2psoc Notes
2psoc Notes
Control area: Most power systems normally control their generators in unison. The
individual control loops have the same regulation parameters. The individual
generator turbines tend to have the same response characteristics then it is possible to
let the control loop in the whole system which then would be referred to as a control
area.
Prime Mover: The engine, turbine, water wheel, or similar machine that drives an electric
generator; or, for reporting purposes, a device that converts energy to electricity directly (e.g.,
photovoltaic solar and fuel cell(s)).
Pumped-Storage Hydroelectric Plant: A plant that usually generates electric energy during
peak-load periods by using water previously pumped into an elevated storage reservoir during
off-peak periods when excess generating capacity is available to do so. When additional
generating capacity is needed, the water can be released from the reservoir through a conduit
to turbine generators located in a power plant at a lower level.
Retail Wheeling: The process of moving electric power from a point of generation across one
or more utility-owned transmission and distribution systems to a retail customer.
Revenue: The total amount of money received by a firm from sales of its products and/or
services, gains from the sales or exchange of assets, interest and dividends earned on
investments, and other increases in the owner's equity except those arising from capital
adjustments.
Real power: The real power in a power system is being controlled by controlling the
driving torque of the individual turbines of the system.
For the analysis, the models for each of the blocks in Fig2 are required. The
generator and the electrical load constitute the power system. The valve and the
hydraulic amplifier represent the speed governing system.Using the
swing
equation, theegenerator can b Using the swing equation, the generator can be
modeled
by �
Turb
∆de1+∆
G(s) =
=
∆
Gt(s) is the TF of the turbine; PV(s) is the change in valve output (due to
action). Pm(s) is the change in the turbine output
The governor can similarly modeled as shown inig2F.7. The output of the governor is by
Where ∆Pref is the reference set power, and ∆w/R is the power given by
governor speed characteristic. The hydraulic amplifier transforms this signal Pg into
valve/gate position corresponding to a power PV.
Thus
PV(s) = (Kg/ (1+sTg)) _Pg(s).
LFC control of single area and derive the steady state frequency error.
All the individual blocks can now be connected to represent the complete ALFC loop as
We have
The generator is synchronized to a network of very large size. So, the speed or
frequency will be essentially independent of any changes in a power output of the generator
ie, ∆F(s) =0
Let us assume that we made a step change of the magnitude ∆Pc of the speed
∆PG (stat) = ∆
(ii)Uncontrolled case
Let us assume that the load suddenly increases by small amount ∆PD.Consider
there is no external work and the generator is delivering a power to a single load.
It has been shown that the load frequency control system posses inherently steady state error
for a step input. Applying the usual procedure, the dynamic response of the control loop can be
evaluated so that the initial response also can be seen for any overshoot.
For this purpose considering the relatively larger time constant of the power system the
governor action can be neglected, treating it as instantaneous action. Further the turbine generator
dynamics also may be neglected at the first instant to derive a simple expression for the time
response.
∆PG(s) = 1/ (1+sTG) (1+sTt) [-∆F(s)/R] For
∆PG(s) = 1/(1+sTG)(1+sTt)[-
Steady State Performance of the ALFC Loop state, and the output is obtained by
In the steady state, the ALFC is in ‘open’
substituting s→0 in the TF.
With s→0, Gg(s) and Gt(s) become unity, then,(note that ∆Pm =∆PT = PG =∆Pe = ∆PD;
That is turbine output = generator/electrical output = load demand)
When the generator is connected to infinite bus (∆f = 0, and ∆V = 0), then ∆Pm = ∆Pref .
If the network is finite, for a fixed speed changer setting (∆Pref = 0), then
∆Pm = (1/R)∆f or∆f=RPm.
Concept of AGC (Supplementary ALFC Loop)
The ALFC loop shown in is called the primary ALFC loop. It achieves the
primary goal of real power balance by adjusting the turbine output ∆Pm to match the
change in load demand ∆PD. All the participating generating units contribute to the change in
generation. But a change in load results in a steady state frequency deviation
∆f. The restoration of the frequency to the nominal value requires an additional control loop
called the supplementary loop. This objective is met by using integral controller which
makes the frequency deviation zero. The ALFC with the supplementary loop is generally
called the AGC. The block diagram of an AGC is shown in Fig3.9. The main objectives of
AGC a r e i) to regulate t h e frequency (using b o t h primary a n d
supplementary controls); ii) and to maintain the scheduled tie-line flows. A secondary
objective of the AGC is to distribute the required change in generation among the connected
generating units economically (to obtain least operating costs).
Block diagram representation of the AGC
`Now we are going to study the effect of a disturbance in the system derived above.
Both loss of generation and loss of load can be simulated by imposing a positive or negative
step input on the variable Pload. A change of the set value of the system frequency f0 is not
considered as this is not meaningful in real power systems. From the block diagram in
Figure 3.9 it is straightforward to derive the transfer function between
In order to calculate an equivalent time constant Teq, Tt is put to 0. This can be done since
for realistic systems the turbine controller time constant Tt is much smaller than the time
constant
AGC IN A MULTI AREA SYSTEM
In an interconnected (multi area) system, there will be one ALFC loop for each control area (located
at the ECC of that area). They are combined as shown in Fig2.10 for the interconnected system
operation. For a total change in load of ∆PD, the steady state Consider a two area system as depicted
in Figure 3.10. The two secondary frequency controllers, AGC1 and AGC2, will adjust the power
reference values of the generators participating in the AGC. In an N-area system, there are N
controllers AGCi, one for each area
A block diagram of such a controller is given in Figure 4.2. A common way is to implement
this as a proportional-integral (PI) controller:
∆f=∆ω 1=∆ω 2
β1= D1+1/R1
Assumption in Analysis:
The following assumptions are made in the analysis of the two area system:
1. The overall governing characteristic of the operating units in any area can be represented
by
a linear curve of frequency versus generation.
2. The governors in both the areas start acting simultaneously to changes in their respective
areas.
3. Supplementary control devices act after the initial governor response is over
The following time instants are defined to explain the control sequence:
To=is the instant when both the areas are operating at the scheduled frequency
and Tie=line interchange and load change takes place.
tl = the instant when governor action is initiated at both A and B.
t2 =the instant when governor action ceases.
t3 =the instant when regulator action begins.
t4 = the instant when regulator action ceases.
`While the initial governor response is the same as for the previous case, the action of
the controller in B will force the generation in area B to absorb the load increment in area A.
When the controller begins to act at t3, the governor characteristic is shifted parallel to itself in
B till the entire load increment in A is absorbed by B and the frequency is restored to normal.
Thus, in this case while the frequency is regulate on one hand, the tie-line schedule is not
maintained on the other hand.
If area B, which is in charge of frequency regulation, is much larger than A, then load
changes in A will not appreciably affect the frequency of the system. Consequently, it can be
said that flat frequency control is useful only when a small system is’ connected to a much
larger system.
Consider two inter connected areas as shown in figure operating at the same frequency fl
power Power flow from area I to area 2
nd V 2 be the voltage magnitudes
voltage phase angles at the two ends of the tie-
line While P flows from area I to area 2 then,
Where X is the reactance of the line. If the angles change by f1o1, and f102 due to load
changes in areas I and 2 respectively. Then, the tie-line power changes by
Block diagram for tie-line power
Dynamic Response:
Let us now turn our attention during the transient period for the sake of simplicity. We
shall assume the two areas to be identical .Further we shall be neglecting the time constants of
generators and turbines as they are negligible as compared to the time constants of power
systems. The equation may be derived for both controlled and uncontrolled cases. There are
four equations with four variables, to be determined for given PDl and PD2. The dynamic
response can be obtained; even though it is a little bit involved. For simplicity assume that the
two areas are equal. Neglect the governor and turbine dynamics, which means that the
dynamics of the system under study is much slower than the fast acting turbine-governor
system in a relative sense. Also assume that the load does not change with frequency (D, = D2
= D = 0).
We obtain under these assumptions the following relations
No hat both K and ro2 are positive. From the roots of the characteristic
equation we notice tha e system is stable and damped. The frequency of the
damped oscillations is given by Since Hand fo are constant, the frequency of
oscillations depends upon the regulation parameter R. Low R gives high K and
high damping and vice versa .We thus conclude from the preceding analysis that
the two area system, just as in the case of a single area system in the uncontrolled
mode, has a steady state error but to a lesser extent and the tie line power deviation and
frequency deviation exhibit oscillations that are damped out later.