience has shown that the successful performance
of this product depends upon the proper selection of the class of pipe, type of bedding and backfill,
and care that the installation conforms to the construction specifications. Owners are cautioned
that they must correlate the field requirements with the class of pipe specified and provide for or
require inspection at the construction site.
2. REFERENCED DOCUMENTS
2.1. AASHTO Standards:
M 6, Fine Aggregate for Hydraulic Cement Concrete
M 80, Coarse Aggregate for Hydraulic Cement Concrete
M 85, Portland Cement
M 194M/M 194, Chemical Admixtures for Concrete
M 240M/M 240, Blended Hydraulic Cement
M 262, Concrete Pipe and Related Products
M 295, Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use in Concrete
M 302, Slag Cement for Use in Concrete and Mortars
T 280, Concrete Pipe, Manhole Sections, or Tile
3. TERMINOLOGY
3.1. Definitions—For definitions of terms relating to concrete pipe, see M 262.
4. CLASSIFICATION
4.1. Pipe manufactured according to this specification shall be of three classes identified as “Class 1
Nonreinforced Concrete Pipe,” “Class 2 Nonreinforced Concrete Pipe,” and “Class 3
Nonreinforced Concrete Pipe.” The corresponding strength requirements are prescribed in Table 1.
5. BASIS OF ACCEPTANCE
5.1. The acceptability of the pipe shall be determined by the results of the test prescribed in this
section, when required, and by inspection to determine whether the pipe conform to this
specification as to design and freedom from defects.
5.2. Acceptance as to Strength Properties—Pipe shall be acceptable under the strength tests when they
have met the requirements as prescribed in Section 10.3.
5.3. Acceptance as to Absorption Properties—Pipe shall be acceptable under the absorption test when
they have met the requirements as prescribed in Section 10.4.
5.5. Acceptance as to Hydrostatic Properties—Pipe shall be acceptable under the hydrostatic test when
they have met the requirements as prescribed in Section 10.6.
6. MATERIALS
6.1. Concrete—The concrete shall consist of cementitious materials, mineral aggregates, and water.
6.2.1. Cement—Cement shall conform to the requirements for portland cement of M 85 or shall be
portland blast-furnace slag cement or slag modified portland cement, or portland-pozzolan cement
conforming to the requirements of M 240M/M 240, except that the pozzolan constituent in the
Type IP portland-pozzolan cement shall be fly ash.
6.2.2. Fly Ash—Fly ash shall conform to the requirements of M 295, Class F or Class C.
6.2.3. Ground Granulated Blast-Furnace Slag (GGBFS)—GGBFS shall conform to the requirements of
Grade 100 or 120 of ASTM C989/C989M.
6.2.4.7. A combination of portland cement, fly ash (not to exceed 25 percent of the total cementitious
weight), and ground granulated blast-furnace slag (not to exceed 25 percent of the total
cementitious weight).
6.3. Aggregates—Aggregates shall conform to M 6 and M 80, except that the requirement for
gradation shall not apply.
6.4. Admixtures and Blends—Admixtures and blends shall conform to M 194M/M 194.
6.5. Synthetic and Non-Synthetic Fibers—Fibers are permitted, at the owner’s option, in concrete pipe
as a nonstructural manufacturing material. Synthetic fibers (Type II and Type III) and Non-
Synthetic fiber (Type I) designed and manufactured specifically for use in concrete and
conforming to the requirements of ASTM C1116/C1116M shall be accepted.
7.2. Modified or Special Design—Manufacturers shall submit to the owner for approval, prior to
manufacture, wall thicknesses other than those shown in Table 1. Such pipe shall meet all of the
physical requirements listed in Section 10 that are specified by the owner.
8. JOINTS
8.1. The joints shall be of such design and the ends of the concrete pipe sections so formed that the
pipe can be laid together to make a continuous line of pipe compatible with the permissible
variations given in Section 11.
9. MANUFACTURE
9.1. Mixture—The aggregates shall be sized, graded, proportioned, and mixed with such proportions of
cementitious materials and water as will produce a homogeneous concrete mixture of such quality
that the pipe will conform to the test and design requirements of this specification. All concrete
shall have a water-cementitious materials ratio not exceeding 0.53 by mass. Cementitious
materials shall be as specified in Section 6.2 and shall be added to the mix in a proportion not less
than 280 kg/m3 [470 lb/yd3] unless mix designs with a lower cementitious materials content
demonstrate that the quality and performance of the pipe meet the requirements of this
specification.
9.2. Curing—Pipe shall be subjected to any one of the methods of curing described in Sections 9.2.1
through 9.2.4 or to any other method or combination of methods approved by the owner that will
give satisfactory results. The pipe shall be adequately cured to obtain the strength properties as
described in Section 5.2.
9.2.1. Steam Curing—Pipe shall be placed in a curing chamber, free from outside drafts, and cured in a
moist atmosphere maintained by the injection of steam for such time and such temperature as
needed to enable the pipe to meet the strength requirements. The curing chamber shall be so
constructed as to allow full circulation of steam around the entire pipe.
9.2.2. Water Curing—Concrete pipe shall be water cured by covering with water-saturated material or
by a system of perforated pipes, mechanical sprinklers, porous hose, or by any other approved
method that will keep the pipe moist during the specified curing period.
9.2.3. The manufacturer is not prohibited from combining the methods described in Sections 9.2.1 and
9.2.2 provided the specified strength is attained.
9.2.4. Membrane Curing—A sealing membrane conforming to the requirements of ASTM C309-03 is
not prohibited from being applied and left intact until the specified strength requirements are met.
The concrete at the time of application shall be within 6°C [10°F] of the atmospheric temperature.
All surfaces shall be kept moist prior to the application of the compounds and shall be damp when
the compound is applied.
9.3.1. General Requirements—Special shapes or fittings such as wyes, tees, bends, and adapters for use
with concrete pipe conforming to this specification shall conform to the applicable requirements
for concrete pipe of corresponding class and internal diameter. Joints shall be compatible with
those used in adjoining concrete pipes.
9.3.2. Fabricated Branches—Fabricated branches for wyes and tees shall be securely attached to the
wall of the pipe in such a manner as not to restrict or otherwise interfere with the flow
characteristics of the pipe.
10.2. Number and Type of Test Specimens Required—The manufacturer shall furnish pipe for crushing
and absorption tests, up to 0.5 percent of the number of pipes of each size included in the order,
except that in no case shall fewer than two pipes be furnished. For the permeability test, 2 percent
of the number of pipes of each size included in the order, but in no case fewer than two pipes, shall
be furnished. For the hydrostatic test, 0.5 percent of the number of pipes of each size included in
the order, but in no case fewer than two pipes, shall be furnished.
10.3. External Load Crushing Requirement—The crushing strength of nonreinforced concrete pipe shall
conform to the requirements prescribed in Table 1. The individual results of the various tests for
each size of pipe and for each shipment and plant shall be tabulated separately. The crushing
strength shall ordinarily be applied to not less than 75 percent of the pipe received for purpose of
test. All tests shall be made in accordance with T 280. Pipe shall be acceptable when all test pipe
conform to the specified requirement. Should any of the test pipe provided in Section 10.2 fail to
meet the strength requirement, the manufacturer will be allowed to test two pipes for each pipe
that failed, and the pipe shall be acceptable only when all of these additional test pipes meet the
strength requirement.
10.5. Permeability Requirement—When subjected to the permeability test as specified in T 280, the
outer pipe surface of not less than 80 percent of the pipe tested shall show no moist or damp spots
at the end of the test period due to water passing through the walls of the pipe.
10.6. Hydrostatic Requirement—When subjected to the hydrostatic test as described in T 280, the pipe
shall show no leakage during 10 min at 70 kPa [10 psi]. Moisture appearing on the surface of the
10.7. Retest—Should more than 20 percent of the samples fail to meet the specified requirements for the
permeability or not more than 20 percent of the samples fail to meet the specified requirement for
absorption or hydrostatic requirements of this section, it is not prohibited for the manufacturer to
cull his stock and eliminate any quantity of pipe and must so mark those pipe that will not be
shipped. The required tests shall be made on the balance of the order and they are acceptable if
they conform to the specified requirements. If the second sample fails to meet the specified
requirements, the whole lot is subject to rejection.
11.2.2. Thickness of Wall—The wall thickness shall be not less than the values shown in Table 1 or the
manufacturer’s designated thickness if greater than shown in Table 1 by more than 2 mm [1/16 in.]
for pipe 250 mm [10 in.] or less in diameter; by more than 3 mm [1/8 in.] for pipe 300 [12 in.] to
600 mm [24 in.] in diameter; and by more than 5 mm [3/16 in.] for pipe more than 600 mm [24 in.]
in diameter; or by more than 5 percent of the tabulated or designated wall thickness, whichever is
greater. Localized variations in wall thickness exceeding those specified above shall be accepted if
the physical test requirements specified herein are met.
11.2.4. Length of Two Opposite Sides—The length of two opposite sides of any section of pipe shall vary
not more than 6 mm [1/4 in.] or 2 percent of the designated diameter, whichever is larger.
11.2.5. Straightness—Pipe intended to be straight shall not vary in alignment more than 10 mm/m
[1/8 in./ft] of length.
12. REPAIRS
12.1. Pipe repaired because of imperfections in manufacturing or damage during handling are
acceptable if, in the opinion of the owner, the repaired pipe conform to the requirements of this
specification.
13. INSPECTION
13.1. The quality of all materials and the finished pipe shall be subject to inspection and approval by the
owner. Such inspection shall be performed either at the point of manufacture or delivery, or both.
The method of marking as to acceptance or rejection of pipe shall be agreed upon, prior to
inspection, between the owner and the manufacturer. Rejected pipe shall be replaced by the
manufacturer with pipe that meet the requirements of this specification.
14. REJECTION
14.1. Pipe shall be subject to rejection if they fail to conform to any of the specification requirements.
This specification is a manufacturing and purchasing specification only. Therefore, damage to pipe
during installation or caused by field loading in the installed condition shall not be cause for
rejection on the basis of not meeting this specification. Individual sections of pipe are subject to
rejection because of any of the following:
14.1.1. Fractures or cracks passing through the wall or joints, except that a single crack not
exceeding 50 mm [2 in.] in length at either end of a pipe or a single fracture or spall in the joints
not exceeding 75 mm [3 in.] around the circumference of the pipe nor 50 mm [2 in.] in length into
joint shall not be considered cause for rejection unless these defects exist in more than 5 percent of
the entire shipment or delivery.
14.1.2. The planes of the ends of the pipe are not perpendicular to the longitudinal axis, subject to the
limits of variation as shown in Section 11.2.4.
14.1.3. Defects that indicates mixing and molding not in accordance with Section 9.1.
14.1.4. Cracks sufficient to impair the strength, durability, or serviceability of the pipe.
15.2. Marking shall be indented on the pipe section or painted thereon with waterproof paint.
16. KEYWORDS
16.1. Concrete sewer; culvert; nonreinforced; pipe; storm drain.
1
Agrees with ASTM C14M-07 and C14-07 except that absorption testing is limited to the 5-h boil method, the use
of fibers in Section 6.5 is at the owner’s option, and the manufacturer is not afforded the option to supply inch-
pound sized pipe when the order is placed in SI units.