Protection and Coordination Study - ETAP
Protection and Coordination Study - ETAP
Study
Introduction to Basic
Overcurrent Protection and
Coordination Study
Zones of Protection
Protective devices are selected and assigned to protect a specific part of
the power system. These part, known as the primary zone of protection, is
the responsibility of the protective device.
While each zone is bounded by the location of the circuit breakers, the
fault detection is dependent on the location of the current transformers
(CTs). The location of the CTs is purposely identified in order to have
overlapping zones. This is shown in the following figures.
Primary and Backup Protection
The overlapping of zones allows a protective device to provide backup
protection to the adjacent zone, also referred to as the backup or
overreached zone. Protective devices operate as fast as possible within
their primary zone of protection while a delayed operation is expected in
the backup zone. This is intentional in order to allow the protective
devices to operate first in their primary zone of protection. Backup
protection is intended to operate only when the primary protection fails to
clear the fault.
In figure 1, the relay A at Bus A primary zone of protection is the line AB,
while its backup zone is the line BC.
Local Backup
A protective device at the same location as the primary protection device
is referred to as local backup. The local backup protection is commonly
fed from a different CT core but operates the same circuit breaker. It
provides a degree of backup against failure DC supply and tripping circuit
failure. However, local backups DO NOT PROVIDE backup against circuit
breaker failure.
Remote Backup
A remote backup protection is located at the adjacent upstream zone of
protection. This backup protection effectively protect against circuit
breaker failure but results otherwise to a wider area of service
interruption.
Figure 5. Remote Backup
Objective of Overcurrent
Coordination
The objective of every protection coordination study is to determine the
characteristics, ratings and settings of OC relays in the system under
study such that after a fault or overload
Short-circuit Currents
½ Cycle 1.5 to 4 Cycles > 30 Cycles
You may want to check out these topics on short-circuit study and circuit
breaker sizing.
Delta-Wye Transformers
Delta-Wye transformers are of great interest when doing a protection
coordination study. Consider for example the figure below. For simplicity,
let us consider a 1:1 transformer. Take note that by setting a 1:1 ratio, the
winding ratio of a delta-wye transformer will be √3:1.
Figure 7. Currents
in a Phase-to-Phase Fault
Fig
ure 8. Phase-to-Phase Fault in terms of the 3-Phase Fault
For a phase-to-phase fault on the wye side of the transformer, the per-unit
secondary line current is approximately equal to 86.6% of the current
magnitude resulting from a three-phase fault. However, on the delta side
of the transformer, the per-unit primary line current magnitude in one
phase reaches a value approximately equal to the three-phase fault
current.
Reliability
and
Selectivity
This the measure of how well the protection system limits service
interruptions by isolating the smallest portion of the affected area. This is
to ensure a very high level of continuity of service.
Speed of Operation
In order to preserve system stability and limit the damage caused by
short circuits, the protection system should isolate the faulted areas as
fast a possible.
Simplicity
Sensitivity
Economics
Normal State
In a normal state, the system is operating within the designed limits and
maximum equipment life expectancy is anticipated.
Abnormal State
An abnormal state is when the system operates outside the designed
limits for short periods that may accelerate equipment aging.
Faulted State
A faulted state is when the system is subjected to severe stress and
where equipment failure is very likely. It may be caused by natural
events, accidents, deterioration of insulation, and other causes that are
impossible or impractical to avoid. Moreover, it can be distinguished
generally by a sudden and significant increase in current. It is because of
this high current that the system is subjected to high levels of stress given
that mechanical and thermal stress are functions of the square of the
current.
Current
Voltage
Power Factor
Power Flow
Impedance
Frequency
Temperature
Pressure
Mechanical movements
Protective Relaying
The IEEE defines a protective relay as
Protective Devices
The following are the most common protective devices on many power
systems around the world.
Fuses
Automatic reclosers
Sectionalizers
Circuit breakers
Protective relays
Protective
Regulating
Reclosing and synchronism check
Monitoring
Auxiliary
1 - Master Element
2 - Time-delay Starting or Closing Relay
3 - Checking or Interlocking Relay, complete Sequence
4 - Master Protective
5 - Stopping Device, Emergency Stop Switch
6 - Starting Circuit Breaker
7 - Rate of Change Relay
8 - Control Power Disconnecting Device
9 - Reversing Device
10 - Unit Sequence Switch
11 - Multifunction Device
12 - Overspeed Device
13 - Synchronous-Speed Device
14 - Underspeed Device
15 - Speed or Frequency Matching Device
16 - Data Communications Device
17 - Shunting or Discharge Switch
18 - Accelerating or Decelerating Device
19 - Starting-to-Running Transition Contactor
20 - Electrically-Operated Valve ( Solenoid Valve )
21 - Distance Relay
21G - Ground Distance
21P - Phase Distance
22 – Equalizer circuit breaker
23 – Temperature control device, Heater
24 – Volts per hertz relay
25 – Synchronizing or synchronism-check device
26 – Apparatus thermal device, Temperature Switch
27 – Undervoltage relay
27P - Phase Undervoltage
27S - DC undervoltage relay
27TN - Third Harmonic Neutral Undervoltage
27TN/59N - 100% Stator Earth Fault
27X - Auxiliary Undervoltage
27 AUX - Undervoltage Auxiliary Input
27/27X - Bus/Line Undervoltage
27/50 - Accidental Generator Energization
28 - Flame Detector
29 - Isolating Contactor
30 - Annunciator Relay
31 - Separate Excitation Device
32 - Directional Power Relay
32L - Low Forward Power
32H - High Directional Power
32N - Wattmetric Zero-Sequence Directional
32P - Directional Power
32R - Reverse Power
33 - Position Switch
34 - Master Sequence Device
35 - Brush-Operating or Slip-ring Short Circuiting Device
36 - Polarity or Polarizing Voltage Device
37 - Undercurrent or Underpower Relay
37P - Underpower
38 - Bearing Protective Device / Bearing Rtd
39 - Mechanical Condition Monitor ( Vibration )
40 - Field Relay / Loss of Excitation
41 - Field Circuit Breaker
42 - Running Circuit Breaker
43 - Manual Transfer or Selector Device
44 - Unit Sequence Starting Relay
45 - Fire Detector
46 - Reverse-Phase or Phase Balance Current Relay or Stator
Current Unbalance
47 - Phase-Sequence or Phase Balance Voltage Relay
48 - Incomplete Sequence Relay / Blocked Rotor
49 - Machine or Transformer Thermal Relay / Thermal Overload
49RTD - RTD Biased Thermal Overload
50 - Instantaneous Overcurrent Relay
50BF - Breaker Failure
50DD - Current Disturbance Detector
50EF - End Fault Protection
50G - Ground Instantaneous Overcurrent
50IG - Isolated Ground Instantaneous Overcurrent
50LR - Acceleration Time
50N - Neutral Instantaneous Overcurrent
50NBF - Neutral Instantaneous Breaker Failure
50P - Phase Instantaneous Overcurrent
50SG - Sensitive Ground Instantaneous Overcurrent
50SP - Split Phase Instantaneous Current
50Q - Negative Sequence Instantaneous Overcurrent
50/27 - Accidental Energization
50/51 - Instantaneous / Time-delay Overcurrent relay
50Ns/51Ns - Sensitive earth-fault protection
50/74 - Ct Trouble
50/87 - Instantaneous Differential
51 - AC Time Overcurrent Relay
51G - Ground Time Overcurrent
51LR - AC inverse time overcurrent (locked rotor) protection
relay
51N - Neutral Time Overcurrent
51P - Phase Time Overcurrent
51R - Locked / Stalled Rotor
51V - Voltage Restrained Time Overcurrent
51Q - Negative Sequence Time Overcurrent
52 – AC circuit breaker
52a - AC circuit breaker position (contact open when circuit
breaker open)
52b - AC circuit breaker position (contact closed when circuit
breaker open)
53 - Exciter or Dc Generator Relay
54 - Turning Gear Engaging Device
55 - Power Factor Relay
56 - Field Application Relay
57 - Short-Circuiting or Grounding Device
58 - Rectification Failure Relay
59 - Overvoltage Relay
59B - Bank Phase Overvoltage
59P - Phase Overvoltage
59N - Neutral Overvoltage
59NU - Neutral Voltage Unbalance
59P - Phase Overvoltage
59X - Auxiliary Overvoltage
59Q - Negative Sequence Overvoltage
60 - Voltage or Current Balance Relay
60N - Neutral Current Unbalance
60P - Phase Current Unbalance
61 - Density Switch or Sensor
62 - Time-Delay Stopping or Opening Relay
63 - Pressure Switch Detector
64 - Ground Protective Relay
64F - Field Ground Protection
64R – Rotor earth fault
64REF – Restricted earth fault differential
64S – Stator earth fault
64S - Sub-harmonic Stator Ground Protection
64TN - 100% Stator Ground
65 - Governor
66 - Notching or Jogging Device/Maximum Starting Rate/Starts Per
Hour/Time Between Starts
67 - AC Directional Overcurrent Relay
67G - Ground Directional Overcurrent
67N - Neutral Directional Overcurrent
67Ns – Earth fault directional
67P - Phase Directional Overcurrent
67SG - Sensitive Ground Directional Overcurrent
67Q - Negative Sequence Directional Overcurrent
68 - Blocking Relay / Power Swing Blocking
69 - Permissive Control Device
70 - Rheostat
71 - Liquid Switch, Level Switch
72 - DC Circuit Breaker
73 - Load-Resistor Contactor
74 - Alarm Relay
75 - Position Changing Mechanism
76 - DC Overcurrent Relay
77 - Telemetering Device, Speed Sensor
78 - Phase Angle Measuring or Out-of-Step Protective Relay
78V - Loss of Mains
79 - AC Reclosing Relay / Auto Reclose
80 - Liquid or Gas Flow Relay
81 - Frequency Relay
81O - Over Frequency
81R - Rate-of-Change Frequency
81U - Under Frequency
82 - DC Reclosing Relay
83 - Automatic Selective Control or Transfer Relay
84 - Operating Mechanism
85 - Pilot Communications, Carrier or Pilot-Wire Relay
86 - Lock-Out Relay, Master Trip Relay
87 - Differential Protective Relay
87B - Bus Differential
87G - Generator Differential
87GT - Generator/Transformer Differential
87L - Segregated Line Current Differential
87LG - Ground Line Current Differential
87M - Motor Differential
87O - Overall Differential
87PC - Phase Comparison
87RGF - Restricted Ground Fault
87S - Stator Differential
87S - Percent Differential
87T - Transformer Differential
87V - Voltage Differential
88 - Auxiliary Motor or Motor Generator
89 - Line Switch
90 - Regulating Device
91 - Voltage Directional Relay
92 - Voltage And Power Directional Relay
93 - Field-Changing Contactor
94 - Tripping or Trip-Free Relay
95 – For specific applications where other numbers are not
suitable
96 – Transmitter
97 – For specific applications where other numbers are not
suitable
98 – For specific applications where other numbers are not
suitable
99 – For specific applications where other numbers are not
suitable
Acronyms Description
Suffixes Description
_1 - Positive-Sequence
_2 - Negative-Sequence
A - Alarm, Auxiliary Power
AC - Alternating Current
AN - Anode
B - Bus, Battery, or Blower
BF - Breaker Failure
BK - Brake
BL - Block (Valve)
BP - Bypass
BT - Bus Tie
BU - Backup
C - Capacitor, Condenser, Compensator, Carrier Current, Case or
Compressor
CA - Cathode
CH - Check (Valve)
D - Discharge (Valve)
DC - Direct Current
DCB - Directional Comparison Blocking
DCUB - Directional Comparison Unblocking
DD - Disturbance Detector
DUTT - Direct Underreaching Transfer Trip
E - Exciter
F - Feeder, Field, Filament, Filter, or Fan
G - Ground or Generator
GC - Ground Check
H - Heater or Housing
L - Line or Logic
M - Motor or Metering
MOC - Mechanism Operated Contact
N - Neutral or Network
O - Over
P - Phase or Pump
PC - Phase Comparison
POTT - Pott: Permissive Overreaching Transfer Trip
PUTT - Putt: Permissive Underreaching Transfer Trip
R - Reactor, Rectifier, or Room
S - Synchronizing, Secondary, Strainer, Sump, or Suction (Valve)
SOTF - Switch On To Fault
T - Transformer or Thyratron
TD - Time Delay
TDC - Time-Delay Closing Contact
TDDO - Time Delayed Relay Coil Drop-Out
TDO - Time-Delay Opening Contact
TDPU - Time Delayed Relay Coil Pickup
THD - Total Harmonic Distortion
TH - Transformer (High-Voltage Side)
TL - Transformer (Low-Voltage Side)
TM - Telemeter
TT - Transformer (Tertiary-Voltage Side)
Q - Lube Oil
W - Water
F - Fuel
G - Gas
U - Under or Unit
X - Auxiliary
Z - Impedance
Overcurrent Protection Devices
and their Time Current Curves
Delta-Wye Transformers
Fuses
Switching Devices
Relays
Fuses
Fuses are essentially made up of a metal wire or strip that melts when
excessive currents flow through. Being such, fuses operate on a
continuous-ampere rating. Low-voltage power fuses can withstand 110%
of their rating under controlled conditions. while medium- and high-
voltage power fuses can withstand currents below 200% of their nominal
rating. Low-level overcurrent takes a long time interval to melt the fuse
while large overcurrent levels tend to melt fuses very quickly. A typical
fuse time-current curve is shown below.
Figure 3.
Fuse Time Current Curve
minimum melting time – the time when the metal strip starts to melt,
and
maximum clearing time – when the strip completely breaks and the
arc fully extinguished.
The difference between these is referred to as the arcing time.
Overcurrent coordination with fuses is a little tricky, especially for a
remote backup fuse. The primary device which can be another fuse should
clear the fault before the minimum melting time of the remote backup
fuse. In other words, for fuse-to-fuse coordination, the maximum clearing
time of the primary fuse (also referred to as the downstream fuse or
the protecting fuse) should be lesser than the minimum melting time of
the remote backup fuse (also referred to as the upstream fuse or
the protected fuse). In most applications, the rating of the upstream
fuse is approximately twice that of the downstream fuse.
Figure 4. Primary and Backup Fuse
Advantages
Simple
Very fast
Little or no maintenance
Disadvantages
Difficult coordination
Single phasing
Fixed characteristic
Switching Devices
Switching devices are another basic category for overcurrent protection
devices. Miniature Circuit Breakers (MCBs), Molded Case Circuit Breakers
(MCCB), Air Circuit Breakers (ACB) fall into this category and are usually
used in low voltage applications.
MCCB
Like fuses, switching devices detects and clears fault but do not need
replacement after every fault clearance. The fault interruption is done
using an integrated trip device. The trip action may be done mechanically
using spring charge or compressed air to separate the contacts, or using
the energy of the fault current to separate the contacts through thermal
expansion or magnetic field.
Trip Device
The trip devices for low voltage circuit breakers are the following:
Thermal Magnetic
Electro-mechanical or Solid-State
Relays
Relays detect and isolate faults indirectly. Unlike fuses and switching
devices, relays require CT and PT input to detect the fault, and a circuit
breaker in order to isolate it. Relays have different functions and use
currents, voltages, or their combination (impedance) to identify a fault.
Basic overcurrent functions such an instantaneous overcurrent (50) and
time-overcurrent (51) are usually common.
Instantaneous Overcurrent Relays (50)
These relays operate instantaneously when the current exceeds the pick-
up value and reset with no intentional time delay. Most instantaneous
overcurrent relays operate on minimum operating time.
Figur
e 9. Inverse Definite Minimum Time Current Curve
ANSI and IEC Standard Curves
There are different characteristic curves available for Inverse Definite
Minimum Time (IDMT) overcurrent relays.
where
ANSI standard curves are provided with a disk emulating reset timer
described by the following general equation
where
The ANSI standard curve constants are defined in the table below.
TCC Type A B D p
where
Overcurrent protection is often the simplest and cheapest to employ but in most
cases, its application tends to be difficult. While the primary objective of power
system protection is to isolate faults as quickly possible, limiting service
interruptions to a minimum cannot be discounted. Effective overcurrent
protection is carried out through an overcurrent coordination study, and with
coordination comes the concept of time-current curves.
Time Current Curves
A Time Current Curve (TCC) is a graphical representation of the operating
characteristics of overcurrent protection devices at different magnitudes
of fault currents. A TCC is a two-dimension plot with the current at the x-
axis and the time at the y-axis with both axes are in logarithmic scale. The
current axis may be expressed in amperes and can be scaled in multiples
of 10 while the time axis is usually in the range of 0.01s to 1000s.
Figure 1 shows a TCC plot of a fuse and an overcurrent relay. Take note of
the current axis. In this plot, the current axis is expressed in amperes with
a current multiplier of 10 and with a reference voltage of 13.8kV.
A caveat.
It is important that the current multiplier and reference voltage be
indicated on the TCC plot to avoid misinterpretation.
Figure 1. TCC
Plot of a Fuse and Overcurrent Relay
Like other protection devices (see biased differential protection), the TCC
plot has ‘operate’ and ‘no operate’ regions. The area to the right and
above the device time-current curve is the ‘operate’ region while the area
to the left and below the device time-current curve is the ‘no operate’
region. In figure 1, the area to the left and below the fuse time-current
curve is its ‘no operate’ region. The area to the right and above the fuse
time-current curve is its ‘operate’ region and at the same time, the ‘no
operate’ region of the overcurrent relay.
For a specific value of fault current, the operating time of the overcurrent
device can be determined from its time-current curve. This is the point on
the y-axis in which the fault current intersects the device time-current
curve.
Figure
2. Fault Current of 2000A
In figure 2, a fault of 2000A is shown as a vertical arrow. At this value of
fault current, the fuse is expected to operate in 0.074s while the
overcurrent relay will operate in 5.73s.
2 cycles
3 cycles
5 cycles
8 cycles
Relay Overtravel
Relay overtravel is basically the inertia of a rotating induction disk in an
electromechanical relay. The induction disk starts to rotate from the
passing of currents above the configured threshold or pick-up value. When
the downstream protective device successfully operates to isolate the
fault, the current through the electromechanical relay drops-out below the
threshold or pick up value. This removes the initiating energy to the
induction disk. However, because of inertia, the induction disk cannot
instantaneously stop rotating and may overtravel up to the
electromechanical relay operating point. The typical relay overtravel
duration is 0.10s.
Figure
4. Electromechanical Relay
Image taken from researchgate.net
To illustrate the use of table 15-3, let us consider the following examples.
Fuse-to-Fuse Coordination
Based on table 15-3, for fuse-to-fuse coordination, there must be a clear
space between the time-current curves. However, IEEE Std 242 did not
specify the CTI between fuses, rather, the standard recommends to
consult the device manufacturer.
Consider for example the figure below, for a fault of 1kA at the protecting
fuse, the maximum clearing time is 0.0632s.
Fi
gure 5. Fuse-to-Fuse Coordination
Using the 75% minimum melting time, the minimum melting time of the
protected fuse is calculated as follows,
It can be seen in the TCC plot that the minimum melting time of the
protected fuse is 0.0901s for a fault of 1kA.
Note that the circuit breaker interrupting time for the values presented in
table 15-3 is 5 cycles, equivalent to 0.08s at 60Hz. A different CTI is
recommended for a different circuit breaker interrupting time. For
example, a 3-cycle circuit breaker will operate in 0.05s at 60Hz. This will
bring down the recommended CTI to 0.17s in the above example.
Conclusion
Understanding time-current curves and the basic considerations in
establishing proper coordination between overcurrent protective devices
is very important. However, when coordination is very difficult, if not
impossible, a compromise should be made. As mentioned in the
book Protective Relaying Principles and Application, coordination is a cut-
and-try process that depends on the confidence or conservatism of the
protection engineer. In other words, it always up to you!
Development of IDMT Relay
Curves
Discrimination by Current
Before the concept of IDMT relay curves, instantaneous overcurrent
protection was very common. These relays operate instantaneously when
the current exceeds the pick-up value and reset with no intentional time
delay. Coordination is done based on the fact that short-circuit currents
generally are higher in magnitude the closer they are to the source.
However, for faults near the zone boundaries, the discrimination of the
faulted section can be very difficult. Consider for example the figure
below.
With the application of the safety margin, there will be no protection for
end zone faults. This is illustrated in the following figure.
Consider the example shown in figure 3. I pu1 is set to 1.2 to 1.3 times the
short-circuit current, IF1, for a source impedance, ZS. Now, if we let Z’S >
ZS (loss of generation), the fault level at the farthest end of zone 1 will
decrease to I’F1. This will result in the underreaching of the protection
element as shown in figure 4.
Figure 4. Underreaching of Protection
On the other hand, in cases where Z’ S < ZS, e.g. parallel operation of
transformers, etc., the fault level at the farthest end of zone 1 will
increase to I’F1. This will result in the overreaching of the protection
element as shown in figure 5.
Discrimination by Time
In order to address the limitations of ‘discrimination by current’,
overcurrent protection using definite-time overcurrent relays was
introduced. These relays operate when the current exceeds the pick-up
value after a set time delay. Take note that the operating time of these
relays is independent of the short-circuit current magnitude. The pickup
setting is based on the maximum expected load and short-time overloads
(in contrast to the maximum short-circuit current set for instantaneous
relays). Coordination is done based on configured time delays i.e. the
relay on the farthest end has the lowest time delay walking towards the
source with progressively higher delay. The relay closest to the source
ends up with the highest time delay. Consider for example the figure
below.
By plotting the IDMT relay curves, one can estimate the relay operating
time for a specific value of short-circuit current. Consider for example the
figure below.
Figure 7. TCC Plot
It can be seen that at any value of current, relay R3 will always operate
first while relay R1 will operate last. Unlike instantaneous overcurrent
relays, IDMT relays operate for a wide range of short-circuit currents
above pickup and unlike definite time relays, IDMT relays operate in a
wide range of time depending on the magnitude of short-circuit current.
IDMT Relay Curves
There are three major types of IDMT relays curves. These are the
following:
Inverse (I)
The operating time of the ‘I’ type IDMT relay curve does not vary much
with the current magnitude. This is commonly used in systems where the
short-circuit current does not vary much with distance and variations to
the source impedance.
The ‘EI’ type IDMT relay curve operates at very fast at high short-circuit
currents and very slow at low short-circuit currents. This type of IDMT
curve is most suited for coordination with fuses.
Ideally, the same type should be used throughout the system. However,
the selection of the IDMT relay curve is often based on preferences or
standardization. In other words, the application is more of an art than a
science.
ETAP Star Coordination on
Focus | Detailed Example
selectivity,
speed of operation,
simplicity,
sensitivity, and
economics.
Next, we discussed the concept of zones of protection, primary and
backup protection, local and remote backup, and basic considerations in a
coordination study.
We went on to discuss overcurrent protection devices, their advantages
and disadvantages, and their time-current curves. Our understanding of
time-current curves was supplemented through a discussion
of Coordination Time Intervals (CTIs).
Lastly, overcurrent coordination through the discrimination by time and
current was highlighted in our discussion on the development of the
Inverse Definite Minimum Time (IDMT) relay.
In this article, we will complete our overcurrent coordination series with a
sample coordination study using ETAP Star Coordination. The example is
taken from the book “Protective Relaying Principles and Application” by J.
Blackburn.
Figure
4. ETAP Project One-Line Diagram
Fig. 5
Begin the ETAP star coordination study by clicking the ‘Star – Protection &
Coordination’ icon in the mode toolbar. To verify that you are in the
coordination module, your ‘Study Mode Toolbar’ located on the right side
of your screen should look like the figure shown in figure 5.
Fuse Ratings
The fuse ratings for this sample project were selected based on the lateral
loads they serve. In addition, type ‘T’ (slow-acting) fuse-links were
selected for lateral taps since they coordinate well with distribution
transformer fuses which generally use the fast-acting type ‘K’. These
ratings are shown in figure 1.
For the power transformer high-side fuse, the fuse rating is based on the
transformer maximum rating (2nd forced-air cooled from class OA/FA/FA)
of 25 MVA. An E-rated fuse is selected to provide current limiting
protection.
To create a time-current characteristic plot in ETAP star coordination,
select the devices or equipment from the one-line diagram and click the
‘Create Star View’ icon from the ‘Study Mode Toolbar’.
In order to show and/or modify the information displayed on the TCC plot,
open the transformer parameters window by double-clicking the
transformer symbol on the one-line diagram, and navigate to the
‘Protection’ tab.
Figure 8. Transformer
‘Protection’ Tab
Recloser Settings
The recloser in the example has a maximum load of 230 A. The phase
overcurrent minimum operating current or pick-up value is set to more
than twice the maximum load, at 560 A, to provide security for cold-load
transients. On the other hand, the ground overcurrent minimum operating
current or pick-up value is set at 50% of the phase pick-up to 280 A.
An Extremely Inverse (EI) curve is chosen since it coordinates well with
the downstream fuse. The time multiplier for the phase overcurrent is set
to establish a coordination time interval (CTI) of at least 0.12 s with
respect to the fault level at the downstream 100 A Type ‘T’ fuse. In this
case, a CTI of 0.127 s at 2.215 kA.
The recloser sequence is set to two operations to lockout with the 1st
operation using the fast curve (TCC 1). The fast curve is set with the same
pick-up level as the delayed curve (TCC 2) but is set to operate
instantaneously in order to avoid fuse operations for transient faults. This
scheme is particularly known as the ‘Fuse Saving’ scheme.
Figures 12 and 13 show the phase and ground TCC plots of the recloser
fast and delayed curve, 100T, and 65T fuses.
Fig
ure 12. Recloser-to-Fuse Phase Coordination
Fig
ure 13. Recloser-to-Fuse Ground Coordination
Figures 12 and 13 also indicate the maximum fault levels at each fuse
location (fault 4 and 5 in figure 1) in which the coordination time interval
with the recloser is evaluated. To do this in ETAP star coordination, open
the ‘Star Mode Study Case’ by clicking the ‘Edit Study Case’ icon.
The ‘Study Case’ contains the study preferences and parameters which
include the selection of the faulted bus, the standard to be used, the
number of protective devices to be considered, calculation tolerance
adjustments, and others.
To verify this, click on any fuse and navigate to the ‘TCC kA’ tab. As shown
in figure 17, two values of TCC currents are displayed, ‘TCC Clipping
Current’ and ‘TCC Minimum Current’. These values are updated based on
the selected ‘Short-Circuit Current’ in the ‘Standard’ tab of the ‘Study
Case’. If ‘1/2 Cycle kA’ is selected, the ‘TCC Clipping Current’ values will
be updated else if ’30 Cycle kA’ is selected, the ‘TCC Minimum Current’
values will be updated.
Figur
e 17a. Fuse TCC kA Tab
Figure 17b. Study Case Standard Tab
The ‘TCC Clipping Current’ indicates the maximum fault level for the
protective device selected. It is shown on the TCC plot as a vertical arrow
pointing upwards. The arrow “clips” the device characteristic curves as
shown in figures 12 and 13. On the other hand, the ‘TCC Minimum
Current’ indicates the minimum fault level for the protective device
selected. It is shown on the TCC plot as a vertical arrow pointing
downwards.
Sequence-of-Operation Analysis
ETAP star coordination features a ‘Sequence-of-Operation’ analysis which
allows the simulation of a fault at any point on the one-line diagram and
assesses the sequence of operation of the protective devices. The
parameters for the ‘Sequence-of-Operation’ is accessible through the ‘Edit
Study Case’.
Figure 21. Sequence-of-
Operation
The protective device sequence operation details are available from the
ETAP star coordination report manager. Click on the ‘Report Manager’ icon
on the ‘Study Mode’ toolbar, navigate to the ‘Summary’, and select the
‘Sequence of Operation’. The report will show the time of operation of the
protective devices.
Note: An additional bus was added after the 65T fuse to simulate a
downstream fault.
Figure 24.
Accessing Report Files in ETAP Star Coordination
In this example, for a 3-phase bolted fault downstream of the 65T fuse,
the recloser acts first with its fast curve issuing a trip signal in 10 ms. The
recloser primary contacts open 42 ms after the issued trip signal saving
the fuse from tripping. The recloser recloses after 1000 ms. If there was
no fuse saving scheme applied, the 65T fuse will have started melting in
240 ms and ultimately clearing the fault in 353 ms. Thus, for a permanent
fault downstream of the fuse, the total operation time to completely
isolate the fault is 1405 ms (the recloser operates on fast curve and
recloses in 1052 ms while the fuse will clear the fault in 353 ms after
reclosing).
If the fuse failed to isolate the fault, the recloser will continue to operate
on its delayed curve, issuing a trip signal in 1596 ms and ultimately
isolating the fault in 1638 ms. The total recloser operation time is 2690
ms. This includes the operation of the fast curve (52 ms), the reclosing
time (1000 s) and the operation of the delayed curve (1638 ms).
If the recloser fails, the substation circuit breaker will isolate the fault in
7955 ms (7871 ms for the relay to issue a tripping signal plus 83.3 ms of
circuit breaker interrupting time).
Device/Equipment Specifications
The specifications used in the example using the ETAP star coordination
were determined by trial and error in order to obtain the fault levels
indicated in figure 1. The values for the 3-phase faults were prioritized
over the 1-phase faults.
Power Grid
Rated kV: 115
X/R 3-Phase: 17
X/R 1-Phase: 17
Model: HPA-PM
Speed: Medium
Size: 125A
Power Transformer
Voltage Rating kV Prim.: 115
MVA: 15
Class: OA/FA/FA
Sec.: 5
Phase Overcurrent:
Phase Instantaneous:
Neutral Overcurrent:
Neutral Instantaneous:
CPT: 3
Unit: m
Height: 37.5
Spacing AB: 2
Spacing BC: 2
GG: 0.8
CG: -2.5
Layer 1 Depth: 30
Layer 2 p(ohms-m): 20
Layer 3 p(ohms-m): 10
100T Fuse
Manufacturer: Chance
Speed: Slow
Size: 100A
Unit: m
Height: 37.5
Spacing AB: 2
Spacing BC: 2
GG: 0.8
CG: -2.78
Layer 1 Depth: 30
Layer 2 p(ohms-m): 20
Layer 3 p(ohms-m): 10
Automatic Recloser
Manufacturer: Cooper
Model: Nova 15
Unit: m
Height: 37.5
CG: -4.75
Unit: m
Height: 37.5
CG: -4.75
65T Fuse
Manufacturer: Chance
Speed: Slow
Size: 65A
Unit: m
Height: 37.5
CG: -4.75