level controller
For steam boilers
EN ASME/MNPT
Model 176
This device guarantees a safe and reliable control, regulation and electronic signalling of the level of electrically conducting
liquids in; steam and hot water boilers, autoclaves, preheaters, pressure vessels, feedwater and condensates tanks, proces-
ses, etc.
In accordance with the requirements of the pressure equipment directive 2014/68/EU.
EC controller verification certified by: TÜV Rheinland Industrie Service GmbH, Notified Body for Pressure Equipment ID-No.
0035.
Type (Module B) EC examination report nº DP B EPR 0535132967, DP B EPR 0535132963 certified by: TÜV Rheinland
Ibérica ICT, S.A.
Conforms to the low voltage directive 73/23/CE version 93/68/CE.
According to the electromagnetic compatibility directive 89/336/CE version 93/68/CE.
Specifications
— The electrode design is technically perfect, being fully tightness in steam, with several sealing points.
— Simplicity of construction, eliminating the need for moving mechanical parts, which leads to minimum maintenance.
— Materials carefully selected for their resistance to wear, temperature and pressure conditions.
— Due to solid construction the electrodes can operate in critical temperature and corrosion.
— Ease of connection and adjustment of operating points. Being a fixed installation greatly inhibits any type of manipulation.
— High reliability and safety which allows operation of steam boilers without permanent supervision.
— Through the elimination of unnecessary equipment and the direct installation of the electrode in the boiler body a mainte-
nance free installation is obtained, with the corresponding financial savings.
— Centralized control and possibility of executing complex regulation and control.
— All controllers and electrodes are rigorously tested and verified.
— Each of the components is numbered, registered and checked. If prior request is made a certificates of materials, batch
and tests will be supplied.
Level controller. RN-1
Level electrode. EN-1
An RN-1 level controller together with two EN-1 level electrodes controls the operation of the boiler feedwater pumps, and
consequently the level of the water in the boiler.
In installations without constant preventative maintenance we recommend the installation of a third EN-1 level electrode,
associated with the same RN-1 level controller, whose function is to cut-off the feedwater pump if the maximum allowed level
in the boiler is exceeded.
Operating principles
The operation of the RN-1 level controller is based on the measurement by conductivity principle. When the probe of the
EN-1 level electrode is submerged or out of the water, the bridging circuit of the switching amplifier is made or broken
respectively. The signal is amplified and is used to energize a relay.
The circuits for water level control and maximum water level are symmetrical and totally separated. The switching relays of
each circuit are independent, but with a common power supply.
In order to avoid disturbances to the control system caused by waves in the boiler water, the power signals from the RN-1
level controller have a built in 10 second delay. This means that the motors and connection elements are protected from
spurious interruptions.
Operation
When the level of water falls below the normal operating level,
the probe of the EN-1.2 level electrode (feedwater pump stop)
is exposed followed by that of the EN-1.3 (feedwater pump
start). Automatically, the RN-1 level controller switching relay is
energized and the feedwater pump is started. The green lamp,
which indicates that the feedwater pump is running, is lit up.
The probe of the EN-1.3 level electrode (feedwater pump start)
is gradually submerged along with that of EN-1.2 (feedwater
pump stop). When the EN-1.2 level electrode probe (feedwater
pump stop) is submerged the switching relay is deenergised,
the green lamp switched off, and the pump shut down. If, due Maximum level
Maintenance
The RN-1 level controller does not require daily checking. However a functional check should be carried out periodically.
Check the electrode probe every six months and clean thoroughly.
After every change of controllers or electrodes, the correct operation of the controls should be checked before putting the boiler
in service.
Breakdown
1- The feedwater pump does not start and the RS-1 minimum level safety controller indicates insufficient water:
1- — Check the state of the thermal protection relay on the feedwater pump motor.
1- — Check the supply voltages on the RN-1 level controller.
1- — Check the connections between controller and electrode (RN-1 / EN-1.3).
1- — Check the RN-1 level controller fuse (M.250/0,10A).
1- — The probe on the EN-1.3 level electrode for feedwater pump start-up is too long.
1- — The probe on the EN-1.2 level electrode for feedwater pump stop is not earthed.
1. — Change the RN-1 level controller.
2- The feedwater pump does not stop and the boiler is over-filled:
2- — Check the controller-electrode connections (RN-1/EN-1.2).
2- — The probe on the EN-1.2 level electrode for feedwater pump stop is too short.
2- — Change the RN-1 level controller.
VYC controllers and electrodes are officially approved by several international organisations and must be repaired only in our
workshops.
Minimum level safety controller. RS-1
Minimum level safety electrode. ES-1
The RS-1 minimum level safety controller, together with the ES-1 minimum level safety electrode, facilitates the measurement
of minimum water level in the boiler.
If a minimum level is detected, the failure signal is automatically activated and the burner is disconnected. The controller and
the electrode are equipped with devices for selfchecking and manual checking, which ensures reliable and safe operation.
Any number of RS-1 minimum level safety controllers, each with its own ES-1 minimum level safety electrode, can be
installed to obtain the required level of protection.
Operating principles
The operation of the RS-1 minimum level safety controller is based on the difference in conductivity of water and steam.
The ES-1 minimum level safety electrode consists of a water measuring probe and a steam compensating ring. These are
concentrically mounted and separated by special insulating covers. When the water measuring probe is out of the water the
bridging circuit in the switching amplifier is lost. The signal is amplified and desenergizes a relay which activates the failure
signal and disconnects the burner.
The RS-1 minimum level safety controller has two channels and is equipped with a self-checking device. At a given switching
frequency, the device carries out a periodic checking of the electronic circuitry and the connection between the electrode
and the controller. This self-checking is generated by simulating a loss of water. In order to avoid disturbances to the safety
system, caused by waves in the boiler water, the signal generated by the RS-1 minimum level safety controller has a built in
5 second delay. This prevents shutdowns caused by spurious failures.
Operation
The green operation lamp is on when the RS-1 minimum level
safety controller is energized indicating that there is sufficient
water in the boiler.
The RS-1 minimum level safety controller is equipped with
buttons for manual checking:
1-Checking electrode (measuring probe): When this button
isn pressed for 5 seconds the electronic circuit and the
connection between controller and electrode are checked.
The simulation of water loss caused by cutting the voltage
to the electrode causes a shutdown of the relay. The
operation lamp goes off, the failure signal is activated and
the burner is disconnected.
2-Isolation checking: When this button is pressed for 5 seconds
the isolation is checked. The isolation of electronic circuitry
Maintenance
The RS-1 minimum level safety controller, as it is self-checking, only requires a 6 monthly inspection by a qualified technician. We
recommend carrying out the above mentioned manual checks once or twice per week.
Check the electrode measuring probe every 6 months and clean thoroughly.
After every change of controller or electrode, the correct functioning of the controls should be checked before putting the boiler
back in service.
Breakdown
The RS-1 minimum level safety controller is an electronic device which is not subject to any mechanical wear or breakage.
In the unlikely case of breakdown:
— Check the boiler water level.
— Check the RS-1 minimum level safety controller fuse (M.250/0,20A).
— Check the connection between controller and electrode (RS-1/ES-1).
— Change the RS-1 minimum level safety controller. If the failure continues the failure is caused by the ES-1 minimum level safety
electrode.
VYC controllers and electrodes are officially approved by several international organisations and must be repaired only in our
workshops.
Electrodes
Connection:
–.Whitworth gas-tght cylindrical male
thread ISO 228/1 (DIN-259) 1”. Electrode connection collector
– NPT thread ASME/ANSI B1.20.1 As the body of the boiler cannot be perforated, the electrode connection collector allows
via adapter. 1” F-GAS to 1” or 11/4” the boiler to be equipped with an electrode based electronic level control device or the
M-NPT. Mod.176 ES-1 only 1”x11/4”. substitution of an old buoy type automatic level controller.
Maximum operating temperature: 238°C.
Maximum operating pressure: 32 bar.
Protection: IP-65. Nominal pressure: PN-40.
MODEL EN-1 ES-1 Allowable pressures and temperatures according to DIN-2401. Sheet 2.
R 1" 1" Flange connection: DN-25 (EN 1092-1).
H 952 952 Electrode connection: Whitworth gas-tigth cylindrical female thread ISO 228/1 (DIN-259) 1”.
H1 700 700
h1 252 252
h2 153 153 We recommend adding a blowoff valve to the equipment, Mod. 999, 1/2” joined to the
h3 547 547 waste pipe for periodic release of sludge. As a minimum a 2 ÷ 3 second release must be
L 53 53
WEIGHT IN kgs. 1,09 1,12 performed every 8 hours.
CODE If an electrode connection is to be taken out of service, the necessary plugs and seals can
71021 71022
2104 - 176. be supplied.
L L DN 25 25 25 25
R 1" 1" 1" 1"
h1(1) 190 190 250 250
N°. OF ELECTRODE CONNECTIONS 1 3 1 3
H 650 650 680 680
h1
h1
h2
L2 95 95 95 95
H
h3
DRILLS N°. 4 4 4 4
WEIGHT IN kgs. 11,74 11,45 12,19 11,90
CODE
EN-1 ES-1 2104 - 176.
83441 83442 83443 83444
Controllers
Voltage: 220 V.A.C. ± 10% 50/60 Hz.
Electrical consumption: Approximately 6 VA. (RN-1), 10 VA. (RS-1).
Relay contact: 250 V., 5 A.
Electrode circuit voltage: Galvanically isolated from mains. 7V. AC.
Output relays delay on deenergising: 10 seconds (RN-1), 5 seconds (RS-1).
Minimum operating conductivity: 3 µs/cm (RN-1), 0,05 ÷ 1 µs/cm (RS-1).
Ambient temperature: 0 to 55°C.
Controller protection: IP-10.