Distribution System Feeder Overcurrent Protection
Distribution System Feeder Overcurrent Protection
Overcurrent Protection
General Electric
GET-6450
HISTORICAL PAPER
from the GE Archive
1. Introduction
With the increasing loads, voltages and short-circuit duty of
distribution substation feeders, distribution overcurrent protection
has become more important today than it was even 10 years ago.
The ability of the protective equipment to minimize damage when
failures do occur and also to minimize service interruption time is
demanded not only for economic reasons but also because the
general public just expects “reliable” service.
Among the areas covered will be such things as: cold load pickup,
ground-fault detection, tripping methods, current-transformer
(CT) connections, line burndown, and coordination between
various devices.
2. Relay Fundamentals
2.1 Required Characteristics
The required characteristics necessary for protective equipment
to perform its function properly are: sensitivity, selectivity, speed
and reliability. This is especially true for relays.
Sensitivity
A basic requirement of protective relaying equipment is that it The application of overcurrent relays is generally more difficult
be reliable. Reliability refers to the ability of the relay system to and less permanent than that of any other type of relaying. This
perform correctly. It denotes the certainty of correct operation is because the operation of overcurrent relays is affected by
together with the assurance against incorrect operation from all variations in short-circuit-current magnitude caused by changes
extraneous causes. The proper application of protective relaying in system operation and configuration. Overcurrent relaying in
equipment involves the correct choice not only of relaying one form or another has been used for relaying of all system
equipment but also of the associated apparatus. For example, components. It is now used primarily on distribution systems
lack of suitable sources of current and voltage for energizing the where low cost is an important factor.
relay may compromise, if not jeopardize, the protection. Figure 3 shows a family of inverse-time curves of the widely used
IAC relay, which is an induction disc type. The time curves for the
2.2 Characteristics of Overcurrent Relays new design IFC relay are similar.
The overcurrent relay is the simplest type of protective relay. (See A curve is shown for each numerical setting of the time dial scale.
Figure 1.) As the name implies, the relay is designed to operate Any intermediate curves can be obtained by interpolation since
when more than a predetermined amount of current flows into a the adjustment is continuous.
particular portion of the power system. There are two basic forms
of overcurrent relays: the instantaneous type and the time-delay It will be noted that the curves shown in Figure 3 are plotted in
type. terms of multiples of pickup value, so that the same curves can be
used for any value of pickup. This is possible with induction-type
The instantaneous overcurrent relay is designed to operate with relays where the pickup adjustment is by coil taps, because the
no intentional time delay when the current exceeds the relay ampere-turns at pickup are the same for each tap. Therefore at
setting. Nonetheless, the operating time of this type of relay can a given multiple of pickup, the coil ampere-turns, and hence the
vary significantly. It may be as low as 0.016 seconds or as high as torque, are the same regardless of the tap used.
0.1 seconds. The operating characteristic of this relay is illustrated
Current tap block Time dial Instantaneous
unit pickup
Sliding top lead Time dial
adjustment
Current tap block
Instantaneous unit
Target and calibration plate
seal-in unit Sliding top lead
Seal-in contact Instantaneous unit
pickup adjustment
Time-overcurrent Instantaneous unit Target and
stationary contact contact seal-in unit Instantaneous
Control spring Target coil tops unit contact
Identification
Operating coil card
Time overcurrent Time-overcurrent
Time-overcurrent
Damping magnet stationary contact moving contact
moving contact
Induction disk Seal-in contact Identification
Chassis contact
card
Cradle block Operating coil
Latch
Typical IAC relay mechanism with standard hinged armature instantaneous unit Typical IFC relay mechanism with standard hinged armature instantaneous unit
withdrawn from case (Model 12IAC53BB10A) withdrawn from case (model 12IFC53B1A)
Figure 1.
Typical IAC and IFC time-overcurrent relays
During light loads, some of the generators are usually shut down. At
other times, the system may be split into several parts. In either case,
the short-circuit current tends to vary with the amount of generation
feeding it. It should be appreciated that a reduction in the magnitude of
shortcircuit current raises all of the characteristic curves of Figure 4.
Figure 4.
Operating time of overcurrent relays with inverse time characteristics
Figure 5.
Reduction in tripping time using instantaneous relaying
Figure 6. Figure 7.
Elementary diagram of overcurrent relays used for Alternative contact seal-in methods
phase- and ground-fault protection of three-phase circuit
Figure 8.
Elementary diagram of overcurrent relays used with DC battery tripping
The capacitor trip unit can be used only with low energy tripping
devices such as the impact trip device used .on modern breaker-
operating mechanisms. Due to the limited amount of energy
available from this device, the breaker must be well maintained to
assure successful operation. This unit provides tripping potential
independent of the magnitude of fault current, which makes it
particularly applicable on lightly loaded, high-impedance circuits
where AC current trip cannot be used and a battery cannot be
justified.
1. the fuse must be replaced every time it blows, To prevent the extremely inverse relay from operating on
cold-load pickup, its minimum pickup should not be less than 200
2. the possibility of blowing one fuse and single-phasing three- to 250 percent of full-load current. In this case. It will be about
phase motors exists, 90-amperes primary current. As Figure 13 shows, the two devices
are coordinated only if the maximum secondary fault current is
3. the operating time of the fuse must be quite slow so that it less than 1500 amperes. If such is not the case, then the size of
coordinates with secondary and feeder breaker relays, and the fuse must be increased, which in turn limits it’s transformer-
finally overload protection capabilities.
Relay:
The percent of total travel of the IAC relay during the various
recloser operations is as follows, where plus means travel in the
contact-closing direction and minus means travel in the re-set
direction:
It is apparent from this that the IAC relay will completely reset
while the recloser is open following each instantaneous opening.
From this analysis, it appears that the relay will have a net travel
of 60.3 percent of the total travel toward the contact-closed
position.
Figure 20 shows what occurs when the current flowing through the
fuse link is interrupted periodically. The oscillogram shows typical
recloser operation. The first time the recloser opens and closes
due to fault or overload, the action is instantaneous, requiring only
two cycles. The second action is also two cycles, while the third
action is delayed to 20 cycles, as is the fourth. Then the recloser
locks itself open.
Curve A’, Figure 21, is the sum of two instantaneous openings (A) Figure 20.
and is compared with the fuse damage curve which is 75 percent Fuse link heating and cooling
of the melting-time curve of the fuse.
Two specific areas where the electromechanical (IAC and IFC) and
static (SFC) relay differ are overtravel and reset.
Figure 23. For practical purposes, these numbers can be given as 0.3
Sample system for recloser-relay coordination illustration seconds for IAC and IFC electromechanical relays and 0.2 seconds
for SFC static relays.
In Figure 25 the system curves are again drawn, but this time for
static SFC 177 relays on the feeder breaker and as the backup
relay, The reset time of the SFC (0.1 seconds) is faster than the
reclosing delay of either the automatic recloser or the reclosing
feeder breaker. Therefore, no consideration at all need be given
to “notching” and the relay settings can be determined by the Figure 26.
time-current curves alone. Also, because overtravel is negligible, Burndown characteristics of several weatherproof conductors
Figure 27.
Curves illustrating coordination between the arc damage and burndown characteristics for a No. l/O conductor land the protective devices which must
operate to prevent serious conductor damage
motorizing effect occurs only on the phase wire since current 24 BUS-TIE CIRCUIT BREAKER serves to connect buses or bus
sections together.
may flow both ways in the neutral. When the 25 percent of the
burndown and the protective equipment should be installed to 27 AC UNDERVOLTAGE RELAY is one which functions on a given
value of singlephase AC undervoltage.
limit the currents and times to less than those given.
TRANSFER DEVICE is a manually operated device which
43 transfers the control circuit to modify the plan of operation of
With tree branches falling on bare conductors, the arc may the switching equipment or of some of the devices.
travel away and clear itself; however, the arc will generally re- SHORT-CIRCUIT SELECTIVE RELAY is one which functions
instantaneously on an excessive value of current or on
establish itself at the original point and continue this procedure 50 an excessive rate of current rise, indicating a fault in the
apparatus or circuit being protected.
until the line burns down or the branch fails off the line. Limbs of
soft spongy wood are more likely to burn clear than hard wood. 51 AC OVERCURRENT RELAY is one which functions when the
current in an AC circuit exceeds a given value.
However, one-half inch diameter branches of any wood, which
AC CIRCUIT BREAKER is one whose principal function is usually
cause a flashover, are apt to burn the lines down unless the fault 52 to interrupt short-circuit or fault currents.
is cleared quickly enough.
Feeders Find the current tap setting by dividing the minimum primary
tripping current by the current transformer ratio: g= 7.5 Since
A similar series of numbers starting.with 101 instead of 1, is used there is no 7.5-ampere tap, use the 8-ampere tap. TO find the time
for the functions which apply to automatic reclosing feeders. setting which will give 1.9-second time delay at 3750 amperes,
divide 3750 by the transformer atio. This gives 62.5-amperes
Hand reset secondary current, which is 7.8 times the 8-ampere tap setting.
The term “Hand Reset” shall be added wherever it applies.
042610-v8