Flowphant T DTT31, DTT35

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

TI00125R/09/EN/03.

18 Products Solutions Services


71415566
2018-02-15

Technical Information
Flowphant T DTT31, DTT35
Flow switch

Applications
Flow switch for monitoring and displaying the relative mass flow rates of liquid
media in the range from 0.03 to 3 m/s (0.1 to 9.84 ft/s):
• Flowphant T DTT31 − with threaded connections or compression fitting
• Flowphant T DTT35 − with process connections for hygienic applications
Applications:
• Monitoring of cooling water circuits of pumps, turbines, compressors and heat
exchangers
• Monitoring of pump functions
• Leak monitoring in process pipes
• Monitoring of lubrication circuits
• Filter monitoring in the beverages industry

Your benefits
The compact flow switch impresses with state-of-the-technology:
• Virtually zero pressure loss
• FieldCare for quick configuration and reliable storage of device settings
• Optional: 4 to 20 mA analog output for outputting the flow as a percentage
• Optional: second switch output or 4 to 20 mA analog output for temperature
monitoring
• Onsite function check and process information with digital display on device
• Top housing section which can be rotated 310° and rotatable display mean
measured values can be read in all installation positions
• Marine approval
• 3-A mark and EHEDG certificate for DTT35
Flowphant T DTT31, DTT35

Table of contents

Function and system design . . . . . . . . . . . . . . . . . . . 3 Operability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16


Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Remote operation with PC . . . . . . . . . . . . . . . . . . . . . . . 18
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Certificates and approvals . . . . . . . . . . . . . . . . . . . 19
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Electromagnetic compatibility (EMC) . . . . . . . . . . . . . . . 19
Hygiene standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Parts in contact with medium . . . . . . . . . . . . . . . . . . . . 19
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Marine approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Other standards and guidelines . . . . . . . . . . . . . . . . . . . 19
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Material certification . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Range of adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Switching capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Ordering information . . . . . . . . . . . . . . . . . . . . . . . 19
Inductive load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Device-specific accessories . . . . . . . . . . . . . . . . . . . . . . 20
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Communication-specific accessories . . . . . . . . . . . . . . . . 21
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Supplementary documentation . . . . . . . . . . . . . . . 23
Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . 23
Performance characteristics . . . . . . . . . . . . . . . . . . . 7 Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . 23
Reference operating conditions . . . . . . . . . . . . . . . . . . . . 7
Maximum measured error . . . . . . . . . . . . . . . . . . . . . . . 7
Switch point non-reproducibility . . . . . . . . . . . . . . . . . . . 9
Temperature gradient . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sensor response time . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Long-term drift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Long-term reliability . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Switch output response time . . . . . . . . . . . . . . . . . . . . . . 9
Analog output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . 10
Inlet and outlet runs . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Ambient temperature range . . . . . . . . . . . . . . . . . . . . . 12
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Shock resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Process temperature range . . . . . . . . . . . . . . . . . . . . . . 12
Process pressure range . . . . . . . . . . . . . . . . . . . . . . . . . 12
Flow limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Operational range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Mechanical construction . . . . . . . . . . . . . . . . . . . . 13
Design, dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
DTT31 design, dimensions of the process connections . . . . 13
DTT35 design, dimensions of the process connections . . . . 14
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

2 Endress+Hauser
Flowphant T DTT31, DTT35

Function and system design


Measuring principle

80%

DJ
vm

A0023188

The device measures the mass flow of a liquid medium using the calorimetric measurement method.
The calorimetric measuring principle is based on the cooling of a heated temperature sensor. Heat is
removed from the sensor by forced convection due to medium flowing by. The extent of this heat
transfer depends on the flow velocity of the medium and the difference in temperature between the
sensor and the medium (King's Law). The higher the flow velocity or the mass flow of the medium,
the greater the temperature sensor cooling.

Measuring system Overview

Flowphant DTT31 DTT35


product
family

A0023194
A0005276

Sensing RTD RTD


element

Field of Monitoring of the mass flow of water, water- Monitoring of the mass flow of liquid media in
application like substances and low-viscosity oils hygienic processes (viscosity:
(viscosity: 0.184 to 20 mPa⋅s; thermal 0.184 to 20 mPa⋅s; thermal conductivity:
conductivity: 29 to 688 mW/mK). Example: 29 to 688 mW/mK). Example: aqueous
aqueous solution monoethylene glycol (20vol solution monoethylene glycol (20 °C vol%) at
%) at 20 °C: viscosity: 1.65 mPa⋅s; thermal 20 °C: viscosity: 1.65 mPa⋅s; thermal
conductivity: 512mW/mK conductivity: 512 mW/mK

Endress+Hauser 3
Flowphant T DTT31, DTT35

Flowphant DTT31 DTT35


product
family

Process • Compression fitting Hygiene:


connection • Thread: • Conical metal-metal G½"
– G½" and G¼" • Clamp 1" - 1½", 2"
– ANSI NPT¼" and NPT½" • Varivent F, N
• DIN 11851
• APV Inline

Measuring Mass flow as a relative value between 0 to 100%.


range Process measuring limit for liquids: 0.03 to 3 m/s (0.1 to 9.84 ft/s)

DC voltage version (DC)


PNP switch output of electronics.
Power supply e.g. with a power supply unit.
Preferably in connection with programmable logic controllers (PLC) or for controlling a relay.

A B

2 2

1 1
RNB130

RNB130
! !

2 3

1
RNB130

A0005373

A 1x PNP switch output


B 2x PNP switch output
C PNP switch output with additional analog output 4 to 20 mA(active)
1 Transmitter power supply unit, e.g. RNB130
2 Load (e.g. programmable logic controller, process control system, relay)
3 Display unit e.g. RIA452 or recorder e.g. Ecograph T or Minilog B (at 4 to 20 mA analog output)

1 "Easy Analog RNB130" transmitter power supply unit:


Primary switched-mode power supply for sensors. Space-saving DIN rail mounting as per IEC 60715.
Wide-range input: 100 to 240 VAC nominal voltage; output: 24 VDC, max. 30 V in the event of an
error;
Nominal current: 1.5 A. Connection to single-phase alternating current networks or to two phase
conductors of three-phase supply networks.
2 process display units RIA452:
If you would like to read off the instantaneous temperature value not only locally, but also directly
from a control room or in the PC network, for example, the process display unit RIA452 is one
possible solution: Digital process display unit in 96 to 96 mm (3.78 to 3.78 in) panel mounted

4 Endress+Hauser
Flowphant T DTT31, DTT35

housing for monitoring and displaying analog measured values with pump control and batch
functions. Multicolored 7-digit 14-segment LC display with bargraph representation. Configuration
and measured value visualization via RS232 interface and PC configuration software.
3 Universal Graphic Data Manager Ecograph T, data logger Minilog B:
If you would not only like to read off the instantaneous temperature value, but also record, analyze
and display it directly in a control room or in the PC network, for example, then the following options
are available:
• Universal Graphic Data Manager Ecograph T in 144 mm (5.67 in) x 144 mm (5.67 in) panel
mounted housing for the electronic capture, display, recording,analysis, remote transmission and
archiving of analog and digital input signals. Multichannel data recording system with
multicolored TFT display (145 mm (5.7 in)) screen size), galvanically isolated universal inputs (U,
I, TC, RTD, pulse, frequency), digital inputs, transmitter power supply, limit relays, communication
interfaces (USB, Ethernet, optionally RS232/485), 128 MB internal memory, external SD card and
USB stick. The Field Data Manager (FDM) software supports data analysis at the PC, the device
can be configured with FieldCare or the integrated Web server.
• Data logger Minilog B measured value recorder with 2 input channels for recording and storing
analog and digital values. Internal 128 kB memory for max. 84 000 measured values.
Configuration and measured value visualization via RS232 interface and PC configuration
software. Optionally available with telealarm function.

Input
Measured variable • Flow velocity of liquid media (calorimetric measuring principle)
• Temperature (RTD), optionally for two switch outputs or additional analog output

Measuring range Flow 0.03 to 3 m/s (0.1 to 9.84 ft/s), as relative value between 0 to 100%; maximum
display resolution: 1%

Temperature –20 to +85 °C (–4 to +185 °F); display resolution: 1 °C (1 °F)

Output
Output signal DC voltage version (short-circuit proof version):
• 1x PNP switch output (flow) or
• 2x PNP switch outputs (flow or temperature, configurable) or
• 1x PNP switch output and 1x 4 to 20 mA output, active (flow or temperature, configurable)
The analog output reports the measured flow as a relative value expressed as a percentage of
the set measuring range.

Signal on alarm Analog output: signal on alarm according to NAMUR NE43

Underranging Linear drop to 3.8 mA

Overranging Linear rise to 20.5 mA

Sensor breakage; sensor ≤3.6 mA or ≥ 21.0 mA (output 21.7 mA is guaranteed for setting ≥ 21.0 mA)
short-circuit

Switch outputs In the safe state (switch open)

Load Max. (Vpower supply- 6.5 V) / 0.022 A (current output)

Range of adjustment Switch output Switch point (SP) and switchback point (RSP) in increments of 1% with min.
hysteresis of 5%

Damping User-configurable 0 = off (no damping) or 10 to 40 s in increments of 1 s

Unit %, optionally °C, °F (with two outputs and temperature monitoring)

Endress+Hauser 5
Flowphant T DTT31, DTT35

Switching capacity DC voltage version:

Switch status ON Ia ≤ 250 mA

Switch status OFF Ia ≤ 1 mA

Switching cycles > 10,000,000

Voltage drop PNP ≤2 V

Overload protection Switching current checked automatically; switched off in event of overcurrent,
switching current checked again every 0.5 s; max. capacitive load: 14 µF for max.
supply voltage (without resistive load); periodic disconnection from a protective
circuit in event of overcurrent (f = 2 Hz) and "Warning" displayed

Inductive load To prevent electrical interference, only operate an inductive load (relays, contactors, solenoid valves)
with a direct protective circuit (free-wheeling diode or capacitor).

Power supply
Electrical connection Plug connector
DTT35: According to the 3-A Standards electrical connecting cables must be smooth, corrosion-
resistant and easy to clean.

M12x1 M16x1.5 / NPT ½”

A B

A0023196

A M12x1 connector
B Valve connector M16x1.5 or NPT ½"

Device connection
DC voltage version with M12x1 connector

A1 A2
L+ A2’ L+
2 1 2 1

3 4 R1 3 4
R1 m
L– L–

A3
L+
2 1

3 4
4...20 mA R2
L–
A0006818

1 Flowphant T with M12x1 connector

6 Endress+Hauser
Flowphant T DTT31, DTT35

Item No. Output setting

A1 1x PNP switch output

A2 A2 2x PNP switch output R1 and m (R2)

A2’ 2x PNP switch output R1 and m (diagnostics/NC contact for "DESINA"


setting)

A3 1x PNP switch output and 1x analog output (4 to 20 mA)

DC voltage version with M16x1.5 valve connector or NPT ½"

B 1 L+

R 2

L–
A0035798

Item No. Output setting

B 1x PNP switch output

Supply voltage DC voltage version: 18 to 30 VDC (reverse polarity protection)


Behavior in the event of overvoltage (>30 V)
• The device works continuously up to 34 VDC without any damage
• No damage in event of transient overvoltage up to 1 kV (according to EN 61000-4-5)
• If the supply voltage is exceeded, the specified characteristics are no longer guaranteed
Behavior in the event of undervoltage
If the supply voltage falls below the minimum value, the device switches off in a defined manner
(status as if not supplied with power = switch open)

Current consumption < 100 mA (no-load) at 24 VDC, max. 150 mA (no-load); with reverse polarity protection

Performance characteristics
The percentage information in the "Performance characteristics" section refers to the full scale value
or the set maximum value (100% value) of the monitoring range.

Reference operating As per DIN IEC 60770 or DIN IEC 61003


conditions T = 25 °C (77 °F) ± 5 °C (9 °F)
– Relative humidity 45 to 75%
– Ambient air pressure 860 to 1 060 kPa (124 to 153 psi), water testing medium
– Supply voltage U = 24 VDC

Maximum measured error Flow


The device records flow velocities relatively in relation to a set flow monitoring range (0 to 100 % as
the display value). Absolute measurement of the flow velocity or the mass flow is not possible. The
sensitivity of the calorimetric flow sensor changes with the flow velocity of the medium. It increases
with decreasing flow velocity (example: in the case of water, the greatest sensor sensitivity is in the
range from 0.03 to 0.5 m/s).

Endress+Hauser 7
Flowphant T DTT31, DTT35

LOWF 0%

Sensor signal

A
HIF 100%

LOWF 0%

B
HIF 100%

0 Flow rate
A0008181-EN

2 Standard characteristic
A, B Configured flow monitoring ranges (example)

LOWF 0%: Setting for the minimum flow velocity occurring in monitoring range A or B (0% value)
HIF 100%: Setting for the maximum flow velocity occurring in monitoring range A or B (100% value)
Temperature
• Accuracy2 K (3.6 °F)
• Reproducibility1 K (1.8 °F)
• Influence of ambient temperature 0.05%/K of full scale value

8 Endress+Hauser
Flowphant T DTT31, DTT35

Switch point non- The values indicated only apply to the device itself without factoring in the temperature-
reproducibility dependent change in the thermophysical properties of the medium. For this reason, it is
advisable to commission the device and set the switch points at the process temperature
→  16

Measuring range (water as medium) % of maximum value Influence of medium temperature Influence of ambient temperature
1)
0.03 to 0.5 m/s (0.1 to 1.6 ft/s) ≤2% ) 0.05 %/K 0.04 %/K

0.03 to 1 m/s (0.1 to 3.28 ft/s) ≤3 %2) 0.10 %/K 0.05 %/K

0.03 to 2 m/s (0.1 to 6.56 ft/s) ≤5 %2) 0.15 %/K 0.10 %/K

0.03 to 3 m/s (0.1 to 9.84 ft/s) ≤10 %2) 0.20 %/K 0.30 %/K

1) For a Reynolds number > 10,000

Temperature gradient If the medium experiences a temperature change of ≥ 0.5 K/min, temporary display drifts are
possible which can exceed the specified non-reproducibility values of the switch point.

Sensor response time 6 to 12 s

Long-term drift < 0.5% per year under reference operating conditions

Long-term reliability Mean time between failure (MTBF) calculated according to SN29500 (at 40 °C)

Low stress environment: < 0.1G 227 years

High stress environment: < 0.1G 48 years

Switch output response time 100 ms

Analog output Maximum measured error Switch point and display deviation + 0.1%

Rise time t90 ≤200 ms

Settling time t99 ≤500 ms

Endress+Hauser 9
Flowphant T DTT31, DTT35

Installation
Orientation No restrictions. However, self-draining in the process must be guaranteed. If there is an opening to
detect leaks at the process connection, this opening must be at the lowest possible point.

Installation instructions • The sensor tip should be completely surrounded by


the medium. 80 %

• Position the sensor tip in the area of maximum flow


velocity (pipe center).
• Minimum sensor immersion length:
Li ≥ 10 mm (0.4 in). 1

vm Li

A0006976

3 Installation instructions (example)

Orientation
• For horizontal pipes: lateral installation. Installation
from above only if the pipe is completely filled with

80
%
medium
• For vertical pipes: installation in the ascending pipe
• For DTT35: install at an angle of at least 3° for self-
draining

%
80
%
80
= 3°

A0006977

4 Correct orientation

 Do not install in down pipes open towards the


end. The sensor tip should never touch the pipe 80
%

wall.
80
%

A0006978

5 Incorrect installation!

• The display can be rotated electronically by 180 °.


• The top housing section can be rotated mechanically by up to 310 °.

10 Endress+Hauser
Flowphant T DTT31, DTT35

A B C
Sensor with
milk pipe
Sensor with
connection
Varivent connection
Groove
slip-on nut
Companion
connection
O-Ring Shaped
Companion gasket
connection
Companion
connection

Sealing
Centering ring
R0.4 R0.4
A0011673-EN

6 Installation in hygienic processes


A Sanitary connection according to DIN 11851 (PL, PG, PH connection), only in conjunction with EHEDG-
certified and self-centering sealing ring as per EHEDG position paper
B Varivent and APV-Inline (LB, LL, HL connection)
C Clamp according to ISO 2852 (DB, DL connection), only in conjunction with seal as per EHEDG position paper

The following action must be taken if a sealing ring (O-ring) or seal fails:
• Remove the thermometer, clean the thread and the O-ring joint/sealing surface
• Replace the sealing ring or seal
• Perform CIP after installation
In the case of weld-in connections, exercise the necessary degree of care when performing the
welding work on the process side:
• Suitable welding material
• Flush-welded or with welding radius > 3.2 mm (0.13 in)
• No recesses, folds or gaps
• Honed and polished surface, Ra ≤ 0.8 mm (0.031 in)
As a general rule, the thermometers should be installed in such a way that does not impact
their ability to be cleaned (the requirements of the 3-A Standard must be observed). The
Varivent® couplings enable flush-mount installation.

Inlet and outlet runs The thermal measuring principle is sensitive to disturbed flow conditions.
• As a general rule, install the measuring device as far away as possible from any flow
disturbances. For further information → ISO 14511.
• If possible, install the sensor upstream from fittings such as valves, T-pieces, elbows etc.
• To attain the specified level of accuracy of the measuring device, the inlet and outlet runs
mentioned below must be maintained at the very minimum.
• If several flow disturbances are present, maintain the longest specified inlet run.

Endress+Hauser 11
Flowphant T DTT31, DTT35

1 2 3
5 × DN 3 × DN 5 × DN 3 × DN 5 × DN 3 × DN

4 5 6
15 × DN 3 × DN 10 × DN 3 × DN 5 × DN 3 × DN

A0023225

1 Reduction
2 Expansion
3 90° elbow or T-piece
4 Pump
5 Control valve
6 2x 90° elbow, 2- or 3-dimensional

Environment
Ambient temperature range –40 to +85 °C (–40 to +185 °F)

Storage temperature –40 to +85 °C (–40 to +185 °F)

Degree of protection IP65 M16 x 1.5 or NPT ½", valve connector

IP66 M12 x 1 connector

Shock resistance 50 g as per DIN IEC 68-2-27 (11 ms)

Vibration resistance • 20 g as per DIN IEC 68-2-6 (10-2000 Hz)


• 4 g as per marine approval

Process
Process temperature range –20 to +85 °C (–4 to +185 °F)
The sensor can be exposed to process temperatures up to 130 °C (266 °F) without being damaged.
The monitoring system switches off automatically at T ≥ 85 °C (185 °F) and starts again at T ≤
85 °C (185 °F).

Process pressure range Maximum permissible process pressure Pmax ≤ 10 MPa = 100 bar (1 450 psi)
The maximum process pressure for the conical metal-metal process connection (MB option) for
the device is 1.6 MPa = 16 bar (232 psi).

Flow limit Liquids: 0 to 3.0 m/s (0 to 9.84 ft/s)

Operational range Liquids: 0.03 to 3.0 m/s (0.1 to 9.84 ft/s)

12 Endress+Hauser
Flowphant T DTT31, DTT35

Mechanical construction
Design, dimensions
M12x1 M16x1.5 / NPT ½”

38.7 (1.52) 38.7 (1.52) !42.3 (1.66)


24 (0.95) 24 (0.95) !38.5 (1.52)
36 (1.42)

52 (2.05)

97.1 (3.82)
42.1 (1.66)
!6 (0.24) !6 (0.24) !6 (0.24)

L L L

A0005279

All dimensions in mm (in)


L = insertion length
M12x1 connector as per IEC 60947-5-2
Valve connector M16x1.5 or NPT ½" as per DIN 43650A/ISO 4400

DTT31 design, dimensions of


the process connections

1
L2 L1 2

L L1 = L2

A B C
A0007101

7 Process connection versions

Item Version Insertion length L Thread length L1 Screw-in length L2


No.

A Without process connection. - -


Suitable welding bosses and
compression fittings. →  20

B Threaded process connection: • 14.3 mm • 5.8 mm (0.23 in)


• 30 mm (1.18 in) (0.56 in) • 8.1 mm (0.32 in)
ANSI NPT ¼" (1 = AF14)
• 50 mm (1.97 in) • 19 mm (0.75 in)
ANSI NPT ½" (1 = AF27)
• 100 mm (3.94 in)
C Threaded process connection, • 12 mm (0.47 in) -
inches, cylindrical as per ISO 228: • 14 mm (0.55 in)
G¼" (2 = AF14)
G½" (2 = AF27)

Endress+Hauser 13
Flowphant T DTT31, DTT35

DTT35 design, dimensions of


the process connections DB (CLAMP 1”) DL(CLAMP 2”)

10 (0.39)
!43.5 (1.71) !56.5 (2.22)
!64 (2.52)
MB !50.5 (1.99)

LB(Varivent F) LL(Varivent N) HL(APV-Inline)


SW/ B

37 (1.46)
L1
AF 22

18 (0.71)

18 (0.71)

19 (0.75)
!50 (1.97) !68 (2.68) !61.5 (2.42)
G½” !66 (2.6) !84 (3.31) !82 (3.23)
!100 (3.94)

L
PL (DIN 11851) PG (DIN 11851) PH(DIN 11851)

13 (0.51)

13 (0.51)
!51 (2.01) !27 (1.06) !39 (1.54)

(0.51)
!68 (2.68) !44 (1.73) !56 (2.21)

13
A0011776

8 Process connection versions


All dimensions in mm (in).
L = insertion length L

Item No. Process connection versions DTT35 Hygiene standard

DB Clamp 1" to 1½" (ISO 2852) or DN 25 to 40(DIN 3-A marked and EHEDG-certified (only
32676) with self-centering seal, as per EHEDG
position paper)
DL Clamp 2" (ISO 2852) or DN 50 (DIN 32676)

HL APV-Inline, DN50, PN40, 316L, B = bores 6 x 3-A marked and EHEDG-certified


⌀8.6 mm (0.34 in) + 2 x thread M8

LB Varivent F DN25-32, PN 40, 316L 3-A marked and EHEDG-certified

LL Varivent N DN40-162, PN 40, 316L 3-A marked and EHEDG-certified

MR Metal sealing system for hygienic processes, G½"


thread, thread length
L1 = 14 mm (0.55 in). Suitable welding boss
available as an accessory. 316L

PG DIN 11851, DN25, PN40 (including coupling 3-A marked and EHEDG-certified (only
nut), 316L with self-centering sealing ring, as per
EHEDG position paper)

PH DIN 11851, DN40, PN40 (including coupling 3-A marked and EHEDG-certified (only
nut), 316L with self-centering sealing ring, as per
EHEDG position paper)

PL DIN 11851, DN50, PN40 (including coupling 3-A marked and EHEDG-certified (only
nut), 316L with self-centering sealing ring, as per
EHEDG position paper)

Weight Approx. 300 g (10.58 oz), depends on process connection and sensor length

Materials

14 Endress+Hauser
Flowphant T DTT31, DTT35

• Process connection AISI 316L


– Surfaces in contact with the process in hygienic version with surface quality Ra ≤
0.8 µm (31.5 µin)
– Coupling nut AISI 304
• AISI 316L housing, with surface quality Ra ≤ 0.8 µm (31.5 µin)
O-ring between housing and sensor module: EPDM
• Electrical connection
– M12 connector, exterior AISI 316L, interior polyamide (PA)
– Valve connector, polyamide (PA)
– M12 connector, exterior 316L
– Cable sheath polyurethane (PUR)
– O-ring between electrical connection and housing: FKM
• Display, polycarbonate PC-FR (Lexan®)
Seal between display and housing: SEBS THERMOPLAST K®
• Keys, polycarbonate PC-FR (Lexan®)

Endress+Hauser 15
Flowphant T DTT31, DTT35

Operability
Operating concept Position of the display and operating elements

Operating keys
E

Digital display
LED for status Illumination white (= ok)
Green = ok Illumination red (= error/fault)
Red = error/fault
LED red/green blinking = warning Yellow LEDs for switching states
LED on = switch closed
LED off = switch open

Communication jack
for personal computer
A0020825-EN

Local operation Menu-guided operation using operating keys.

Function group Function (display) Description

BASE DISP Display Display assignment:


(basic functions) • OFF
• Display of current measured value or of configured switch point
(switch 1)
• Display of current measured value or of configured switch point
(switch 1) rotated by 180°
• Display of current medium temperature
• Display of current medium temperature rotated by 180°
• Factory setting: current measured value

UNIT Technical unit Medium temperature displayed in the unit °C or °F


Factory setting: °C

 selected
Only visible if the current medium temperature TMP is
in the DISP mode.

TAU Damping Measured value damping with regard to display value and output:
0 (no damping) or 9 to 40 s (in increments of 1 s)
Factory setting: 0 s

DESI DESINA Behavior as per DESINA:


Only for 2 x PNP switch The PIN assignment of the M12 connector is in accordance with
outputs the DESINA Guidelines
(DESINA = distributed and standardized installation technology for
machine tools and manufacturing systems)
Factory setting: NO

CAL HIF Learn High Flow Setting for the maximum flow rate that occurs. 100% value
Calibration
LOWF Learn Low Flow Setting for the maximum flow rate that occurs. 0% value

Switch outputs MODE Switching mode Process value for analog output: flow or temperature
OUT (setting for the 1st Factory setting: flow
output)
OUT2 (setting for the 2nd UNIT Technical unit Temperature unit selection (°C or °F)
output)
OUT  Function is only visible if the switching mode MODE is set to
temperature TEMP in the 2nd output.
Output 2
Factory setting: °C

FUNC Function 1 Switch output function:


FNC2 Function 2, optional Hysteresis function NC contact or NO contact (see the following
diagram)

16 Endress+Hauser
Flowphant T DTT31, DTT35

Function group Function (display) Description

SP Switch point Enter value 5 to 100% in increments of 1%, only if High and Low
SP2 Switch point 2, optional Flow (HIF and LOWF) have been configured beforehand. Factory
setting: 50 %
or optionally for SP2:
Enter value –15 to +85 °C (–5 to +185 °F) in increments of
1 °C (1 °F) if the switching mode MODE is set to temperature
TEMP. Factory setting: 55 °C

SPL Switch point learn Take current flow rate as SP.


SP2L Switch point learn 2,
optional

RSP Switchback point Enter value 0 to 95% in increments of 1%.


RSP2 Switchback point 2, Factory setting: 40%
optional
 Value must be at least 5% smaller than switch point 2 (SP2).
or optionally for RSP2:
Enter value –20 to +80 °C (–4 to +176 °F) in increments of
1 °C (1 °F) if the switching mode MODE is set to temperature
TEMP.
Factory setting: 50 °C

 Value
SP2.
must be at least 5 °C (9 °F) smaller than switch point

TSP Switch point delay Can be set anywhere between 0 to 99 sin increments of 1 s
TSP2 Switch point 2 delay, Factory setting: 0 s
optional

TRSP Switchback point delay Can be set anywhere between 0 to 99 s in increments of 1 s


TRSP2 Switchback point 2 delay, Factory setting: 0 s
optional

Analog output 4-20 MODE Output mode Process value for analog output: flow or temperature
(setting for the analog Factory setting: flow
output, optional)
FCUR Failure current Specify the failure current:
Choice of MIN = ≤3.6 mA
MAX = ≥21.7 mA
HOLD = last current value
Factory setting: MAX

SERV PRES Reset Reset all entries to the delivery settings.


(service functions)
REV'C Static revision counter Configuration counter, incremented each time the configuration is
changed.

LOCK Locking code Enter the device locking code.

Code Edit locking code Locking, only visible if the locking code is valid.

STAT Device status

LSTA Last error Displays the last error to occur.

Simulation: SIMU Simulation 1 Simulation switch output 1: on/off with display, optionally
Version 2 x switch output SIM2 Simulation 2, optional corresponding to switch output 2.

Simulation: SIM Simulation 1 - switch Simulation switch output 1: on/off with display
Version 1 x analog output SIMA output Simulation values for analog output in mA.
and 1 x switch output Simulation 2 - analog
output

Endress+Hauser 17
Flowphant T DTT31, DTT35

Functions of the switch point %


• Hysteresis function: The hysteresis function enables
two-point control via a hysteresis. Depending on the 1
mass flow, the hysteresis can be set via the switch
point SP and switchback point RSP SP
• NO contact or NC contact: This switch function can RSP
be selected as required.
• Delay times for switch point SP and switchback
point RSP can be configured in increments of 1 s.
t
This makes it possible to filter out undesired
temperature peaks of short duration or of high 1
0 2
frequency
1
0 3

A0005280

9 SP switch point; RSP switchback point


1 Hysteresis function
2 NO contact
3 NC contact

Remote operation with PC Operation, visualization and maintenance with PC and FieldCare PC configuration software.

1 2 3

A0008072

 10 Operation, visualization and maintenance with PC and configuration software


1 PC with FieldCare configuration software
2 Configuration kit TXU10-AA or FXA291 with USB port
3 Flow switch

In addition to the operating options listed in the previous "Onsite operation" section, further
information about the Flowphant T is available via the FieldCare configuration software:

Function group Function (display) Description

SERV (service function) Switching operations 1 Number of changes in the switching state for
Switching operations 2, optional switch output 1; optionally for switch output 2

INFO (device information) TAG 1 Tagging, 18-digit


TAG 2, optional

Order code Order code

Serial number Device serial number

Sensor serial number Sensor serial number

Electronics serial number Electronics serial number

Device version Displays overall version

Hardware revision Hardware version

Software revision Software version

18 Endress+Hauser
Flowphant T DTT31, DTT35

Certificates and approvals


Electromagnetic EMC to all relevant requirements of the IEC/EN 61326-series and NAMUR Recommendation EMC
compatibility (EMC) (NE21). For details, refer to the Declaration of Conformity.
Maximum fluctuations during EMC-tests: < 1 % of measuring span.
Interference immunity to IEC/EN 61326-series, requirements for industrial areas
Interference emission to IEC/EN 61326-series, electrical equipment Class B

Hygiene standard • EHEDG certification, TYPE EL CLASS I. Permitted process connections in accordance with EHEDG,
see 'Process connections' section →  13
• 3-A Authorization No. 1144. 3-A Sanitary Standard. Permitted process connections in accordance
with 3-A, see also "Process connections" section
• 3-A marked process connections →  14

Parts in contact with medium The thermometer parts in contact with the medium meet the following European regulations:
• (EC) No. 1935/2004, Article 3, Paragraph 1, Articles 5 and 17 on materials and articles intended
to come into contact with food.
• (EC) No. 2023/2006 on good manufacturing practice (GMP) for materials and articles intended to
come into contact with food.
• (EC) No. 10/2011 on plastic materials and articles intended to come into contact with food.
• All surfaces in contact with the medium are free from materials derived from bovine animals or
other livestock (ADI/TSE)

Marine approval Information on the "Type Approval Certificates" currently available (DNVGL, BV, etc.) can be obtained
from the sales organization.

Other standards and • IEC 60529


guidelines Degrees of protection provided by enclosures (IP code)
• IEC/EN 61010-1
Protection Measures for Electrical Equipment for Measurement, Control, Regulation and
Laboratory Procedures
• NAMUR
International user association of automation technology in process industries (www.namur.de)
• NEMA
United States National Electrical Manufacturers Association.

Material certification The material certificate 3.1 (according to standard EN 10204) can be requested separately. The
"short form" certificate includes a simplified declaration with no enclosures of documents related to
the materials used in the construction of the individual sensor. It does, however, guarantee the
traceability of the materials through the identification number of the thermometer. The data related
to the origin of the materials can subsequently be requested by the client if necessary.

Ordering information
Detailed ordering information is available from the following sources:
• In the Product Configurator on the Endress+Hauser website: www.endress.com -> Click "Corporate"
-> Select your country -> Click "Products" -> Select the product using the filters and search field ->
Open product page -> The "Configure" button to the right of the product image opens the Product
Configurator.
• From your Endress+Hauser Sales Center: www.addresses.endress.com
Product Configurator - the tool for individual product configuration
• Up-to-the-minute configuration data
• Depending on the device: Direct input of measuring point-specific information such as
measuring range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop

Endress+Hauser 19
Flowphant T DTT31, DTT35

Accessories
Device-specific accessories Welding boss with sealing taper

• Collar welding boss movable with sealing taper, "6 (0.24)


washer and pressure screw G½"
• Material of parts in contact with the process: 316L, G½”
1
PEEK,
• Max. process pressure 10 bar (145 psi) AF24
• Order number: 51004751

36 (1.42)
2

25 (0.98)
3
4

"30 (1.18)
A0020709-EN

 11 Dimensions in mm (in)
1 Pressure screw, 303/304
2 Washer, 303/304
3 Sealing taper, PEEK
4 Collar welding boss, 316L

Collar welding boss

• Collar welding boss movable with sealing taper, G½”


washer and pressure screw G½"
• Material of parts in contact with the process: 316L,
PEEK,
• Max. process pressure 10 bar (145 psi)
• Order number: 51004752
25 (0.98)

!6 (0.24)

!30 (1.18)
A0020710

 12 Dimensions in mm (in)

Welding boss with sealing taper (metal-metal)

• Collar welding boss, metal-metal seal !30 (1.18)


• Material of parts in contact with the process: 316L,
Max.
• Process pressure 16 bar
16 (0.63)

• Order No. 60021387 G½”


34 (1.34)
15 (0.6)

A0006621

 13 Dimensions in mm (in)

20 Endress+Hauser
Flowphant T DTT31, DTT35

Compression fitting

• Movable clamping ring, various process connections "6 (0.24)


• Material of compression fitting and parts in contact
with the process: 316L
• Order number: TA50-..... (depending on the process
connection)
AF14

45+1 (1.77+0.04)
15 (0.59)
AF27

G½”
A0020174-EN

 14 Dimensions in mm (in)

Version F in mm (in) L ~ in mm (in) C in mm B in mm Clamping Max. process Max. process


(in) (in) ring temperature pressure
material

TA50 G½" SW/AF 27 47 (1.85) - 15 (0.6) SS316 1) 800 °C (1 472 °F) 40 bar at 20 °C
(580 psi at 68 °F)

PTFE 2) 200 °C (392 °F) 5 bar at 20 °C


(72.5 psi at 68 °F)

G¾" SW/AF 32 63 (2.48) - 20 (0.8) SS316 1) 800 °C (1 472 °F) 40 bar at 20 °C


(580 psi at 68 °F)

PTFE 2) 200 °C (392 °F) 5 bar at 20 °C


(72.5 psi at 68 °F)

G1" SW/AF 41 65 (2.56) - 25 (0.98) SS316 1) 800 °C (1 472 °F) 40 bar at 20 °C


(580 psi at 68 °F)

PTFE 2) 200 °C (392 °F) 5 bar at 20 °C


(72.5 psi at 68 °F)

NPT½" SW/AF 22 50 (1.97) - 20 (0.8) SS316 1) 800 °C (1 472 °F) 40 bar at 20 °C


(580 psi at 68 °F)

R½" SW/AF 22 52 (2.05) - 20 (0.8) PTFE 2) 200 °C (392 °F) 5 bar at 20 °C


(72.5 psi at 68 °F)

R¾" SW/AF 27 52 (2.05) - 20 (0.8) PTFE 2) 200 °C (392 °F) 5 bar at 20 °C


(72.5 psi at 68 °F)

TA70 For weld-in 30 (1.18) 76 (3) 34 (1.34) - Silopren® 2) 180 °C (356 °F) 20 bar at 20 °C
(290 psi at 68 °F)

1) SS316 clamping ring: can only be used once. Once released the compression fitting cannot be repositioned on the thermowell. Fully adjustable
immersion length on initial installation
2) PTFE/Silopren® clamping ring: can be reused, once released the fitting can be moved up and down the thermowell. Fully adjustable immersion
length

Communication-specific Coupling; connecting cable


accessories
• Coupling M12x1; straight
• Connection to M12x1 housing connector
• Materials: body PA, coupling nut CuZn, nickel-
plated
• Degree of protection (connected): IP 67
• Order number: 52006263 A0035843

Endress+Hauser 21
Flowphant T DTT31, DTT35

• M12x1 coupling; elbowed, for termination of 35 (1.38)


connecting cable by user
• Connection to M12x1 housing connector
• Materials: body PBT/PA,

(0.79)
20
• Coupling nut GD-Zn, nickel-plated
• Degree of protection (connected): IP 67

(1.61)
• Order number: 51006327

41
14.8
(0.58)
A0020722

 15 Dimensions in mm (in)

• PVC cable (terminated), 4 x 0.34 mm2 with M12x1 1 2

coupling, elbowed, screw plug, length 5 m (16.4 ft) 4 3


• Degree of protection: IP67
• Order number: 51005148 1 (BN) +
Core colors: 2 (WH) nc
• 1 = BN brown 3 (BU) -
• 2 = WH white 4 (BK) nc
A0020723
• 3 = BU blue
• 4 = BK black

• PVC cable, 4x 0.34 mm2with M12x1 coupling, with ye1


LED, elbowed,
• 316L screw plug, length5 m (16.4 ft), specially for ye2 gn
hygiene applications,
• Degree of protection (connected): IP69K
• Order number: 52018763
Display:
• gn: device is operational
• ye1: switch status 1
• ye2: switch status 2

 Not suitable for 4 to 20 mA analog output! A0035844

Configuration kit

• Configuration kit for PC-programmable USB


transmitters;
Configuration software and interface cable for PC
with USB port and 4-pin post connector
Order code: TXU10-AA
• "Commubox FXA291" configuration kit with
interface cable for PC with USB port. Intrinsically
safe CDI interface (Endress+Hauser Common Data
Interface) for transmitters with 4-pin post
connector. Suitable configuration software is A0008067
FieldCare for example.
Order code: FXA291

Configuration software
The FieldCare 'Device Setup' configuration programs can be downloaded free of charge from the
Internet at:
www.products.endress.com/fieldcare
FieldCare ’Device Setup’ can also be ordered from an Endress+Hauser sales office.

22 Endress+Hauser
Flowphant T DTT31, DTT35

Supplementary documentation
Technical Information • Easy Analog RNB130: TI120R/09/en
• Process display unit RIA452: TI113R/09/en
• Universal data manager Ecograph T: TI01079R/09/en
• Data logger Minilog B: TI089R/09/en

Operating Instructions Flow switch Flowphant T DTT31, DTT35: BA00235R/09/en

Endress+Hauser 23
www.addresses.endress.com