StarterKit

Portable simulator for


InteliGen 1000 controller

1 Document information 3
2 System overview 6
3 Step by step instruction 10
4 Technical data 13

Copyright © 2021 ComAp a.s.


Written by Vladimír Malý
Prague, Czech Republic
ComAp a.s., U Uranie 1612/14a,
170 00 Prague 7, Czech Republic
Tel: +420 246 012 111
E-mail: [email protected], www.comap-control.com Operator Guide
Table of contents
1 Document information 3
1.1 Clarification of Notation 3
1.2 About this guide 3
1.3 Legal notice 3
1.3.1 Dangerous voltage 5
1.4 Document history 5

2 System overview 6
2.1 StarterKit content 6
2.2 Block scheme 7
2.3 StarterKit overview 7
2.3.1 Front panel elements 7
2.3.2 Shipping and handling 9

3 Step by step instruction 10


3.1 Work with StarterKit 10
3.1.1 Binary inputs (BIN) 10
3.1.2 Binary outputs (BOUT) 10
3.1.3 Analog inputs 11
3.1.4 Simulator control 12
3.2 StarterKit first launch guidelines 12
3.3 Custom configuration 12

4 Technical data 13

IG1000 StarterKit Operator Guide 2


1 Document information
1.1 Clarification of Notation 3
1.2 About this guide 3
1.3 Legal notice 3
1.4 Document history 5

1.1 Clarification of Notation


Note: This type of paragraph calls the reader’s attention to a notice or related theme.

IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.

Example: This type of paragraph contains information that is used to illustrate how a specific function
works.

1.2 About this guide


This guide contains a description of StarterKit. It is described how to start using and control the StarterKit. It is
intended for trained specialist in electrical engineering.
It is not described controlling and configuration of the controller. For detailed information about controller
operation please see InteliGen 1000 Global Guide.

1.3 Legal notice


This End User's Guide/Manual as part of the Documentation is an inseparable part of ComAp’s Product
and may be used exclusively according to the conditions defined in the “END USER or Distributor LICENSE
AGREEMENT CONDITIONS – COMAP CONTROL SYSTEMS SOFTWARE” (License Agreement) and/or in
the “ComAp a.s. Global terms and conditions for sale of Products and provision of Services” (Terms) and/or in
the “Standardní podmínky projektů komplexního řešení ke smlouvě o dílo, Standard Conditions for Supply of
Complete Solutions” (Conditions) as applicable.
ComAp’s License Agreement is governed by the Czech Civil Code 89/2012 Col., by the Authorship Act
121/2000 Col., by international treaties and by other relevant legal documents regulating protection of the
intellectual properties (TRIPS).
The End User and/or ComAp’s Distributor shall only be permitted to use this End User's Guide/Manual with
ComAp Control System Registered Products. The Documentation is not intended and applicable for any
other purpose.
Official version of the ComAp’s End User's Guide/Manual is the version published in English. ComAp
reserves the right to update this End User's Guide/Manual at any time. ComAp does not assume any
responsibility for its use outside of the scope of the Terms or the Conditions and the License Agreement.
Licensed End User is entitled to make only necessary number of copies of the End User's Guide/Manual. Any
translation of this End User's Guide/Manual without the prior written consent of ComAp is expressly
prohibited!
Even if the prior written consent from ComAp is acquired, ComAp does not take any responsibility for the
content, trustworthiness and quality of any such translation. ComAp will deem a translation equal to this End

IG1000 StarterKit Operator Guide 3


User's Guide/Manual only if it agrees to verify such translation. The terms and conditions of such verification
must be agreed in the written form and in advance.
For more details relating to the Ownership, Extent of Permitted Reproductions Term of Use of the
Documentation and to the Confidentiality rules please review and comply with the ComAp’s License
Agreement, Terms and Conditions available on www.comap-control.com.
Security Risk Disclaimer
Pay attention to the following recommendations and measures to increase the level of security of ComAp
products and services.
Please note that possible cyber-attacks cannot be fully avoided by the below mentioned recommendations
and set of measures already performed by ComAp, but by following them the cyber-attacks can be
considerably reduced and thereby to reduce the risk of damage. ComAp does not take any responsibility for
the actions of persons responsible for cyber-attacks, nor for any damage caused by the cyber-attack.
However, ComAp is prepared to provide technical support to resolve problems arising from such actions,
including but not limited to restoring settings prior to the cyber-attacks, backing up data, recommending other
preventive measures against any further attacks.
Warning: Some forms of technical support may be provided against payment. There is no legal or factual
entitlement for technical services provided in connection to resolving problems arising from cyber-attack or
other unauthorized accesses to ComAp's Products or Services.
General security recommendations and set of measures
1. AccessCode
• Change the AccessCode BEFORE the device is connected to a network.
• Use a secure AccessCode – ideally a random string of 8 characters containing lowercase, uppercase letters
and digits.
• For each device use a different AccessCode.
2. Password
• Change the password BEFORE the device enters a regular operation.
• Do not leave displays or PC tools unattended if an user, especially administrator, is logged in.
3. Controller Web interface
• The controller web interface at port TCP/80 is based on http, not https, and thus it is intended to be used only
in closed private network infrastructures.
• Avoid exposing the port TCP/80 to the public Internet.
4. MODBUS/TCP
• The MODBUS/TCP protocol (port TCP/502) is an instrumentation protocol designed to exchange data
between locally connected devices like sensors, I/O modules, controllers etc. From it’s nature it does not
contain any kind of security – neither encryption nor authentication. Thus it is intended to be used only in
closed private network infrastructures.
• Avoid exposing the port TCP/502 to the public Internet.
5. SNMP
• The SNMP protocol (port UDP/161) version 1,2 is not encrypted. Thus it is intended to be used only in
closed private network infrastructures.
• Avoid exposing the port UDP/161 to the public Internet.

IG1000 StarterKit Operator Guide 4


1.3.1 Dangerous voltage
In no case touch the terminals for voltage and current measurement!
Always connect grounding terminals!
In any case do not disconnect controller CT terminals!

IMPORTANT: Before using please be sure that the external power source (socket) for StarterKit is
equipped with an Overcurrent protection that is based dimension and parameters of the
connection.

1.4 Document history


Revision number Related SW version Date Author
2 1.0.0 22.11.2021 Vladimír Malý
1 1.0.0 3.9.2021 Vladimír Malý

IG1000 StarterKit Operator Guide 5


2 System overview
StarterKit is dedicated for the simulation of basic application using ComAp controller InteliGen 1000 (IG1000).
StarterKit allows to simulate various states of mains, Gen-set, network elements (especially breakers) and
other devices. StarterKit also enable basic user connection for monitoring and configuration from the front
panel of StarterKit.
For more possibilities of simulation it is a need of advanced configuration.

2.1 StarterKit content 6


2.2 Block scheme 7
2.3 StarterKit overview 7
2.3.1 Front panel elements 7
2.3.2 Shipping and handling 9
6 back to Table of contents

2.1 StarterKit content


DC Power supply for the controller
Front panel
ON/OFF button
Binary inputs levers connected to switches
Binary outputs states indicated by LEDs
Analog inputs changeable by potentiometers
USB (type B) connection to PC -> USB (type A to type B)
On the StarterKit there is a USB sockets available, which are used for InteliVision 5.2 connection.

IG1000 StarterKit Operator Guide 6


2.2 Block scheme

Image 2.1 StarterKit - block scheme

2.3 StarterKit overview


2.3.1 Front panel elements
There are two types of the StarterKits. The first type StarterKit is based on InteliSys controller and as a display
is used InteliVision 8. The second type is based on InteliGen controller and as a display is used InteliVision 5.

SK item number
Controller SK name
(order code)
InteliGen InteliGen 1000 InteliGen 1000 + IV5.2 StarterKit SM4IG1K5BAB

IG1000 StarterKit Operator Guide 7


Image 2.2 StarterKit – front panel

IV5.2 display unit For more information about display see InteliVision 5.2 Global Guide.
LEDs indication Binary output LEDs indication
Levers Binary inputs adjustment
Potentiometers Analog inputs adjustment
USB A and B USB A port connected to the InteliVision 5.2 display

IG1000 StarterKit Operator Guide 8


2.3.2 Shipping and handling

Image 2.3 StarterKit – air valve

Image 2.4 StarterKit – secure for transportation

6 back to System overview

IG1000 StarterKit Operator Guide 9


3 Step by step instruction
3.1 Work with StarterKit
StarterKit Default configuration

3.1.1 Binary inputs (BIN)


Allows to change BI of the controller

Input number Default function or protection Input option / Default position


BIN 1 GCB Feedback ON / AUT / OFF
BIN 2 MCB Feedback ON / AUT / OFF
BIN 3 Remote Start/Stop Normally Open
BIN 4 Emergency Stop Normally Close
BIN 5 Access Lock int Normally Open
BIN 6 Remote Off Normally Open
BIN 7 Remote Test Normally Open
BIN 8 Warning 8 Normally Open
BIN 9 Warning 9 Normally Open
BIN 10 Warning 10 Normally Open
BIN 11 SD11 Normally Open
BIN 12 SD12 Normally Open

E-STOP Default function or protection Normally Open

IMPORTANT: For the correct function of the Starterkit it is necessary to setup first two BI
according to the above table and put the levers to AUT position.

3.1.2 Binary outputs (BOUT)


Output number Default function
BOUT 1 Starter
BOUT 2 Fuel solenoid
BOUT 3 GCB close/open

IG1000 StarterKit Operator Guide 10


Output number Default function
BOUT 4 MCB close/open
BOUT 5 Alarm
BOUT 6 Horn
BOUT 7 Prestart
BOUT 8 Idle/Nominal
BOUT 9 Ready
BOUT 10 Running
BOUT 11 Ready to load
BOUT 12 Cooling pump

IMPORTANT: For the correct function of the StarterKit it is necessary to setup first four BOUTs to
functions according to the table above.

3.1.3 Analog inputs

AIN1 Oil Pressure


AIN2 Water Temp
AIN3 Fuel Level
AIN4 Sec Water Temp

Before work with StarterKit begins please be sure that the latest software is installed on your computer. It is
recommended to install the latest InteliConfig Installation Suite or Upgrade package, Firmware package.

IG1000 StarterKit Operator Guide 11


3.1.4 Simulator control
The Um lever is dedicated to a simulation of Mains fail.
StarterKit also allows you to set up the level of:

Um Mains Voltage
Ugen Generator voltage
Igen Generator current (and Power)
RPM Engine RPM and Generator frequency

3.2 StarterKit first launch guidelines


1. Connect the power wire to a power socket
2. Turn on the power switch
3. START/STOP the simulator
Manually via START/STOP Buttons – when the controller is switched to MAN mode
Automatically – For activation of the SK in AUT mode, you should activate BIN 3: Remote Start/Stop.
4. Starting process
During the starting procedure a StarterKit operator should change values manually according to the
controller configuration.
RPM – RPM must be set to nominal RPM via RPM potentiometer

OIL PRESSURE – Oil pressure has to be set above the Shutdown protection Setpoint level.

U GEN – Generator voltage must be set to nominal voltage via UGen potentiometer

I GEN – Generator current must be set to nominal current via IGen potentiometer
More detailed information is available in the "Engine running conditions" chapter in theGlobal Guide.

3.3 Custom configuration


For your own configuration tests, you need to change the configuration in the following way:
Binary inputs and outputs settings
Binary inputs – First two binary inputs (BI) must be setup to specific functions
BI1 – GCB Feedback
BI2 – MCB Feedback
Binary outputs – First four binary outputs (BOUT) must be setup to specific functions
BOUT1 – Starter
BOUT2 – Fuel Solenoid
BOUT3 – GCB Open/Close
BUT4 – MCB Open/Close
Setpoints – There are a few setpoints which must be setup properly

Setpoint Groups Setpoint Name Setpoint Value


Basic Settings Gen CT Ratio Prim Modify maximum current (power)
Basic Settings Gear Teeth 0 (FGen ->RPM) or 256

Note: All information about controllers configuration is available in Global Guide of the controller.

IG1000 StarterKit Operator Guide 12


4 Technical data
Power supply 1 × 100-240 V AC
DC Power supply 1 × 24 V, 3, 2 A
Fuse T2A/250 V 5 × 20 mm
Protection for opened/closed StarterKit IP20/IP53
Operating conditions 0 – 40 °C
Operating humidity 95 % (without condensation)
Dimensions (h × w × l) 214 mm × 415 mm × 474 mm
2
Power cord 300 V / 500 V; 3 × 0.75 mm

6 back to Table of contents

IG1000 StarterKit Operator Guide 13