Enetek - Manual - SMU01 (Modbus Protocol) V2.2 (G)
Enetek - Manual - SMU01 (Modbus Protocol) V2.2 (G)
MODBUS Protocol
Page 1 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Contact Information:
[email protected]
www.enetek-power.com
Page 2 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
All rights reserved: Enetek reserves the right to change the product and the content of this manual
without prior WARNING. Users are recommended to visit the company website at
www.enetek-power.com for more information about our new products and the latest versions of the
user manuals.
Page 3 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Table of Contents
3. Message Format 6
4. Message Type 7
4.1 Remote Telemetry and Signaling..............................................................................................7
4.2 Remote Controlling ..................................................................................................................7
4.3 Error Check Return ...................................................................................................................8
Page 4 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
6.15 System Configuration .............................................................................................................76
6.16 System Information ................................................................................................................77
6.17 Generator & Fuel Tank Parameters ........................................................................................81
6.18 Peak Shaving Parameters .......................................................................................................84
6.19 Password Data ........................................................................................................................85
6.21 System Data............................................................................................................................85
6.22 Test Mode Data ......................................................................................................................86
Page 5 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
1. Introduction
This document provides the MODBUS protocol specific to Enetek’s SMU01 controller module.
2. Physical Interface
SMU01 utilizes TCP/IP port whereas SMU01L utilizes serial communication port RS485.
3. Message Format
Device Address: Controller communication address 1-247. 0, which is broadcast address, is not used here
Function Code:
Controller command function - 03H reads specific location register data, including a group of holding
registers.
06H sets specific location register data, only for a single register.
10H sets specific location register data, including a group of holding
registers.
Parity Check: Cyclic Redundancy Check (CRC) parity, the result will be 0 if correct.
NOTE: A frame can fetch up to 120 registers, and if there are more than 120 registers, it should be in
multiple frames.
Page 6 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
4. Message Type
a. Downlink Data
Device 03H Register Start Register Start Number of Number of CRC Check
Address Address Address Registers Registers (2 byte)
(High-order) (Low-order) (High-order) (Low-order)
b. Uplink Data
a. Downlink Data
Device 06H Register Address Register Address Data Set Data Set CRC Check
Address (High-order) (Low-order) Value Value (2 byte)
(High-order) (Low-order)
b. Uplink Data
Device 06H Register Address Register Address Data Set Data Set CRC Check
Address (High-order) (Low-order) Value Value (2 byte)
(High-order) (Low-order)
a. Downlink Data
b. Uplink Data
Page 7 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
4.3 Error Check Return
There will be an error check return when the slave device receives an error in the transmission. However,
this does not apply to parity check error or other transmission error.
Format: Device address 0x80+function code error code CRC Check (2 byte)
Function code < 0x80+
a. Uplink Data
Device Address 0x80+function code Error code (1 byte) CRC Check (2 byte)
Page 8 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Module Startup [0x06]
Module Shutdown [0x07]
All Modules Shutdown [0x08]
All Modules Restart [0x09]
Invalid Event [0x0A]
Configuration Update [0x0B]
Configuration Restore [0x0C]
Config Parameter Err [0x0D]
000DH Current New Alarm 2 - Read Only u16 Reference to Alarm 1
000EH Current New Alarm 3 - Read Only u16 Reference to Alarm 1
000FH Current New Alarm 4 - Read Only u16 Reference to Alarm 1
0010H Current New Alarm 5 - Read Only u16 Reference to Alarm 1
0011H Current New Alarm 6 - Read Only u16 Reference to Alarm 1
0012H Current New Alarm 7 - Read Only u16 Reference to Alarm 1
0013H Current New Alarm 8 - Read Only u16 Reference to Alarm 1
0014H Current New Alarm 9 - Read Only u16 Reference to Alarm 1
0015H Current New Alarm 10 - Read Only u16 Reference to Alarm 1
0016H Current New Alarm 11 - Read Only u16 Reference to Alarm 1
0017H Current New Alarm 12 - Read Only u16 Reference to Alarm 1
0018H Current New Alarm 13 - Read Only u16 Reference to Alarm 1
0019H Current New Alarm 14 - Read Only u16 Reference to Alarm 1
001AH Current New Alarm 15 - Read Only u16 Reference to Alarm 1
001BH Current New Alarm 16 - Read Only u16 Reference to Alarm 1
001CH Current New Alarm 17 - Read Only u16 Reference to Alarm 1
001DH Current New Alarm 18 - Read Only u16 Reference to Alarm 1
001EH Current New Alarm 19 - Read Only u16 Reference to Alarm 1
001FH Current New Alarm 20 - Read Only u16 Reference to Alarm 1
0020H Reserved
~ 0FFFH
5.2 DC Information
Register Description Unit Read/Write Type Remarks
1000H Bus 1 Voltage 0.1V Read Only u16
1001H Total Load Current 0.1A Read Only u16
1002H Load 1 Current 0.1A Read Only u16
1003H Load 2 Current 0.1A Read Only u16
1004H Load 3 Current 0.1A Read Only u16
1005H Load 4 Current 0.1A Read Only u16
1006H Load 5 Current 0.1A Read Only u16
1007H Load 6 Current 0.1A Read Only u16
1008H Load 7 Current 0.1A Read Only u16
1009H Load 8 Current 0.1A Read Only u16
100AH Load 9 Current 0.1A Read Only u16
100BH Load 10 Current 0.1A Read Only u16
100CH Load 10 Current 0.1A Read Only u16
100DH Load 12 Current 0.1A Read Only u16
100EH Load 13 Current 0.1A Read Only u16
100FH Load 14 Current 0.1A Read Only u16
1010H Load 15 Current 0.1A Read Only u16
1011H Load 16 Current 0.1A Read Only u16
Page 9 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
1012H Special Load 1 Current 0.1A Read Only u16
1013H Special Load 1 Current 0.1A Read Only u16
1014H Special Load 1 Current 0.1A Read Only u16
1015H Special Load 1 Current 0.1A Read Only u16
1016H Total Load Power W.h. Read Only u32 The high byte is transferred first,
1017H followed by the low byte
1018H Load 1 Power W.h. Read Only u32 The high byte is transferred first,
1019H followed by the low byte
101AH Load 2 Power W.h. Read Only u32 The high byte is transferred first,
101BH followed by the low byte
101CH Load 3 Power W.h. Read Only u32 The high byte is transferred first,
101DH followed by the low byte
101EH Load 4 Power W.h. Read Only u32 The high byte is transferred first,
101FH followed by the low byte
1020H Load 5 Power W.h. Read Only u32 The high byte is transferred first,
1021H followed by the low byte
1022H Load 6 Power W.h. Read Only u32 The high byte is transferred first,
1023H followed by the low byte
1024H Load 7 Power W.h. Read Only u32 The high byte is transferred first,
1025H followed by the low byte
1026H Load 8 Power W.h. Read Only u32 The high byte is transferred first,
1027H followed by the low byte
1028H Load 9 Power W.h. Read Only u32 The high byte is transferred first,
1029H followed by the low byte
102AH Load 10 Power W.h. Read Only u32 The high byte is transferred first,
102BH followed by the low byte
102CH Load 11 Power W.h. Read Only u32 The high byte is transferred first,
102DH followed by the low byte
102EH Load 12 Power W.h. Read Only u32 The high byte is transferred first,
102FH followed by the low byte
1030H Load 13 Power W.h. Read Only u32 The high byte is transferred first,
1031H followed by the low byte
1032H Load 14 Power W.h. Read Only u32 The high byte is transferred first,
1033H followed by the low byte
1034H Load 15 Power W.h. Read Only u32 The high byte is transferred first,
1035H followed by the low byte
1036H Load 16 Power W.h. Read Only u32 The high byte is transferred first,
1037H followed by the low byte
1038H Special Load 1 Power W.h. Read Only u32 The high byte is transferred first,
1039H followed by the low byte
103AH Special Load 2 Power W.h. Read Only u32 The high byte is transferred first,
103BH followed by the low byte
103CH Special Load 3 Power W.h. Read Only u32 The high byte is transferred first,
103DH followed by the low byte
103EH Special Load 4 Power W.h. Read Only u32 The high byte is transferred first,
103FH followed by the low byte
1040H Reserved
~ 104FH
1050H Bus 2 Voltage 0.1V Read Only u16
1051H Bus 3 Voltage 0.1V Read Only u16
1052H Reserved
~ 11FFH
Page 10 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
5.3 AC Information
Register Description Unit Read/Write Type Remarks
1200H AC 1 Phase A Voltage 0.01V Read Only u16
1201H AC 1 Phase B Voltage 0.01V Read Only u16
1202H AC 1 Phase C Voltage 0.01V Read Only u16
1203H AC 1 Frequency Hz Read Only u16
1204H AC 2 Phase A Voltage 0.01V Read Only u16
1205H AC 2 Phase B Voltage 0.01V Read Only u16
1206H AC 2 Phase C Voltage 0.01V Read Only u16
1207H AC 2 Frequency Hz Read Only u16
1208H AC 1 Phase A Voltage 0.1A Read Only u16
1209H AC 1 Phase B Voltage 0.1A Read Only u16
120AH AC 1 Phase C Voltage 0.1A Read Only u16
120BH AC 2 Phase A Voltage 0.1A Read Only u16
120CH AC 2 Phase B Voltage 0.1A Read Only u16
120DH AC 2 Phase C Voltage 0.1A Read Only u16
120EH ~ Reserved
12FFH
Page 11 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
………. ……….
142FH #1 Batt, Cell 48 Voltage 0.001V Read Only u16
1430H Reserved
~ 143FH
1440H #2 Batt, Cell 1 Voltage 0.001V Read Only u16
1441H #2 Batt, Cell 2 Voltage 0.001V Read Only u16
………. ……….
146FH #2 Batt, Cell 48 Voltage 0.001V Read Only u16
1470H Reserved
~ 147FH
1480H #3 Batt, Cell 1 Voltage 0.001V Read Only u16
1481H #3 Batt, Cell 2 Voltage 0.001V Read Only u16
………. ……….
14AFH #3 Batt, Cell 48 Voltage 0.001V Read Only u16
14B0H Reserved
~14BFH
14C0H #4 Batt, Cell 1 Voltage 0.001V Read Only u16
14C1H #4 Batt, Cell 2 Voltage 0.001V Read Only u16
………. ……….
14EFH #4 Batt, Cell 48 Voltage 0.001V Read Only u16
14F0H Reserved
~14FFH
1500H Reserved
~15FFH
1600H #1 Batt, Cell 1 Resistance 0.001Ω Read Only u16
1601H #1 Batt, Cell 2 Resistance 0.001Ω Read Only u16
………. ……….
162FH #1 Batt, Cell 48 Resistance 0.001Ω Read Only u16
1630H Reserved
~ 163FH
1640H #2 Batt, Cell 1 Resistance 0.001Ω Read Only u16
1641H #2 Batt, Cell 2 Resistance 0.001Ω Read Only u16
………. ……….
166FH #2 Batt, Cell 48 Resistance 0.001Ω Read Only u16
1670H Reserved
~ 167FH
1680H #3 Batt, Cell 1 Resistance 0.001Ω Read Only u16
1681H #3 Batt, Cell 2 Resistance 0.001Ω Read Only u16
………. ……….
16AFH #3 Batt, Cell 48 Resistance 0.001Ω Read Only u16
16B0H Reserved
~16BFH
16C0H #4 Batt, Cell 1 Resistance 0.001Ω Read Only u16
16C1H #4 Batt, Cell 2 Resistance 0.001Ω Read Only u16
………. ……….
16EFH #4 Batt, Cell 48 Resistance 0.001Ω Read Only u16
16F0H Reserved
~17FFH
Page 12 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
5.5 DI Information
Register Description Unit Read/Write Type Remarks
1800H Open (0-15) Level State - Read Only u32 Open level signal, each bit
represents 1 channel open state,
low level [0], high level [1]
bit0~bit15 open 1~ open 16
1801H Open (16-27) Level state - Read Only u32 Open level signal, each bit
represents 1 channel open state,
low level [0], high level [1]
bit0~bit5 open 1 ~ open 6
(extension board 1)
bit6~bit11 open 1 ~ open 6
(extension board 2)
bit12--bit15: Reserved
1802H Reserved
~ 181FH
5.6 DO Information
Register Description Unit Read/Write Type Remarks
1820H Output Signal - Read Only u32 DO output signal, disconnect [0],
1821H close [1]
bit0~bit5 DO0~DO5 (main board)
bit6~bit11 DO0-DO5 (extension
board 1)
bit12~bit17 DO0-DO5 (extension
board 2)
bit17--bit31: Reserved
1822H Reserved
~ 182FH
Page 13 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Manual connection warning
[0x0F]
Manual connection recovery
[0x10]
Manual connection alarm [0x11]
Prohibit [0x12]
1831H LVD 1 Control Timer s Read Only u16
1832H LVD 1 AC Normal Timer s Read Only u16
1833H LVD 1 AC Abnormal Timer s Read Only u16
1834H LVD 1 Control Input Signal - Read Only u16 Connect [0x00], Disconnect [0x01]
1835H LVD 1 Control Output - Read Only u16 Connect [0x00], Disconnect [0x01]
Signal
1836H LVD 2 Status - Read Only u16 Auto connection normal [0x00]
Auto disconnect normal [0x01]
Auto disconnect prepare [0x02]
Auto connection prepare [0x03]
Auto connection warning [0x04]
Auto connection recovery [0x05]
Auto connection alarm [0x06]
Auto disconnect warning [0x07]
Auto disconnect recovery [0x08]
Auto disconnect alarm [0x09]
Manual disconnect normal [0x0A]
Manual disconnect alarm [0x0B]
Manual disconnect recovery
[0x0C]
Manual disconnect alarm [0x0D]
Manual connection normal [0x0E]
Manual connection warning
[0x0F]
Manual connection recovery
[0x10]
Manual connection alarm [0x11]
Prohibit [0x12]
1837H LVD 2 Control Timer Sec Read Only u16
1838H LVD 2 AC Normal Timer Sec Read Only u16
1839H LVD 2 AC Abnormal Timer Sec Read Only u16
183AH LVD 2 Control Input Signal - Read Only u16 Connect [0x00], Disconnect [0x01]
183BH LVD 2 Control Output - Read Only u16 Connect [0x00], Disconnect [0x01]
Signal
183CH LVD 3 Status - Read Only u16 Auto connection normal [0x00]
Auto disconnect normal [0x01]
Auto disconnect prepare [0x02]
Auto connection prepare [0x03]
Auto connection warning [0x04]
Auto connection recovery [0x05]
Auto connection alarm [0x06]
Auto disconnect warning [0x07]
Auto disconnect recovery [0x08]
Auto disconnect alarm [0x09]
Manual disconnect normal [0x0A]
Manual disconnect alarm [0x0B]
Manual disconnect recovery
Page 14 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
[0x0C]
Manual disconnect alarm [0x0D]
Manual connection normal [0x0E]
Manual connection warning
[0x0F]
Manual connection recovery
[0x10]
Manual connection alarm [0x11]
Prohibit [0x12]
183DH LVD 3 Control Timer Sec Read Only u16
183EH LVD 3 AC Normal Timer Sec Read Only u16
183FH LVD 3 AC Abnormal Timer Sec Read Only u16
1840H LVD 3 Control Input Signal - Read Only u16 Connect [0x00], Disconnect [0x01]
1841H LVD 3 Control Output - Read Only u16 Connect [0x00], Disconnect [0x01]
Signal
1842H LVD 4 Status - Read Only u16 Auto connection normal [0x00]
Auto disconnect normal [0x01]
Auto disconnect prepare [0x02]
Auto connection prepare [0x03]
Auto connection warning [0x04]
Auto connection recovery [0x05]
Auto connection alarm [0x06]
Auto disconnect warning [0x07]
Auto disconnect recovery [0x08]
Auto disconnect alarm [0x09]
Manual disconnect normal [0x0A]
Manual disconnect alarm [0x0B]
Manual disconnect recovery
[0x0C]
Manual disconnect alarm [0x0D]
Manual connection normal [0x0E]
Manual connection warning
[0x0F]
Manual connection recovery
[0x10]
Manual connection alarm [0x11]
Prohibit [0x12]
1843H LVD 4 Control Timer Sec Read Only u16
1844H LVD 4 AC Normal Timer Sec Read Only u16
1845H LVD 4 AC Abnormal Timer Sec Read Only u16
1846H LVD 4 Control Input Signal - Read Only u16 Connect [0x00], Disconnect [0x01]
1847H LVD 4 Control Output - Read Only u16 Connect [0x00], Disconnect [0x01]
Signal
1848H LVD 5 Status - Read Only u16 Auto connection normal [0x00]
Auto disconnect normal [0x01]
Auto disconnect prepare [0x02]
Auto connection prepare [0x03]
Auto connection warning [0x04]
Auto connection recovery [0x05]
Auto connection alarm [0x06]
Auto disconnect warning [0x07]
Auto disconnect recovery [0x08]
Auto disconnect alarm [0x09]
Page 15 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Manual disconnect normal [0x0A]
Manual disconnect alarm [0x0B]
Manual disconnect recovery
[0x0C]
Manual disconnect alarm [0x0D]
Manual connection normal [0x0E]
Manual connection warning
[0x0F]
Manual connection recovery
[0x10]
Manual connection alarm [0x11]
Prohibit [0x12]
1849H LVD 5 Control Timer Sec Read Only u16
184AH LVD 5 AC Normal Timer Sec Read Only u16
184BH LVD 5 AC Abnormal Timer Sec Read Only u16
184CH LVD 5 Control Input Signal - Read Only u16 Connect [0x00], Disconnect [0x01]
184DH LVD 5 Control Output - Read Only u16 Connect [0x00], Disconnect [0x01]
Signal
184EH ~ Reserved
1AFFH
Page 16 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Power %
1B15H #1 Rectifier Max Power W Read Only u16
o
1B16H #1 Rectifier Temperature C Read Only u16
1B17H #1 Rectifier Fault Status - Read Only u16 The bit indicates the fault
status, normal [0], fault [1]
Bit0: fan failure
Bit1: Over temperature
Bit2: Current limit
Bit5: Overvoltage
Bit8: AC failure
Bit9: Shutdown
Bit10: Module failure
Bit15: Communication failure
1B18H #1 Rectifier Hardware - Read Only u16
Version Number
1B19H #1 Rectifier Software - Read Only u16
Version Number
1B1AH #2 Rectifier S/No (low) - Read Only u16
1B1BH #2 Rectifier S/No (high) - Read Only u16
1B1CH #2 Rectifier Output 0.01V Read Only u16
Voltage
1B1DH #2 Rectifier Output 0.01A Read Only u16
Current
1B1EH #2 Rectifier Output 0.01% Read Only u16
Power %
1B1FH #2 Rectifier Max Power W Read Only u16
oC
1B20H #2 Rectifier Temperature Read Only u16
1B21H #2 Rectifier Fault Status - Read Only u16 The bit indicates the fault
status, normal [0], fault [1]
Bit0: fan failure
Bit1: Over temperature
Bit2: Current limit
Bit5: Overvoltage
Bit8: AC failure
Bit9: Shutdown
Bit10: Module failure
Bit15: Communication failure
1B22H #2 Rectifier Hardware - Read Only u16
Version Number
1B23H #2 Rectifier Software - Read Only u16
Version Number
……….
1C96H #40 Rectifier S/No (low) - Read Only u16
1C97H #40 Rectifier S/No (high) - Read Only u16
1C98H #40 Rectifier Output 0.01V Read Only u16
Voltage
1C99H #40 Rectifier Output 0.01A Read Only u16
Current
1C9AH #40 Rectifier Output 0.01% Read Only u16
Power %
1C9BH #40 Rectifier Max Power W Read Only u16
1C9CH #40 Rectifier oC Read Only u16
Temperature
Page 17 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
1C9DH #40 Rectifier Fault Status - Read Only u16 The bit indicates the fault
status, normal [0], fault [1]
Bit0: fan failure
Bit1: Over temperature
Bit2: Current limit
Bit5: Overvoltage
Bit8: AC failure
Bit9: Shutdown
Bit10: Module failure
Bit14: Module Type (0: Rectifier
Module, 1: Solar Module)
Bit15: Communication failure
1C9EH #40 Rectifier Hardware - Read Only u16
Version Number
1C9FH #40 Rectifier Software - Read Only u16
Version Number
1CA0H #1 Input Voltage 0.01V Read Only u16
1CA1H #1 Input Current - Read Only u16
1CA2H #2 Input Voltage 0.01V Read Only u16
1CA3H #2 Input Current - Read Only u16
1CA4H #3 Input Voltage 0.01V Read Only u16
1CA5H #3 Input Current - Read Only u16
1CA6H #4 Input Voltage 0.01V Read Only u16
1CA7H #4 Input Current - Read Only u16
….. u16
1CEEH #40 Input Voltage 0.01V Read Only u16
1CEFH #40 Input Current - Read Only u16
1CF0H ~ Reserved
1DFFH
Page 18 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
1E19H IO Board 1 Temp Sensor 1 0.01oC Read Only u16
1E1AH IO Board 1 Temp Sensor 2 - Read Only u16 Normal [0x00]; Fault [0x01]
Status
1E1BH IO Board 1 Temp Sensor 2 0.01oC Read Only u16
1E1CH IO Board 2 Temp Sensor 1 - Read Only u16 Normal [0x00]; Fault [0x01]
Status
1E1DH IO Board 2 Temp Sensor 1 0.01oC Read Only u16
1E1EH IO Board 2 Temp Sensor 2 - Read Only u16 Normal [0x00]; Fault [0x01]
Status
1E1FH IO Board 2 Temp Sensor 2 0.01oC Read Only u16
Page 19 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
modules @ Phase C
1E32H No. of rectifier modules - Read Only u16
operating normally
1E33H Rectifier S/No (low) - Read Only u16 No 1 position sequence serial
1E34H Rectifier S/No (high) - Read Only u16 number setting
1E35H Rectifier S/No (low) - Read Only u16 No 2 position sequence serial
1E36H Rectifier S/No (high) - Read Only u16 number setting
1E37H Rectifier S/No (low) - Read Only u16 No 3 position sequence serial
1E38H Rectifier S/No (high) - Read Only u16 number setting
1E39H Rectifier S/No (low) - Read Only u16 No 4 position sequence serial
1E3AH Rectifier S/No (high) - Read Only u16 number setting
1E3BH Rectifier S/No (low) - Read Only u16 No 5 position sequence serial
1E3CH Rectifier S/No (high) - Read Only u16 number setting
1E3DH Rectifier S/No (low) - Read Only u16 No 6 position sequence serial
1E3EH Rectifier S/No (high) - Read Only u16 number setting
1E3FH Rectifier S/No (low) - Read Only u16 No 7 position sequence serial
1E40H Rectifier S/No (high) - Read Only u16 number setting
1E41H Rectifier S/No (low) - Read Only u16 No 8 position sequence serial
1E42H Rectifier S/No (high) - Read Only u16 number setting
1E43H Rectifier S/No (low) - Read Only u16 No 9 position sequence serial
1E44H Rectifier S/No (high) - Read Only u16 number setting
1E45H Rectifier S/No (low) - Read Only u16 No 10 position sequence serial
1E46H Rectifier S/No (high) - Read Only u16 number setting
1E47H Rectifier S/No (low) - Read Only u16 No 11 position sequence serial
1E48H Rectifier S/No (high) - Read Only u16 number setting
1E49H Rectifier S/No (low) - Read Only u16 No 12 position sequence serial
1E4AH Rectifier S/No (high) - Read Only u16 number setting
1E4BH Rectifier S/No (low) - Read Only u16 No 13 position sequence serial
1E4CH Rectifier S/No (high) - Read Only u16 number setting
1E4DH Rectifier S/No (low) - Read Only u16 No 14 position sequence serial
1E4EH Rectifier S/No (high) - Read Only u16 number setting
1E4FH Rectifier S/No (low) - Read Only u16 No 15 position sequence serial
1E50H Rectifier S/No (high) - Read Only u16 number setting
1E51H Rectifier S/No (low) - Read Only u16 No 16 position sequence serial
1E52H Rectifier S/No (high) - Read Only u16 number setting
1E53H Rectifier S/No (low) - Read Only u16 No 17 position sequence serial
1E54H Rectifier S/No (high) - Read Only u16 number setting
1E55H Rectifier S/No (low) - Read Only u16 No 18 position sequence serial
1E56H Rectifier S/No (high) - Read Only u16 number setting
1E57H Rectifier S/No (low) - Read Only u16 No 19 position sequence serial
1E58H Rectifier S/No (high) - Read Only u16 number setting
1E59H Rectifier S/No (low) - Read Only u16 No 20 position sequence serial
1E5AH Rectifier S/No (high) - Read Only u16 number setting
1E5BH Rectifier S/No (low) - Read Only u16 No 21 position sequence serial
1E5CH Rectifier S/No (high) - Read Only u16 number setting
1E5DH Rectifier S/No (low) - Read Only u16 No 22 position sequence serial
1E5EH Rectifier S/No (high) - Read Only u16 number setting
1E5FH Rectifier S/No (low) - Read Only u16 No 23 position sequence serial
1E60H Rectifier S/No (high) - Read Only u16 number setting
1E61H Rectifier S/No (low) - Read Only u16 No 24 position sequence serial
1E62H Rectifier S/No (high) - Read Only u16 number setting
1E63H Rectifier S/No (low) - Read Only u16 No 25 position sequence serial
Page 20 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
1E64H Rectifier S/No (high) - Read Only u16 number setting
1E65H Rectifier S/No (low) - Read Only u16 No 26 position sequence serial
1E66H Rectifier S/No (high) - Read Only u16 number setting
1E67H Rectifier S/No (low) - Read Only u16 No 27 position sequence serial
1E68H Rectifier S/No (high) - Read Only u16 number setting
1E69H Rectifier S/No (low) - Read Only u16 No 28 position sequence serial
1E6AH Rectifier S/No (high) - Read Only u16 number setting
1E6BH Rectifier S/No (low) - Read Only u16 No 29 position sequence serial
1E6CH Rectifier S/No (high) - Read Only u16 number setting
1E6DH Rectifier S/No (low) - Read Only u16 No 30 position sequence serial
1E6EH Rectifier S/No (high) - Read Only u16 number setting
1E6FH Rectifier S/No (low) - Read Only u16 No 31 position sequence serial
1E70H Rectifier S/No (high) - Read Only u16 number setting
1E71H Rectifier S/No (low) - Read Only u16 No 32 position sequence serial
1E72H Rectifier S/No (high) - Read Only u16 number setting
1E73H Rectifier S/No (low) - Read Only u16 No 33 position sequence serial
1E74H Rectifier S/No (high) - Read Only u16 number setting
1E75H Rectifier S/No (low) - Read Only u16 No 34 position sequence serial
1E76H Rectifier S/No (high) - Read Only u16 number setting
1E77H Rectifier S/No (low) - Read Only u16 No 35 position sequence serial
1E78H Rectifier S/No (high) - Read Only u16 number setting
1E79H Rectifier S/No (low) - Read Only u16 No 36 position sequence serial
1E7AH Rectifier S/No (high) - Read Only u16 number setting
1E7BH Rectifier S/No (low) - Read Only u16 No 37 position sequence serial
1E7CH Rectifier S/No (high) - Read Only u16 number setting
1E7DH Rectifier S/No (low) - Read Only u16 No 38 position sequence serial
1E7EH Rectifier S/No (high) - Read Only u16 number setting
1E7FH Rectifier S/No (low) - Read Only u16 No 39 position sequence serial
1E80H Rectifier S/No (high) - Read Only u16 number setting
1E81H Rectifier S/No (low) - Read Only u16 No 40 position sequence serial
1E82H Rectifier S/No (high) - Read Only u16 number setting
1E83H ~ Reserved
1FFFH
Page 21 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
200DH Batt 2 Midpoint Voltage - Read Only u16
Sample Value
200EH Batt 3 Midpoint Voltage - Read Only u16
Sample Value
200FH Batt 4 Midpoint Voltage - Read Only u16
Sample Value
2010H Current 1 Sample Value - Read Only u16
2011H Current 2 Sample Value - Read Only u16
2012H Batt Fuse 1 Open Voltage 0.01V Read Only u16
2013H Batt Fuse 2 Open Voltage 0.01V Read Only u16
2014H Batt Fuse 3 Open Voltage 0.01V Read Only u16
2015H Batt Fuse 4 Open Voltage 0.01V Read Only u16
2016H Batt Fuse 5 Open Voltage 0.01V Read Only u16
2017H Batt Fuse 6 Open Voltage 0.01V Read Only u16
2018H Batt Fuse 7 Open Voltage 0.01V Read Only u16
2019H Batt Fuse 8 Open Voltage 0.01V Read Only u16
201AH Batt Fuse 1 Open Voltage - Read Only u16
Sample Value
201BH Batt Fuse 2 Open Voltage - Read Only u16
Sample Value
201CH Batt Fuse 3 Open Voltage - Read Only u16
Sample Value
201DH Batt Fuse 4 Open Voltage - Read Only u16
Sample Value
201EH Batt Fuse 5 Open Voltage - Read Only u16
Sample Value
201FH Batt Fuse 6 Open Voltage - Read Only u16
Sample Value
2020H Batt Fuse 7 Open Voltage - Read Only u16
Sample Value
2021H Batt Fuse 8 Open Voltage - Read Only u16
Sample Value
2022H Reserved
~ 2FFFH
Page 22 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Bit12: AC incoming line 2 phase B
overcurrent
Bit13: AC incoming line 2 phase C
overcurrent
Bit14--bit15: Reserved
3001H AC Alarm (Field 2) Read Only u16 Alarm field, bit indicates the
alarm status, normal [0], alarm [1]
Bit0: AC incoming line 1 phase A
overvoltage
Bit1: AC incoming line 1 phase B
overvoltage
Bit2: AC incoming line 1 phase C
overvoltage
Bit3: AC incoming line 1 phase A
undervoltage
Bit4: AC incoming line 1 phase B
undervoltage
Bit5: AC incoming line 1 phase C
undervoltage
Bit6: AC incoming line 1 phase A
missing phase
Bit7: AC incoming line 1 phase B
missing phase
Bit8: AC incoming line 1 phase C
missing phase
Bit9: AC incoming line 1 high
frequency
Bit10: AC incoming line 1 low
frequency
Bit11--bit15: Reserved
3002H AC Alarm (Field 3) Read Only u16 Alarm field, bit indicates the
alarm status, normal [0], alarm [1]
Bit0: AC incoming line 2 phase A
overvoltage
Bit1: AC incoming line 2 phase B
overvoltage
Bit2: AC incoming line 2 phase C
overvoltage
Bit3: AC incoming line 2 phase A
undervoltage
Bit4: AC incoming line 2 phase B
undervoltage
Bit5: AC incoming line 2 phase C
undervoltage
Bit6: AC incoming line 2 phase A
missing phase
Bit7: AC incoming line 2 phase B
missing phase
Bit8: AC incoming line 2 phase C
missing phase
Bit9: AC incoming line 2 high
frequency
Bit10: AC incoming line 2 low
frequency
Page 23 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Bit11--bit15: Reserved
3003H DC Alarm Read Only u16 Alarm field, bit indicates the
alarm status, normal [0], alarm [1]
Bit0: Bus voltage low -1
Bit1: Bus voltage low -2
Bit2: Bus voltage high -1
Bit3: Bus voltage high -2
Bit4: Low ambient temperature
Bit5: high ambient temperature
Bit6--bit7: Reserved
Bit8: Sensor failure
Bit9: Bus voltage sensing fault
Bit10: Temperature sensor 1 fault
Bit11: Current sensor failure
Bit12: Temperature sensor 2 fault
Bit13--bit15: Reserved
3004H Rectifier module and fan Read Only u16 Alarm field, bit indicates the
alarm alarm status, normal [0], alarm [1]
Bit0: System overload
Bit1: Single rectifier failure
Bit2: Multiple rectifiers failure
Bit3: Single rectifier loss
Bit4: Multiple rectifiers loss
Bit5: Rectifier no load
Bit6: Rectifier current limit
Bit7: Rectifier over temperature
Bit8: All rectifiers are off
Bit9: Fan 1 is faulty
Bit10: Fan 2 is faulty
Bit11: Fan 3 is faulty
Bit12: Fan 4 is faulty
Bit13: Rectifier fan failure
Bit14--bit15: Reserved
3005H Battery Alarm Read Only u16 Alarm field, bit indicates the
alarm status, normal [0], alarm [1]
Bit0: Battery test failed
Bit1: Battery overcurrent
Bit2: Battery discharging
Bit3: Equalize charge
Bit4: Battery test
Bit5: Battery current limit
Bit6: Single cell high voltage
Bit7: Single cell low voltage
Bit8: LVD1 disconnected
Bit9: LVD2 disconnected
Bit10: LVD1 fault
Bit11: LVD2 fault
Bit12: Low battery temperature
Bit13: High battery temperature
Bit14: Battery symmetry alarm
Bit15: Reserved
3006H Digital Input (DI) Alarm Read Only u16 Alarm field, bit indicates the
(Field 1) alarm status, normal [0], alarm [1]
Bit0: MOV1 fault
Page 24 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Bit1: MOV2 failure
Bit2: AC 1 open state
Bit3: AC 2 open state
Bit4: Battery fuse 1 fault
Bit5: Battery fuse 2 fault
Bit6: Battery fuse 3 fault
Bit7: Battery fuse 4 fault
Bit8: Battery fuse 5 fault
Bit9: Battery fuse 6 fault
Bit10: Battery fuse 7 fault
Bit11: Battery fuse 8 fault
Bit12: ACD fault
Bit13: Load fuse A fault
Bit14: Load fuse B fault
Bit15: Custom AC fault
3007H Digital Input (DI) Alarm Read Only u16 Alarm field, bit indicates the
(Field 2) alarm status, normal [0], alarm [1]
Bit0: Digital input 1
Bit1: Digital input 2
Bit2: Digital input 3
Bit3: Digital input 4
Bit4: Digital input 5
Bit5: Digital input 6
Bit6: Digital Input 7
Bit7: Digital input 8
Bit8: Digital input 9
Bit9: Digital input 10
Bit10: Digital input 11
Bit11: Digital input 12
Bit12: Digital input 13
Bit13: Digital input 14
Bit14: Digital input 15
Bit15: Digital input 16
3008H Digital Input (DI) Alarm Read Only u16 Alarm field, bit indicates the
(Field 3) alarm status, normal [0], alarm [1]
Bit0: Digital input 17
Bit1: Digital input 18
Bit2: Digital input 19
Bit3: Digital input 20
Bit4: Digital input 21
Bit5: Digital input 22
Bit6: Digital input 23
Bit7: Digital input 24
Bit8: Digital input 25
Bit9: Digital Input 26
Bit10: Digital Input 27
Bit11: Digital input 28
Bit12--bit15: Reserved
3009H AC Sampling Unit Alarm - Read Only u16 Alarm field, bit indicates the
alarm status, normal [0], alarm [1]
Bit0: AC sampling unit 1 loss
Bit1: AC sampling unit 2 loss
Bit2: AC sampling unit 1 fault
Bit3: AC sampling unit 2 fault
Page 25 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Bit4--bit15: Reserved
300AH DC Sampling Unit Alarm - Read Only u16 Alarm field, bit indicates the
alarm status, normal [0], alarm [1]
Bit0: DC sampling unit 1 loss
Bit1: DC sampling unit 2 loss
Bit2: DC sampling unit 1 fault
Bit3: DC sampling unit 2 fault
Bit4: IO expansion unit 1 loss
Bit5: IO expansion unit 2 loss
Bit6: DC sampling unit 3 loss
Bit7: DC sampling unit 4 loss
Bit8: DC sampling unit 5 loss
Bit9: DC sampling unit 3 fault
Bit10: DC sampling unit 4 fault
Bit11: DC sampling unit 5 fault
Bit12: IO expansion unit 1 fault
Bit13: IO expansion unit 2 fault
Bit14--bit15: Reserved
300BH Battery Sampling Unit - Read Only u16 Alarm field, bit indicates the
Alarm alarm status, normal [0], alarm [1]
Bit0: Battery sampling unit 1 loss
Bit1: Battery sampling unit 2 loss
Bit2: Battery sampling unit 3 loss
Bit3: Battery sampling unit 4 loss
Bit4: Battery sampling unit 5 loss
Bit5: Battery sampling unit 6 loss
Bit6: Battery sampling unit 7 loss
Bit7: Battery sampling unit 8 loss
Bit8: Batt sampling unit 1 fault
Bit9: Batt sampling unit 2 fault
Bit10: Batt sampling unit 3 fault
Bit11: Batt sampling unit 4 fault
Bit12: Batt sampling unit 5 fault
Bit13: Batt sampling unit 6 fault
Bit14: Batt sampling unit 7 fault
Bit15: Batt sampling unit 8 fault
300CH Genset Alarm - Read Only u16 Alarm field, bit indicates the
alarm status, normal [0], alarm [1]
Bit0: Genset 1 start
Bit1: Genset 2 start
Bit2: Genset 1 fault
Bit3: Genset 2 fault
Bit4: Fuel Level 1 Low
Bit5: Fuel Level 2 Low
Bit6: Incoming DC voltage high
Bit7: Incoming DC voltage low
Bit8: Solar module fault
Bit9: Solar module overcurrent
Bit10--bit15: Reserved
300DH Reserved
~ 34FFH
3500H Software App No. (field 1) - Read Only u16 Software Application Product
3501H Software App No. (field 2) - Read Only u16 Number
3502H Software App No. (field 3) - Read Only u16
Page 26 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
3503H Software App No. (field 4) - Read Only u16
3504H Software App No. (field 5) - Read Only u16
3505H Product Item No. (field 1) - Read Only u16 Product Item Number
3506H Product Item No. (field 2) - Read Only u16
3507H Product Item No. (field 3) - Read Only u16
3508H Product Item No. (field 4) - Read Only u16
3509H Product Item No. (field 5) - Read Only u16
Page 27 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Bit2 1:Pack OV Protect
0:None
Bit3 1:Pack UV Protect
0:None
Bit4 1:SC Protect 0:None
Bit5 1:OC Protect 0:None
Bit6 1:Chg OT Protect
0:None
Bit7 1:Chg UT Protect
0:None
Byte1
Bit0 1:Disg OT Protect
0:None
Bit1 1:Disg UT Protect
0:None
Bit2-Bit7 Reserved
A009H NADA_BAT1_FaultStatus Read Only u16 Byte0(Fault)
Bit0 1:Front-end Sample
Error 0:None
Bit1 1:Temp Sense
Disconnect 0:None
Bit2 1: Inversed Graft Error
0:None
Bit3-Bit7 Reserved
Byte1(Status)
Bit0 1:Charging 0:None
Bit1 1:Discharging 0:None
Bit2 1:Chg MOS Connect
0:Chg MOS Disconnect
Bit3 1:Disg MOS Connect
0:Disg MOS Disconnect
Bit4 1:Limit Current Enable
0:Limit Current Disable
Bit5-Bit7 Reserved
A00AH Model Version (Field1) Read Only u16
A00BH Model Version (Field2) Read Only u16
A00CH Model Version (Field3) Read Only u16
A00DH Model Version (Field4) Read Only u16
A00EH Model Version (Field5) Read Only u16
A00FH Model Version (Field6) Read Only u16 ASCII
A010H Model Version (Field7) Read Only u16
A011H Model Version (Field8) Read Only u16
A012H Model Version (Field9) Read Only u16
A013H Model Version (Field10) Read Only u16
A014H NADA_BAT1_Serial (Field1) Read Only u16
A015H NADA_BAT1_Serial (Field2) Read Only u16
A016H NADA_BAT1_Serial (Field3) - Read Only u16
A017H NADA_BAT1_Serial (Field4) Read Only u16
A018H NADA_BAT1_Serial (Field5) Read Only u16
A019H NADA_BAT1_Serial (Field6) Read Only u16 ASCII
A01AH NADA_BAT1_Serial (Field7) Read Only u16
A01BH NADA_BAT1_Serial (Field8) Read Only u16
Page 28 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
A01CH NADA_BAT1_Serial (Field9) Read Only u16
A01DH NADA_BAT1_Serial (Field10) Read Only u16
A01EH Reserved
A026H
A027H
A028H NADA_BAT2_PackVolt 0.01V Read Only u16
A029H NADA_BAT2_Curr 0.01A Read Only u16 (-10000)*0.1A 9505#-49.5
A02AH NADA_BAT2_RemCap 0.1AH Read Only u16
A02BH NADA_BAT2_AverCellT 0.1oC Read Only u16 (-400)*0.1oC
A02CH NADA_BAT2_EnvT 0.1oC Read Only u16 (-400)*0.1oC
A02DH NADA_BAT2_SOH 1.00% Read Only u16 Nada0.01%
A02EH NADA_BAT2_SOC 1.00% Read Only u16 Nada0.01%
A02FH NADA_BAT2_WarnFlag - Read Only u16 Byte0
Bit0 1:Cell OV Alarm
0:None
Bit1 1:Cell UV Alarm
0:None
Bit2 1:Pack OV Alarm
0:None
Bit3 1:Pack UV Alarm
0:None
Bit4 1:Chg OC Alarm
0:None
Bit5 1:Disg OC Alarm
0:None
Bit6 1:Cell OT Alarm
0:None
Bit7 1:Cell UT Alarm
0:None
Byte1
Bit0 1:Env OT Alarm
0:None
Bit1 1:Env UT Alarm
0:None
Bit2 1:PCB OT Alarm
0:None
Bit3 1:SOC Low Alarm
0:None
Bit4 1:Diff Volt Alarm
0:None
Bit5-Bit7 Reserved
A030H NADA_BAT2_ProtectionFlag Read Only u16 Byte0
Bit0 1:Cell OV Protect
0:None
Bit1 1:Cell UV Protect
0:None
Bit2 1:Pack OV Protect
0:None
Bit3 1:Pack UV Protect
0:None
Bit4 1:SC Protect 0:None
Bit5 1:OC Protect 0:None
Bit6 1:Chg OT Protect
Page 29 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
0:None
Bit7 1:Chg UT Protect
0:None
Byte1
Bit0 1:Disg OT Protect
0:None
Bit1 1:Disg UT Protect
0:None
Bit2-Bit7 Reserved
A031H NADA_BAT2_FaultStatus Read Only u16 Byte0(Fault)
Bit0 1:Front-end Sample
Error 0:None
Bit1 1:Temp Sense
Disconnect 0:None
Bit2 1: Inversed Graft Error
0:None
Bit3-Bit7 Reserved
Byte1(Status)
Bit0 1:Charging 0:None
Bit1 1:Discharging 0:None
Bit2 1:Chg MOS Connect
0:Chg MOS Disconnect
Bit3 1:Disg MOS Connect
0:Disg MOS Disconnect
Bit4 1:Limit Current Enable
0:Limit Current Disable
Bit5-Bit7 Reserved
A032H Model Version (Field1) Read Only u16
A033H Model Version (Field2) Read Only u16
A034H Model Version (Field3) Read Only u16
A035H Model Version (Field4) Read Only u16
A036H Model Version (Field5) Read Only u16
A037H Model Version (Field6) Read Only u16 ASCII
A038H Model Version (Field7) Read Only u16
A039H Model Version (Field8) Read Only u16
A03AH Model Version (Field9) Read Only u16
A03BH Model Version (Field10) Read Only u16
A03CH NADA_BAT2_Serial (Field1) Read Only u16
A03DH NADA_BAT2_Serial (Field2) Read Only u16
A03EH NADA_BAT2_Serial (Field3) - Read Only u16
A03FH NADA_BAT2_Serial (Field4) Read Only u16
A040H NADA_BAT2_Serial (Field5) Read Only u16
A041H NADA_BAT2_Serial (Field6) Read Only u16 ASCII
A042H NADA_BAT2_Serial (Field7) Read Only u16
A043H NADA_BAT2_Serial (Field8) Read Only u16
A044H NADA_BAT2_Serial (Field9) Read Only u16
A045H NADA_BAT2_Serial (Field10) Read Only u16
A046H Reserved
A047H
A048H
A049H
A04AH
Page 30 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
A04BH
A04CH
A04DH
A04EH
A04FH
A050H NADA_BAT3_PackVolt 0.01V Read Only u16
A051H NADA_BAT3_Curr 0.01A Read Only u16 (-10000)*0.1A 9505#-49.5
A052H NADA_BAT3_RemCap 0.1AH Read Only u16
A053H NADA_BAT3_AverCellT 0.1oC Read Only u16 (-400)*0.1oC
A054H NADA_BAT3_EnvT 0.1oC Read Only u16 (-400)*0.1oC
A055H NADA_BAT3_SOH 1.00% Read Only u16 Nada0.01%
A056H NADA_BAT3_SOC 1.00% Read Only u16 Nada0.01%
A057H NADA_BAT3_WarnFlag - Read Only u16 Byte0
Bit0 1:Cell OV Alarm
0:None
Bit1 1:Cell UV Alarm
0:None
Bit2 1:Pack OV Alarm
0:None
Bit3 1:Pack UV Alarm
0:None
Bit4 1:Chg OC Alarm
0:None
Bit5 1:Disg OC Alarm
0:None
Bit6 1:Cell OT Alarm
0:None
Bit7 1:Cell UT Alarm
0:None
Byte1
Bit0 1:Env OT Alarm
0:None
Bit1 1:Env UT Alarm
0:None
Bit2 1:PCB OT Alarm
0:None
Bit3 1:SOC Low Alarm
0:None
Bit4 1:Diff Volt Alarm
0:None
Bit5-Bit7 Reserved
A058H NADA_BAT3_ProtectionFlag Read Only u16 Byte0
Bit0 1:Cell OV Protect
0:None
Bit1 1:Cell UV Protect
0:None
Bit2 1:Pack OV Protect
0:None
Bit3 1:Pack UV Protect
0:None
Bit4 1:SC Protect 0:None
Bit5 1:OC Protect 0:None
Bit6 1:Chg OT Protect
Page 31 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
0:None
Bit7 1:Chg UT Protect
0:None
Byte1
Bit0 1:Disg OT Protect
0:None
Bit1 1:Disg UT Protect
0:None
Bit2-Bit7 Reserved
A059H NADA_BAT3_FaultStatus Read Only u16 Byte0(Fault)
Bit0 1:Front-end Sample
Error 0:None
Bit1 1:Temp Sense
Disconnect 0:None
Bit2 1: Inversed Graft Error
0:None
Bit3-Bit7 Reserved
Byte1(Status)
Bit0 1:Charging 0:None
Bit1 1:Discharging 0:None
Bit2 1:Chg MOS Connect
0:Chg MOS Disconnect
Bit3 1:Disg MOS Connect
0:Disg MOS Disconnect
Bit4 1:Limit Current Enable
0:Limit Current Disable
Bit5-Bit7 Reserved
A05AH Model Version (Field1) Read Only u16
A05BH Model Version (Field2) Read Only u16
A05CH Model Version (Field3) Read Only u16
A05DH Model Version (Field4) Read Only u16
A05EH Model Version (Field5) Read Only u16
A05FH Model Version (Field6) Read Only u16 ASCII
A060H Model Version (Field7) Read Only u16
A061H Model Version (Field8) Read Only u16
A062H Model Version (Field9) Read Only u16
A063H Model Version (Field10) Read Only u16
A064H NADA_BAT3_Serial (Field1) Read Only u16
A065H NADA_BAT3_Serial (Field2) Read Only u16
A066H NADA_BAT3_Serial (Field3) - Read Only u16
A067H NADA_BAT3_Serial (Field4) Read Only u16
A068H NADA_BAT3_Serial (Field5) Read Only u16
A069H NADA_BAT3_Serial (Field6) Read Only u16 ASCII
A06AH NADA_BAT3_Serial (Field7) Read Only u16
A06BH NADA_BAT3_Serial (Field8) Read Only u16
A06CH NADA_BAT3_Serial (Field9) Read Only u16
A06DH NADA_BAT3_Serial (Field10) Read Only u16
A06EH Reserved
A06FH
A070H
A071H
A072H
Page 32 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
A073H
A074H
A075H
A076H
A077H
A078H NADA_BAT4
---
A09FH
A0A0H NADA_BAT5
---
A0C7H
A0C8H NADA_BAT6
---
A0EFH
A0F0H NADA_BAT7
---
A117H
A118H NADA_BAT8
---
A13FH
A140H NADA_BAT9
---
A167H
A168H NADA_BAT10
---
A18FH
Page 33 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
3709H IO Module 1 Level 2 - Read Only u16
370AH IO Module 2 Level 1 - Read Only u16
370BH IO Module 2 Level 2 - Read Only u16
370CH IO Module 1 Level 1 Sensor - Read Only u16 0:Normal, 1:Fault
370DH IO Module 1 Level 2 Sensor - Read Only u16 0:Normal, 1:Fault
370EH IO Module 2 Level 1 Sensor - Read Only u16 0:Normal, 1:Fault
370FH IO Module 2 Level 2 Sensor - Read Only u16 0:Normal, 1:Fault
3710H Generator ON state - Read Only u16 Bit0: Gen-1-ON
Bit1: GEN-2-ON
3711H Generator Trigger state - Read Only u16 Bit0: Gen-1-ON
Bit1: GEN-2-ON
3712H Reserved
~ 371FH
3720H - Read Only u32 Day 1 (send low 16
3721H Log Record 1 followed by high 16); 15 9C
01 34 - 20190620
3722H - Read Only u16 Day 1: Energy consumption
for the day
3723H min Read Only u16 Day 1: Operating time of
the day
……..
3784H - Read Only u32 Day 26
3785H Log Record 26
3786H - Read Only u16 Day 26: Energy
consumption for the day
3787H min Read Only u16 Day 26: Operating time of
the day
……..
37ECH - Read Only u32 Day 52
37EDH Log Record 52
37EEH - Read Only u16 Day 52: Energy
consumption for the day
37EFH min Read Only u16 Day 52: Operating time of
the day
37F0H ~ Reserved
37FFH
Page 34 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
5.17 DC Monitoring Module
Register Description Unit Read/Write Type Remarks
B000H DCM#1 Busbar Voltage 0.1V Read Only u16
B001H DCM#1 Temperature 0.1oC Read Only u16 Offset is 500, such that
when temperature is 0oC,
the value is 500; when the
temperature is +20oC, the
value is 700; and when the
temperature is -10oC, the
value is 400
B002H DCM#1 Total Load Current 0.1A Read Only u16
B003H DCM#1 Battery 1 Current 0.1A Read Only u16
B004H DCM#1 Battery 2 Current 0.1A Read Only u16
B005H DCM#1 Battery 3 Current 0.1A Read Only u16
B006H DCM#1 Battery 4 Current 0.1A Read Only u16
B007H DCM#1 Load 1 Current Read Only u16
B008H DCM#1 Load 2 Current Read Only u16
B009H DCM#1 Load 3 Current Read Only u16
B00AH DCM#1 Load 4 Current Read Only u16
… Read Only u16
B01AH DCM#1 Load20 Current Read Only u16
B01BH DCM#1 Total Load Current - Read Only u32
B01CH
B01DH DCM#1 Total Energy 1 (Reserved) - Read Only u32
B01EH
B01FH DCM#1 Total Energy 2 (Reserved) - Read Only u32
B020H
… - Read Only u32
…
B043H DCM#1 Total Energy 20 - Read Only u32
B044H (Reserved)
B045H DCM#1 Batt Fuse Status - Read Only u16 Bit0-Batt 1 fuse status
1: Fused 0: Not fused
Bit1-Batt 2 fuse status
1: Fused 0: Not fused
Bit2-Batt 3 fuse status
1: Fused 0: Not fused
Bit3-Batt 4 fuse status
1: Fused 0: Not fused
Bit4-Reserved
…
Bit13-Bit15 Reserved
B046H DCM#1 Load Fuse Status (17-30) - Read Only u16 Bit0-Load 17 fuse status
1: Fused 0: Not fused
Bit1-Load 18 fuse status
1: Fused 0: Not fused
…
Bit13-Load 30 fuse status
1: Fused 0: Not fused
Bit14-Bit15 Reserved
B047H DCM#1 Load Fuse Status (1-16) - Read Only u16 Bit0-Load 1 fuse status
1: Fused 0: Not fused
Page 35 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Bit1-Load 2 fuse status
1: Fused 0: Not fused
…
Bit15-Load 16 fuse status
1: Fused 0: Not fused
B048H DCM#1 Open State - Read Only u16 Bit0-Channel 1 open state
1: Open 0: Closed
Bit1-Channel 2 open state
1: Open 0: Closed
Bit2—Bit15 reserved
B049H DCM#1 Busbar Voltage upper/ - Read Only u16 Bit0: 0: Normal
lower limit over-value alarm 1: Overvoltage
Bit1: 0: Normal
1: Undervoltage
Bit2~Bit15 reserved
B04AH DCM#1 Battery Current exceeds - Read Only u16 Bit0: Battery 1
the upper limit alarm 0: Normal 1: Overcurrent
Bit1: Battery 2
0: Normal 1: Overcurrent
Bit2: Battery 3
0: Normal 1: Overcurrent
Bit3: Battery 4
0: Normal 1: Overcurrent
Bit4~Bit15 reserved
B04BH DCM#1 Load Current exceeds - Read Only u16 Bit0: Load 17
upper limit alarm (17-20) 0: Normal 1: Overcurrent
Bit1: Load 18
0: Normal 1: Overcurrent
Bit2: Load 19
0: Normal 1: Overcurrent
Bit3: Load 20
0: Normal 1: Overcurrent
Bit4~Bit15: reserved
B04CH DCM#1 Load Current exceeds - Read Only u16 Bit0: Load 1
upper limit alarm (1-16) 0: Normal 1: Overcurrent
Bit1: Load 2
0: Normal 1: Overcurrent
...
Bit15: Load 16
0: Normal 1: Overcurrent
B04DH DCM#1 Temperature exceeds - Read Only u16 Bit0: Temperature
upper/lower limit alarm 0: normal
1: over temperature
Bit1: Temperature
0: normal
1: under temperature
Bit2~Bit15: reserved
B04EH DCM#1 Total Load Current - Read Only u16 Bit0: 0: Normal
exceeds upper limit alarm 1: Overcurrent
Bit1~Bit15: reserved
B04FH DCM#1 Battery Sensor Fail - Read Only u16 Bit0: Battery 1
0: Normal 1: Fault
Bit1: Battery 2
0: Normal 1: Fault
Page 36 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Bit2: Battery 3
0: Normal 1: Fault
Bit3: Battery 4
0: Normal 1: Fault
Bit4~Bit15 reserved
B050H DCM#1 Load Sensor Fail (17-20) - Read Only u16 Bit0: Load 17
0: Normal 1: Fault
Bit1: Load 18
0: Normal 1: Fault
Bit2: Load 19
0: Normal 1: Fault
Bit3: Load 20
0: Normal 1: Fault
Bit4~Bit15: reserved
B051H DCM#1 Load Sensor Fail (1-16) - Read Only u16 Bit0: Load 1
0: Normal 1: Fault
Bit1: Load 2
0: Normal 1: Fault
...
Bit15: Load 16
0: Normal 1: Fault
B052H DCM#1 Temperature Sensor Fail - Read Only u16 Bit0: 0: Normal 1: Fault
Bit1~Bit15: reserved
B053H DCM#1 Total Load Current - Read Only u16 Bit0: 0: Normal 1: Fault
Sensor Fail Bit1~Bit15: reserved
…. RESERVED
B060H DCM#2 Busbar Voltage 0.1V Read Only u16
B061H DCM#2 Temperature 0.1oC Read Only u16 Offset is 500, such that
when temperature is 0oC,
the value is 500; when the
temperature is +20oC, the
value is 700; and when the
temperature is -10oC, the
value is 400
B062H DCM#2 Total Load Current 0.1A Read Only u16
B063H DCM#2 Battery 1 Current 0.1A Read Only u16
B064H DCM#2 Battery 2 Current 0.1A Read Only u16
B065H DCM#2 Battery 3 Current 0.1A Read Only u16
B066H DCM#2 Battery 4 Current 0.1A Read Only u16
B067H DCM#2 Load 1 Current Read Only u16
B068H DCM#2 Load 2 Current Read Only u16
B069H DCM#2 Load 3 Current Read Only u16
B06AH DCM#2 Load 4 Current Read Only u16
… Read Only u16
B07AH DCM#2 Load20 Current Read Only u16
B07BH DCM#2 Total Load Current - Read Only u32
B07CH
B07DH DCM#2 Total Energy 1 (Reserved) - Read Only u32
B07EH
B07FH DCM#2 Total Energy 2 (Reserved) - Read Only u32
B080H
… - Read Only u32
…
Page 37 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
B0A3H DCM#2 Total Energy 20 - Read Only u32
B0A4H (Reserved)
B0A5H DCM#2 Batt Fuse Status - Read Only u16 Bit0-Batt 1 fuse status
1: Fused 0: Not fused
Bit1-Batt 2 fuse status
1: Fused 0: Not fused
Bit2-Batt 3 fuse status
1: Fused 0: Not fused
Bit3-Batt 4 fuse status
1: Fused 0: Not fused
Bit4-Reserved
…
Bit13-Bit15 Reserved
B0A6H DCM#2 Load Fuse Status (17-30) - Read Only u16 Bit0-Load 17 fuse status
1: Fused 0: Not fused
Bit1-Load 18 fuse status
1: Fused 0: Not fused
…
Bit13-Load 30 fuse status
1: Fused 0: Not fused
Bit14-Bit15 Reserved
B0A7H DCM#2 Load Fuse Status (1-16) - Read Only u16 Bit0-Load 1 fuse status
1: Fused 0: Not fused
Bit1-Load 2 fuse status
1: Fused 0: Not fused
…
Bit15-Load 16 fuse status
1: Fused 0: Not fused
B0A8H DCM#2 Open State - Read Only u16 Bit0-Channel 1 open state
1: Open 0: Closed
Bit1-Channel 2 open state
1: Open 0: Closed
Bit2—Bit15 reserved
B0A9H DCM#2 Busbar Voltage upper/ - Read Only u16 Bit0: 0: Normal
lower limit over-value alarm 1: Overvoltage
Bit1: 0: Normal
1: Undervoltage
Bit2~Bit15 reserved
B0AAH DCM#2 Battery Current exceeds - Read Only u16 Bit0: Battery 1
the upper limit alarm 0: Normal 1: Overcurrent
Bit1: Battery 2
0: Normal 1: Overcurrent
Bit2: Battery 3
0: Normal 1: Overcurrent
Bit3: Battery 4
0: Normal 1: Overcurrent
Bit4~Bit15 reserved
B0ABH DCM#2 Load Current exceeds - Read Only u16 Bit0: Load 17
upper limit alarm (17-20) 0: Normal 1: Overcurrent
Bit1: Load 18
0: Normal 1: Overcurrent
Bit2: Load 19
0: Normal 1: Overcurrent
Bit3: Load 20
Page 38 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
0: Normal 1: Overcurrent
Bit4~Bit15: reserved
B0ACH DCM#2 Load Current exceeds - Read Only u16 Bit0: Load 1
upper limit alarm (1-16) 0: Normal 1: Overcurrent
Bit1: Load 2
0: Normal 1: Overcurrent
...
Bit15: Load 16
0: Normal 1: Overcurrent
B0ADH DCM#2 Temperature exceeds - Read Only u16 Bit0: Temperature
upper/lower limit alarm 0: normal
1: over temperature
Bit1: Temperature
0: normal
1: under temperature
Bit2~Bit15: reserved
B0AEH DCM#2 Total Load Current - Read Only u16 Bit0: 0: Normal
exceeds upper limit alarm 1: Overcurrent
Bit1~Bit15: reserved
B0AFH DCM#2 Battery Sensor Fail - Read Only u16 Bit0: Battery 1
0: Normal 1: Fault
Bit1: Battery 2
0: Normal 1: Fault
Bit2: Battery 3
0: Normal 1: Fault
Bit3: Battery 4
0: Normal 1: Fault
Bit4~Bit15 reserved
B0B0H DCM#2 Load Sensor Fail (17-20) - Read Only u16 Bit0: Load 17
0: Normal 1: Fault
Bit1: Load 18
0: Normal 1: Fault
Bit2: Load 19
0: Normal 1: Fault
Bit3: Load 20
0: Normal 1: Fault
Bit4~Bit15: reserved
B0B1H DCM#2 Load Sensor Fail (1-16) - Read Only u16 Bit0: Load 1
0: Normal 1: Fault
Bit1: Load 2
0: Normal 1: Fault
...
Bit15: Load 16
0: Normal 1: Fault
B0B2H DCM#2 Temperature Sensor Fail - Read Only u16 Bit0: 0: Normal 1: Fault
Bit1~Bit15: reserved
B0B3H DCM#2 Total Load Current - Read Only u16 Bit0: 0: Normal 1: Fault
Sensor Fail Bit1~Bit15: reserved
…. RESERVED
B0C0H DCM#3 Busbar Voltage 0.1V Read Only u16
B0C1H DCM#3 Temperature 0.1oC Read Only u16 Offset is 500, such that
when temperature is 0oC,
the value is 500; when the
Page 39 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
temperature is +20oC, the
value is 700; and when the
temperature is -10oC, the
value is 400
B0C2H DCM#3 Total Load Current 0.1A Read Only u16
B0C3H DCM#3 Battery 1 Current 0.1A Read Only u16
B0C4H DCM#3 Battery 2 Current 0.1A Read Only u16
B0C5H DCM#3 Battery 3 Current 0.1A Read Only u16
B0C6H DCM#3 Battery 4 Current 0.1A Read Only u16
B0C7H DCM#3 Load 1 Current Read Only u16
B0C8H DCM#3 Load 2 Current Read Only u16
B0C9H DCM#3 Load 3 Current Read Only u16
B0CAH DCM#3 Load 4 Current Read Only u16
… Read Only u16
B0DAH DCM#3 Load20 Current Read Only u16
B0DBH DCM#3 Total Load Current - Read Only u32
B0DCH
B0DDH DCM#3 Total Energy 1 (Reserved) - Read Only u32
B0DEH
B0DFH DCM#3 Total Energy 2 (Reserved) - Read Only u32
B0E0H
… - Read Only u32
…
B103H DCM#3 Total Energy 20 - Read Only u32
B104H (Reserved)
B105H DCM#3 Batt Fuse Status - Read Only u16 Bit0-Batt 1 fuse status
1: Fused 0: Not fused
Bit1-Batt 2 fuse status
1: Fused 0: Not fused
Bit2-Batt 3 fuse status
1: Fused 0: Not fused
Bit3-Batt 4 fuse status
1: Fused 0: Not fused
Bit4-Reserved
…
Bit13-Bit15 Reserved
B106H DCM#3 Load Fuse Status (17-30) - Read Only u16 Bit0-Load 17 fuse status
1: Fused 0: Not fused
Bit1-Load 18 fuse status
1: Fused 0: Not fused
…
Bit13-Load 30 fuse status
1: Fused 0: Not fused
Bit14-Bit15 Reserved
B107H DCM#3 Load Fuse Status (1-16) - Read Only u16 Bit0-Load 1 fuse status
1: Fused 0: Not fused
Bit1-Load 2 fuse status
1: Fused 0: Not fused
…
Bit15-Load 16 fuse status
1: Fused 0: Not fused
B108H DCM#3 Open State - Read Only u16 Bit0-Channel 1 open state
1: Open 0: Closed
Page 40 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Bit1-Channel 2 open state
1: Open 0: Closed
Bit2—Bit15 reserved
B109H DCM#3 Busbar Voltage upper/ - Read Only u16 Bit0: 0: Normal
lower limit over-value alarm 1: Overvoltage
Bit1: 0: Normal
1: Undervoltage
Bit2~Bit15 reserved
B10AH DCM#3 Battery Current exceeds - Read Only u16 Bit0: Battery 1
the upper limit alarm 0: Normal 1: Overcurrent
Bit1: Battery 2
0: Normal 1: Overcurrent
Bit2: Battery 3
0: Normal 1: Overcurrent
Bit3: Battery 4
0: Normal 1: Overcurrent
Bit4~Bit15 reserved
B10BH DCM#3 Load Current exceeds - Read Only u16 Bit0: Load 17
upper limit alarm (17-20) 0: Normal 1: Overcurrent
Bit1: Load 18
0: Normal 1: Overcurrent
Bit2: Load 19
0: Normal 1: Overcurrent
Bit3: Load 20
0: Normal 1: Overcurrent
Bit4~Bit15: reserved
B10CH DCM#3 Load Current exceeds - Read Only u16 Bit0: Load 1
upper limit alarm (1-16) 0: Normal 1: Overcurrent
Bit1: Load 2
0: Normal 1: Overcurrent
...
Bit15: Load 16
0: Normal 1: Overcurrent
B10DH DCM#3 Temperature exceeds - Read Only u16 Bit0: Temperature
upper/lower limit alarm 0: normal
1: over temperature
Bit1: Temperature
0: normal
1: under temperature
Bit2~Bit15: reserved
B10EH DCM#3 Total Load Current - Read Only u16 Bit0: 0: Normal
exceeds upper limit alarm 1: Overcurrent
Bit1~Bit15: reserved
B10FH DCM#3 Battery Sensor Fail - Read Only u16 Bit0: Battery 1
0: Normal 1: Fault
Bit1: Battery 2
0: Normal 1: Fault
Bit2: Battery 3
0: Normal 1: Fault
Bit3: Battery 4
0: Normal 1: Fault
Bit4~Bit15 reserved
B110H DCM#3 Load Sensor Fail (17-20) - Read Only u16 Bit0: Load 17
0: Normal 1: Fault
Page 41 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Bit1: Load 18
0: Normal 1: Fault
Bit2: Load 19
0: Normal 1: Fault
Bit3: Load 20
0: Normal 1: Fault
Bit4~Bit15: reserved
B111H DCM#3 Load Sensor Fail (1-16) - Read Only u16 Bit0: Load 1
0: Normal 1: Fault
Bit1: Load 2
0: Normal 1: Fault
...
Bit15: Load 16
0: Normal 1: Fault
B112H DCM#3 Temperature Sensor Fail - Read Only u16 Bit0: 0: Normal 1: Fault
Bit1~Bit15: reserved
B113H DCM#3 Total Load Current - Read Only u16 Bit0: 0: Normal 1: Fault
Sensor Fail Bit1~Bit15: reserved
…. RESERVED
B120H DCM#4 Busbar Voltage 0.1V Read Only u16
B121H DCM#4 Temperature 0.1oC Read Only u16 Offset is 500, such that
when temperature is 0oC,
the value is 500; when the
temperature is +20oC, the
value is 700; and when the
temperature is -10oC, the
value is 400
B122H DCM#4 Total Load Current 0.1A Read Only u16
B123H DCM#4 Battery 1 Current 0.1A Read Only u16
B124H DCM#4 Battery 2 Current 0.1A Read Only u16
B125H DCM#4 Battery 3 Current 0.1A Read Only u16
B126H DCM#4 Battery 4 Current 0.1A Read Only u16
B127H DCM#4 Load 1 Current Read Only u16
B128H DCM#4 Load 2 Current Read Only u16
B129H DCM#4 Load 3 Current Read Only u16
B12AH DCM#4 Load 4 Current Read Only u16
… Read Only u16
B13AH DCM#4 Load20 Current Read Only u16
B13BH DCM#4 Total Load Current - Read Only u32
B13CH
B13DH DCM#4 Total Energy 1 (Reserved) - Read Only u32
B13EH
B13FH DCM#4 Total Energy 2 (Reserved) - Read Only u32
B140H
… - Read Only u32
…
B163H DCM#4 Total Energy 20 - Read Only u32
B164H (Reserved)
B165H DCM#4 Batt Fuse Status - Read Only u16 Bit0-Batt 1 fuse status
1: Fused 0: Not fused
Bit1-Batt 2 fuse status
1: Fused 0: Not fused
Bit2-Batt 3 fuse status
Page 42 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
1: Fused 0: Not fused
Bit3-Batt 4 fuse status
1: Fused 0: Not fused
Bit4-Reserved
…
Bit13-Bit15 Reserved
B166H DCM#4 Load Fuse Status (17-30) - Read Only u16 Bit0-Load 17 fuse status
1: Fused 0: Not fused
Bit1-Load 18 fuse status
1: Fused 0: Not fused
…
Bit13-Load 30 fuse status
1: Fused 0: Not fused
Bit14-Bit15 Reserved
B167H DCM#4 Load Fuse Status (1-16) - Read Only u16 Bit0-Load 1 fuse status
1: Fused 0: Not fused
Bit1-Load 2 fuse status
1: Fused 0: Not fused
…
Bit15-Load 16 fuse status
1: Fused 0: Not fused
B168H DCM#4 Open State - Read Only u16 Bit0-Channel 1 open state
1: Open 0: Closed
Bit1-Channel 2 open state
1: Open 0: Closed
Bit2—Bit15 reserved
B169H DCM#4 Busbar Voltage upper/ - Read Only u16 Bit0: 0: Normal
lower limit over-value alarm 1: Overvoltage
Bit1: 0: Normal
1: Undervoltage
Bit2~Bit15 reserved
B16AH DCM#4 Battery Current exceeds - Read Only u16 Bit0: Battery 1
the upper limit alarm 0: Normal 1: Overcurrent
Bit1: Battery 2
0: Normal 1: Overcurrent
Bit2: Battery 3
0: Normal 1: Overcurrent
Bit3: Battery 4
0: Normal 1: Overcurrent
Bit4~Bit15 reserved
B16BH DCM#4 Load Current exceeds - Read Only u16 Bit0: Load 17
upper limit alarm (17-20) 0: Normal 1: Overcurrent
Bit1: Load 18
0: Normal 1: Overcurrent
Bit2: Load 19
0: Normal 1: Overcurrent
Bit3: Load 20
0: Normal 1: Overcurrent
Bit4~Bit15: reserved
B16CH DCM#4 Load Current exceeds - Read Only u16 Bit0: Load 1
upper limit alarm (1-16) 0: Normal 1: Overcurrent
Bit1: Load 2
0: Normal 1: Overcurrent
...
Page 43 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Bit15: Load 16
0: Normal 1: Overcurrent
B16DH DCM#2 Temperature exceeds - Read Only u16 Bit0: Temperature
upper/lower limit alarm 0: normal
1: over temperature
Bit1: Temperature
0: normal
1: under temperature
Bit2~Bit15: reserved
B16EH DCM#4 Total Load Current - Read Only u16 Bit0: 0: Normal
exceeds upper limit alarm 1: Overcurrent
Bit1~Bit15: reserved
B16FH DCM#4 Battery Sensor Fail - Read Only u16 Bit0: Battery 1
0: Normal 1: Fault
Bit1: Battery 2
0: Normal 1: Fault
Bit2: Battery 3
0: Normal 1: Fault
Bit3: Battery 4
0: Normal 1: Fault
Bit4~Bit15 reserved
B170H DCM#4 Load Sensor Fail (17-20) - Read Only u16 Bit0: Load 17
0: Normal 1: Fault
Bit1: Load 18
0: Normal 1: Fault
Bit2: Load 19
0: Normal 1: Fault
Bit3: Load 20
0: Normal 1: Fault
Bit4~Bit15: reserved
B171H DCM#4 Load Sensor Fail (1-16) - Read Only u16 Bit0: Load 1
0: Normal 1: Fault
Bit1: Load 2
0: Normal 1: Fault
...
Bit15: Load 16
0: Normal 1: Fault
B172H DCM#4 Temperature Sensor Fail - Read Only u16 Bit0: 0: Normal 1: Fault
Bit1~Bit15: reserved
B073H DCM#4 Total Load Current - Read Only u16 Bit0: 0: Normal 1: Fault
Sensor Fail Bit1~Bit15: reserved
…. RESERVED
B180H DCM#5 Busbar Voltage 0.1V Read Only u16
B181H DCM#5 Temperature 0.1oC Read Only u16 Offset is 500, such that
when temperature is 0oC,
the value is 500; when the
temperature is +20oC, the
value is 700; and when the
temperature is -10oC, the
value is 400
B182H DCM#5 Total Load Current 0.1A Read Only u16
B183H DCM#5 Battery 1 Current 0.1A Read Only u16
B184H DCM#5 Battery 2 Current 0.1A Read Only u16
Page 44 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
B185H DCM#5 Battery 3 Current 0.1A Read Only u16
B186H DCM#5 Battery 4 Current 0.1A Read Only u16
B187H DCM#5 Load 1 Current Read Only u16
B188H DCM#5 Load 2 Current Read Only u16
B189H DCM#5 Load 3 Current Read Only u16
B18AH DCM#5 Load 4 Current Read Only u16
… Read Only u16
B19AH DCM#5 Load20 Current Read Only u16
B19BH DCM#5 Total Load Current - Read Only u32
B19CH
B19DH DCM#5 Total Energy 1 (Reserved) - Read Only u32
B19EH
B19FH DCM#5 Total Energy 2 (Reserved) - Read Only u32
B1A0H
… - Read Only u32
…
B1C3H DCM#5 Total Energy 20 - Read Only u32
B1C4H (Reserved)
B1C5H DCM#5 Batt Fuse Status - Read Only u16 Bit0-Batt 1 fuse status
1: Fused 0: Not fused
Bit1-Batt 2 fuse status
1: Fused 0: Not fused
Bit2-Batt 3 fuse status
1: Fused 0: Not fused
Bit3-Batt 4 fuse status
1: Fused 0: Not fused
Bit4-Reserved
…
Bit13-Bit15 Reserved
B1C6H DCM#5 Load Fuse Status (17-30) - Read Only u16 Bit0-Load 17 fuse status
1: Fused 0: Not fused
Bit1-Load 18 fuse status
1: Fused 0: Not fused
…
Bit13-Load 30 fuse status
1: Fused 0: Not fused
Bit14-Bit15 Reserved
B1C7H DCM#5 Load Fuse Status (1-16) - Read Only u16 Bit0-Load 1 fuse status
1: Fused 0: Not fused
Bit1-Load 2 fuse status
1: Fused 0: Not fused
…
Bit15-Load 16 fuse status
1: Fused 0: Not fused
B1C8H DCM#5 Open State - Read Only u16 Bit0-Channel 1 open state
1: Open 0: Closed
Bit1-Channel 2 open state
1: Open 0: Closed
Bit2—Bit15 reserved
B1C9H DCM#5 Busbar Voltage upper/ - Read Only u16 Bit0: 0: Normal
lower limit over-value alarm 1: Overvoltage
Bit1: 0: Normal
1: Undervoltage
Page 45 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Bit2~Bit15 reserved
B1CAH DCM#5 Battery Current exceeds - Read Only u16 Bit0: Battery 1
the upper limit alarm 0: Normal 1: Overcurrent
Bit1: Battery 2
0: Normal 1: Overcurrent
Bit2: Battery 3
0: Normal 1: Overcurrent
Bit3: Battery 4
0: Normal 1: Overcurrent
Bit4~Bit15 reserved
B1CBH DCM#5 Load Current exceeds - Read Only u16 Bit0: Load 17
upper limit alarm (17-20) 0: Normal 1: Overcurrent
Bit1: Load 18
0: Normal 1: Overcurrent
Bit2: Load 19
0: Normal 1: Overcurrent
Bit3: Load 20
0: Normal 1: Overcurrent
Bit4~Bit15: reserved
B1CCH DCM#5 Load Current exceeds - Read Only u16 Bit0: Load 1
upper limit alarm (1-16) 0: Normal 1: Overcurrent
Bit1: Load 2
0: Normal 1: Overcurrent
...
Bit15: Load 16
0: Normal 1: Overcurrent
B1CDH DCM#5 Temperature exceeds - Read Only u16 Bit0: Temperature
upper/lower limit alarm 0: normal
1: over temperature
Bit1: Temperature
0: normal
1: under temperature
Bit2~Bit15: reserved
B1CEH DCM#5 Total Load Current - Read Only u16 Bit0: 0: Normal
exceeds upper limit alarm 1: Overcurrent
Bit1~Bit15: reserved
B1CFH DCM#5 Battery Sensor Fail - Read Only u16 Bit0: Battery 1
0: Normal 1: Fault
Bit1: Battery 2
0: Normal 1: Fault
Bit2: Battery 3
0: Normal 1: Fault
Bit3: Battery 4
0: Normal 1: Fault
Bit4~Bit15 reserved
B1D0H DCM#5 Load Sensor Fail (17-20) - Read Only u16 Bit0: Load 17
0: Normal 1: Fault
Bit1: Load 18
0: Normal 1: Fault
Bit2: Load 19
0: Normal 1: Fault
Bit3: Load 20
0: Normal 1: Fault
Bit4~Bit15: reserved
Page 46 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
B1D1H DCM#5 Load Sensor Fail (1-16) - Read Only u16 Bit0: Load 1
0: Normal 1: Fault
Bit1: Load 2
0: Normal 1: Fault
...
Bit15: Load 16
0: Normal 1: Fault
B1D2H DCM#5 Temperature Sensor Fail - Read Only u16 Bit0: 0: Normal 1: Fault
Bit1~Bit15: reserved
B1D3H DCM#5 Total Load Current - Read Only u16 Bit0: 0: Normal 1: Fault
Sensor Fail Bit1~Bit15: reserved
Page 47 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Page 48 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
4038H Batt Sampling Unit 3 - Read/Write u16 [0, 0, 54]
4039H Batt Sampling Unit 4 - Read/Write u16 [0, 0, 54]
403AH Batt Sampling Unit 5 - Read/Write u16 [0, 0, 54]
403BH Batt Sampling Unit 6 - Read/Write u16 [0, 0, 54]
403CH Batt Sampling Unit 7 - Read/Write u16 [0, 0, 54]
403DH Batt Sampling Unit 8 - Read/Write u16 [0, 0, 54]
403EH ~ Reserved
403FH
4040H Equalize Charge Voltage 0.01V Read/Write u16 [4000, 4500, 6000]
Threshold
4041H Float to Equalize Current - Read/Write u16 Enable [0x14]; Disable [0x15]
Flow % Enable
4042H Float to Equalize Current 1% Read/Write u16 [1, 5, 100]
Flow %
4043H Float to Equalize Start - Read/Write u16 Enable [0x14]; Disable [0x15]
Threshold Cap % Enable
4044H Float to Equalize Start 1% Read/Write u16 [1, 60, 100]
Threshold Capacity %
4045H Float to Equalize Sec Read/Write u16 [1, 10, 600]
Confirmation Time
4046H Float to Equalize AC-ERR - Read/Write u16 Enable [0x14]; Disable [0x15]
Confirmation Time Enable
4047H Float to Equalize AC-ERR Min Read/Write u16 [1, 30, 60000]
Confirmation Time
4048H Periodic Equalize Time - Read/Write u16 Enable [0x14]; Disable [0x15]
Enable
4049H Periodic Equalize Time Hour Read/Write u16 [1, 90*24, 60000]
Limit
404AH Float Target Voltage 0.01V Read/Write u16 [4000, 5400, 6000]
404BH Float Current Limit % 1% Read/Write u16 [0, 50, 400]
404CH Reserved
~ 404FH
4050H Equalize Charge Enable - Read/Write u16 Enable [0x14]; Disable [0x15]
4051H Equalization Time Limit Min Read/Write u16 [1, 600, 60000]
4052H Equalization Capacity % - Read/Write u16 Enable [0x14]; Disable [0x15]
Enable
4053H Equalization Capacity % 1% Read/Write u16 [1, 100, 200]
4054H Equalize Charge Capacity % - Read/Write u16 Enable [0x14]; Disable [0x15]
Enable
4055H Equalize Charge Capacity % 1% Read/Write u16 [1, 100, 200]
4056H Equalize to Float Current % 1% Read/Write u16 [0, 1, 100]
4057H Equalize Charge Complete Min Read/Write u16 [0, 180, 60000]
Time Limit
4058H Equalize Charge Target 0.01V Read/Write u16 [4000, 5640, 6000]
Voltage
4059H Equalize Charge Limit % 1% Read/Write u16 [0, 10, 400]
405AH Equalize Charge Fixed Time Min Read/Write u16 [0, 1440, 60000]
Limit
405BH Exit Equalize Charge due to - Read/Write u16 Enable [0x14]; Disable [0x15]
Fault Enable
405CH Reserved
~ 405FH
4060H Battery Test Enable - Read/Write u16 Enable [0x14]; Disable [0x15]
Page 49 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
4061H Test Process Time Limit Min Read/Write u16 [0, 180, 600]
4062H Test Fixed Time Limit Min Read/Write u16 [0, 1440, 60000]
4063H Automatic Discharge Test - Read/Write u16 Enable [0x14]; Disable [0x15]
Cycle Enable
4064H Automatic Discharge Test Day Read/Write u16 [1, 180, 720]
Cycle
4065H Test Process Capacity - Read/Write u16 Enable [0x14]; Disable [0x15]
Enable
4066H Test Process Capacity % 1% Read/Write u16 [1, 20, 100]
4067H Test Total Capacity Enable - Read/Write u16 Enable [0x14]; Disable [0x15]
4068H Test Total Capacity % 1% Read/Write u16 [1, 80, 100]
4069H Test Completion Time Sec Read/Write u16 [0, 3, 60000]
Limit
406AH Test Target Voltage 0.01V Read/Write u16 [4000, 5000, 6000]
406BH Test Current Limit % 1% Read/Write u16 [-400, -10, 0]
406CH Reserved
~ 406FH
4070H Batt Current Limit Enable - Read/Write u16 Enable [0x14]; Disable [0x15]
4071H Temp Compensation - Read/Write u16 Enable [0x14]; Disable [0x15]
Enable
4072H Temp Compensation 0.01oC Read/Write u16 [0, 2000, 4000]
Reference Value
4073H Temp Compensation mV/oC Read/Write u16 [-40, -2, 40]
Gradient
4074H AVC Enable - Read/Write u16 Enable [0x14]; Disable [0x15]
4075H Batt Discharge Limit % 1% Read/Write u16 [-20, -3, 20]
4076H Batt Overcurrent Limit 1% Read/Write u16 [5, 30, 400]
4077H Single Cell High Voltage 0.01V Read/Write u16 [0, 240, 2000]
Threshold
4078H Single Cell Low Voltage 0.01V Read/Write u16 [0, 180, 2000]
Threshold
4079H Equalize Charge Trigger - Read/Write u16 Trigger [0x01]; Stop [0x02]
407AH Battery Test Trigger - Read/Write u16 Trigger [0x01]; Stop [0x02]
407BH Types of Battery - Read/Write u16 Lead Acid Battery [0x01];
Nada [0x02]; Leoch [0x03];
Lithium [0x04]
407CH Manual update of battery - Read/Write u16 Capacity update trigger
capacity [0: none 1: trigger]
407DH Battery capacity ratio - Read/Write u16 (1, 10)
(current limit)
407EH ~ Reserved
407FH
4080H Batt Sym Check Enable - Read/Write u16 Enable [0x14]; Disable [0x15]
4081H Batt Sym Voltage Check - Read/Write u16 12V [0x01]; 24V [0x02]
Level
4082H Batt Sym Check Mode - Read/Write u16 Continuous Mode [0x01];
Check during discharge [0x02]
4083H Batt Sym Check Delay Min Read/Write u16 [0, 8, 60]
No. of mins to delay the
symmetry measurements after
the start of discharge mode
4084H Batt Sym High Voltage 0.01V Read/Write u16
Alarm Threshold
Page 50 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
4085H Batt Sym Low Voltage 0.01V Read/Write u16
Alarm Threshold
4086H Reserved
~ 408FH
4090H Number of Lithium Battery - Read/Write u16
4091H Reserved
~40FFH
Page 51 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
411AH Open 24 Function Definition - Read/Write u16
411BH Open 25 Function Definition - Read/Write u16
411CH Open 26 Function Definition - Read/Write u16
411DH Open 27 Function Definition - Read/Write u16
411EH ~ Reserved
411FH
4120H Open 0 Custom Function - Read/Write u16 Open 0 custom function name.
Name (field 1) Length is 12bytes, high byte is
4121H Open 0 Custom Function - Read/Write u16 transmitted first.
Name (field 2)
4122H Open 0 Custom Function - Read/Write u16
Name (field 3)
4123H Open 0 Custom Function - Read/Write u16
Name (field 4)
4124H Open 0 Custom Function - Read/Write u16
Name (field 5)
4125H Open 0 Custom Function - Read/Write u16
Name (field 6)
4126H Open 1 Custom Function - Read/Write u16 Open 1 custom function name.
Name (field 1) Length is 12bytes, high byte is
4127H Open 1 Custom Function - Read/Write u16 transmitted first.
Name (field 2)
4128H Open 1 Custom Function - Read/Write u16
Name (field 3)
4129H Open 1 Custom Function - Read/Write u16
Name (field 4)
412AH Open 1 Custom Function - Read/Write u16
Name (field 5)
412BH Open 1 Custom Function - Read/Write u16
Name (field 6)
……….
41C2H Open 27 Custom Function - Read/Write u16 Open 27 custom function name.
Name (field 1) Length is 12bytes, high byte is
41C3H Open 27 Custom Function - Read/Write u16 transmitted first.
Name (field 2)
41C4H Open 27 Custom Function - Read/Write u16
Name (field 3)
41C5H Open 27 Custom Function - Read/Write u16
Name (field 4)
41C6H Open 27 Custom Function - Read/Write u16
Name (field 5)
41C7H Open 27 Custom Function - Read/Write u16
Name (field 6)
41C8H Reserved
~ 41CFH
41D0H Batt Fuse 1 Digital Sampling 0.01V Read/Write u16 [0, 50, 250]
Size Simulation Limit
41D1H Batt Fuse 2 Digital Sampling 0.01V Read/Write u16 [0, 50, 250]
Size Simulation Limit
41D2H Batt Fuse 3 Digital Sampling 0.01V Read/Write u16 [0, 50, 250]
Size Simulation Limit
41D3H Batt Fuse 4 Digital Sampling 0.01V Read/Write u16 [0, 50, 250]
Size Simulation Limit
Page 52 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
41D4H Batt Fuse 5 Digital Sampling 0.01V Read/Write u16 [0, 50, 250]
Size Simulation Limit
41D5H Batt Fuse 6 Digital Sampling 0.01V Read/Write u16 [0, 50, 250]
Size Simulation Limit
41D6H Batt Fuse 7 Digital Sampling 0.01V Read/Write u16 [0, 50, 250]
Size Simulation Limit
41D7H Batt Fuse 8 Digital Sampling 0.01V Read/Write u16 [0, 50, 250]
Size Simulation Limit
41D8H Reserved
~ 41FFH
Page 53 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
6.6 LVD Data
Register Description Unit Read/Write Type Remarks
4300H LVD inhibit time Sec Read/Write u16 [10, 30, 600]
4301H LVD1 control mode - Read/Write u16 Auto [0x14], Disable [0x15],
Manually connect [0x16],
Manually disconnect [0x17]
4302H LVD1 control confirm time Sec Read/Write u16 [10, 30, 600]
4303H LVD1 disable mode - Read/Write u16 Connect [0x00], Disconnect [0x01]
4304H LVD1 auto failure mode - Read/Write u16 Keep the status [0x00], Connect
[0x01], Disconnect [0x02]
4305H LVD1 self-recovery enable - Read/Write u16 Enable-0; Disable-1; Default-0
4306H LVD1 self-mode - Read/Write u16 Normally open with contact
[0x00]; Normally closed with
contact [0x01]; Normally open
without contact [0x02];
Normally closed without contact
[0x03]
4307H LVD1 connect voltage 0.01V Read/Write u16 [3500, 5000, 6000]
4308H LVD1 disconnect voltage 0.01V Read/Write u16 [3500, 4700, 6000]
4309H LVD1 AC connect enable - Read/Write u16 Enable [0x14]; Disable [0x15]
430AH LVD1 AC connect confirm Min Read/Write u16 [1, 30, 60000]
time
430BH LVD1 AC disconnect enable - Read/Write u16 Enable [0x14]; Disable [0x15]
430CH LVD1 AC disconnect Min Read/Write u16 [1, 30, 60000]
confirm time
430DH LVD1 auxiliary temp enable - Read/Write u16 Enable [0x14]; Disable [0x15]
430EH LVD2 control mode - Read/Write u16 Auto [0x14], Disable [0x15],
Manually connect [0x16],
Manually disconnect [0x17]
430FH LVD2 control confirm time Sec Read/Write u16 [10, 30, 600]
4310H LVD2 disable mode - Read/Write u16 Connect [0x00], Disconnect [0x01]
4311H LVD2 auto failure mode - Read/Write u16 Keep the status [0x00], Connect
[0x01], Disconnect [0x02]
4312H LVD2 self-recovery enable - Read/Write u16 Enable-0; Disable-1; Default-0
4313H LVD2 self-mode - Read/Write u16 Normally open with contact
[0x00]; Normally closed with
contact [0x01]; Normally open
without contact [0x02];
Normally closed without contact
[0x03]
4314H LVD2 connect voltage 0.01V Read/Write u16 [3500, 5000, 6000]
4315H LVD2 disconnect voltage 0.01V Read/Write u16 [3500, 4700, 6000]
4316H LVD2 AC connect enable - Read/Write u16 Enable [0x14]; Disable [0x15]
4317H LVD2 AC connect confirm Min Read/Write u16 [1, 30, 60000]
time
4318H LVD2 AC disconnect enable - Read/Write u16 Enable [0x14]; Disable [0x15]
4319H LVD2 AC disconnect Min Read/Write u16 [1, 30, 60000]
confirm time
431AH LVD2 auxiliary temp enable - Read/Write u16 Enable [0x14]; Disable [0x15]
431BH LVD3 control mode - Read/Write u16 Auto [0x14], Disable [0x15],
Manually connect [0x16],
Page 54 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Manually disconnect [0x17]
431CH LVD3 control confirm time Sec Read/Write u16 [10, 30, 600]
431DH LVD3 disable mode - Read/Write u16 Connect [0x00], Disconnect [0x01]
431EH LVD3 auto failure mode - Read/Write u16 Keep the status [0x00], Connect
[0x01], Disconnect [0x02]
431EH LVD3 self-recovery enable - Read/Write u16 Enable-0; Disable-1; Default-0
4320H LVD3 self-mode - Read/Write u16 Normally open with contact
[0x00]; Normally closed with
contact [0x01]; Normally open
without contact [0x02];
Normally closed without contact
[0x03]
4321H LVD3 connect voltage 0.01V Read/Write u16 [3500, 5000, 6000]
4322H LVD3 disconnect voltage 0.01V Read/Write u16 [3500, 4700, 6000]
4323H LVD3 AC connect enable - Read/Write u16 Enable [0x14]; Disable [0x15]
4324H LVD3 AC connect confirm Min Read/Write u16 [1, 30, 60000]
time
4325H LVD3 AC disconnect enable - Read/Write u16 Enable [0x14]; Disable [0x15]
4326H LVD3 AC disconnect Min Read/Write u16 [1, 30, 60000]
confirm time
4327H LVD3 auxiliary temp enable - Read/Write u16 Enable [0x14]; Disable [0x15]
4328H LVD4 control mode - Read/Write u16 Auto [0x14], Disable [0x15],
Manually connect [0x16],
Manually disconnect [0x17]
4329H LVD4 control confirm time Sec Read/Write u16 [10, 30, 600]
432AH LVD4 disable mode - Read/Write u16 Connect [0x00], Disconnect [0x01]
432BH LVD4 auto failure mode - Read/Write u16 Keep the status [0x00], Connect
[0x01], Disconnect [0x02]
432CH LVD4 self-recovery enable - Read/Write u16 Enable-0; Disable-1; Default-0
432DH LVD4 self-mode - Read/Write u16 Normally open with contact
[0x00]; Normally closed with
contact [0x01]; Normally open
without contact [0x02];
Normally closed without contact
[0x03]
432EH LVD4 connect voltage 0.01V Read/Write u16 [3500, 5000, 6000]
432FH LVD4 disconnect voltage 0.01V Read/Write u16 [3500, 4700, 6000]
4330H LVD4 AC connect enable - Read/Write u16 Enable [0x14]; Disable [0x15]
4331H LVD4 AC connect confirm Min Read/Write u16 [1, 30, 60000]
time
4332H LVD4 AC disconnect enable - Read/Write u16 Enable [0x14]; Disable [0x15]
4333H LVD4 AC disconnect Min Read/Write u16 [1, 30, 60000]
confirm time
4334H LVD4 auxiliary temp enable - Read/Write u16 Enable [0x14]; Disable [0x15]
4335H LVD5 control mode - Read/Write u16 Auto [0x14], Disable [0x15],
Manually connect [0x16],
Manually disconnect [0x17]
4336H LVD5 control confirm time Sec Read/Write u16 [10, 30, 600]
4337H LVD5 disable mode - Read/Write u16 Connect [0x00], Disconnect [0x01]
4338H LVD5 auto failure mode - Read/Write u16 Keep the status [0x00], Connect
[0x01], Disconnect [0x02]
4339H LVD5 self-recovery enable - Read/Write u16 Enable-0; Disable-1; Default-0
433AH LVD5 self-mode - Read/Write u16 Normally open with contact
Page 55 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
[0x00]; Normally closed with
contact [0x01]; Normally open
without contact [0x02];
Normally closed without contact
[0x03]
433BH LVD5 connect voltage 0.01V Read/Write u16 [3500, 5000, 6000]
433CH LVD5 disconnect voltage 0.01V Read/Write u16 [3500, 4700, 6000]
433DH LVD5 AC connect enable - Read/Write u16 Enable [0x14]; Disable [0x15]
433EH LVD5 AC connect confirm Min Read/Write u16 [1, 30, 60000]
time
433FH LVD5 AC disconnect enable - Read/Write u16 Enable [0x14]; Disable [0x15]
4340H LVD5 AC disconnect Min Read/Write u16 [1, 30, 60000]
confirm time
4341H LVD5 auxiliary temp enable - Read/Write u16 Enable [0x14]; Disable [0x15]
4342F Reserved
43FFF
Page 56 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Bit1: #18 module
......
Bit15: #32 module
4412H Rectifier on/off control - Read/Write - The bit controls module on/off.
(#33 to #40) Shut down [0], power on [1]
Bit0: #33 module
Bit1: #34 module
......
Bit7: #40 module
Bit8-bit15: Reserved
4413H Rectifier on/off control - Read/Write - Reserved
(reserved)
4414H Rectifier LED control (#1 to - Read/Write - The bit manages LED control.
#16) Shut down [0], power on [1]
Bit0: #1 module
Bit1: #2 module
......
Bit15: #16 module
4415H Rectifier LED control (#17 - Read/Write - The bit manages LED control.
to #32) Shut down [0], power on [1]
Bit0: #17 module
Bit1: #18 module
......
Bit15: #32 module
4416H Rectifier LED control (#33 - Read/Write - The bit manages LED control.
to #40) Shut down [0], power on [1]
Bit0: #33 module
Bit1: #34 module
......
Bit7: #40 module
Bit8-bit15: Reserved
4417H Rectifier LED control - Read/Write - Reserved
(reserved)
4418H- Reserved
441FH
4420H Rectifier Fault Masking - Read/Write - Enable [0x14]; Disable [0x15]
during AC Fault
4421H Module Walk-in time - Read/Write - Reserved
4422H Genset Enable - Read/Write - Enable [0x14]; Disable [0x15]
4423H Genset Delay - Read/Write - Reserved
4424H No. of redundant modules - Read/Write - Reserved
4425H No. of modules critical - Read/Write - Reserved
alarm
4426H No. of modules general - Read/Write - Reserved
alarm
4427H- Reserved
45FFH
Page 57 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
6.8 Temperature Data
Register Description Unit Read/Write Type Remarks
4600H High Ambient Temperature 0.01oC Read/Write s16 [2000, 4000, 10000]
Threshold
4601H Low Ambient Temperature 0.01oC Read/Write s16 [-4000, 0, 2000]
Threshold
4602H High Batt Temperature 0.01oC Read/Write s16 [2000, 4000, 10000]
Threshold
4603H Low Batt Temperature 0.01oC Read/Write s16 [-4000, 0, 2000]
Threshold
4604H Ambient Over Temp - Read/Write u16 Enable [0x14]; Disable [0x15]
Shutdown Enable
4605H High Ambient Temperature 0.01oC Read/Write s16 [3000, 7000, 10000]
Shutdown Threshold
4606H High Ambient Temperature 0.01oC Read/Write s16 [0, 6000, 10000]
Start Threshold
4607H Low Ambient Temperature 0.01oC Read/Write s16 [-4000, -500, 6000]
Shutdown Threshold
4608H Low Ambient Temperature 0.01oC Read/Write s16 [-4000, 0, 6000]
Start Threshold
4609H- Reserved
463FH
Page 58 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
[bit14, bit15]: #8 module position
Unmatched [0,0], A[1,0],
B[0,1],C[1,1]
464CH Module position #9- #16 - Read/Write u16 [bit0, bit1]: #9 module position
Unmatched [0,0], A[1,0],
B[0,1],C[1,1]
[bit2, bit3]: #10 module position
Unmatched [0,0], A[1,0],
B[0,1],C[1,1]
......
[bit14, bit15]: #16 module
position Unmatched [0,0], A[1,0],
B[0,1],C[1,1]
464DH Module position #17- #24 - Read/Write u16 [bit0, bit1]: #17 module position
Unmatched [0,0], A[1,0],
B[0,1],C[1,1]
[bit2, bit3]: #18 module position
Unmatched [0,0], A[1,0],
B[0,1],C[1,1]
......
[bit14, bit15]: #24 module
position Unmatched [0,0], A[1,0],
B[0,1],C[1,1]
464EH Module position #25- #32 - Read/Write u16 [bit0, bit1]: #25 module position
Unmatched [0,0], A[1,0],
B[0,1],C[1,1]
[bit2, bit3]: #26 module position
Unmatched [0,0], A[1,0],
B[0,1],C[1,1]
......
[bit14, bit15]: #32 module
position Unmatched [0,0], A[1,0],
B[0,1],C[1,1]
464FH Module position #33- #40 Read/Write u16 [bit0, bit1]: #33 module position
Unmatched [0,0], A[1,0],
B[0,1],C[1,1]
[bit2, bit3]: #34 module position
Unmatched [0,0], A[1,0],
B[0,1],C[1,1]
......
[bit14, bit15]: #40 module
position Unmatched [0,0], A[1,0],
B[0,1],C[1,1]
4650H- Reserved
469FH
Page 59 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
6.10 ADC Data
Register Description Unit Read/Write Type Remarks
4700H Custom 1 Channel 1 - Read/Write u16
4701H Custom 1 Channel 2 - Read/Write u16
4702H Custom 2 Channel 1 - Read/Write u16
4703H Custom 2 Channel 2 - Read/Write u16
4704H Custom 3 Channel 1 - Read/Write u16
4705H Custom 3 Channel 2 - Read/Write u16
4706H Custom 4 Channel 1 - Read/Write u16
4707H Custom 4 Channel 2 - Read/Write u16
4708H Current Enable - Read/Write u32 bit representation
4709H Bit0: Total battery current OFF [0],
ON [1]
Bit1: Batt bank 1 current OFF [0],
ON [1]
Bit2: Batt bank 2 current OFF [0],
ON [1]
Bit3: Batt bank 3 current OFF [0],
ON [1]
Bit4: Batt bank 4 current OFF [0],
ON [1]
Bit5: Total load current OFF [0],
ON [1]
Bit6: Load 1 current OFF [0], ON
[1]
Bit7: Load 2 current OFF [0], ON
[1]
Bit8: Load 3 current OFF [0], ON
[1]
Bit9: Load 4 current OFF [0], ON
[1]
Bit10: Load 5 current OFF [0], ON
[1]
Bit11: Load 6 current OFF [0], ON
[1]
Bit12: Load 7 current OFF [0], ON
[1]
Bit13: Load 8 current OFF [0], ON
[1]
Bit14: Load 9 current OFF [0], ON
[1]
Bit15: Load 10 current OFF [0], ON
[1]
Bit16: Load 11 current OFF [0], ON
[1]
Bit17: Load 12 current OFF [0], ON
[1]
Bit18: Load 13 current OFF [0], ON
[1]
Bit19: Load 14 current OFF [0], ON
[1]
Bit20: Load 15 current OFF [0], ON
Page 60 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
[1]
Bit21: Load 16 current OFF [0], ON
[1]
470AH Current channel 1 function - Read/Write u16 None [0x60]
definition Total load current [0x61]
Total battery current [0x62]
Total rectifier output current
[0x63]
Battery Bank 1 Current [0x64]
Battery Bank 2 Current [0x65]
Battery Bank 3 Current [0x66]
Battery Bank 4 Current [0x67]
Load 1 current [0x68]
Load 2 current [0x69]
Load 3 current [0x6A]
Load 4 current [0x6B]
Load 5 current [0x6C]
Load 6 current [0x6D]
Load 7 current [0x6E]
Load 8 current [0x6F]
Load 9 current [0x70]
Load 10 current [0x71]
Load 11 current [0x72]
Load 12 current [0x73]
Load 13 current [0x74]
Load 14 current [0x75]
Load 15 current [0x76]
Load 16 current [0x77]
470BH Current channel 1 offset - Read/Write s16 Sample Value
470CH Batt channel 1 shunt A Read/Write u16 Current Parameters
specifications (current) [0, 100, 4000]
470DH Batt channel 1 shunt mV Read/Write u16 Voltage Parameters
specifications (voltage) [0, 50, 100]
470EH Current channel 1 +ve/-ve - Read/Write u16 Positive [0x00]; Negative [0x01]
470FH Current channel 2 function - Read/Write u16 None [0x60]
definition Total load current [0x61]
Total battery current [0x62]
Total rectifier output current
[0x63]
Battery Bank 1 Current [0x64]
Battery Bank 2 Current [0x65]
Battery Bank 3 Current [0x66]
Battery Bank 4 Current [0x67]
Load 1 current [0x68]
Load 2 current [0x69]
Load 3 current [0x6A]
Load 4 current [0x6B]
Load 5 current [0x6C]
Load 6 current [0x6D]
Load 7 current [0x6E]
Load 8 current [0x6F]
4710H Current channel 2 offset - Read/Write s16 Sample Value
4711H Batt channel 2 shunt A Read/Write u16 Current Parameters
specifications (current) [0, 100, 4000]
Page 61 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
4712H Batt channel 2 shunt mV Read/Write u16 Voltage Parameters
specifications (voltage) [0, 50, 100]
4713H Current channel 2 +ve/-ve - Read/Write u16 Positive [0x00]; Negative [0x01]
4714H Current channel 3 function - Read/Write u16 Current channel 3 - 26 is the DC
definition sample box channel. See current
channel 1 function definition
4715H Current channel 4 function - Read/Write u16 Current channel 3 - 26 is the DC
definition sample box channel. See current
channel 1 function definition
4716H Current channel 5 function - Read/Write u16 Current channel 3 - 26 is the DC
definition sample box channel. See current
channel 1 function definition
4717H Current channel 6 function - Read/Write u16 Current channel 3 - 26 is the DC
definition sample box channel. See current
channel 1 function definition
4718H Current channel 7 function - Read/Write u16 Current channel 3 - 26 is the DC
definition sample box channel. See current
channel 1 function definition
4719H Current channel 8 function - Read/Write u16 Current channel 3 - 26 is the DC
definition sample box channel. See current
channel 1 function definition
471AH Current channel 9 function - Read/Write u16 Current channel 3 - 26 is the DC
definition sample box channel. See current
channel 1 function definition
471BH Current channel 10 - Read/Write u16 Current channel 3 - 26 is the DC
function definition sample box channel. See current
channel 1 function definition
471CH Current channel 11 - Read/Write u16 Current channel 3 - 26 is the DC
function definition sample box channel. See current
channel 1 function definition
471DH Current channel 12 - Read/Write u16 Current channel 3 - 26 is the DC
function definition sample box channel. See current
channel 1 function definition
471EH Current channel 13 - Read/Write u16 Current channel 3 - 26 is the DC
function definition sample box channel. See current
channel 1 function definition
471FH Current channel 14 - Read/Write u16 Current channel 3 - 26 is the DC
function definition sample box channel. See current
channel 1 function definition
4720H Current channel 15 - Read/Write u16 Current channel 3 - 26 is the DC
function definition sample box channel. See current
channel 1 function definition
4721H Current channel 16 - Read/Write u16 Current channel 3 - 26 is the DC
function definition sample box channel. See current
channel 1 function definition
4722H Current channel 17 - Read/Write u16 Current channel 3 - 26 is the DC
function definition sample box channel. See current
channel 1 function definition
4723H Current channel 18 - Read/Write u16 Current channel 3 - 26 is the DC
function definition sample box channel. See current
channel 1 function definition
4724H Current channel 19 - Read/Write u16 Current channel 3 - 26 is the DC
function definition sample box channel. See current
Page 62 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
channel 1 function definition
4725H Current channel 20 - Read/Write u16 Current channel 3 - 26 is the DC
function definition sample box channel. See current
channel 1 function definition
4726H Current channel 21 - Read/Write u16 Current channel 3 - 26 is the DC
function definition sample box channel. See current
channel 1 function definition
4727H Current channel 22 - Read/Write u16 Current channel 3 - 26 is the DC
function definition sample box channel. See current
channel 1 function definition
4728H Current channel 23 - Read/Write u16 Current channel 3 - 26 is the DC
function definition sample box channel. See current
channel 1 function definition
4729H Current channel 24 - Read/Write u16 Current channel 3 - 26 is the DC
function definition sample box channel. See current
channel 1 function definition
472AH Current channel 26 - Read/Write u16 Current channel 3 - 26 is the DC
function definition sample box channel. See current
channel 1 function definition
472BH Current channel 26 - Read/Write u16 Current channel 3 - 26 is the DC
function definition sample box channel. See current
channel 1 function definition
472CH Temperature channel 1 - Read/Write u16 None [0x00];
function definition Battery temperature [0x01];
Ambient temperature [0x02]
472DH Temperature channel 2 - Read/Write u16 None [0x00];
function definition Battery temperature [0x01];
Ambient temperature [0x02]
472EH Zero drift clearing point - Read/Write u16
472FH- Reserved
47FFH
Page 63 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Bit12: DO12 mapping
Bit13: DO13 mapping
Bit14: DO14 mapping
Bit15: DO15 mapping
Bit16: DO16 mapping
Bit17: DO17 mapping
Bit18: Spk
Bit19: LVD1
Bit20: LVD2
Bit21: Trap
Bit22--bit27: Reserved
Bit28: Alarm status
Bit29--bit31: Alarm level
0x00: None
0x01: General (Minor)
0x02: Major
0x03: Critical
Self-alarm, only map DO0--DO5
4802H AC Incoming Line 1 Fault - Read/Write u32
4803H alarm mapping and level
4804H AC Incoming Line 2 Fault - Read/Write u32
4805H alarm mapping and level
4806H AC Phase Loss alarm - Read/Write u32
4807H mapping and level
4808H AC Incoming Line 1 Phase - Read/Write u32
4809H A overvoltage alarm
mapping and level
480AH AC Incoming Line 1 Phase - Read/Write u32
480BH B overvoltage alarm
mapping and level
480CH AC Incoming Line 1 Phase - Read/Write u32
480DH C overvoltage alarm
mapping and level
480EH AC Incoming Line 1 Phase - Read/Write u32
480FH A undervoltage alarm
mapping and level
4810H AC Incoming Line 1 Phase - Read/Write u32
4811H B undervoltage alarm
mapping and level
4812H AC Incoming Line 1 Phase - Read/Write u32
4813H C undervoltage alarm
mapping and level
4814H AC Incoming Line 1 Phase - Read/Write u32
4815H A missing phase alarm
mapping and level
4816H AC Incoming Line 1 Phase - Read/Write u32
4817H B missing phase alarm
mapping and level
4818H AC Incoming Line 1 Phase - Read/Write u32
4819H C missing phase alarm
mapping and level
481AH AC Incoming Line 1 Phase - Read/Write u32
481BH A overcurrent alarm
Page 64 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
mapping and level
481CH AC Incoming Line 1 Phase - Read/Write u32
481DH B overcurrent alarm
mapping and level
481EH AC Incoming Line 1 Phase - Read/Write u32
481FH C overcurrent alarm
mapping and level
4820H AC Incoming Line 1 high - Read/Write u32
4821H frequency alarm mapping
and level
4822H AC Incoming Line 1 low - Read/Write u32
4823H frequency alarm mapping
and level
4824H AC Incoming Line 2 Phase - Read/Write u32
4825H A overvoltage alarm
mapping and level
4826H AC Incoming Line 2 Phase - Read/Write u32
4827H B overvoltage alarm
mapping and level
4828H AC Incoming Line 2 Phase - Read/Write u32
4829H C overvoltage alarm
mapping and level
482AH AC Incoming Line 2 Phase - Read/Write u32
482BH A undervoltage alarm
mapping and level
482CH AC Incoming Line 2 Phase - Read/Write u32
482DH B undervoltage alarm
mapping and level
482EH AC Incoming Line 2 Phase - Read/Write u32
482FH C undervoltage alarm
mapping and level
4830H AC Incoming Line 2 Phase - Read/Write u32
4831H A missing phase alarm
mapping and level
4832H AC Incoming Line 2 Phase - Read/Write u32
4833H B missing phase alarm
mapping and level
4834H AC Incoming Line 2 Phase - Read/Write u32
4835H C missing phase alarm
mapping and level
4836H AC Incoming Line 2 Phase - Read/Write u32
4837H A overcurrent alarm
mapping and level
4838H AC Incoming Line 2 Phase - Read/Write u32
4839H B overcurrent alarm
mapping and level
483AH AC Incoming Line 2 Phase - Read/Write u32
483BH C overcurrent alarm
mapping and level
483CH AC Incoming Line 2 high - Read/Write u32
483DH frequency alarm mapping
and level
483EH AC Incoming Line 2 low - Read/Write u32
Page 65 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
483FH frequency alarm mapping
and level
4840H Bus Voltage low -1 alarm - Read/Write u32
4841H mapping and level
4842H Bus Voltage low -2 alarm - Read/Write u32
4843H mapping and level
4844H Bus Voltage high -1 alarm - Read/Write u32
4845H mapping and level
4846H Bus Voltage high -2 alarm - Read/Write u32
4847H mapping and level
4848H System Overload alarm - Read/Write u32
4849H mapping and level
484AH Single Rectifier Fault alarm - Read/Write u32
484BH mapping and level
484CH Multiple Rectifier Fault - Read/Write u32
484DH alarm mapping and level
484EH Single Rectifier Loss alarm - Read/Write u32
484FH mapping and level
4850H Multiple Rectifier Loss - Read/Write u32
4851H alarm mapping and level
4852H Rectifier No-load alarm - Read/Write u32
4853H mapping and level
4854H Rectifier Current Limit - Read/Write u32
4855H alarm mapping and level
4856H Rectifier Overtemperature - Read/Write u32
4857H alarm mapping and level
4858H All Rectifiers OFF alarm - Read/Write u32
4859H mapping and level
485AH Module Fan Failure alarm - Read/Write u32
485BH mapping and level
485CH Battery Test Failure alarm - Read/Write u32
485DH mapping and level
485EH Battery Overcurrent alarm - Read/Write u32
485FH mapping and level
4860H Battery Discharge alarm - Read/Write u32
4861H mapping and level
4862H Single Cell High Voltage - Read/Write u32
4863H alarm mapping and level
4864H Single Cell Low Voltage - Read/Write u32
4865H alarm mapping and level
4866H Battery Symmetry alarm - Read/Write u32
4867H mapping and level
4868H LVD1 Disconnect alarm - Read/Write u32
4869H mapping and level
486AH LVD2 Disconnect alarm - Read/Write u32
486BH mapping and level
486CH LVD1 Fault alarm mapping - Read/Write u32
486DH and level
486EH LVD2 Fault alarm mapping - Read/Write u32
486FH and level
4870H Sensor Failure alarm - Read/Write u32
4871H mapping and level
Page 66 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
4872H Bus Voltage Sensing Fault - Read/Write u32
4873H alarm mapping and level
4874H Current Sensor Fault alarm - Read/Write u32
4875H mapping and level
4876H Temp Sensor 1 Fault alarm - Read/Write u32
4877H mapping and level
4878H Temp Sensor 2 Fault alarm - Read/Write u32
4879H mapping and level
487AH Low Batt Temp alarm - Read/Write u32
487BH mapping and level
487CH High Batt Temp alarm - Read/Write u32
487DH mapping and level
487EH Low Ambient Temp alarm - Read/Write u32
487FH mapping and level
4880H High Ambient Temp alarm - Read/Write u32
4881H mapping and level
4882H Equalize Charge alarm - Read/Write u32
4883H mapping and level
4884H Battery Test alarm - Read/Write u32
4885H mapping and level
4886H Battery Current Limit - Read/Write u32
4887H alarm mapping and level
4888H Batt Fuse 1 Fault alarm - Read/Write u32
4889H mapping and level
488AH Batt Fuse 2 Fault alarm - Read/Write u32
488BH mapping and level
488CH Batt Fuse 3 Fault alarm - Read/Write u32
488DH mapping and level
488EH Batt Fuse 4 Fault alarm - Read/Write u32
488FH mapping and level
4890H Batt Fuse 5 Fault alarm - Read/Write u32
4891H mapping and level
4892H Batt Fuse 6 Fault alarm - Read/Write u32
4893H mapping and level
4894H Batt Fuse 7 Fault alarm - Read/Write u32
4895H mapping and level
4896H Batt Fuse 8 Fault alarm - Read/Write u32
4897H mapping and level
4898H Load Fuse -ve Fault alarm - Read/Write u32
4899H mapping and level
489AH Load Fuse +ve Fault alarm - Read/Write u32
489BH mapping and level
489CH MOV1 Fault alarm - Read/Write u32
489DH mapping and level
489EH MOV2 Fault alarm - Read/Write u32
489FH mapping and level
48A0H ACD Failure alarm mapping - Read/Write u32
48A1H and level
48A2H Custom Communication - Read/Write u32
48A3H Failure
48A4H AC 1 Relay Disconnect - Read/Write u32
48A5H alarm mapping and level
Page 67 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
48A6H AC 2 Relay Disconnect - Read/Write u32
48A7H alarm mapping and level
48A8H Digital Input (DI) 1 alarm - Read/Write u32
48A9H mapping and level
48AAH Digital Input (DI) 2 alarm - Read/Write u32
48ABH mapping and level
48ACH Digital Input (DI) 3 alarm - Read/Write u32
48ADH mapping and level
48AEH Digital Input (DI) 4 alarm - Read/Write u32
48AFH mapping and level
48B0H Digital Input (DI) 5 alarm - Read/Write u32
48B1H mapping and level
48B2H Digital Input (DI) 6 alarm - Read/Write u32
48B3H mapping and level
48B4H Digital Input (DI) 7 alarm - Read/Write u32
48B5H mapping and level
48B6H Digital Input (DI) 8 alarm - Read/Write u32
48B7H mapping and level
48B8H Digital Input (DI) 9 alarm - Read/Write u32
48B9H mapping and level
48BAH Digital Input (DI) 10 alarm - Read/Write u32
48BBH mapping and level
48BCH Digital Input (DI) 11 alarm - Read/Write u32
48BDH mapping and level
48BEH Digital Input (DI) 12 alarm - Read/Write u32
48BFH mapping and level
48C0H Digital Input (DI) 13 alarm - Read/Write u32
48C1H mapping and level
48C2H Digital Input (DI) 14 alarm - Read/Write u32
48C3H mapping and level
48C4H Digital Input (DI) 15 alarm - Read/Write u32
48C5H mapping and level
48C6H Digital Input (DI) 16 alarm - Read/Write u32
48C7H mapping and level
48C8H Digital Input (DI) 17 alarm - Read/Write u32
48C9H mapping and level
48CAH Digital Input (DI) 18 alarm - Read/Write u32
48CBH mapping and level
48CCH Digital Input (DI) 19 alarm - Read/Write u32
48CDH mapping and level
48CEH Digital Input (DI) 20 alarm - Read/Write u32
48CFH mapping and level
48D0H Digital Input (DI) 21 alarm - Read/Write u32
48D1H mapping and level
48D2H Digital Input (DI) 22 alarm - Read/Write u32
48D3H mapping and level
48D4H Digital Input (DI) 23 alarm - Read/Write u32
48D5H mapping and level
48D6H Digital Input (DI) 24 alarm - Read/Write u32
48D7H mapping and level
48D8H Digital Input (DI) 25 alarm - Read/Write u32
48D9H mapping and level
Page 68 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
48DAH Digital Input (DI) 26 alarm - Read/Write u32
48DBH mapping and level
48DCH Digital Input (DI) 27 alarm - Read/Write u32
48DDH mapping and level
48DEH Digital Input (DI) 28 alarm - Read/Write u32
48DFH mapping and level
48E0H Fan 1 Failure - Read/Write u32
48E1H
48E2H Fan 2 Failure - Read/Write u32
48E3H
48E4H Fan 3 Failure - Read/Write u32
48E5H
48E6H Fan 4 Failure - Read/Write u32
48E7H
48E8H Batt Sampling Unit 1 Loss - Read/Write u32
48E9H alarm mapping and level
48EAH Batt Sampling Unit 2 Loss - Read/Write u32
48EBH alarm mapping and level
48ECH Batt Sampling Unit 3 Loss - Read/Write u32
48EDH alarm mapping and level
48EEH Batt Sampling Unit 4 Loss - Read/Write u32
48EFH alarm mapping and level
48F0H Batt Sampling Unit 5 Loss - Read/Write u32
48F1H alarm mapping and level
48F2H Batt Sampling Unit 6 Loss - Read/Write u32
48F3H alarm mapping and level
48F4H Batt Sampling Unit 7 Loss - Read/Write u32
48F5H alarm mapping and level
48F6H Batt Sampling Unit 8 Loss - Read/Write u32
48F7H alarm mapping and level
48F8H Batt Sampling Unit 1 Fault - Read/Write u32
48F9H alarm mapping and level
48FAH Batt Sampling Unit 2 Fault - Read/Write u32
48FBH alarm mapping and level
48FCH Batt Sampling Unit 3 Fault - Read/Write u32
48FDH alarm mapping and level
48FEH Batt Sampling Unit 4 Fault - Read/Write u32
48FFH alarm mapping and level
4900H Batt Sampling Unit 5 Fault - Read/Write u32
4901H alarm mapping and level
4902H Batt Sampling Unit 6 Fault - Read/Write u32
4903H alarm mapping and level
4904H Batt Sampling Unit 7 Fault - Read/Write u32
4905H alarm mapping and level
4906H Batt Sampling Unit 8 Fault - Read/Write u32
4907H alarm mapping and level
4908H AC Sampling Unit 1 Loss - Read/Write u32
4909H alarm mapping and level
490AH AC Sampling Unit 2 Loss - Read/Write u32
490BH alarm mapping and level
490CH AC Sampling Unit 1 Fault - Read/Write u32
490DH alarm mapping and level
Page 69 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
490EH AC Sampling Unit 2 Fault - Read/Write u32
490FH alarm mapping and level
4910H DC Sampling Unit 1 Loss - Read/Write u32
4911H alarm mapping and level
4912H DC Sampling Unit 2 Loss - Read/Write u32
4913H alarm mapping and level
4914H DC Sampling Unit 3 Loss - Read/Write u32
4915H alarm mapping and level
4916H DC Sampling Unit 4 Loss - Read/Write u32
4917H alarm mapping and level
4918H DC Sampling Unit 5 Loss - Read/Write u32
4919H alarm mapping and level
491AH DC Sampling Unit 1 Fault - Read/Write u32
491BH alarm mapping and level
491CH DC Sampling Unit 2 Fault - Read/Write u32
491DH alarm mapping and level
491EH DC Sampling Unit 3 Fault - Read/Write u32
491FH alarm mapping and level
4920H DC Sampling Unit 4 Fault - Read/Write u32
4921H alarm mapping and level
4922H DC Sampling Unit 5 Fault - Read/Write u32
4923H alarm mapping and level
4924H IO Expansion Unit 1 Loss - Read/Write u32
4925H alarm mapping and level
4926H IO Expansion Unit 2 Loss - Read/Write u32
4927H alarm mapping and level
4928H IO Expansion Unit 1 Fault - Read/Write u32
4929H alarm mapping and level
492AH IO Expansion Unit 2 Fault - Read/Write u32
492BH alarm mapping and level
492CH Generator 1 Start alarm - Read/Write u32
492DH mapping and level
492EH Generator 2 Start alarm - Read/Write u32
492FH mapping and level
4030H Generator 1 Fault alarm - Read/Write u32
4931H mapping and level
4932H Generator 2 Fault alarm - Read/Write u32
4933H mapping and level
4934H Fuel Level 1 Low alarm - Read/Write u32
4935H mapping and level
4936H Fuel Level 2 low alarm - Read/Write u32
4937H mapping and level
4938H DC Input High Voltage - Read/Write u32
4939H alarm mapping and level
493AH DC Input Low Voltage - Read/Write u32
493BH alarm mapping and level
493CH Rectifier Module Fault - Read/Write u32
493DH alarm mapping and level
493EH Rectifier Over Current - Read/Write u32
493FH alarm mapping and level
4940H Extended LVD3 disconnect - Read/Write u32
4941H alarm mapping and level
Page 70 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
4942H Extended LVD4 disconnect - Read/Write u32
4943H alarm mapping and level
4944H Extended LVD5 disconnect - Read/Write u32
4945H alarm mapping and level
4946H Extended LVD3 fault alarm - Read/Write u32
4947H mapping and level
4948H Extended LVD3 fault alarm - Read/Write u32
4949H mapping and level
494AH Extended LVD3 fault alarm - Read/Write u32
494BH mapping and level
494CH BMS 1 Lost - Read/Write u32
494DH
494EH BMS 2 Lost - Read/Write u32
494FH
4950H BMS 3 Lost - Read/Write u32
4951H
4952H BMS 4 Lost - Read/Write u32
4953H
4954H BMS 5 Lost - Read/Write u32
4955H
4956H BMS 6 Lost - Read/Write u32
4957H
4958H BMS 7 Lost - Read/Write u32
4959H
495AH BMS 8 Lost - Read/Write u32
495BH
495CH BMS 9 Lost - Read/Write u32
495DH
495EH BMS 10 Lost - Read/Write u32
495FH
4960H BMS 1 Fault - Read/Write u32
4961H
4962H BMS 2 Fault - Read/Write u32
4963H
4964H BMS 3 Fault - Read/Write u32
4965H
4966H BMS 4 Fault - Read/Write u32
4967H
4968H BMS 5 Fault - Read/Write u32
4969H
496AH BMS 6 Fault - Read/Write u32
496BH
496CH BMS 7 Fault - Read/Write u32
496DH
496EH BMS 8 Fault - Read/Write u32
496FH
4970H BMS 9 Fault - Read/Write u32
4971H
4972H BMS 10 Fault - Read/Write u32
4973H
4974H Reserved 7 - Read/Write u32
4975H
Page 71 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
4976H Reserved 8 - Read/Write u32
4977H
4978H Reserved 9 - Read/Write u32
4979H
497AH Reserved - Read/Write u32
497FH
4980H Reserved 10 - Read/Write u32
4981H
4982H- Reserved
4983H
Page 72 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
threshold
4B1BH Fan 4 high temp turn ON 0.01oC Read/Write s16
threshold
4B1CH Fan 4 start/stop difference 0.01oC Read/Write u16
4B1DH Fan 4 minimum ON time Sec Read/Write u16
4B1EH Fan 4 minimum fan speed % Read/Write u16
4B1FH Fan 4 alarm clears - Write 0x5A5A: clear alarm
4B20H Reserved
~ 4BFFH
Page 73 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
4C26H Rectifier S/No (low) - Read/Write u16 Position 20 Serial Number Setting
4C27H Rectifier S/No (high) - Read/Write u16
4C28H Rectifier S/No (low) - Read/Write u16 Position 21 Serial Number Setting
4C29H Rectifier S/No (high) - Read/Write u16
4C2AH Rectifier S/No (low) - Read/Write u16 Position 22 Serial Number Setting
4C2BH Rectifier S/No (high) - Read/Write u16
4C2CH Rectifier S/No (low) - Read/Write u16 Position 23 Serial Number Setting
4C2DH Rectifier S/No (high) - Read/Write u16
4C2EH Rectifier S/No (low) - Read/Write u16 Position 24 Serial Number Setting
4C2FH Rectifier S/No (high) - Read/Write u16
4C30H Rectifier S/No (low) - Read/Write u16 Position 25 Serial Number Setting
4C31H Rectifier S/No (high) - Read/Write u16
4C32H Rectifier S/No (low) - Read/Write u16 Position 26 Serial Number Setting
4C33H Rectifier S/No (high) - Read/Write u16
4C34H Rectifier S/No (low) - Read/Write u16 Position 27 Serial Number Setting
4C35H Rectifier S/No (high) - Read/Write u16
4C36H Rectifier S/No (low) - Read/Write u16 Position 28 Serial Number Setting
4C37H Rectifier S/No (high) - Read/Write u16
4C38H Rectifier S/No (low) - Read/Write u16 Position 29 Serial Number Setting
4C39H Rectifier S/No (high) - Read/Write u16
4C3AH Rectifier S/No (low) - Read/Write u16 Position 30 Serial Number Setting
4C3BH Rectifier S/No (high) - Read/Write u16
4C3CH Rectifier S/No (low) - Read/Write u16 Position 31 Serial Number Setting
4C3DH Rectifier S/No (high) - Read/Write u16
4C3EH Rectifier S/No (low) - Read/Write u16 Position 32 Serial Number Setting
4C3FH Rectifier S/No (high) - Read/Write u16
4C40H Rectifier S/No (low) - Read/Write u16 Position 33 Serial Number Setting
4C41H Rectifier S/No (high) - Read/Write u16
4C42H Rectifier S/No (low) - Read/Write u16 Position 34 Serial Number Setting
4C43H Rectifier S/No (high) - Read/Write u16
4C44H Rectifier S/No (low) - Read/Write u16 Position 35 Serial Number Setting
4C45H Rectifier S/No (high) - Read/Write u16
4C46H Rectifier S/No (low) - Read/Write u16 Position 36 Serial Number Setting
4C47H Rectifier S/No (high) - Read/Write u16
4C48H Rectifier S/No (low) - Read/Write u16 Position 37 Serial Number Setting
4C49H Rectifier S/No (high) - Read/Write u16
4C4AH Rectifier S/No (low) - Read/Write u16 Position 38 Serial Number Setting
4C4BH Rectifier S/No (high) - Read/Write u16
4C4CH Rectifier S/No (low) - Read/Write u16 Position 39 Serial Number Setting
4C4DH Rectifier S/No (high) - Read/Write u16
4C4EH Rectifier S/No (low) - Read/Write u16 Position 40 Serial Number Setting
4C4FH Rectifier S/No (high) - Read/Write u16
4C50H Reserved
~ 4FFFH
Page 74 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
6.14 Calibration Data
Register Description Unit Read/Write Type Remarks
5000H Temperature 1 calibration V Read/Write float Vref after Temperature 1
5001H parameter 1 (Vref) calibration
5002H Temperature 1 calibration V Read/Write float Vt after Temperature 1 calibration
5003H parameter 2 (Vt)
5004H Temperature 2 calibration V Read/Write float Vref after Temperature 2
5005H parameter 1 (Vref) calibration
5006H Temperature 2 calibration V Read/Write float Vt after Temperature 2 calibration
5007H parameter 2 (Vt)
5008H Bus Voltage calibration - Read/Write float Using float data type, the high
5009H parameter k subsection is transmitted first,
500AH Bus Voltage calibration - Read/Write float followed by the low byte
500BH parameter b
500CH Batt 1 midpoint voltage - Read/Write float
500DH calibration parameter k
500EH Batt 1 midpoint voltage - Read/Write float
500FH calibration parameter b
5010H Batt 2 midpoint voltage - Read/Write float
5011H calibration parameter k
5012H Batt 2 midpoint voltage - Read/Write float
5013H calibration parameter b
5014H Batt 3 midpoint voltage - Read/Write float
5015H calibration parameter k
5016H Batt 3 midpoint voltage - Read/Write float
5017H calibration parameter b
5018H Batt 4 midpoint voltage - Read/Write float
5019H calibration parameter k
501AH Batt 4 midpoint voltage - Read/Write float
501BH calibration parameter b
501CH Current 1 calibration - Read/Write float Using float data type, the high
501DH parameter k (+ve half) subsection is transmitted first,
501EH Current 1 calibration - Read/Write float followed by the low byte
501FH parameter b (+ve half)
5020H Current 1 calibration - Read/Write float
5021H parameter k (-ve half)
5022H Current 1 calibration - Read/Write float
5023H parameter b (-ve half)
5024H Current 2 calibration - Read/Write float
5025H parameter k (+ve half)
5026H Current 2 calibration - Read/Write float
5027H parameter b (+ve half)
5028H Current 2 calibration - Read/Write float
5029H parameter k (-ve half)
502AH Current 2 calibration - Read/Write float
502BH parameter b (-ve half)
502CH Batt Fuse 1 open voltage - Read/Write float Using float data type, the high
502DH calibration parameter k subsection is transmitted first,
502EH Batt Fuse 1 open voltage - Read/Write float followed by the low byte
502FH calibration parameter b
5030H Batt Fuse 2 open voltage - Read/Write float
Page 75 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
5031H calibration parameter k
5032H Batt Fuse 2 open voltage - Read/Write float
5033H calibration parameter b
5034H Batt Fuse 3 open voltage - Read/Write float
5035H calibration parameter k
5036H Batt Fuse 3 open voltage - Read/Write float
5037H calibration parameter b
5038H Batt Fuse 4 open voltage - Read/Write float
5039H calibration parameter k
503AH Batt Fuse 4 open voltage - Read/Write float
503BH calibration parameter b
503CH Batt Fuse 5 open voltage - Read/Write float
503DH calibration parameter k
503EH Batt Fuse 5 open voltage - Read/Write float
503FH calibration parameter b
5040H Batt Fuse 6 open voltage - Read/Write float
5041H calibration parameter k
5042H Batt Fuse 6 open voltage - Read/Write float
5043H calibration parameter b
5044H Batt Fuse 7 open voltage - Read/Write float
5045H calibration parameter k
5046H Batt Fuse 7 open voltage - Read/Write float
5047H calibration parameter b
5048H Batt Fuse 8 open voltage - Read/Write float
5049H calibration parameter k
504AH Batt Fuse 8 open voltage - Read/Write float
504BH calibration parameter b
504CH Reserved
~ 5FFFH
Page 76 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
600CH Master Alarm Timer Limit ms Read/Write u16
600DH AC Alarm Timer Limit ms Read/Write u16
600EH DC Alarm Timer Limit ms Read/Write u16
600FH Temp Alarm Timer Limit ms Read/Write u16
6010H LVD Alarm Timer Limit ms Read/Write u16
6011H ADC Alarm Timer Limit ms Read/Write u16
6012H DI Alarm Timer Limit ms Read/Write u16
6013H ALARM Alarm Timer Limit ms Read/Write u16
6014H REC Alarm Timer Limit ms Read/Write u16
6015H BAT Alarm Timer Limit ms Read/Write u16
6016H GEN Alarm Timer Limit ms Read/Write u16
6017H Batt Float to Equalize Sec Read/Write u16
Charge Confirm Time
6018H Battery Test Failed - Read/Write - Normal – 0; Failed – 1
6019H Module Comms Lost Reset - Read/Write - Not triggered – 0, Triggered – 1
601AH Data Log Clear - Read/Write - Not triggered – 0, Triggered – 1
601BH Event Log Clear - Read/Write - Not triggered – 0, Triggered – 1
601CH System Voltage Type - Read/Write - 1:48Vdc; 2:24Vdc
601DH LVD Extension Board - Read/Write - [0, 0, 3]
601EH ARM historical data Min Read/Write u16 [1, 10, 3600]
recording interval
601FH System Reset - Read/Write -
6020H Reserved
~ 603FH
Page 77 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
6054H Controller Sys Alias field 6 - Read/Write u16
6055H Controller Sys Alias field 7 - Read/Write u16
6056H Controller Sys Alias field 8 - Read/Write u16
6057H Controller Sys Alias field 9 - Read/Write u16
6058H Controller Sys Alias field 10 - Read/Write u16
6059H Controller Sys Alias field 11 - Read/Write u16
605AH Controller Sys Alias field 12 - Read/Write u16
605BH Controller Sys Alias field 13 - Read/Write u16
605CH Controller Sys Alias field 14 - Read/Write u16
605DH Controller Sys Alias field 15 - Read/Write u16
605EH Controller Sys Alias field 16 - Read/Write u16
605FH Installation Date - Read/Write u32
6060H
6061H Authorization Date - Read/Write u32
6062H
6063H Person-in-charge field 1 - Read/Write u16 Transfer the ASCII value of a
6064H Person-in-charge field 2 - Read/Write u16 character.
6065H Person-in-charge field 3 - Read/Write u16 Transfer the low byte, followed by
6066H Person-in-charge field 4 - Read/Write u16 the high byte
6067H Person-in-charge field 5 - Read/Write u16 Use in >Installation Information
6068H Person-in-charge field 6 - Read/Write u16 → Service Engineer
6069H Remark 1 field 1 - Read/Write u16 Transfer the ASCII value of a
606AH Remark 1 field 2 - Read/Write u16 character.
606BH Remark 1 field 3 - Read/Write u16 Transfer the low byte, followed by
606CH Remark 1 field 4 - Read/Write u16 the high byte
606DH Remark 1 field 5 - Read/Write u16 Use in >Installation Information
606EH Remark 1 field 6 - Read/Write u16 → Remarks
606FH Remark 1 field 7 - Read/Write u16
6070H Remark1 field 8 - Read/Write u16
6071H Remark 1 field 9 - Read/Write u16
6072H Remark 1 field 10 - Read/Write u16
6073H Remark 1 field 11 - Read/Write u16
6074H Remark 1 field 12 - Read/Write u16
6075H Remark 1 field 13 - Read/Write u16
6076H Remark 1 field 14 - Read/Write u16
6077H Remark 1 field 15 - Read/Write u16
6078H Remark 1 field 16 - Read/Write u16
6079H Remark 1 field 17 - Read/Write u16
607AH Remark 1 field 18 - Read/Write u16
607BH Remark 1 field 19 - Read/Write u16
607CH Remark 1 field 20 - Read/Write u16
607DH Remark 1 field 21 - Read/Write u16
607EH Remark 1 field 22 - Read/Write u16
607FH Remark 1 field 23 - Read/Write u16
6080H Remark 1 field 24 - Read/Write u16
6081H Remark 1 field 25 - Read/Write u16
6082H Remark 1 field 26 - Read/Write u16
6083H Remark 1 field 27 - Read/Write u16
6084H Remark 1 field 28 - Read/Write u16
6085H Remark 1 field 29 - Read/Write u16
6086H Remark 1 field 30 - Read/Write u16
6087H Remark 1 field 31 - Read/Write u16
Page 78 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
6088H Remark 1 field 32 - Read/Write u16
6089H Remark 2 field 1 - Read/Write u16 Transfer the ASCII value of a
608AH Remark 2 field 2 - Read/Write u16 character.
608BH Remark 2 field 3 - Read/Write u16 Transfer the low byte, followed by
608CH Remark 2 field 4 - Read/Write u16 the high byte
608DH Remark 2 field 5 - Read/Write u16 Use in >Installation Information
608EH Remark 2 field 6 - Read/Write u16 → Remarks
608FH Remark 2 field 7 - Read/Write u16
6090H Remark 2 field 8 - Read/Write u16
6091H Remark 2 field 9 - Read/Write u16
6092H Remark 2 field 10 - Read/Write u16
6093H Remark 2 field 11 - Read/Write u16
6094H Remark 2 field 12 - Read/Write u16
6095H Remark 2 field 13 - Read/Write u16
6096H Remark 2 field 14 - Read/Write u16
6097H Remark 2 field 15 - Read/Write u16
6098H Remark 2 field 16 - Read/Write u16
6099H Remark 2 field 17 - Read/Write u16
609AH Remark 2 field 18 - Read/Write u16
609BH Remark 2 field 19 - Read/Write u16
609CH Remark 2 field 20 - Read/Write u16
609DH Remark 2 field 21 - Read/Write u16
609EH Remark 2 field 22 - Read/Write u16
609FH Remark 2 field 23 - Read/Write u16
60A0H Remark 2 field 24 - Read/Write u16
60A1H Remark 2 field 25 - Read/Write u16
60A2H Remark 2 field 26 - Read/Write u16
60A3H Remark 2 field 27 - Read/Write u16
60A4H Remark 2 field 28 - Read/Write u16
60A5H Remark 2 field 29 - Read/Write u16
60A6H Remark 2 field 30 - Read/Write u16
60A7H Remark 2 field 31 - Read/Write u16
60A8H Remark 2 field 32 - Read/Write u16
60A9H Remark 3 field 1 - Read/Write u16 Transfer the ASCII value of a
60AAH Remark 3 field 2 - Read/Write u16 character.
60ABH Remark 3 field 3 - Read/Write u16 Transfer the low byte, followed by
60ACH Remark 3 field 4 - Read/Write u16 the high byte
60ADH Remark 3 field 5 - Read/Write u16 Use in >Installation Information
60AEH Remark 3 field 6 - Read/Write u16 → Remarks
60AFH Remark 3 field 7 - Read/Write u16
60B0H Remark 3 field 8 - Read/Write u16
60B1H Remark 3 field 9 - Read/Write u16
60B2H Remark 3 field 10 - Read/Write u16
60B3H Remark 3 field 11 - Read/Write u16
60B4H Remark 3 field 12 - Read/Write u16
60B5H Remark 3 field 13 - Read/Write u16
60B6H Remark 3 field 14 - Read/Write u16
60B7H Remark 3 field 15 - Read/Write u16
60B8H Remark 3 field 16 - Read/Write u16
60B9H Remark 3 field 17 - Read/Write u16
60BAH Remark 3 field 18 - Read/Write u16
60BBH Remark 3 field 19 - Read/Write u16
Page 79 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
60BCH Remark 3 field 20 - Read/Write u16
60BDH Remark 3 field 21 - Read/Write u16
60BEH Remark 3 field 22 - Read/Write u16
60BFH Remark 3 field 23 - Read/Write u16
60C0H Remark 3 field 24 - Read/Write u16
60C1H Remark 3 field 25 - Read/Write u16
60C2H Remark 3 field 26 - Read/Write u16
60C3H Remark 3 field 27 - Read/Write u16
60C4H Remark 3 field 28 - Read/Write u16
60C5H Remark 3 field 29 - Read/Write u16
60C6H Remark 3 field 30 - Read/Write u16
60C7H Remark 3 field 31 - Read/Write u16
60C8H Remark 3 field 32 - Read/Write u16
60C9H Remark 4 field 1 (GPS) - Read/Write u16 0:S, 1:N
60CAH Remark 4 field 2 (GPS) - Read/Write u16 xxxxo
60CBH Remark 4 field 3 (GPS) - Read/Write u16 xxxx'
60CCH Remark 4 field 4 (GPS) - Read/Write u16 0:W, 1:E
60CDH Remark 4 field 5 (GPS) - Read/Write u16 xxxxo
60CEH Remark 4 field 6 (GPS) - Read/Write u16 xxxx'
60CFH Remark 4 field 7 (boot - Read Only u16 Bootloader version number
loader version number
6OD0H Remark 4 field 8 (reserve) - Read/Write u16
60D1H Remark 4 field 9 (reserve) - Read/Write u16
60D2H Remark 4 field 10 (reserve) - Read/Write u16
60D3H Remark 4 field 11 (reserve) - Read/Write u16
60D4H Remark 4 field 12 (reserve) - Read/Write u16
60D5H Remark 4 field 13 (reserve) - Read/Write u16
60D6H Remark 4 field 14 (reserve) - Read/Write u16
60D7H Remark 4 field 15 (reserve) - Read/Write u16
60D8H Remark 4 field 16 (reserve) - Read/Write u16
60D9H Remark 4 field 17 (reserve) - Read/Write u16
60DAH Remark 4 field 18 (reserve) - Read/Write u16
60DBH Remark 4 field 19 (reserve) - Read/Write u16
60DCH Remark 4 field 20 (reserve) - Read/Write u16
60DDH Remark 4 field 21 (reserve) - Read/Write u16
60DEH Remark 4 field 22 (reserve) - Read/Write u16
60DFH Remark 4 field 23 (reserve) - Read/Write u16
60E0H Remark 4 field 24 (reserve) - Read/Write u16
60E1H Remark 4 field 25 (reserve) - Read/Write u16
60E2H Remark 4 field 26 (reserve) - Read/Write u16
60E3H Remark 4 field 27 (reserve) - Read/Write u16
60E4H Remark 4 field 28 (reserve) - Read/Write u16
60E5H Remark 4 field 29 (reserve) - Read/Write u16
60E6H Remark 4 field 30 (reserve) - Read/Write u16
60E7H Remark 4 field 31 (reserve) - Read/Write u16
60E8H Remark 4 field 32 (reserve) - Read/Write u16
60E9H ~ Reserved
60FFH
6100H Customer Name field 1 - Read/Write u16 Transfer the ASCII value of a
6101H Customer Name field 2 - Read/Write u16 character.
6102H Customer Name field 3 - Read/Write u16 Transfer the low byte, followed by
6103H Customer Name field 4 - Read/Write u16 the high byte
Page 80 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
6104H Customer Name field 5 - Read/Write u16 Use in >System Information →
6105H Customer Name field 6 - Read/Write u16 Customer Name
6106H System S/No field 1 - Read/Write u16 Transfer the ASCII value of a
6107H System S/No field 2 - Read/Write u16 character.
6108H System S/No field 3 - Read/Write u16 Transfer the low byte, followed by
6109H System S/No field 4 - Read/Write u16 the high byte
610AH System S/No field 5 - Read/Write u16 Use in >System Information →
610BH System S/No field 6 - Read/Write u16 Serial Number
610CH System ID field 1 - Read/Write u16 Transfer the ASCII value of a
610DH System ID field 2 - Read/Write u16 character.
610EH System ID field 3 - Read/Write u16 Transfer the low byte, followed by
610FH System ID field 4 - Read/Write u16 the high byte
6110H System ID field 5 - Read/Write u16 Use in >System Information →
6111H System ID field 6 - Read/Write u16 Model
6112H System ID field 7 - Read/Write u16
6113H System ID field 8 - Read/Write u16
6114H System Site ID field 1 - Read/Write u16 Transfer the ASCII value of a
6115H System Site ID field 2 - Read/Write u16 character.
6116H System Site ID field 3 - Read/Write u16 Transfer the low byte, followed by
6117H System Site ID field 4 - Read/Write u16 the high byte
6118H System Site ID field 5 - Read/Write u16 Use in >System Information →
6119H System Site ID field 6 - Read/Write u16 Site ID
611AH System Site ID field 7 - Read/Write u16
611BH System Site ID field 8 - Read/Write u16
611CH System Site ID field 9 - Read/Write u16
611DH System Site ID field 10 - Read/Write u16
611EH System Site ID field 11 - Read/Write u16
611FH System Site ID field 12 - Read/Write u16
6120H System Site ID field 13 - Read/Write u16
6121H System Site ID field 14 - Read/Write u16
6122H System Site ID field 15 - Read/Write u16
6123H System Site ID field 16 - Read/Write u16
6124H Reserved
~ 61FFH
Page 81 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
630AH Low Charge Current Stop 0.01A Read/Write u16 [100, 100, 2000]
630BH Low Voltage Start Enable - Read/Write u16 Enable [0x14]; Disable [0x15]
630CH Voltage Start 0.01V Read/Write u16 [4000, 4800, 5800]
630DH Charging Duration hour Read/Write u16 [1, 12, 24]
630EH Daily Setup Enable - Read/Write u16 Enable [0x14]; Disable [0x15]
630FH Daily Charge Start Monday - Read/Write u16 The high byte is hour (0,23) and
6310H Daily Charge Start Tuesday - Read/Write u16 the low byte is minute (0,59).
6311H Daily Charge Start - Read/Write u16 Example: 09:30 --- 0x091e
Wednesday
6312H Daily Charge Start - Read/Write u16
Thursday
6313H Daily Charge Start Friday - Read/Write u16
6314H Daily Charge Start Saturday - Read/Write u16
6315H Daily Charge Start Sunday - Read/Write u16
6316H Daily Charge Stop Monday - Read/Write u16
6317H Daily Charge Stop Tuesday - Read/Write u16
6318H Daily Charge Stop - Read/Write u16
Wednesday
6319H Daily Charge Stop - Read/Write u16
Thursday
631AH Daily Charge Stop Friday - Read/Write u16
631BH Daily Charge Stop Saturday - Read/Write u16
631CH Daily Charge Stop Sunday - Read/Write u16
631DH Daily Charge Genset - Read/Write u16 [0,0,2]
Selection Monday bit0 - Genset 1 Start
631EH Daily Charge Genset - Read/Write u16 bit1 - Genset 2 Start
Selection Tuesday
631FH Daily Charge Genset - Read/Write u16
Selection Wednesday
6320H Daily Charge Genset - Read/Write u16
Selection Thursday
6321H Daily Charge Genset - Read/Write u16
Selection Friday
6322H Daily Charge Genset - Read/Write u16
Selection Saturday
6323H Daily Charge Genset - Read/Write u16
Selection Sunday
6324H Monthly Setup Enable - Read/Write u16 Enable [0x14]; Disable [0x15]
6325H Monthly Start Schedule 1 - Read/Write u16 The high byte is hour (0,23) and
6326H Monthly Start Schedule 2 - Read/Write u16 the low byte is minute (0,59).
Example: 09:30 --- 0x091e
6327H Monthly Start Day 1 - Read/Write u16 [1, 31]
6328H Monthly Start Day 2 - Read/Write u16 [1, 31]
6329H Monthly Start Genset - Read/Write u16 [0,0,2]
Selection 1 bit0 - Genset 1 Start
632AH Monthly Start Genset - Read/Write u16 bit1 - Genset 2 Start
Selection 2
632BH Genset Input Option - Read/Write u16 [1, 2] 1-AC+GEN; 2-GEN
632CH Solar Module Offset 0.01V Read/Write u16 [0, 10, 100]
Voltage
632DH Manual Genset Start - Read/Write u16 0-No action; 1-Start Genset;
2-Stop Genset
632EH Reserved
Page 82 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
632FH
6330H Erase Log Trigger - Read/Write u16 0-not triggered; 1-triggered
6331H Number of Fuel Tank - Read/Write u16
6332H Fuel Tank 1 Total Capacity - Read/Write u16
6333H Fuel Tank 2 Total Capacity - Read/Write u16
6334H Fuel Tank 1 Sensor Offset - Read/Write u16
6335H Fuel Tank 2 Sensor Offset - Read/Write u16
6336H Fuel Tank 1 Level Indicator cm Read/Write u16
6337H Fuel Tank 2 Level Indicator cm Read/Write u16
6338H Fuel Tank 1 Data (Field 1) - Read/Write u16 Description Data
6339H Fuel Tank 1 Data (Field 2) - Read/Write u16 - To transmit the ASCII
633AH Fuel Tank 1 Data (Field 3) - Read/Write u16 value of a character, the
633BH Fuel Tank 1 Data (Field 4) - Read/Write u16 low byte is transmitted
633CH Fuel Tank 1 Data (Field 5) - Read/Write u16 first, then followed by the
633DH Fuel Tank 1 Data (Field 6) - Read/Write u16 transmission of the high
633EH Fuel Tank 1 Data (Field 7) - Read/Write u16 byte.
633FH Fuel Tank 1 Data (Field 8) - Read/Write u16
6340H Fuel Tank 1 Data (Field 9) - Read/Write u16
6341H Fuel Tank 1 Data (Field 10) - Read/Write u16
6342H Fuel Tank 1 Data (Field 11) - Read/Write u16
6343H Fuel Tank 1 Data (Field 12) - Read/Write u16
6344H Fuel Tank 1 Data (Field 13) - Read/Write u16
6345H Fuel Tank 1 Data (Field 14) - Read/Write u16
6346H Fuel Tank 1 Data (Field 15) - Read/Write u16
6347H Fuel Tank 1 Data (Field 16) - Read/Write u16
6348H Fuel Tank 2 Data (Field 1) - Read/Write u16 Description Data
6349H Fuel Tank 2 Data (Field 2) - Read/Write u16 To transmit the ASCII value of a
634AH Fuel Tank 2 Data (Field 3) - Read/Write u16 character, the low byte is
634BH Fuel Tank 2 Data (Field 4) - Read/Write u16 transmitted first, then followed by
634CH Fuel Tank 2 Data (Field 5) - Read/Write u16 the transmission of the high byte.
634DH Fuel Tank 2 Data (Field 6) - Read/Write u16
634EH Fuel Tank 2 Data (Field 7) - Read/Write u16
634FH Fuel Tank 2 Data (Field 8) - Read/Write u16
6350H Fuel Tank 2 Data (Field 9) - Read/Write u16
6351H Fuel Tank 2 Data (Field 10) - Read/Write u16
6352H Fuel Tank 2 Data (Field 11) - Read/Write u16
6353H Fuel Tank 2 Data (Field 12) - Read/Write u16
6354H Fuel Tank 2 Data (Field 13) - Read/Write u16
6355H Fuel Tank 2 Data (Field 14) - Read/Write u16
6356H Fuel Tank 2 Data (Field 15) - Read/Write u16
6357H Fuel Tank 2 Data (Field 16) - Read/Write u16
6358H Fuel 1 Sensor - Read/Write u16 [0-none, 1-IO1.1, 2-IO1.2, 3-IO2.1,
4-IO2.2]
6359H Fuel 2 Sensor - Read/Write u16 [0-none, 1-IO1.1, 2-IO1.2, 3-IO2.1,
4-IO2.2]
635AH Fuel 1 Table (Row 1) - Read/Write u16
… … - Read/Write u16
636EH Fuel 1 Table (Row 21) - Read/Write u16
636FH Fuel 2 Table (Row 1) - Read/Write u16
… … - Read/Write u16
6383H Fuel 2 Table (Row 21) - Read/Write u16
6384H Fuel 1 Low Alarm 1% Read/Write u16 [1, 30, 100]
Page 83 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
6385H Fuel 2 Low Alarm 1% Read/Write u16 [1, 30, 100]
6386H Reserved
~ 63FFH
Page 84 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
6428H Electricity Cost Period 15 0.001 Read/Write u16
6249H Electricity Cost Period 16 0.001 Read/Write u16
642AH Electricity Cost Period 17 0.001 Read/Write u16
642BH Electricity Cost Period 18 0.001 Read/Write u16
642CH Electricity Cost Period 19 0.001 Read/Write u16
642DH Electricity Cost Period 20 0.001 Read/Write u16
642EH Electricity Cost Period 21 0.001 Read/Write u16
642FH Electricity Cost Period 22 0.001 Read/Write u16
6430H Electricity Cost Period 23 0.001 Read/Write u16
6431H Electricity Cost Period 24 0.001 Read/Write u16
6432H Peak Shaving Manual Start - Read/Write u16 0- No action; 1- Start, 2- Stop
6433H Reserved
643FH
Page 85 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
6.22 Test Mode Data
Register Description Unit Read/Write Type Remarks
9100H Test Mode - Read/Write u16 Normal program [0x00]
Test program [0x01]
9101H Red LED - Read/Write u16 Trigger [0x01]; Off [0x00]
9102H Yellow LED - Read/Write u16 Trigger [0x01]; Off [0x00]
9103H Green LED - Read/Write u16 Trigger [0x01]; Off [0x00]
9104H Buzzer - Read/Write u16 Trigger [0x01]; Off [0x00]
9105H Test Communication Count - Read u32
9106H USART 1 Sent
9107H Test Communication Count - Read u32
9108H USART 1 Receive
9109H Test Communication Count - Read u32
910AH USART 2 Sent
910BH Test Communication Count - Read u32
910CH USART 2 Receive
910DH Test Communication Count - Read u32
910EH CAN Sent
910FH Test Communication Count - Read u32
9110H CAN Receive
Page 86 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)
Enetek Power Group Pte Ltd
Page 87 Copyright Enetek Power Group Pte Ltd REV 2.2 (G)