Im01c25b01-01en 014

Download as pdf or txt
Download as pdf or txt
You are on page 1of 91

User’s

Manual Differential Pressure and


Pressure Transmitters
EJ110, EJ120,
EJ130, EJ310,
EJ430, and EJ440
IM 01C25B01-01E

IM 01C25B01-01E
14th Edition
i

Differential Pressure and Pressure Transmitters


EJ110, EJ120, EJ130,
EJ310, EJ430, and EJ440
IM 01C25B01-01E 14th Edition

Contents
1. Introduction................................................................................................ 1-1
 Regarding This Manual................................................................................................. 1-1
1.1 Safe Use of This Product ................................................................................. 1-2
1.2 Warranty.............................................................................................................. 1-3
1.3 ATEX Documentation........................................................................................ 1-4
2. Handling Cautions..................................................................................... 2-1
2.1 Model and Specifications Check...................................................................... 2-1
2.2 Unpacking........................................................................................................... 2-1
2.3 Storage................................................................................................................ 2-1
2.4 Selecting the Installation Location ................................................................. 2-2
2.5 Pressure Connection......................................................................................... 2-2
2.6 Waterproofing of Cable Conduit Connections............................................... 2-2
2.7 Restrictions on Use of Radio Transceivers.................................................... 2-2
2.8 Insulation Resistance and Dielectric Strength Test....................................... 2-2
2.9 Installation of an Explosion-Protected Instrument........................................ 2-3
2.9.1 FM Approval........................................................................................ 2-4
2.9.2 CSA Certification................................................................................. 2-6
2.9.3 ATEX Certification............................................................................... 2-8
2.9.4 IECEx Certification............................................................................ 2-11
2.10 EMC Conformity Standards............................................................................ 2-12
2.11 Pressure Equipment Directive (PED)............................................................ 2-13
2.12 Safety Requirement Standards...................................................................... 2-13
3. Component Names................................................................................... 3-1
4. Installation.................................................................................................. 4-1
4.1 Precautions ....................................................................................................... 4-1
4.2 Mounting ............................................................................................................ 4-1
4.3 Changing the Process Connection.................................................................. 4-2
4.4 Swapping the High/Low-pressure Side Connection...................................... 4-3
4.4.1 Rotating Pressure-detector Section 180° .......................................... 4-3
4.4.2 Using the Communicator.................................................................... 4-3
4.5 Rotating Transmitter Section............................................................................ 4-4
4.6 Changing the Direction of Integral Indicator ................................................. 4-4

14th Edition: June 2014 (KP) IM 01C25B01-01E


All Rights Reserved, Copyright © 2004, Yokogawa Electric Corporation
ii
5. Installing Impulse Piping.......................................................................... 5-1
5.1 Impulse Piping Installation Precautions......................................................... 5-1
5.1.1 Connecting Impulse Piping to a Transmitter....................................... 5-1
5.1.2 Routing the Impulse Piping................................................................. 5-3
5.2 Impulse Piping Connection Examples............................................................ 5-4
6. Wiring.......................................................................................................... 6-1
6.1 Wiring Precautions............................................................................................ 6-1
6.2 Selecting the Wiring Materials.......................................................................... 6-1
6.3 Connections of External Wiring to Terminal Box........................................... 6-1
6.3.1 Power Supply Wiring Connection....................................................... 6-1
6.3.2 External Indicator Connection............................................................ 6-1
6.3.3 Communicator Connection................................................................. 6-2
6.3.4 Check Meter Connection.................................................................... 6-2
6.3.5 Status Output Connection................................................................... 6-2
6.4 Wiring.................................................................................................................. 6-2
6.4.1 Loop Configuration............................................................................. 6-2
6.4.2 Wiring Installation................................................................................ 6-3
6.5 Grounding........................................................................................................... 6-4
6.6 Power Supply Voltage and Load Resistance.................................................. 6-4
7. Operation.................................................................................................... 7-1
7.1 Preparation for Starting Operation.................................................................. 7-1
7.2 Zero Point Adjustment...................................................................................... 7-3
7.2.1 Adjusting Zero Point for Differential Pressure Transmitters............... 7-3
7.2.2 Adjusting Zero Point for Gauge/Absolute Pressure Transmitters .... 7-3
7.3 Starting Operation............................................................................................. 7-4
7.4 Shutting Down the Transmitter........................................................................ 7-4
7.5 Venting or Draining Transmitter Pressure-detector Section........................ 7-5
7.5.1 Draining Condensate.......................................................................... 7-5
7.5.2 Venting Gas........................................................................................ 7-5
7.6 Local Parameter Setting.................................................................................... 7-5
7.6.1 Local Parameter Setting (LPS) Overview........................................... 7-6
7.6.2 Activating Local Parameter Setting.................................................... 7-7
7.6.3 Parameter Setting Review.................................................................. 7-7
7.6.4 Tag Number Configuration.................................................................. 7-8
7.6.5 Pressure Unit Configuration............................................................... 7-8
7.6.6 Damping Time Constant Configuration.............................................. 7-9
7.6.7 Re-range by applying actual pressure (LRV/URV)............................. 7-9
7.6.8 Save or Cancel................................................................................. 7-10
7.6.9 Abort Configuration........................................................................... 7-10
7.6.9.1 Abort Configuration (Menu)............................................. 7-10
7.6.9.2 Abort Configuration (Parameter)..................................... 7-10
7.6.10 Local Parameter Setting Lock........................................................... 7-10

IM 01C25B01-01E
iii
7.6.11 Others............................................................................................... 7-10
8. Maintenance............................................................................................... 8-1
8.1 Overview............................................................................................................. 8-1
8.2 Calibration Instruments Selection................................................................... 8-1
8.3 Calibration.......................................................................................................... 8-1
8.4 Disassembly and Reassembly......................................................................... 8-3
8.4.1 Replacing the Integral Indicator.......................................................... 8-3
8.4.2 Replacing the CPU Board Assembly.................................................. 8-4
8.4.3 Cleaning and Replacing the Capsule Assembly................................ 8-4
8.4.4 Replacing the Process Connector Gaskets........................................ 8-6
8.5 Troubleshooting................................................................................................. 8-6
8.5.1 Basic Troubleshooting........................................................................ 8-6
8.5.2 Troubleshooting Flowcharts................................................................ 8-7
8.5.3 Alarms and Countermeasures............................................................ 8-9
9. General Specifications............................................................................. 9-1
9.1 Standard Specifications.................................................................................... 9-1
9.2 Model and Suffix Codes.................................................................................... 9-6
9.3 Optional Specifications .................................................................................. 9-19
9.4 Dimensions....................................................................................................... 9-22
Revision Information

When using the Transmitters in a Safety Instrumented Systems(SIS)


application, refer to Appendix A in either IM 01C25T01-06EN for the
HART protocol or IM 01C25T03-01E for the BRAIN protocol.

IM 01C25B01-01E
<1. Introduction> 1-1

1. Introduction
Thank you for purchasing the DPharp Differential
Pressure and pressure transmitter. NOTE
Your transmitter was precisely calibrated at the When describing the model name like EJ110,
factory before shipment. To ensure both safety and it shows the applicability for both EJX110A and
efficiency, please read this manual carefully before EJA110E. The same representations are used
you operate the instrument. for the other models, too.

NOTE
NOTE
This manual describes the hardware
configurations of the transmitters listed in below. Unless otherwise stated, the illustrations in
For information on the software configuration this manual are of the EJ110 differential
and operation, please refer to either pressure transmitter. Users of the other models
IM 01C25T03-01E for the BRAIN communication should bear in mind that certain features of their
type, or IM 01C25T01-06EN for the HART instrument will differ from those shown in the
communication type. illustrations of the EJ110.
For FOUNDATION Fieldbus protocol type, please
refer to IM 01C25T02-01E.
For PROFIBUS PA protocol type, please refer to  Regarding This Manual
IM 01C25T04-01EN. • This manual should be provided to the end
Model Style code user.
EJX110A S3 • The contents of this manual are subject to
EJX120A S1 change without prior notice.
EJX130A S2
EJX310A S2
• All rights reserved. No part of this manual may
EJX430A S2 be reproduced in any form without Yokogawa’s
EJX440A S2 written permission.
EJA110E S1 • Yokogawa makes no warranty of any kind with
EJA120E S1 regard to this manual, including, but not limited
EJA130E S1 to, implied warranty of merchantability and
EJA310E S1 fitness for a particular purpose.
EJA430E S1
EJA440E S1 • If any question arises or errors are found, or if
any information is missing from this manual,
To ensure correct use of this instrument, read please inform the nearest Yokogawa sales
both the hardware and software manuals office.
thoroughly before use.
• The specifications covered by this manual are
limited to those for the standard type under the
specified model number break-down and do not
WARNING cover custom-made instruments.
When using the transmitters in a Safety • Please note that changes in the specifications,
Instrumented Systems (SIS) application, refer construction, or component parts of the
to Appendix 1 in either IM 01C25T01-06EN for instrument may not immediately be reflected
the HART protocol or IM 01C25T03-01E for the in this manual at the time of change, provided
BRAIN protocol. The instructions and procedures that postponement of revisions will not cause
in this section must be strictly followed in order to difficulty to the user from a functional or
maintain the transmitter for this safety level. performance standpoint.

IM 01C25B01-01E
<1. Introduction> 1-2
• Yokogawa assumes no responsibilities for this 1.1 Safe Use of This Product
product except as stated in the warranty.
For the safety of the operator and to protect the
• If the customer or any third party is harmed by instrument and the system, please be sure to follow
the use of this product, Yokogawa assumes this manual’s safety instructions when handling this
no responsibility for any such harm owing to instrument. If these instructions are not heeded,
any defects in the product which were not the protection provided by this instrument may be
predictable, or for any indirect damages. impaired. In this case, Yokogawa cannot guarantee
• The following safety symbols are used in this that the instrument can be safely operated. Please
manual: pay special attention to the following points:

(a) Installation
WARNING • This instrument may only be installed by an
engineer or technician who has an expert
Indicates a potentially hazardous situation which, knowledge of this device. Operators are not
if not avoided, could result in death or serious allowed to carry out installation unless they
injury. meet this condition.
• With high process temperatures, care must
be taken not to burn yourself by touching the
CAUTION instrument or its casing.

Indicates a potentially hazardous situation which, • Never loosen the process connector nuts when
if not avoided, may result in minor or moderate the instrument is installed in a process. This can
injury. It may also be used to alert against unsafe lead to a sudden, explosive release of process
practices. fluids.
• When draining condensate from the pressure
detector section, take appropriate precautions
IMPORTANT to prevent the inhalation of harmful vapors and
the contact of toxic process fluids with the skin
Indicates that operating the hardware or software
or eyes.
in this manner may damage it or lead to system
failure. • When removing the instrument from a
hazardous process, avoid contact with the fluid
and the interior of the meter.
NOTE • All installation shall comply with local installation
requirements and the local electrical code.
Draws attention to information essential for
understanding the operation and features. (b) Wiring
• The instrument must be installed by an
Direct current engineer or technician who has an expert
knowledge of this instrument. Operators are not
Functional grounding terminal permitted to carry out wiring unless they meet
this condition.
Caution
• Before connecting the power cables, please
This symbol indicates that the operator must
confirm that there is no current flowing through
refer to an explanation in the user’s manual
the cables and that the power supply to the
in order to avoid the risk of injury or death of
instrument is switched off.
personnel or damage to the instrument.

IM 01C25B01-01E
<1. Introduction> 1-3
(c) Operation 1.2 Warranty
• Wait 5 min. after the power is turned off, before • The warranty shall cover the period noted on
opening the covers. the quotation presented to the purchaser at the
time of purchase. Problems occurring during
(d) Maintenance
the warranty period shall basically be repaired
• Please carry out only the maintenance free of charge.
procedures described in this manual. If you • If any problems are experienced with this
require further assistance, please contact the instrument, the customer should contact the
nearest Yokogawa office. Yokogawa representative from which this
• Care should be taken to prevent the build up of instrument was purchased or the nearest
dust or other materials on the display glass and Yokogawa office.
the name plate. To clean these surfaces, use a • If a problem arises with this instrument,
soft, dry cloth. please inform us of the nature of the problem
and the circumstances under which it
(e) Explosion Protected Type Instrument
developed, including the model specification
• Users of explosion proof instruments should and serial number. Any diagrams, data and
refer first to section 2.9 (Installation of an other information you can include in your
Explosion Protected Instrument) of this manual. communication will also be helpful.
• The use of this instrument is restricted to those • The party responsible for the cost of fixing the
who have received appropriate training in the problem shall be determined by Yokogawa
device. following an investigation conducted by
• Take care not to create sparks when accessing Yokogawa.
the instrument or peripheral devices in a • The purchaser shall bear the responsibility for
hazardous location. repair costs, even during the warranty period, if
the malfunction is due to:
(f) Modification
• Yokogawa will not be liable for malfunctions or - Improper and/or inadequate maintenance by
damage resulting from any modification made the purchaser.
to this instrument by the customer. - Malfunction or damage due to a failure
to handle, use, or store the instrument in
accordance with the design specifications.
- Use of the product in question in a location
not conforming to the standards specified by
Yokogawa, or due to improper maintenance
of the installation location.
- Failure or damage due to modification or
repair by any party except Yokogawa or an
approved representative of Yokogawa.
- Malfunction or damage from improper
relocation of the product in question after
delivery.
- Reason of force majeure such as fires,
earthquakes, storms/floods, thunder/
lightening, or other natural disasters, or
disturbances, riots, warfare, or radioactive
contamination.

IM 01C25B01-01E
<1. Introduction> 1-4
1.3 ATEX Documentation
This is only applicable to the countries in European Union.

GB SK

CZ
DK

I LT

E LV

EST
NL

PL

SF

SLO
P

BG

RO

S
M

GR

IM 01C25B01-01E
<2. Handling Cautions> 2-1

2. Handling Cautions
This chapter provides important information on how 2.1 Model and Specifications
to handle the transmitter. Read this carefully before
using the transmitter.
Check
The model name and specifications are written on
The transmitters are thoroughly tested at the
the name plate attached to the case.
factory before shipment. When taking delivery of an
instrument, visually check them to make sure that
no damage occurred during shipment.
Also check that all transmitter mounting hardware
shown in figure 2.1 is included. If the transmitter
is ordered without the mounting bracket and the F0202.ai

process connector, the transmitter mounting Figure 2.2 Name Plate (EJX110A)
hardware will not be included. After checking the
transmitter, carefully repack it in its box and keep it
there until you are ready to install it. 2.2 Unpacking
Bolt Keep the transmitter in its original packaging to
Process connector (Note 1) prevent it from being damaged during shipment.
Process connector Do not unpack the transmitter until it reaches the
Gasket
installation site.
U-bolt

2.3 Storage
The following precautions must be observed when
storing the instrument, especially for a long period.
Mounting bracket (a) Select a storage area which meets the following
(L type)
conditions:
U-bolt nut Transmitter mounting bolt
• It is not exposed to rain or subject to water
seepage/leaks.
• Vibration and shock are kept to a minimum.
• It has an ambient temperature and relative
humidity within the following ranges.
Ambient temperature:
–40* to 85°C without integral indicator
–30* to 80°C with integral indicator
* –15°C when /HE is specified.
Relative humidity:
Mounting bracket 0% to 100% R.H.
(Flat type)
Preferred temperature and humidity:
F0201.ai
approx. 25°C and 65% R.H.
Figure 2.1 Transmitter Mounting Hardware
(b) When storing the transmitter, repack it carefully
in the packaging that it was originally shipped
with.
(c) If the transmitter has been used, thoroughly
clean the chambers inside the cover flanges, so
that there is no process fluid remaining inside.
Before placing it in storage, also make sure that
the pressure-detector is securely connected to
the transmitter section.

IM 01C25B01-01E
<2. Handling Cautions> 2-2
2.4 Selecting the Installation The following precautions must be observed
in order to safely operate the transmitter under
Location pressure.
The transmitter is designed to withstand severe
(a) Make sure that all the process connector bolts
environmental conditions. However, to ensure
are tightened firmly.
that it will provide years of stable and accurate
(b) Make sure that there are no leaks in the impulse
performance, take the following precautions when
piping.
selecting the installation location.
(c) Never apply a pressure higher than the
(a) Ambient Temperature specified maximum working pressure.
Avoid locations subject to wide temperature
variations or a significant temperature gradient. 2.6 Waterproofing of Cable
If the location is exposed to radiant heat from
plant equipment, provide adequate thermal
Conduit Connections
insulation and/or ventilation. Apply a non-hardening sealant to the threads
to waterproof the transmitter cable conduit
(b) Ambient Atmosphere
connections. (See figure 6.8, 6.9 and 6.10.)
Do not install the transmitter in a corrosive
atmosphere. If this cannot be avoided, there
must be adequate ventilation as well as 2.7 Restrictions on Use of Radio
measures to prevent the leaking of rain water
and the presence of standing water in the Transceivers
conduits.
IMPORTANT
(c) Shock and Vibration
Although the transmitter is designed to be Although the transmitter has been designed to
relatively resistant to shock and vibration, an resist high frequency electrical noise, if a radio
installation site should be selected where this is transceiver is used near the transmitter or its
kept to a minimum. external wiring, the transmitter may be affected
by high frequency noise pickup. To test this, start
(d) Installation of Explosion-protected Transmitters
out from a distance of several meters and slowly
An explosion-protected transmitters is
approach the transmitter with the transceiver
certified for installation in a hazardous area
while observing the measurement loop for noise
containing specific gas types. See subsection
effects. Thereafter use the transceiver outside
2.9 “Installation of an Explosion-Protected
the range where the noise effects were first
Transmitters.”
observed.

2.5 Pressure Connection


2.8 Insulation Resistance and
WARNING Dielectric Strength Test
• Never loosen the process connector bolts Since the transmitter has undergone insulation
when an instrument is installed in a process. resistance and dielectric strength tests at the factory
The device is under pressure, and a loss of before shipment, normally these tests are not
seal can result in a sudden and uncontrolled required. If the need arises to conduct these tests,
release of process fluid. heed the following:
• When draining toxic process fluids that have
(a) Do not perform such tests more frequently than
condensed inside the pressure detector,
is absolutely necessary. Even test voltages that
take appropriate steps to prevent the contact
do not cause visible damage to the insulation
of such fluids with the skin or eyes and the
may degrade the insulation and reduce safety
inhalation of vapors from these fluids.
margins.

IM 01C25B01-01E
<2. Handling Cautions> 2-3
(b) Never apply a voltage exceeding 500 V DC 2.9 Installation of an Explosion-
(100 V DC with an internal lightning protector)
for the insulation resistance test, nor a voltage
Protected Instrument
exceeding 500 V AC (100 V AC with an internal
lightning protector) for the dielectric strength NOTE
test. For FOUNDATION Fieldbus explosion protected
(c) Before conducting these tests, disconnect type, please refer to IM 01C22T02-01E.
all signal lines from the transmitter terminals. For PROFIBUS PA explosion protected type,
The procedure for conducting these tests is as please refer to IM 01C25T04-01EN.
follows:
• Insulation Resistance Test If a customer makes a repair or modification to
an intrinsically safe or explosionproof instrument
1) Short-circuit the + and – SUPPLY terminals in
and the instrument is not restored to its original
the terminal box.
condition, its intrinsically safe or explosionproof
2) Turn OFF the insulation tester. Then connect
construction may be compromised and the
the insulation tester plus (+) lead wire to the
instrument may be hazardous to operate. Please
shorted SUPPLY terminals and the minus (–)
contact Yokogawa before making any repair or
leadwire to the grounding terminal.
modification to an instrument.
3) Turn ON the insulation tester power and
measure the insulation resistance. The voltage
should be applied as briefly as possible to verify CAUTION
that the insulation resistance is at least 20 MΩ.
This instrument has been tested and certified
4) After completing the test and being very careful
as being intrinsically safe or explosionproof.
not to touch exposed conductors disconnect the
Please note that severe restrictions apply to this
insulation tester and connect a 100 kΩ resistor
instrument’s construction, installation, external
between the grounding terminal and the short-
wiring, maintenance and repair. A failure to abide
circuiting SUPPLY terminals. Leave this resistor
by these restrictions could make the instrument a
connected at least one second to discharge any
hazard to operate.
static potential. Do not touch the terminals while
it is discharging.
• Dielectric Strength Test
WARNING
1) Short-circuit the + and – SUPPLY terminals in
the terminal box. Maintaining the safety of explosionproof
2) Turn OFF the dielectric strength tester. Then equipment requires great care during mounting,
connect the tester between the shorted wiring, and piping. Safety requirements also
SUPPLY terminals and the grounding terminal. place restrictions on maintenance and repair.
Be sure to connect the grounding lead of the Please read the following sections very carefully.
dielectric strength tester to the ground terminal.
3) Set the current limit on the dielectric strength
tester to 10 mA, then turn ON the power and WARNING
gradually increase the test voltage from ‘0’ to
the specified voltage. The range setting switch must not be used in a
4) When the specified voltage is reached, hold it hazardous area.
for one minute.
5) After completing this test, slowly decrease the
voltage to avoid any voltage surges.

IM 01C25B01-01E
<2. Handling Cautions> 2-4
Note 2. Entity Parameters
IMPORTANT • Intrinsically Safe Apparatus Parameters
For combined approval types [Groups A, B, C, D, E, F and G]
Once a device of multiple approval type is Vmax = 30 V Ci = 6 nF
installed, it should not be re-installed using any Imax = 200 mA Li = 0 µH
other approval types. Apply a permanent mark Pmax = 1 W
in the check box of the selected approval type * Associated Apparatus Parameters
on the certification label on the transmitter to (FM approved barriers)
distinguish it from unused approval types. Voc ≤ 30 V Ca > 6 nF
Isc ≤ 200 mA La > 0 µH
Pmax ≤ 1W
IMPORTANT
• Intrinsically Safe Apparatus Parameters
All the blind plugs which accompany the EJX/ [Groups C, D, E, F and G]
EJA-E transmitters upon shipment from the Vmax = 30 V Ci = 6 nF
factory are certified by the applicable agency in Imax = 225 mA Li = 0 µH
combination with those transmitters. The plugs Pmax = 1 W
which are marked with the symbols “◊ Ex” on
their surfaces are certified only in combination * Associated Apparatus Parameters
with the EJX/EJA-E series transmitters. (FM approved barriers)
Voc ≤ 30 V Ca > 6 nF
Isc ≤ 225 mA La > 0 µH
2.9.1 FM Approval Pmax ≤ 1 W

a. FM Intrinsically Safe Type • Entity Installation Requirements


Vmax ≥ Voc or Uo or Vt, Imax ≥ Isc or Io or It,
Caution for FM intrinsically safe type. (Following Pmax (or Po) ≤ Pi, Ca or Co ≥ Ci + Ccable,
contents refer “DOC. No. IFM022-A12”) La or Lo ≥ Li + Lcable
Note 1. Model EJX/EJA-E Series Differential, Note 3. Installation
gauge and absolute pressure transmitters • Barrier must be installed in an enclosure that
with optional code /FS1 are applicable for meets the requirements of ANSI/ISA S82.01.
use in hazardous locations. • Control equipment connected to barrier must
• Applicable Standard: FM3600, FM3610, not use or generate more than 250 V rms or
FM3611, FM3810 V dc.
• Intrinsically Safe for Class I, Division 1, • Installation should be in accordance with
Groups A, B, C & D. Class II, Division 1, ANSI/ISA RP12.6 “Installation of Intrinsically
Groups E, F & G and Class III, Division 1, Safe Systems for Hazardous (Classified)
Class I, Zone 0 in Hazardous Locations, AEx Locations” and the National Electric Code
ia IIC (ANSI/NFPA 70).
• Nonincendive for Class I, Division 2, Groups • The configuration of associated apparatus
A, B, C & D. Class II, Division 2, Groups F & must be FMRC Approved.
G, Class I, Zone 2, Groups IIC, in Hazardous • Dust-tight conduit seal must be used when
Locations. installed in a Class II, III, Group E, F and G
• Outdoor hazardous locations, NEMA TYPE environments.
4X. • Associated apparatus manufacturer’s
• Temperature Class: T4 installation drawing must be followed when
• Ambient temperature: –60 to 60°C installing this apparatus.
• The maximum power delivered from the
barrier must not exceed 1 W.
• Note a warning label worded
“SUBSTITUTION OF COMPONENTS MAY
IMPAIR INTRINSIC SAFETY,” and “INSTALL
IN ACCORDANCE WITH DOC. No. IFM022-
A12”

IM 01C25B01-01E
<2. Handling Cautions> 2-5
Note 4. Maintenance and Repair Note 2. Wiring
• The instrument modification or parts • All wiring shall comply with National Electrical
replacement by other than authorized Code ANSI/NFPA70 and Local Electrical
representative of Yokogawa Electric Codes.
Corporation is prohibited and will void • When installed in Division 1, “FACTORY
Factory Mutual Intrinsically safe and SEALED, CONDUIT SEAL NOT
Nonincendive Approval. REQUIRED.”
[Intrinsically Safe] Note 3. Operation
Hazardous Location Nonhazardous Location • Keep the “WARNING” nameplate attached to
Class I, II, III, Division 1, the transmitter.
Groups A, B, C, D, E, F, G WARNING: OPEN CIRCUIT BEFORE
Class 1, Zone 0 in REMOVING COVER. FACTORY SEALED,
Hazardous (Classified) General
Locations AEx ia IIC CONDUIT SEAL NOT REQUIRED.
Purpose
Pressure Transmitters Safety Barrier Equipment INSTALL IN ACCORDANCE WITH THE
+ + + + USERS MANUAL IM 01C25.
Supply – – – – • Take care not to generate mechanical
sparking when accessing to the instrument
and peripheral devices in a hazardous
F0203-1.ai
location.
[Nonincendive]
Note 4. Maintenance and Repair
Hazardous Location Nonhazardous Location
• The instrument modification or parts
Class I, II, Division 2,
replacement by other than authorized
Groups A, B, C, D, F, G
Class 1, Zone 2, Group IIC, representative of Yokogawa Electric
in Hazardous (Classified)
General Corporation is prohibited and will void
Locations
Purpose Factory Mutual Explosionproof Approval.
Pressure Transmitters Equipment
+ + c. FM Intrinsically Safe Type/FM
Supply – –
Explosionproof Type
Not Use Model EJX/EJA-E Series pressure transmitters
Safety Barrier
with optional code /FU1 or /V1U1 can be
F0203-2.ai
selected the type of protection (FM Intrinsically
b. FM Explosionproof Type Safe or FM Explosionproof) for use in
hazardous locations.
Caution for FM explosionproof type.
Note 1. For the installation of this transmitter,
Note 1. Model EJX/EJA-E Series pressure
once a particular type of protection is
transmitters with optional code /FF1 are
selected, any other type of protection
applicable for use in hazardous locations.
cannot be used. The installation must be in
• Applicable Standard: FM3600, FM3615,
accordance with the description about the
FM3810, ANSI/NEMA 250
type of protection in this instruction manual.
• Explosionproof for Class I, Division 1,
Groups B, C and D. Note 2. In order to avoid confusion, unnecessary
• Dust-ignitionproof for Class II/III, Division 1, marking is crossed out on the label other
Groups E, F and G. than the selected type of protection when
• Enclosure rating: NEMA TYPE 4X. the transmitter is installed.
• Temperature Class: T6
• Ambient Temperature: –40 to 60°C
• Supply Voltage: 42 V dc max.
• Output signal: 4 to 20 mA

IM 01C25B01-01E
<2. Handling Cautions> 2-6
2.9.2 CSA Certification Note 3. Installation
• In any safety barreir used output current
a. CSA Intrinsically Safe Type must be limited by a resistor 'R' such that
Caution for CSA Intrinsically safe and Io=Uo/R or Isc=Voc/R.
nonincendive type. (Following contents refer to • The safety barrier must be CSA certified.
“DOC No. ICS013-A13”) • Input voltage of the safety barrier must be
less than 250 Vrms/Vdc.
Note 1. Model EJX/EJA-E Series differential, • Installation should be in accordance with
gauge, and absolute pressure transmitters Canadian Electrical Code Part I and Local
with optional code /CS1 are applicable for Electrical Code.
use in hazardous locations • Dust-tight conduit seal must be used when
Certificate: 1606623 installed in Class II and III environments.
[For CSA C22.2] • The instrument modification or parts
• Applicable Standard: C22.2 No.0, C22.2 replacement by other than authorized
No.0.4, C22.2 No.25, C22.2 No.94, C22.2 representative of Yokogawa Electric
No.157, C22.2 No.213, C22.2 No.61010-1, Corporation and Yokogawa Corporation
C22.2 No.60079-0 of America is prohibited and will void
• Intrinsically Safe for Class I, Division 1, Canadian Standards Intrinsically safe and
Groups A, B, C & D, Class II, Division 1, nonincendive Certification.
Groups E, F & G, Class III, Division 1 [Intrinsically Safe]
• Nonincendive for Class I, Division 2, Groups Hazardous Location Nonhazardous Location
A, B, C & D, Class II, Division 2, Groups F & Group IIC, Zone 0
G, Class III, Division 1 Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G General
• Enclosure: NEMA TYPE 4X Purpose
• Temp. Code: T4 Pressure Transmitters Safety Barrier Equipment
• Amb. Temp.:–50* to 60°C + + + +
* –15°C when /HE is specified. Supply – – – –
• Process Temperature: 120°C max.
[For CSA E60079]
• Applicable Standard: CAN/CSA E60079-11,
F0204-1.ai

CAN/CSA E60079-15, IEC 60529:2001 [Nonincendive]


• Ex ia IIC T4, Ex nL IIC T4 Hazardous Location Nonhazardous Location
• Ambient Temperature: –50* to 60°C Group IIC, Zone 2
* –15°C when /HE is specified. Class I, II, Division 2,
Groups A, B, C, D, F, G CSA Certified
• Max. Process Temp.: 120°C Equipment
Class III, Division 1.
• Enclosure: IP66/IP67 ([nL] or
Pressure Transmitters nonincendive)
Note 2. Entity Parameters + +
• Intrinsically safe ratings are as follows:
Supply – –
Maximum Input Voltage (Vmax/Ui) = 30 V Not Use
Maximum Input Current (Imax/Ii) = 200 mA Safety Barrier
Maximum Input Power (Pmax/Pi) = 0.9 W F0204-2.ai

Maximum Internal Capacitance (Ci) = 10 nF


Maximum Internal Inductance (Li) = 0 µH b. CSA Explosionproof Type
• Type "n" or Nonincendive ratings are as Caution for CSA explosionproof type.
follows:
Note 1. Model EJX/EJA-E Series pressure
Maximum Input Voltage (Vmax/Ui) = 30 V
transmitters with optional code /CF1 are
Maximum Internal Capacitance (Ci) = 10 nF
applicable for use in hazardous locations:
Maximum Internal Inductance (Li) = 0 µH
• Certificate: 2014354
• Installation Requirements
• Applicable Standard: C22.2 No.0,
Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi,
C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25,
Co ≥ Ci + Ccable, Lo ≥ Li + Lcable
C22.2 No.30, C22.2 No.94,
Voc ≤ Vmax, Isc ≤ Imax,
C22.2 No.61010-1, C22.2 No.60079-0,
Ca ≥ Ci + Ccable, La ≥ Li + Lcable
C22.2 No.60079-1
Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are
parameters of barrier.
IM 01C25B01-01E
<2. Handling Cautions> 2-7
• Explosion-proof for Class I, Groups B, C and • All wiring shall comply with local installation
D. requirements and local electrical code.
• Dustignition-proof for Class II/III, Groups E, F • In hazardous locations, the cable entry
and G. devices shall be of a certified flameproof
• Enclosure: NEMA TYPE 4X type, suitable for the conditions of use and
• Temperature Code: T6...T4 correctly installed.
• Ex d IIC T6...T4 • Unused apertures shall be closed with
• Enclosure: IP66/IP67 suitable flameproof certified blanking
• Maximum Process Temperature: 120°C (T4), elements. (The plug attached is flameproof
100°C (T5), 85°C (T6) certified.)
• Ambient Temperature: –50* to 75°C (T4),
Note 3. Operation
–50* to 80°C (T5), –50* to 75°C (T6)
* –15°C when /HE is specified. • WARNING:
• Supply Voltage: 42 V dc max. AFTER DE-ENERGIZING, DELAY 5
• Output Signal: 4 to 20 mA dc MINUTES BEFORE OPENING.
APRÉS POWER-OFF, ATTENDRE 5
Note 2. Wiring MINUTES AVANT D'OUVRIR.
• All wiring shall comply with Canadian • WARNING:
Electrical Code Part I and Local Electrical WHEN AMBIENT TEMPERATURE ≥ 65°C,
Codes. USE THE HEAT-RESISTING CABLES ≥
• In hazardous location, wiring shall be in 90°C.
conduit as shown in the figure. QUAND LA TEMPÉRATURE AMBIANTE
• WARNING: ≥ 65°C, UTILISEZ DES CÂBLES
A SEAL SHALL BE INSTALLED WITHIN RÉSISTANTES Á LA CHALEUR ≥ 90°C.
50cm OF THE ENCLOSURE. • Take care not to generate mechanical
UN SCELLEMENT DOIT ÊTRE INSTALLÉ À sparking when accessing to the instrument
MOINS DE 50cm DU BOÎTIER. and peripheral devices in a hazardous
• WARNING: location.
WHEN INSTALLED IN CL.I, DIV 2, SEAL
NOT REQUIRED. Note 4. Maintenance and Repair
UNE FOIS INSTALLÉ DANS CL I, DIV 2, • The instrument modification or parts
AUCUN JOINT N'EST REQUIS. replacement by other than authorized
Non-Hazardous Hazardous Locations Division 1
representative of Yokogawa Electric
Locations Corporation and Yokogawa Corporation of
Non-hazardous America is prohibited and will void Canadian
Location
Equipment 50 cm Max. Standards Explosionproof Certification.
c CSA Intrinsically Safe Type/CSA
Explosionproof Type
42 V DC Max. Conduit
4 to 20 mA DC Sealing Fitting Model EJX/EJA-E Series pressure transmitters
Signal with optional code /CU1 or /V1U1 can be
Transmitter
F0205-1.ai selected the type of protection (CSA Intrinsically
Non-Hazardous Hazardous Locations Division 2 Safe or CSA Explosionproof) for use in
Locations hazardous locations.
Non-hazardous
Location Note 1. For the installation of this transmitter,
Equipment once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be in
42 V DC Max.
4 to 20 mA DC Sealing Fitting accordance with the description about the
Signal type of protection in this instruction manual.
Transmitter
F0205-2.ai
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other
than the selected type of protection when
the transmitter is installed.

IM 01C25B01-01E
<2. Handling Cautions> 2-8
2.9.3 ATEX Certification [Control Drawing]

Hazardous Location Nonhazardous Location


(1) Technical Data
Transmitter
a. ATEX Intrinsically Safe Ex ia + +
Supply Safety Barrier *1
Caution for ATEX Intrinsically safe type. – –

Note 1. Model EJX/EJA-E Series pressure


transmitters with optional code /KS21 for
potentially explosive atmospheres: F0206.ai

• No. DEKRA 11ATEX0228 X *1: In any safety barriers used the output current must be
• Applicable Standard: limited by a resistor “R” such that Io=Uz/R.

EN 60079-0:2009, EN 60079-11:2007, Note 4. Maintenance and Repair


EN 60079-26:2007, EN 61241-11:2006 • The instrument modification or parts
• Type of Protection and Marking code: replacement by other than authorized
Ex ia IIC T4 Ga representative of Yokogawa Electric
Ex ia IIIC T85 ºC T100 ºC T120 ºC Db Corporation is prohibited and will void
• Group: II DEKRA Intrinsically safe Certification.
• Category: 1G, 2D
• Ambient Temperature for EPL Ga: Note 5. Special Conditions for Safe Use
–50 to 60°C
• Ambient Temperature for EPL Db: WARNING
–30* to 60°C
* –15°C when /HE is specified. • In the case where the enclosure of the
• Process Temperature (Tp.): 120°C max. Pressure Transmitter is made of aluminium,
• Maximum Surface Temperature for EPL Db: if it is mounted in an area where the use of
T85°C (Tp.: 80°C) category 1 G apparatus is required, it must
T100°C (Tp.: 100°C) be installed such, that, even in the event of
T120°C (Tp.: 120°C) rare incidents, ignition sources due to impact
• Enclosure: IP66 / IP67 and friction sparks are excluded.
• Electrostatic charge may cause an exlosion
Note 2 Electrical Data hazard. Avoid any actions that cause the
• In type of explosion protection intrinsic safety gerenation of eletrostatic charge, such as
Ex ia IIC or Ex ia IIIC, only for connection to a rubbing with a dry cloth on coating face of
certified intrinsically safe circuit with following the product.
maximum values: • In case of the enclosure of the Pressure
Ui = 30 V Transmitter with paint layers, if it is mounted
Ii = 200 mA in an area where the use of category 2D
Pi = 0.9 W apparatus is required, it shall be installed in
(Linear Source) such a way that the risk from electrostatic
Maximum internal capacitance; Ci = 27.6 nF discharges and propagating brush
Maximum internal inductance; Li = 0 µH discharges caused by rapid flow of dust is
Note 3. Installation avoided.
• Refer to the control drawing. All wiring shall • To satisfy IP66 or IP67, apply waterproof
comply with local installation requirements. glands to the electrical connection port.
• When the lightning protector option is
specified, the apparatus is not capable
of withstanding the 500V insulation test
required by EN60079-11. This must be taken
into account when installing the apparatus.

IM 01C25B01-01E
<2. Handling Cautions> 2-9
b. ATEX Flameproof Type
Caution for ATEX flameproof type. WARNING
Note 1. Model EJX/EJA-E Series pressure • Electrostatic charge may cause an exlosion
transmitters with optional code /KF22 for hazard. Avoid any actions that cause the
potentially explosive atmospheres: gerenation of eletrostatic charge, such as
• No. KEMA 07ATEX0109 X rubbing with a dry cloth on coating face of the
• Applicable Standard: EN 60079-0:2009, product.
EN 60079-1:2007, EN 60079-31:2009 • In the case where the enclosure of the
• Type of Protection and Marking Code: Pressure Transmitter is made of aluminium,
Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db if it is mounted in an area where the use of
• Group: II category 2D apparatus is required, it shall
• Category: 2G, 2D be installed in such a way that the risk from
• Enclosure: IP66 / IP67 electrostatic discharges and propagating
• Temperature Class for gas-poof: brush discharges caused by rapid flow of
T6, T5, and T4 dust is avoided.
• Ambient Temperature for gas-proof: • The instrument modification or parts
–50 to 75°C (T6), –50 to 80°C (T5), and replacement by other than an authorized
–50 to 75°C (T4) Representative of Yokogawa Electric
• Maximum Process Temperature (Tp.) for Corporation is prohibited and will void the
gas-proof: certification.
85°C (T6), 100°C (T5), and 120°C (T4) • To satisfy IP66 or IP67, apply waterproof
• Maximum Surface Temperature for dust- glands to the electrical connection port.
proof:
T85°C (Tamb.: –30* to 75°C, Tp.: 85°C)
* –15°C when /HE is specified.
c. ATEX Intrinsically Safe Type/ATEX
Note 2. Electrical Data Flameproof Type
• Supply voltage: 42 V dc max. Model EJX/EJA-E Series pressure transmitters
• Output signal: 4 to 20 mA with optional code /KU22 or /V1U1 can
Note 3. Installation be selected the type of protection ATEX
• All wiring shall comply with local installation Flameproof, Intrinsically Safe. Ex ia, or Ex ic for
requirement. use in hazardous area.
• The cable entry devices shall be of a certified Note 1. For the installation of this transmitter,
flameproof type, suitable for the conditions of once a particular type of protection is
use. selected, any other type of protection
Note 4. Operation cannot be used. The installation must be in
• Keep the “WARNING” label attached to the accordance with the description about the
transmitter. type of protection in this user’s manual.
WARNING: AFTER DE-ENERGIZING, Note 2. For combined approval types Once a
DELAY 5 MINUTES BEFORE OPENING. device of multiple approval type is installed,
WHEN THE AMBIENT TEMP.≥65°C, USE it should not be re-installed using any
HEAT-RESISTING CABLE AND CABLE other approval types. Apply a permanent
GLAND ≥90°C. mark in the check box of the selected
• Take care not to generate mechanical approval type on the certification label on
sparking when accessing to the instrument the transmitter to distinguish it from unused
and peripheral devices in a hazardous approval types.
location.
Note 5. Special Conditions for Safe Use

IM 01C25B01-01E
<2. Handling Cautions> 2-10
● ATEX Intrinsically Safe Ex ic
Caution for ATEX intrinsically safe Ex ic WARNING
• Applicable Standard:
• Electrostatic charge may cause an explosion
EN 60079-0:2009/EN 60079-0:2012,
hazard. Avoid any actions that cause the
EN 60079-11:2012
gerenation of eletrostatic charge, such as
• Type of Protection and Marking Code:
rubbing with a dry cloth on coating face of
II 3G Ex ic IIC T4 Gc
the product.
• Ambient Temperature: –30* to +60°C
* –15°C when /HE is specified. • When the lightning protector option is
• Ambient Humidity: specified, the apparatus is not capable
0 to 100% (No condensation) of withstanding the 500V insulation test
• Maximum Process Temperature: 120°C required by EN60079-11. This must be taken
• IP Code: IP66 into account when installing the apparatus.
• Ambient pollution degree: 2
• Overvoltage category: I
(2) Electrical Connection
Note 1. Electrical Data
A mark indicating the electrical connection type
Ui = 30 V
is stamped near the electrical connection port.
Ci = 27.6 nF
These marks are as followed.
Li = 0 µH
Screw Size Marking
Note 2. Installation
• All wiring shall comply with local installation ISO M20 × 1.5 female M
requirements. (refer to the control drawing) ANSI 1/2 NPT female N or W
• Cable glands, adapters and/or blanking
elements shall be of Ex “n”, Ex “e” or Ex “d”
and shall be installed so as to maintain the
specified degree of protection (IP Code) of
the transmitters.
Location of the mark
Note 3. Maintenance and Repair
• The instrument modification or parts F0208.ai

replacement by other than authorized


(3) Installation
representative of Yokogawa Electric
Corporation is prohibited and will void ATEX
intrinsically safe. WARNING
[Control drawing]
• All wiring shall comply with local installation
Hazardous Area Nonhazardous Area
requirements and the local electrical code.
+ • There is no need for conduit seal in Division
Associated
Transmitter
Apparatus 1 and Division 2 hazardous locations

because this product is sealed at the factory.

F0207.ai (4) Operation

Note 4. Specific Conditions of Use


WARNING
• OPEN CIRCUIT BEFORE REMOVING
COVER. INSTALL IN ACCORDANCE WITH
THIS USER’S MANUAL
• Take care not to generate mechanical
sparking when access to the instrument and
peripheral devices in a hazardous location.

IM 01C25B01-01E
<2. Handling Cautions> 2-11
(5) Maintenance and Repair *1: The first digit in the three numbers next to the nine
letters of the serial number appearing after “NO.”
on the nameplate indicates the year of production.
WARNING The following is an example of a serial number for a
product that was produced in 2010:
91K819857 032
The instrument modification or parts replacement
by other than an authorized Representative of The year 2010
Yokogawa Electric Corporation is prohibited and
*2: “180-8750” is a zip code which represents the
will void the certification. following address.
2-9-32 Nakacho, Musashino-shi, Tokyo Japan
*3: The identification number of Notified Body.
(6) Name Plate
2.9.4 IECEx Certification
 Name plate
Model EJX Series pressure transmitters with
optional code /SU2 can be selected the type of
protection (IECEx Intrinsically Safe/type n or
flameproof) for use in hazardous locations.

 Tag plate for flameproof type


Note 1. For the installation of this transmitter,
No. KEMA 07ATEX0109 X
once a particular type of protection is
selected, any other type of protection
Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db
Enlcosure : IP66/IP67
TEMP. CLASS T6 T5 T4
MAX PROCESS TEMP.(Tp.) 85 100 120 °C

cannot be used. The installation must be in


Tamb. -50 to 75 80 75 °C
T85°C(Tamb.:-30(-15) to 75°C, Tp.:85°C)(for Dust)

accordance with the description about the


*3 D
WARNING
type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary
AFTER DE-ENERGIZING, DELAY 5 MINUTES BEFORE
OPENING.
marking is crossed out on the label other
than the selected type of protection when
WHEN THE AMBIENT TEMP. ≥ 65°C, USE THE
HEAT-RESISTING CABLE & CABLE GLAND ≥ 90°C
POTENTIAL ELECTROSTATIC CHARGING HAZARD

 Tag plate for intrinsically safe type


the transmitter is installed.
No. DEKRA 11ATEX 0228 X
Ex ia IIC T4 Ga Ta: -50 TO 60°C
Ex ia IIIC T85°C T100°C T120°C Db Ta:-30(-15) TO 60°C
a. IECEx Intrinsically Safe Type / type n
IP66/IP67
MAX. PROCESS TEMP.(Tp.) 120°C

Caution for IECEx Intrinsically safe and type n.


T85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C)
Ui=30V, Ii=200mA , Pi=0.9W, Ci=27.6nF, Li=0µH

*3 D Note 1. Model EJX Series differential, gauge,


WARNING and absolute pressure transmitters with
optional code /SU2 are applicable for use
POTENTIAL ELECTROSTATIC
CHARGING HAZARD
- SEE USER’S MANUAL
in hazardous locations
• No. IECEx CSA 05.0005
 Tag plate for intrinsically safe Ex ic
Ex ic IIC T4 Gc • Applicable Standard: IEC 60079-0:2000,
IP66
Tamb -30(-15) TO 60°C
MAX. PROCESS TEMP. 120°C
Ui=30V, Ci=27.6nF, Li=0µH
IEC 60079-11:1999, IEC 60079-15:2001
• Ex ia IIC T4, Ex nL IIC T4
• Ambient Temperature: –50 to 60°C
WARNING
• Max. Process Temp.: 120°C
• Enclosure: IP66/IP67
POTENTIAL ELECTROSTATIC
CHARGING HAZARD

Note 2. Entity Parameters


- SEE USER’S MANUAL

F0209.ai
• Intrinsically safe ratings are as follows:
MODEL: Specified model code.
Maximum Input Voltage (Vmax/Ui) = 30 V
STYLE: Style code.
Maximum Input Current (Imax/Ii) = 200 mA
SUFFIX: Specified suffix code.
Maximum Input Power (Pmax/Pi) = 0.9 W
SUPPLY: Supply voltage.
Maximum Internal Capacitance (Ci) = 10 nF
OUTPUT: Output signal.
Maximum Internal Inductance (Li) = 0 µH
MWP: Maximum working pressure.
• Type "n" ratings are as follows:
CAL RNG: Specified calibration range.
Maximum Input Voltage (Vmax/Ui) = 30 V
NO.: Serial number and year of production*1.
Maximum Internal Capacitance (Ci) = 10 nF
TOKYO 180-8750 JAPAN:
Maximum Internal Inductance (Li) = 0 µH
The manufacturer name and the address*2.

IM 01C25B01-01E
<2. Handling Cautions> 2-12
• Installation Requirements • Maximum Process Temperature: 120°C (T4),
Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi, 100°C (T5), 85°C (T6)
Co ≥ Ci + Ccable, Lo ≥ Li + Lcable • Ambient Temperature: –50 to 75°C (T4),
Voc ≤ Vmax, Isc ≤ Imax, –50 to 80°C (T5), –50 to 75°C (T6)
Ca ≥ Ci + Ccable, La ≥ Li + Lcable • Supply Voltage: 42 V dc max.
Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are • Output Signal: 4 to 20 mA dc
parameters of barrier.
Note 2. Wiring
Note 3. Installation • In hazardous locations, the cable entry
• In any safety barrier used output current devices shall be of a certified flameproof
must be limited by a resistor 'R' such that type, suitable for the conditions of use and
Io=Uo/R. correctly installed.
• The safety barrier must be IECEx certified. • Unused apertures shall be closed with
• Input voltage of the safety barrier must be suitable flameproof certified blanking
less than 250 Vrms/Vdc. elements.
• The instrument modification or parts
Note 3. Operation
replacement by other than authorized
• WARNING:
representative of Yokogawa Electric
AFTER DE-ENERGIZING, DELAY 5
Corporation and will void IECEx Intrinsically
MINUTES BEFORE OPENING.
safe and type n certification.
• WARNING:
[Intrinsically Safe] WHEN AMBIENT TEMPERATURE ≥ 65°C,
Hazardous Location Nonhazardous Location USE THE HEAT-RESISTING CABLES ≥
Group IIC, Zone 0 90°C.
General
• Take care not to generate mechanical
IECEx certified Purpose
Pressure Transmitters Safety Barrier Equipment sparking when accessing to the instrument
+ + + + and peripheral devices in a hazardous
Supply – – – – location.
Note 4. Maintenance and Repair
F0210-1.ai • The instrument modification or parts
replacement by other than authorized
[type n]
representative of Yokogawa Electric
Hazardous Location Nonhazardous Location
Corporation is prohibited and will void IECEx
Group IIC, Zone 2
IECEx Certified Certification.
Pressure Transmitters Equipment [nL]
+ +
2.10 EMC Conformity Standards
Supply – –
Not Use EN61326-1 Class A, Table2 (For use in industrial
Safety Barrier
locations)
F0210-2.ai
EN61326-2-3
b. IECEx Flameproof Type
Caution for IECEx flameproof type. CAUTION
Note 1. Model EJX/EJA-E Series pressure To meet EMC regulations, Yokogawa
transmitters with optional code /SF2 or recommends that customers run signal wiring
/SU2 are applicable for use in hazardous through metal conduits or use shielded twisted-
locations: pair cabling when installing EJX/EJA-E series
• No. IECEx CSA 07.0008 transmitters in a plant.
• Applicable Standard: IEC60079-0:2004,
IEC60079-1:2003
• Flameproof for Zone 1, Ex d IIC T6...T4
• Enclosure: IP66/IP67

IM 01C25B01-01E
<2. Handling Cautions> 2-13
2.11 Pressure Equipment *1: PS is maximum pressure for vessel itself based on
Pressure Equipment Directive 97/23/EC. Refer to
Directive (PED) General Specification for maximum working pressure of a
transmitter.
*2: Referred to Table 1 covered by ANNEX II of EC Directive
(1) General on Pressure Equipment Directive 97/23/EC

• EJX/EJA-E Series pressure transmitters are (3) Operation


categorized as piping under the pressure
accessories section of directive 97/23/EC,
which corresponds to Article 3, Paragraph 3 of
CAUTION
PED, denoted as Sound Engineering Practice • The temperature and pressure of fluid should
(SEP). be maintained at levels that are consistent
• EJX110A-MS, EJX110A-HS, with normal operating conditions.
EJX110A-VS, EJ130, EJ440, and • The ambient temperature should be
EJA110E with /HG can be used above 200 maintained at a level that is consistent with
bar and therefore considered as a part of a normal operating conditions.
pressure retaining vessel where category III, • Please take care to prevent water hammer
Module H applies. These models with option and the like from inducing excessive
code /PE3 conform to that category. pressures in pipes and valves. If phenomena
(2) Technical Data are likely, install a safety valve or take
some other appropriate measure to prevent
• Models without /PE3 pressure from exceeding PS.
Article 3, Paragraph 3 of PED, denoted as • Take appropriate measures at the device or
Sound Engineering Practice (SEP). system level to protect transmitters if they
• Models with /PE3 are to be operated near an external heat
Module: H source.
Type of Equipment: Pressure Accessory-Vessel
Type of fluid: Liquid and Gas
Group of fluid: 1 and 2
2.12 Safety Requirement
Capsule PS*1 PS.V
Model
code (bar)
V(L)
(bar.L)
Category*2
Standards
EJA110E M, H, V
160 0.01 1.6 Applicable standard: EN61010-1,
EJ110 F, L
Article 3,
EN61010-2-30
EJX110A Paragraph 3 (1) Pollution Degree 2
EJA110E (SEP)
M, H, V 250 0.01 2.5
with code "Pollution degree" describes the degree to
/HG which a solid, liquid, or gas which deteriorates
EJ110 dielectric strength or surface resistivity is
with code M, H, V 250 0.01 2.5 III adhering. " 2 " applies to normal indoor
/PE3 atmosphere. Normally, only non-conductive
Article 3, pollution occurs. Occasionally, however,
EJ130 M, H 500 0.01 5.0 Paragraph 3
(SEP)
temporary conductivity caused by condensation
EJ130
must be expected.
with code M, H 500 0.01 5.0 III (2) Installation Category I
/PE3
Article 3, "Overvoltage category (Installation category)"
EJ310 L, M, A, B 160 0.01 1.6 Paragraph 3 describes a number which defines a transient
(SEP) overvoltage condition. It implies the regulation
Article 3,
for impulse withstand voltage. " I " applies to
EJ430 H, A, B 160 0.01 1.6 Paragraph 3
(SEP) electrical equipment which is supplied from the
Article 3, circuit when appropriate transient overvoltage
EJ440 C, D 500 0.1 5.0 Paragraph 3 control means (interfaces) are provided.
(SEP)
(3) Altitude of installation site:
EJ440
with code C, D 500 0.1 5.0 III Max. 2,000 m above sea level
/PE3
(4) Indoor/Outdoor use

IM 01C25B01-01E
<3. Component Names> 3-1

3. Component Names
Vertical impulse piping type

Pressure-detector section
Terminal box cover

Cover flange
Horizontal impulse piping type

External indicator
conduit connection (Note 1)

Conduit
connection

Zero-
adjustment
screw
(Note 2)
Slide switch

Integral
indicator (Note 1)
Mounting screw Vent plug

CPU assembly
Drain plug
Process
Process connection
connector (Note 1)
Range-setting Burnout direction switch
switch (Note 1)
(See section 7.6) BO H L

Transmitter section WR E D
Amplifier Cover
Write protection switch
Burnout direction switch (BO) Hardware write protection switch (WR)

Burnout Direction H L H L Write Protection H L H L


Switch Position Switch Position E D E D

NO YES
Burnout Direction HIGH LOW Write Protection (Write enabled) (Write disabled)
F0301.ai

Note 1: See subsection 9.2, “Model and Suffix Codes,” for details. A process connector will not be applied for lower side of EJ310,
EJ430, and EJ440.
Note 2: Applicable for BRAIN/HART communication type. Set the switches as shown in the figure above to set the burn-out direction
and write protection. The Burnout switch is set to the H side for delivery (unless option code /C1 or /C2 is specified in the order),
and the hardware write protection switch is set to E side. The setting of the switches can be confirmed via communication. An
external zero adjustment screw can only be disabled by communication. To disable the screw, set a parameter before activating
the hardware write protect function. See each communication manual.
Figure 3.1 Component Names

Table 3.1 Display Symbol


Display Symbol Meaning of Display Symbol
Display mode is ‘square root’. (Display is not lit when ‘linear’ mode.)
The output signal being zero-adjusted is increasing.
Besides, this symbol lights when local parameter setting is in progress.
The output signal being zero-adjusted is decreasing.
Besides, this symbol lights when local parameter setting is in progress.
Write protect function is enabled.
F0302.ai

IM 01C25B01-01E
<4. Installation> 4-1

4. Installation
4.1 Precautions
Before installing the transmitter, read the cautionary
notes in section 2.4, “Selecting the Installation
Location.” For additional information on the
ambient conditions allowed at the installation 57 mm 54 mm 51 mm
location, refer to subsection 9.1 “Standard F0401.ai

Specifications.” Figure 4.1 Process Connector Impulse Piping


Connection Distances for Differential
Pressure Transmitters
IMPORTANT
• When welding piping during construction, Figure 4.1 and 4.2 shows the mounting of the
take care not to allow welding currents to transmitter for horizontal piping and vertical piping
flow through the transmitter. with using the mounting bracket. The transmitters
• Do not step on this instrument after with the installation code -U (Universal flange) can
installation. be used for either type of mounting.
• For the EJ430 and EJ440, the Vertical pipe mounting
atmospheric opening is located on the low
pressure side cover flange. The opening
must not face upward. See section 9.4,
“Dimensions,” for the location of the opening. Transmitter
mounting bolt

4.2 Mounting
■ The transmitter is shipped with the process
connection, according to the ordering
U-bolt nut
specifications. To change the orientation of the
process connections, refer to section 4.3. Mounting bracket
■ With differential pressure transmitters, U-bolt
the distance between the impulse piping 50 mm(2-inch) pipe
connection ports is usually 54 mm (figure 4.1).
Horizontal pipe mounting
By changing the orientation of the process
connector, the dimension can be changed to 51
mm or 57 mm.
■ The transmitter can be mounted on a nominal
Transmitter
50 mm (2-inch) pipe using the mounting mounting bolt
bracket supplied, as shown in figure 4.2 and
4.3 The transmitter can be mounted on either a
horizontal or a vertical pipe.
■ When mounting the bracket on the transmitter,
tighten the (four) bolts that hold the transmitter
U-bolt nut
with a torque of approximately 39 N·m {4kgf·m}.
Mounting bracket
U-bolt
50 mm(2-inch) pipe F0402.ai

Figure 4.2 Transmitter Mounting (Horizontal


Impulse Piping Type)

IM 01C25B01-01E
<4. Installation> 4-2
Vertical pipe mounting 4.3 Changing the Process
(Process connector downside)
Connection
Transmitter
mounting bolt The transmitter is shipped with the process
Mounting bracket connection specified at the time of ordering. To
change the process connection, the drain (vent)
50 mm(2-inch) pipe
plug must be repositioned.
U-bolt nut
U-bolt To reposition a drain (vent) plug, use a wrench to
slowly and gently unscrew it. Then, remove and
remount it on the opposite side. Wrap sealing tape
around the drain (vent) plug threads (*1 in the figure
below), and apply a lubricant to the threads of the
drain (vent) screw(s) (*2 below). To tighten the drain
(vent) plugs, apply a torque of 34 to 39 N·m (3.5 to 4
kgf·m). Process connector bolts are to be tightened
Vertical pipe mounting uniformly to a torque shown in table 4.1.
(Process connector upside)
Table 4.1 Torque
EJ110
EJ120 EJ440
Model EJ130
Mounting bracket EJ310 C capsule D capsule
EJ430
50 mm(2-inch) pipe Torque(N·m) 49 to 59
39 to 49 {4 to 5}
{kgf·m} {5 to 6}
U-bolt nut
U-bolt
Vertical impulse piping type Horizontal impulse piping type

Bolt
Transmitter
mounting bolt F0403.ai Process gasket
connector
Figure 4.3 Transmitter Mounting (Vertical Impulse
Piping Type)

*1
Vent/Drain plug *2 Note: For a horizontal impulse
piping type, moving the
process connectors from
the front side to the
back cannot be made.
F0404.ai

Figure 4.4 Changing Process Connection

IM 01C25B01-01E
<4. Installation> 4-3
4.4 Swapping the High/Low- 4.4.2 Using the Communicator
pressure Side Connection This method is applicable only to the Model
EJ110, EJ120, and EJ130.
IMPORTANT With a communicator, you can change which
This section is applicable only for EJ110, process connection is used as the high-pressure
EJ120, and EJ130 differential side without mechanically rotating the pressure-
transmitters, and not applicable for gauge or detector section 180 as described in subsection
absolute pressure transmitters. 4.4.1. To change, call parameter ‘D15: H/L SWAP’
for BRAIN Communication or ‘H/L swap’ for HART
Communication and select REVERSE (right side:
4.4.1 Rotating Pressure-detector Section low pressure; left side: high pressure) or select
180° NORMAL to change back to normal (right side: high
This procedure can be applied only to a transmitter pressure; left side: low pressure).
with a vertical impulse piping type. NORMAL

The procedure below can be used to turn the Output


pressure detector assembly 180°. Perform
this operation in a maintenance shop with the
necessary tools laid out and ready for use, and then
install the transmitter in the field after making the
change. Input

1) Use an Allen wrench (JIS B4648, nominal 2.5


mm) to remove the two setscrews at the joint
between the pressure-detector section and
transmitter section.
REVERSE
2) Leaving the transmitter section in position, F0406.ai

rotate the pressure-detector section 180°. Figure 4.6 Input/Output Relationship


3) Tighten the two setscrews to fix the pressure-
detector section and transmitter section
IMPORTANT
together (at a torque of 1.5 N·m).
Reposition the process connector and drain Since the H/L label plate on the capsule
(vent) plugs to the opposite side as described in assembly will remain unchanged, use this
subsection 4.3. function only when you cannot switch the
Process connector impulse piping. If the ‘H/L SWAP’ parameter
setting is changed, the input/output relationship
is reversed as shown in figure 4.6; be sure this is
understood by all.

Setscrew
Before After rotating 180°
F0405.ai

Figure 4.5 Before and After Modification

IM 01C25B01-01E
<4. Installation> 4-4
4.5 Rotating Transmitter Section 4.6 Changing the Direction of
The transmitter section can be rotated Integral Indicator
approximately 360° (180° to either direction or
360° to one direction from the original position at IMPORTANT
shipment, depending on the configuration of the
Always turn OFF power, release pressure and
instrument.) It can be fixed at any angle within
remove a transmitter to non-hazardous area
above range.
before disassembling and reassmbling an
1) Remove the two setscrews that fasten the indicator.
transmitter section and capsule assembly,
using the Allen wrench. An integral indicator can be installed in the
2) Rotate the transmitter section slowly and stop it following three directions. Follow the instructions in
at designated position. section 8.4 for removing and attaching the integral
3) Tighten the two setscrews to a torque of 1.5 indicator.
N·m.

IMPORTANT
Do not rotate the transmitter section more than
the above limit.
F0408.ai

Vertical impulse piping type Figure 4.8 Integral Indicator Direction

Pressure-detector section
Stopper
Rotate 0 to ±180° segments

Conduit connection

Transmitter section

Horizontal impulse piping type

Transmitter section

Rotate 0 to ±180° segments

Conduit connection
Zero-adjustment screw

Pressure-detector section

F0407.ai

Figure 4.7 Rotating Transmitter Section (Left Side


High Pressure Type)

IM 01C25B01-01E
<5. Installing Impulse Piping> 5-1

5. Installing Impulse Piping


5.1 Impulse Piping Installation (2) Changing the Process Connector Piping
Connections (Figure 4.1) (for differential
Precautions pressure transmitters)
The impulse piping that connects the process The impulse piping connection distances can be
outputs to the transmitter must convey the process changed between 51 mm, 54 mm and 57 mm by
pressure accurately. If, for example, gas collects changing the orientation of the process connectors.
in a liquid-filled impulse line, or the drain for a This is convenient for aligning an impulse line with a
gas-filled impulse line becomes plugged, it will process connectors.
not convey the pressure accurately. Since this will
cause errors in the measurement output, select (3) Tightening the Process Connector Mounting
the proper piping method for the process fluid Bolts
(gas, liquid, or steam). Pay careful attention to the
following points when routing the impulse piping After connecting an impulse line, tighten the
and connecting the impulse piping to a transmitter. process connector mounting bolts uniformly.

5.1.1 Connecting Impulse Piping to a (4) Removing the Impulse Piping Connecting
Transmitter Port Dustproof Cap
The impulse piping connecting port on the
(1) Check the High and Low Pressure transmitter is covered with a plastic cap to keep out
Connections on the Transmitter (Figure 5.1) dust. This cap must be removed before connecting
Symbols “H” and “L” have been placed on the the line. (Be careful not to damage the threads
capsule assembly to indicate high and low pressure when removing this cap. Never insert a screwdriver
side. With differential pressure transmitters, connect or other tool between the cap and port threads to
the high pressure side impulse line to the “H” side, remove the cap.)
and the low pressure side impulse line to the “L”
side. (5) Connecting the Transmitter and 3-
Valve Manifold (for differential pressure
With gauge/absolute pressure transmitters, connect transmitters)
the impulse line to the ‘H’ side.
A 3-valve manifold consists of two stop valves to
Differential Pressure Transmitter block process pressure and an equalizing valve
to equalize the pressures on the high and low
“H” and “L” are shown
pressure sides of the transmitter. Such a manifold
Process connection
Pressure makes it easier to disconnect the transmitter
connection
Process connector from the impulse piping, and is convenient when
Bolt
adjusting the transmitter zero point.
There are two 3-valve manifold types: the pipe-
Gauge/Absolute Pressure Transmitters
mounting type and the direct-mounting type; care
“H” and “L” are shown should be taken with respect to the following points
when connecting the manifold to the transmitter.
Process connection

Process connector

Bolt
F0501.ai

Figure 5.1 “H” and “L” Symbols on a Capsule


Assembly

IM 01C25B01-01E
<5. Installing Impulse Piping> 5-2
 Pipe-Mounting Type 3-Valve Manifold  Direct-Mounting Type 3-Valve Manifold
(Figure 5.2) (Figure 5.3)
1) Screw nipples into the connection ports on the 1) Mount the 3-valve manifold on the transmitter.
transmitter side of the 3-valve manifold, and (When mounting, use the two gaskets and the
into the impulse piping connecting ports on four bolts provided with the 3-valve manifold.
the process connectors. (To maintain proper Tighten the bolts evenly.)
sealing, wind sealing tape around the nipple 2) Mount the process connectors and gaskets
threads.) on the top of the 3-valve manifold (the side on
2) Mount the 3-valve manifold on the 50 mm (2- which the impulse piping will be connected).
inch) pipe by fastening a U-bolt to its mounting Bolts Impulse
piping
bracket. Tighten the U-bolt nuts only lightly at Process Stop valve
connector 3-valve
this time.
Gasket manifold
3) Install the pipe assemblies between the 3-valve Equalizing
valve
manifold and the process connectors and lightly
tighten the ball head lock nuts. (The ball-shaped
Stop valve
ends of the pipes must be handled carefully,
since they will not seal properly if the ball
surface is scratched or otherwise damaged.)
Equalizing valve
4) Now tighten the nuts and bolts securely in the
Stop valve
following sequence:
Impulse
Process connector bolts → transmitter-end ball piping
head lock nuts → 3-valve manifold ball head
Gasket Bolts
lock nuts → 3-valve manifold mounting bracket
Process Stop valve 3-valve
U-bolt nuts connector manifold
F0503.ai
Impulse piping
Nipple Figure 5.3 3-Valve Manifold (Direct-Mounting
Vent plug 3-valve Type)
(optional) manifold Ball head
lock nut
Stop valve
(low pressure side)
NOTE
Pipe
Equalizing valve Pipes After completing the connection of the transmitter
(balancing) and 3-valve manifold, be sure to CLOSE the low
Ball head pressure and high pressure stop valves, OPEN
lock nut
Stop valve the equalizing valve, and leave the manifold with
(high pressure side) Nipple the equalizing valve OPEN.
50 mm(2-inch) pipe Process You must do this in order to avoid overloading
Process connector
connector bolts
the transmitter from either the high or the low
F0502.ai
pressure side when beginning operation.
This instruction must also be followed as part of
Figure 5.2 3-Valve Manifold (Pipe-Mounting Type)
the startup procedure (chapter 7.)

IM 01C25B01-01E
<5. Installing Impulse Piping> 5-3
5.1.2 Routing the Impulse Piping (3) Impulse Piping Slope
The impulse piping must be routed with only an
(1) Process Pressure Tap Angles
upward or downward slope. Even for horizontal
If condensate, gas, sediment or other extraneous routing, the impulse piping should have a slope of
material in the process piping gets into the impulse at least 1/10 to prevent condensate (or gases) from
piping, pressure measurement errors may result. To accumulating in the pipes.
prevent such problems, the process pressure taps
must be angled as shown in figure 5.4 according to (4) Temperature Difference Between Impulse
the kind of fluid being measured. Lines (for differential pressure transmitters)
If there is a temperature difference between the
NOTE high and low impulse lines, the density difference
• If the process fluid is a gas, the taps must be of the fluids in the two lines will cause an error in
vertical or within 45° either side of vertical. the measurement pressure. When measuring flow,
• If the process fluid is a liquid, the taps must impulse lines must be routed together so that there
be horizontal or below horizontal, but not is no temperature difference between them.
more than 45° below horizontal.
(5) Condensate Pots for Steam Flow
• If the process fluid is steam or other
Measurement (for differential pressure
condensing vapor, the taps must be
transmitters)
horizontal or above horizontal, but not more
than 45° above horizontal. If the liquid in the impulse piping repeatedly
condenses or vaporizes as a result of changes
[Gas] [Liquid] [Steam]
in the ambient or process temperature, this will
45° 45°
Pressure cause a difference in the fluid head between the
taps 45° 45°
high pressure and low pressure sides. To prevent
Process 45° 45° measurement errors due to these head differences,
piping condensate pots are used when measuring steam
F0504.ai
flow.
Figure 5.4 Process Pressure Tap Angle
(For Horizontal Piping)
(6) Preventing Wind Speed Effects in Very Low
Differential Pressure Measurement
(2) Position of Process Pressure Taps and (for differential pressure transmitters)
Transmitter
If condensate (or gas) accumulates in the impulse IMPORTANT
piping, it should be removed periodically by When using a differential pressure transmitter
opening the drain (or vent) plugs. However, this will to measure very low pressures (draft pressure),
generate a transient disturbance in the pressure the low pressure connection port is left open
measurement, and therefore it is necessary to to atmospheric pressure (the reference
position the taps and route the impulse piping so pressure). Any wind around the differential
that any extraneous liquid or gas generated in the pressure transmitter will therefore cause errors
leadlines returns naturally to the process piping. in the measurement. To prevent this, it will be
• If the process fluid is a gas, then as a rule the necessary either to enclose the transmitter in
transmitter must be located higher than the a box, or to connect an impulse line to the low
process pressure taps. pressure side and insert its end into a wind-
• If the process fluid is a liquid or steam, then as a excluding pot (cylindrical with a base plate).
rule the transmitter must be located lower than
the process pressure taps.

IM 01C25B01-01E
<5. Installing Impulse Piping> 5-4
(7) Preventing Freezing Liguid Gas Steam
If there is any risk that the process fluid in the Orifice Condensate pot
impulse piping or transmitter could freeze, use a Tap
valve
steam jacket or heater to maintain the temperature
of the fluid.
Union
or flange
NOTE
Tee
After completing the connections, close the
valves on the process pressure taps (main 3-valve
valves), the valves at the transmitter (stop manifold
valves), and the impulse piping drain valves, Drain
so that condensate, sediment, dust and other valve Drain
plug
extraneous material cannot enter the impulse F0505.ai
piping. Figure 5.5 Impulse Piping Connection Examples
for Differential Pressure Transmitters

5.2 Impulse Piping Connection Liquid Gas Steam

Examples Union or flange


Tap valve
Figure 5.5 and 5.6 show examples of typical
Union or flange
impulse piping connections. Before connecting the Drain plug
transmitter to the process, study the transmitter Drain valve Tap valve
installation location, the process piping layout,
and the characteristics of the process fluid
Union or
(corrosiveness, toxicity, flammability, etc.), in order flange
to make appropriate changes and additions to the Tee
Tee Tee
connection configurations.
Note the following points when referring to these Union or flange
piping examples. Tap valve
• The high pressure connecting port on the Drain valve Drain valve
transmitter is shown on the right (as viewed Drain plug Drain plug
from the front). F0506.ai

• The transmitter impulse piping connection is Figure 5.6 Impulse Piping Connection Examples
shown for a vertical impulse piping connection for Gauge/absolute Pressure
configuration in which the direction of Transmitters
connection is either upwards or downwards.
• If the impulse line is long, bracing or supports
should be provided to prevent vibration.
• The impulse piping material used must
be compatible with the process pressure,
temperature, and other conditions.
• A variety of process pressure tap valves (main
valves) are available according to the type
of connection (flanged, screwed, welded),
construction (globe, gate, or ball valve),
temperature and pressure. Select the type of
valve most appropriate for the application.

IM 01C25B01-01E
<6. Wiring> 6-1

6. Wiring
6.1 Wiring Precautions 6.3 Connections of External
IMPORTANT Wiring to Terminal Box
• Lay wiring as far as possible from electrical 6.3.1 Power Supply Wiring Connection
noise sources such as large capacity
transformers, motors, and power supplies. IMPORTANT
• Remove the electrical connection dust cap
Connecting with the commercial AC power
before wiring.
supply will damage the device. Be sure to use
• All threaded parts must be treated with
the DC power supply in the predetermined
waterproofing sealant. (A non-hardening
range.
silicone group sealant is recommended.)
• To prevent noise pickup, do not pass signal
Connect the power supply wiring to the SUPPLY +
and power cables through the same ducts.
and – terminals. When /AL is specified, also refer to
• Explosion-protected instruments must
subsection 6.3.5.
be wired in accordance with specific
requirements (and, in certain countries, Transmitter terminal box
legal regulations) in order to preserve the +
Power supply
effectiveness of their explosion-protected

features.
• The terminal box cover is locked by an F0601.ai

Allen head bolt (a shrouding bolt) on ATEX Figure 6.1 Power Supply Wiring Connection
flameproof type transmitters. When the
shrouding bolt is driven clockwise using
6.3.2 External Indicator Connection
an Allen wrench, it goes in. The cover lock
can then be released and the cover can Available only when /AL is not specified.
be opened by hand. See subsection 8.4 Connect wiring for external indicators to the CHECK
“Disassembly and Reassembly” for details. A (+) and SUPPLY – terminals.
• Plug and seal an unused conduit connection.
(Note) Use a external indicator whose internal resistance is 10 Ω
or less.

External indicator
6.2 Selecting the Wiring Power supply
+
Materials

(a) Use stranded leadwires or cables which are
the same as or better than 600 V grade PVC
insulated wire (JIS C3307) or its equivalent. Transmitter terminal box
F0602.ai
(b) Use shielded wires in areas that are susceptible
Figure 6.2 External Indicator Connection
to electrical noise.
(c) In areas with higher or lower ambient
temperatures, use appropriate wires or cables.
(d) In environment where oils, solvents, corrosive
gases or liquids may be present, use wires or
cables that are resistant to such substances.
(e) It is recommended that crimp-on solderless
terminal lugs (for 4 mm screws) with insulating
sleeves be used for leadwire ends.

IM 01C25B01-01E
<6. Wiring> 6-2
6.3.3 Communicator Connection 6.3.5 Status Output Connection
When option code /AL is specified, connect the
IMPORTANT external wiring as shown in Figure 6.5.
Analog output may change temporally in To configure and activate the process alarm
connecting with BRAIN terminal due to an initial function and status output, it is necessary to set
current flowed to it. To prevent communication some parameters. Refer to each communication
signal affecting the upper system, it is manual for procedures.
recommended to install a low-pass filter
(approximately 0.1s) Transmitter
24V DC
terminal box Shielded cable
+
Distributor
Connect the BT200 or HART Communicator to the – 250Ω
SUPPLY + and – terminals. (Use hooks.)
Transmitter terminal box Power supply Magnetic
+ External power
valve

supply 30V DC,


– 120mA max
Ignore the polarity since the Use two-wire separately shielded cables. AC power supply
BT200 is AC-coupled to the F0605.ai
terminal box.
BT200
Figure 6.5 Status Output Connection
F0603.ai

Figure 6.3 BT200 Connection

6.4 Wiring
6.3.4 Check Meter Connection
Available only when /AL is not specified. 6.4.1 Loop Configuration
Connect the check meter to the CHECK A (+) and Since the DPharp uses a two-wire transmission
SUPPLY – terminals. (Use hooks.) system, signal wiring is also used as power wiring.

• A 4 to 20 mA DC output signal from the CHECK DC power is required for the transmitter loop. The
A (+) and SUPPLY – terminals. transmitter and distributor are connected as shown
(Note) Use a check meter whose internal resistance is 10 Ω or
below.
less.
For details of the power supply voltage and load
Check meter Transmitter terminal box Power supply resistance, see section 6.6; for communications line
+ requirements, see section 9.1.

(1) General-use Type and Flameproof Type

Hazardous Location Nonhazardous Location

Transmitter terminal box


F0604.ai
Distributor
(Power supply unit)
Figure 6.4 Check Meter Connection

Receiver
instrument

F0606.ai

Figure 6.6 Connection between Transmitter and


Distributor

IM 01C25B01-01E
<6. Wiring> 6-3
(2) Intrinsically Safe Type (2) Flameproof Type
With the intrinsically safe type, a safety barrier must Wire cables through a flameproof packing adapter,
be included in the loop. or use a flameproof metal conduit.
Hazardous Location Nonhazardous Location ■ Wiring cable through flameproof packing
adapter.
Transmitter terminal box
Distributor
• Apply a non-hardening sealant to the terminal
(Power supply unit) box connection port and to the threads on the
flameproof packing adapter for waterproofing.
Receiver
instrument
Flameproof packing
adapter

Safety barrier Flexible metal conduit


F0607.ai

Figure 6.7 Connection between Transmitter and Wiring metal


Apply a non-hardening
Distributor conduit
sealant to the threads for
waterproofing.
Tee
6.4.2 Wiring Installation
Drain plug
F0609.ai

(1) General-use Type and Intrinsically Safe Figure 6.9 Typical Cable Wiring Using Flameproof
Type Packing Adapter
With the cable wiring, use a metallic conduit or
■ Flameproof metal conduit wiring
waterproof glands.
• A seal fitting must be installed near the terminal
• Apply a non-hardening sealant to the terminal box connection port for a sealed construction.
box connection port and to the threads on the • Apply a non-hardening sealant to the threads of
flexible metal conduit for waterproofing. the terminal box connection port, flexible metal
conduit and seal fitting for waterproofing.
Gas sealing device
Non-hazardous area

Flexible metal conduit


Flameproof flexible
Wiring metal Apply a non-hardening metal conduit
conduit sealant to the threads for
waterproofing. Hazardous area
Flameproof Apply a non-hardening
Tee heavy-gauge sealant to the threads of
steel conduit these fittings for
Drain plug waterproofing
F0608.ai

Figure 6.8 Typical Wiring Using Flexible Metal Tee Seal fitting
Conduit After wiring, impregnate the fitting
Drain plug
with a compound to seal tubing.
F0610.ai

Figure 6.10 Typical Wiring Using Flameproof Metal


Conduit

IM 01C25B01-01E
<6. Wiring> 6-4

6.5 Grounding
Grounding is always required for the proper
operation of transmitters. Follow the domestic
electrical requirements as regulated in each
country. For a transmitter with a built-in lightning
protector, grounding should satisfy ground
resistance of 10Ω or less.
Ground terminals are located on the inside and
outside of the terminal box. Either of these terminals
may be used.

Ground terminal
(inside)

Ground terminal
(outside)

F0611.ai

Figure 6.11 Ground Terminals

6.6 Power Supply Voltage and


Load Resistance
When configuring the loop, make sure that the
external load resistance is within the range in the
figure below.
(Note) In case of an intrinsically safe transmitter, external load
resistance includes safety barrier resistance.

600

External E–10.5
R= Communication
load 0.0244
applicable range
resistance BRAIN and HART
R (Ω)

250

0 10.5 16.6 25.2 42


Power supply voltage E (V DC)
F0612.ai

Figure 6.12 Relationship between Power Supply


Voltage and External Load Resistance

IM 01C25B01-01E
<7. Operation> 7-1

7. Operation
7.1 Preparation for Starting Venting Gas from the Transmitter Pressure-
detector Section
Operation
• Since the piping in the example of figure 7.1
This section describes the operation procedure for
is constructed to be self-venting, no venting
the EJ110, EJ120 and EJ130 as shown
operation is required. If it is not possible to
in figure 7.1a (vertical impulse piping type, high-
make the piping self-venting, refer to subsection
pressure connection: right side) when measuring
7.5 for instructions. Leave the equalizing valve
the liquid flow rate, and EJ430, EJ440 and
open even after venting gas.
EJ310 as shown in figure 7.1b when measuring
(b) Turn ON power and connect the communicator.
pressure.
Open the terminal box cover, and connect
the communicator to the SUPPLY + and
NOTE – terminals.
Check that the process pressure tap valves, (c) Using the communicator, confirm that the
drain valves, and 3-valve manifold stop valves transmitter is operating properly. Check
on both the low pressure and high pressure parameter values or change the setpoints as
sides are closed, and that the 3-valve manifold necessary.
equalizing valve is opened. See IM 01C25T03-01E (BRAIN
communication) or IM 01C25T01-06EN (HART
(a) Follow the procedures below to introduce communication) for communicator operation.
process pressure into the impulse piping and If the transmitter is equipped with an integral
transmitter. indicator, its indication can be used to confirm
that the transmitter is operating properly.
■ Differential Pressure Transmitters
Orifice
1) Open the low pressure and high pressure tap Tap valve
(high pressure)
valves to fill the impulse piping with process Tap valve
liquid. (low pressure)

2) Slowly open the high pressure stop valve to fill


the transmitter pressure-detector section with
process liquid.
3) Close the high pressure stop valve.
4) Gradually open the low pressure stop valve and
completely fill the transmitter pressure-detector
section with process liquid.
Stop valve
5) Close the low pressure stop valve. (low pressure)
3-valve manifold
6) Gradually open the high pressure stop valve. At
this time, equal pressure is applied to the low Equalizing valve
and high pressure sides of the transmitter.
Stop valve
7) Check that there are no liquid leaks in the (high pressure)
impulse piping, 3-valve manifold, transmitter, or
other components. Drain valve
(high pressure)
■ Gauge/Absolute Pressure Transmitters F0701.ai

1) Open the tap valve (main valve) to fill the Figure 7.1a Liquid Flow Measurement
impulse piping with process fluid.
2) Gradually open the stop valve to introduce
process fluid into the transmitter pressure-
detector section.
3) Confirm that there is no pressure leak in
the impulse piping, transmitter, or other
components.

IM 01C25B01-01E
<7. Operation> 7-2

PARAM
C60:SELF CHECK
ERROR
Vent plug (Fill plug)
communication error

Tap valve DATA DIAG PRNT ESC

Communication error Self-diagnostic error


(Faulty wiring) (Faulty transmitter)
Stop valve F0703.ai

Figure 7.2 BT200 Display

Using the integral indicator


• If the wiring system is faulty, the display stays
blank.
• If the transmitter is faulty, an error code is
Drain valve displayed.
F0702.ai

Figure 7.1b Liquid Pressure Measurement

■ Confirming that Transmitter is Operating


Properly
Self-diagnostic error on the integral indicator
Using the BT200 (Faulty transmitter) F0704.ai

Figure 7.3 Integral Indicator with Error Code


IMPORTANT
• Analog output may change temporally in NOTE
connecting with BRAIN terminal due to
an initial current flowed to it. To prevent If any of the above errors are indicated on
communication signal affecting the upper the display of the integral indicator or the
system, it is recommended to install a low- communicator, refer to subsection 8.5.3 for the
pass filter (approximately 0.1s). corrective action.
• Communication signal is superimposed on
analog output signal. It is recommended
■ Verify and Change Transmitter Parameter
to set a low-pass filter (approximately
Setting and Values
0.1s) to the receiver in order to reduce the
output effect from communication signal. The parameters related to the following items are
Before online-communication, confirm that set at factory as specified in order.
communication signal does not give effect on • Calibration range
the upper system. • Integral indicator display
• Output mode
• If the wiring system is faulty, ‘communication • Software damping (optional)
error’ appears on the display. Other parameters like following are shipped with the
• If the transmitter is faulty, ‘SELF CHECK default setting.
ERROR’ appears on the display. • Low-cut
• Process alarm setting
• Static pressure range
• Signal characterizer
• Write protection
To confirm or change the values, see IM 01C25T01-
06EN or 01C25T03-01E.

IM 01C25B01-01E
<7. Operation> 7-3
7.2 Zero Point Adjustment The zero-adjustment screw is located inside the
cover.
After completing preparations for operating the Use a slotted screwdriver to turn the zero-
transmitter, adjust the zero point. adjustment screw. Equalize the transmitter, then
Zero point adjustment can be done by turning the turn the screw clockwise to increase the output or
transmitter’s zero-adjustment screw or by using counterclockwise to decrease the output. The zero
the communicator. This section describes the point adjustment can be made with a resolution
procedure for the zero-adjustment screw. For the of 0.01% of the setting range. The degree of zero
communicator procedure, see the communication adjustments varies with the screw turning speed;
manual. turn the screw slowly to make a fine adjustment,
quickly to make a rough adjustment.
IMPORTANT When using differential pressure transmitters for
Do not turn off the power to the transmitter level measurement and if you cannot obtain the
immediately after performing a zero point lower range value from the actual measurement
adjustment. Powering off within 30 seconds of value of 0%, refer to subsection 7.2.2(2).
performing this procedure will return the zero
7.2.2 Adjusting Zero Point for Gauge/
point to its previous setting.
Absolute Pressure Transmitters

(1) When you can obtain the Low Range Value


NOTE from the actual measured value of 0% (0
Before performing this adjustment, make sure kPa, atmospheric pressure);
that the external zero adjustment function has For pressure measurement using gauge pressure
NOT been disabled by a parameter setting. transmitters, follow the steps below before
performing zero point adjustment.
To check the output signal, use a digital multimeter,
1) Close the tap valve (main valve).
calibrator, or communicator.
2) Loosen the fill plug so that the pressure applied
7.2.1 Adjusting Zero Point for Differential to the transmitter is only the head of the seal
Pressure Transmitters liquid.
3) Adjust the zero point at this status.
Before adjusting zero point, make sure that the 4) After the adjustment, close the fill plug and then
equalizing valve is open. gradually open the tap valve.
Use a slotted screwdriver to turn the zero-
adjustment screw. Turn the screw clockwise
to increase the output or counterclockwise to
decrease the output. The zero point adjustment can
be made with a resolution of 0.01% of the setting
Zero-adjustment range. Since the degree of the zero adjustment
screw cover
F0705.ai
varies with the screw turning speed, turn the screw
slowly to make a fine adjustment and quickly to
Figure 7.4 External Zero Adjustment Screw make a rough adjustment.

IM 01C25B01-01E
<7. Operation> 7-4
(2) When you cannot obtain the Low Range
Value from the actual measured value of IMPORTANT
0%;
• Remove the communicator from the terminal
Adjust the transmitter output to the actual measured box, and confirm that none of the terminal
value obtained by a digital manometer or a glass screws are loose.
gauge. • Close the terminal box cover and the
[Example] amplifier cover. Screw each cover in tightly
until it will not turn further.
The measuring range of 50 to 250 kPa; the actual • There are two covers that must be locked
measured value of 130 kPa. on the ATEX Flameproof type transmitters.
130–50 An Allen head bolt (shrouding bolt) under
Actual measured value= x100=40.0% the edge of each cover is used to lock the
250–50
(=10.4mA) cover. When the shrouding bolt is driven
counterclockwise with an Allen wrench, the
Turn the screw to match the output signal to the
bolt rotates upward and locks the cover. (See
actual measured value.
section 8.4.) After locking the covers, confirm
that they are secure and cannot be opened
7.3 Starting Operation by hand.
Tighten the zero-adjustment cover mounting
After completing the zero point adjustment, follow screw to secure the cover.
the procedures below to start operation. Steps • Tighten the zero-adjustment cover mounting
1) and 2) are specific to the differential pressure screw to secure the cover.
transmitters.
1) Close the equalizing valve.
2) Gradually open the low pressure stop valve. 7.4 Shutting Down the
This places the transmitter in an operational
condition. Transmitter
3) Confirm the operating status. If the output Shut down the transmitter as follows.
signal exhibits wide fluctuations (hunting) due to Steps 2) and 3) are specific to the differential
periodic variation in the process pressure, use pressure transmitters.
the communicator to dampen the transmitter
1) Turn off the power.
output signal. Confirm the hunting using a
2) Close the low pressure stop valve.
receiving instrument or the integral indicator,
3) Open the equalizing valve.
and set the optimum damping time constant.
4) Close the high pressure stop valve.
4) After confirming the operating status, perform
5) Close the high pressure and low pressure tap
the following.
valves.

NOTE
• Whenever shutting down the transmitter for a
long period, remove any process fluid that is
in the transmitter pressure-detector section.
• The equalizing valve must be left OPEN.

IM 01C25B01-01E
<7. Operation> 7-5
7.5 Venting or Draining 7.5.2 Venting Gas
Transmitter Pressure- 1) Gradually open the vent screw to vent gas from
the transmitter pressure-detector section. (See
detector Section figure 7.6.)
Since this transmitter is designed to be self- 2) When the transmitter is completely vented,
draining and self-venting with vertical impulse close the vent screw.
piping connections, neither draining nor venting 3) Tighten the vent screw to a torque of 10 N·m.
will be required if the impulse piping is configured
appropriately for self-draining or self-venting
Vent screw
operation.
If condensate (or gas) collects in the transmitter
pressure-detector section, the measured pressure
may be in error. If it is not possible to configure the
piping for self-draining (or self-venting) operation,
you will need to loosen the drain (vent) screw on the
Vent screw
transmitter to completely drain (vent) any stagnated
liquid (gas.)
When you loosen the vent screw, the gas
escpes in the direction of the arrow.
However, since draining condensate or bleeding off F0707.ai

gas disturbs the pressure measurement, this should Figure 7.6 Venting the Transmitter
not be done when the loop is in operation.

WARNING 7.6 Local Parameter Setting


Since the accumulated liquid (or gas) may be
toxic or otherwise harmful, take appropriate care
WARNING
to avoid contact with the body, or inhalation of The local push button on the integral indicator
vapors. must not be used in a hazardous area. When it is
necessary to use the push button, operate it in a
7.5.1 Draining Condensate non- hazardous location.

1) Gradually open the drain screw or drain plug


and drain the transmitter pressure-detector IMPORTANT
section. (See figure 7.5.)
2) When all accumulated liquid is completely • Do not turn off the power to the transmitter
removed, close the drain screw or drain plug. immediately after performing parameter
3) Tighten the drain screw to a torque of 10 N·m, setting. Powering off within 30 seconds of
and the drain plug to a torque of 34 to 39 N·m. performing this procedure will return the
parameter to its previous setting.
• The parameter of Ext SW must be“Enabled”
to perform this configuration. See the user’s
manual IM 01C25T (HART/BRAIN) for the
setting procedure.
• The Local Parameter Setting function
is available with HART or BRAIN
Drain plug communication type.

Drain screw

When you loosen the drain screw or drain


plug, the accumulated liquid will be expelled
in the direction of the arrow.
F0706.ai

Figure 7.5 Draining the Transmitter

IM 01C25B01-01E
<7. Operation> 7-6
7.6.1 Local Parameter Setting (LPS)
Overview
Parameter configuration by the external adjustment
screw and push button (integral indicator code E)
offers easy and quick setup for parameters of Tag
number, Unit, LRV, URV, Damping,Output mode
(linear/square root), Display out 1, and Re-range
by applying actual pressure (LRV/URV). There is
no effect on measurement signal (analog output
or communication signal) when Local Parameter
Setting is carried out.
Integral indicator

External adjustment
screw cover
Push-button

F0708.ai F0709.ai

Figure 7.7 External Adjustment Screw Figure 7.8 Range –Setting Switch (push button)

screw

push

Process
Measurement Zero adjustment
Display

Activate LPS mode


push
*
1. Tag Number Edit Tag number Save/Cancel the value

*
2. Press Unit Edit Press unit Save/Cancel the value

push *
3. Press LRV Edit Press LRV Save/Cancel the value

*
4. Press URV Edit Press URV Save/Cancel the value

push *
5. Damping Time Edit Damping time Save/Cancel the value

*
6. Output Mode Edit Output mode Save/Cancel the value

push *
7. Display Out1 Edit Display Out1 Save/Cancel the value

8. LRV-Apply Press Set LRV Save/Cancel the value

push
9. URV-Apply Press Set URV Save/Cancel the value

8, 9 : Re-range by applying actual pressure

Process
Measurement
Display F0710.ai

*Note that the above 1 to 7 parameter configurations are available with the software revision (SOFT REV)2.03 or later.
Software revision can be checked via a field communicator (HART/BRAIN) or DTM. Please refer to IM 01C25T01 for HART parameter
“Software rev” and IM 01C25T03 for BRAIN “SOFT REV”.

Figure 7.9

IM 01C25B01-01E
<7. Operation> 7-7
7.6.2 Activating Local Parameter Setting
Press the push button on the integral indicator to
activate the Local Parameter Setting mode. The
transmitter will exit automatically from the Local
Parameter Setting mode if no operation is carried
out for 10 minutes.

7.6.3 Parameter Setting Review


Current setting value for the below parameters
are shown sequentially by each press of the push
button.
Tag number, Unit, LRV, URV, Damping,Output
mode (linear/square root), Display out 1.
Process
Measurement
Display

push

push

push
push

push
push

push
push

push Process
Measurement
Display
F0711.ai

To configure each parameter value, turn the


external adjustment screw on each parameter
screen after activating the Local Parameter Setting
mode.

IM 01C25B01-01E
<7. Operation> 7-8
7.6.4 Tag Number Configuration
Tag Number is edited by turning the external
adjustment screw. Up to 8 alphanumeric characters
for HART or 16 alphanumeric characters for BRAIN
can be set.

Save ?/
Cancel ?

Blinking Blinking
Set all other
characters in the
Go to the next Character same way
Change the first Character

screw

push
F0712.ai

7.6.5 Pressure Unit Configuration


Pressure unit for the below table can be changed
as below. By turning the external adjustment screw,
user can scroll between the various available
pressure units.

Save ?/
Cancel ?

Blinking Blinking
[Available pressure units]
Select by the push button
kPa bar inH2O@4degC(39.2degF)
Torr mbar inH2O@20degC(68degF)
atm g/cm2 inHg
MPa kg/cm2 ftH2O@4degC(39.2degF)
screw hPa Pa ftH2O@20degC(68degF)
push mmHg mmH2O@4degC(39.2degF)
psi mmH2O@20degC(68degF)
In addition to the above units, mmAq@4degC,
mmAq@20degC, mmWG@4degC and mmWG@20degC
are available for BRAIN communication type.
F0713.ai

IM 01C25B01-01E
<7. Operation> 7-9
7.6.6 Damping Time Constant
Configuration
The damping time constant for the amplifier
assembly can be set. Quick Response Parameter
is automatically set to ON when the damping time
constant is set to less than 0.5 seconds. Damping
time constant is rounded off to two decimal places.

Save ?/
Cancel ?

Blinking Blinking Blinking Save


Set all other
characters in the
same way
Change the first digit Go to the next
Character
screw

push
F0714.ai

7.6.7 Re-range by applying actual 6) Press the push-button. The integral indicator
pressure (LRV/URV). then displays “URV.SET.”
7) Apply a pressure of 3 MPa to the transmitter.
This feature allows the lower and upper range
(Note 1)
values to be setup with the actual input applied.
8) Turn the external adjustment screw in the
desired direction. The integral indicator displays
the output signal in %. (Note 2)
9) Adjust the output signal to 100% (5 V DC)
by rotating the external adjustment screw.
F0715.ai
Press the button to save the value.Doing so
completes the URV setting.
Follow the procedure below to change the LRV and 10) Press the push-button. The transmitter then
URV settings. switches back to the normal operation mode
[Example] with the measurement range of 0 to 3 MPa.
Note 1: Wait until the pressure inside the pressure-detector
Rerange LRV to 0 and URV to 3 MPa. section has stabilized before proceeding to the next
step.
1) Connect the transmitter and apparatus as Note 2: If the pressure applied to the transmitter exceeds the
shown in Figure 8.1 and warm it up for at least previous LRV (or URV), the integral indicator may
display error number “AL.30” (In this case, the output
five minutes. signal percent and “AL.30” are displayed alternately
2) Press the push-button. The integral indicator every two seconds). Although “AL.30” is displayed,
then displays “LRV.SET.” you may proceed to the next step. However, should
any other error number be displayed, take the
3) Apply a pressure of 0 kPa (atmospheric appropriate measure in reference to , “Errors and
pressure) to the transmitter. (Note 1) Countermeasures” in each communication manual.
Note 3 : Changing the lower range value (LRV) also
4) Turn the external adjustment screw in the automatically changes the upper range value (URV),
desired direction. The integral indicator displays keeping the span constant. New URV=previous
URV+(new LRV–previous LRV)
the output signal in %. (Note 2)
5) Adjust the output signal to 0% (1 V DC) by
rotating the external adjustment screw. Press
the push button to save the value. Doing so
completes the LRV setting. (Note 3)

IM 01C25B01-01E
<7. Operation> 7-10
7.6.8 Save or Cancel 7.6.9.2 Abort Configuration (Parameter)
At the end of each parameter setting, select “Save” To exit the configuration while editing the value,
or “Cancel” by the external adjustment screw hold down the button for over 2 seconds and select
and press the push button to save or cancel the “Save” or “Cancel”.
configuration.

Save or Cancel

Tag editing Return to


(3rd Character) parameter review window
Save? Saved
Push for Save or Cancel?
After push Over 2 seconds
F0718.ai
parameter screw
setting
7.6.10 Local Parameter Setting Lock
To disable parameter changes by the Local
Parameter Setting there are three different ways.
Locked features
Cancel? Canceled Communication Parameter • External Zero
push Ext SW =disable Adjustment
(EXT ZERO ADJ = disable) • Local Parameter Setting
F0716.ai Communication Parameter • Local Parameter Setting
Write Protect = On • All Communication
7.6.9 Abort Configuration (WRT PROTECT = Yes) Parameters *
Hardware write protection • Local Parameter Setting
7.6.9.1 Abort Configuration (Menu) switch on CPU assembly = • All Communication
D (Disable) Parameters *
Hold down the push button for over 2 seconds to *External Zero Adjustment is unlocked.
exit the Local Parameter Setting mode.
The above parameter setting is carried out by
Process Measurement Display using field communicator or DTM. See the user’s
manual IM 01C25T (HART/BRAIN) for the setting
1. Tag Number
procedure.
Reviewing local parameter setting by push button
2. Press Unit
on the integral indicator is available at any time
3. Press LRV
even when the Local Parameter Setting is locked.
7.6.11 Others
4. Press URV
Hold down the button • Difference between BRAIN and HART
for over 2 seconds
Jump to the normal mode

5. Damping Time HART BRAIN


Up to 8 Up to 16
6. Output Mode Tag Number characters can characters can
be set be set
“TRNS.FC” “OUT.MOD”
7. Display Out1 Output Mode
shown on the shown on the
(Linear/Sq root)
integral indicator integral indicator
8. LRV-Apply Press
• The degree of adjustment depends on the
9. URV-Apply Press speed of turning the adjustment screw. Turn the
screw slowly for fine tuning and turn the screw
Process Measurement Display fast for quick tuning.

Proccess Value

F0717.ai

IM 01C25B01-01E
<8. Maintenance> 8-1

8. Maintenance
8.1 Overview 8.3 Calibration
Use the procedure below to check instrument
WARNING operation and accuracy during periodic
maintenance or troubleshooting.
Since the accumulated process fluid may be
toxic or otherwise harmful, take appropriate care 1) Connect the instruments as shown in figure 8.1
to avoid contact with the body or inhalation of and warm up the instruments for at least five
vapors when draining condensate or venting gas minutes (ten minutes for EJ310.)
from the transmitter pressure-detector section
and even after dismounting the instrument from IMPORTANT
the process line for maintenance.
• To adjust the transmitter for highest
accuracy, make adjustments with the
Maintenance of the transmitter is easy due to its power supply voltage and load resistance
modular construction. This chapter describes the including leadwire resistances set close to
procedures for calibration, adjustment, and the the conditions under which the transmitter is
disassembly and reassembly procedures required installed.
for component replacement. • If the measurement range 0% point is
Transmitters are precision instruments. Please 0 kPa or shifted in the positive direction
carefully and thoroughly read the following sections (suppressed zero), the reference pressure
for information on how to properly handle them should be applied as shown in the figure.
while performing maintenance. If the measurement range 0% point is shifted
in the negative direction (elevated zero), the
IMPORTANT reference pressure should be applied using
a vacuum pump.
• As a rule, maintenance of this transmitter
should be done in a shop that has all the 2) Apply reference pressures of 0%, 50%,
necessary tools. and 100% of the measurement range to the
• The CPU assembly contains sensitive parts transmitter. Calculate the errors (differences
that can be damaged by static electricity. between digital voltmeter readings and
Take precautions such as using a grounded reference pressures) as the pressure is
wrist strap when handling electronic parts or increased from 0% to 100% and is decreased
touching the board circuit patterns. Also be from 100% to 0%, and confirm that the errors
sure to place the removed CPU assembly are within the required accuracy.
into a bag with an antistatic coating.

8.2 Calibration Instruments


Selection
Table 8.1 lists the instruments that can be used
to calibrate a transmitter. When selecting an
instrument, consider the required accuracy level.
Exercise care when handling these instruments to
ensure they maintain the specified accuracy.

IM 01C25B01-01E
<8. Maintenance> 8-2
Table 8.1 Instruments Required for Calibration
Name Yokogawa-recommended Instrument Remarks
Power supply Model SDBT or SDBS distributor 4 to 20 mA DC signal
Load resistor Model 2792 standard resistor [250 Ω ±0.005%, 3 W]
Load adjustment resistor [100 Ω ±1%, 1 W]
Voltmeter Model 2501 A digital multimeter
Accuracy (10V DC range): ±(0.002% of rdg + 1 dgt)
Digital Model MT220 precision digital manometer Select a manometer having
manometer 1) For 10 kPa class a pressure range close to
Accuracy: ±(0.015% of rdg + 0.015% of F.S.) . . . . for 0 to 10 kPa that of the transmitter.
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -10 to 0 kPa
2) For 130 kPa class
Accuracy: ±0.02% of rdg . . . . . . . . . . . . . . . . . . . . for 25 to 130 kPa
±5digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 25 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
3) For 700 kPa class
Accuracy: ±(0.02% of rdg + 3digits) . . . . . . . . . . . . for 100 to 700 kPa
±5 digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 100 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
4) For 3000 kPa class
Accuracy: ±(0.02% of rdg + 10 digits) . . . . . . . . . . for 0 to 3000 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
5) For 130 kPa abs class
Accuracy: ±(0.03% of rdg + 6 digits) . . . . . . . . . . . for 0 to 130 kPa abs
Pressure Model 7674 pneumatic pressure standard for 200 kPa {2 kgf/cm2}, 25 kPa Requires air pressure
generator {2500 mmH2O} supply.
Accuracy: ±0.05% of F.S.
Dead weight gauge tester 25 kPa {2500 mmH2O} Select the one having a
Accuracy: ±0.03% of setting pressure range close to that
of the transmitter.
Pressure Model 6919 pressure regulator (pressure pump) Prepare the vacuum pump
source Pressure range: 0 to 133 kPa {1000 mmHg} for negative pressure
ranges.
Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and
management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1%
or higher level, there may be difficulties in calibration to this level in the field. For calibration to the 0.1% level, contact Yokogawa
representatives from which the instrument was purchased or the nearest Yokogawa office.

Supply pressure Pressure source


Using pressure Using pressure
generator source with
manometer Model MT220
P Pressure generator P precision digital manometer
Low pressure side Reference pressure Low pressure side Reference pressure
open to atmosphere open to atmosphere

High pressure side High pressure side

Load resistance, Power Load resistance, Power


250Ω supply 250Ω supply
E E
Rc R Load Rc R
Load
adjusting
adjusting V V
resistance,
resistance,
Digital voltmeter 100Ω Digital voltmeter
100Ω

F0801.ai

Figure 8.1 Instrument Connections (EJX110A)

IM 01C25B01-01E
<8. Maintenance> 8-3
8.4 Disassembly and 8.4.1 Replacing the Integral Indicator
Reassembly
CAUTION
This section describes procedures for disassembly
and reassembly for maintenance and component Cautions for Flameproof Type Transmitters
replacement. Users are prohibited by law from modifying the
Always turn OFF power and shut off and release construction of a flameproof type transmitter.
pressures before disassembly. Use proper tools for This would invalidate the agency approval for the
all operations. Table 8.2 shows the tools required. use of the transmitter in a rated area.
It follows that the user is prohibited from using
Table 8.2 Tools for Disassembly and Reassembly a flameproof type transmitter with its integral
Tool Quantity Remarks indicator removed, or from adding an integral
Phillips 1 JIS B4633, No. 2 indicator to a transmitter. If such modification is
screwdriver absolutely required, contact Yokogawa.
Slotted 1
screwdriver
This subsection describes the procedure for
Allen wrenches 3 JIS B4648
One each, nominal 3, 4 and replacing an integral indicator. (See figure 8.3)
2.5 mm Allen wrenches
Wrench 1 Width across flats, 17 mm ■ Removing the Integral Indicator
Torque wrench 1
1) Remove the cover.
Adjustable 1
wrench 2) While supporting the integral indicator with one
Socket wrench 1 Width across flats, 16 mm hand, loosen its two mounting screws.
Socket driver 1 Width across flats, 5.5 mm 3) Dismount the LCD board assembly from the
Tweezers 1 CPU assembly.
When doing this, carefully pull the LCD board
assembly straight forward so as not to damage
CAUTION the connector pins between it and the CPU
assembly.
Precautions for ATEX Flameproof Type
■ Attaching the Integral Indicator
Transmitters
• Flameproof type transmitters must be, as 1) Align both the LCD board assembly and CPU
a rule, removed to a non-hazardous area assembly connectors and engage them.
for maintenance and be disassembled and 2) Insert and tighten the two mounting screws.
reassembled to the original state. 3) Replace the cover.
• On the flameproof type transmitters the two Output terminal cable
covers are locked, each by an Allen head
bolt (shrouding bolt). When a shrouding bolt
is driven clockwise by an Allen wrench, it is
going in and cover lock is released, and then Press
the cover can be opened. forward

When a cover is closed it should be locked Slide


by a shrouding bolt without fail. Tighten the switch

shrouding bolt to a torque of 0.7 N·m. Integral


Boss Zero-
indicator adjustment
CPU assembly screw
Bracket
(for zero-adjustment
screw pin)
Zero-adjustment
LCD board assembly screw pin
Mounting screw
Amplifier Cover

Shrouding Bolt
F0803.ai

Shrouding Bolt F0802.ai Figure 8.3 Removing and Attaching LCD Board
Figure 8.2 Shrouding Bolts Assembly and CPU Assembly

IM 01C25B01-01E
<8. Maintenance> 8-4
8.4.2 Replacing the CPU Board Assembly
NOTE
This subsection describes the procedure for
replacing the CPU assembly. (See figure 8.3) Confirm that the zero-adjustment screw pin is
placed properly in the groove on the bracket prior
■ Removing the CPU Assembly to tightening the two bosses. If it is not, the zero-
1) Remove the cover. If an integral indicator is adjustment mechanism will be damaged.
mounted, refer to subsection 8.4.1 and remove
the indicator. 5) Replace the cover.
2) Turn the zero-adjustment screw to the position
(where the screw head slot is horizontal) as 8.4.3 Cleaning and Replacing the Capsule
shown in figure 8.3. Assembly
3) Disconnect the output terminal cable (cable
This subsection describes the procedures for
with brown connector at the end). When doing
cleaning and replacing the capsule assembly. (See
this, lightly press the side of the CPU assembly
figure 8.4.)
connector and pull the cable connector to
disengage.
4) Use a socket driver (width across flats, 5.5mm) CAUTION
to loosen the two bosses.
Cautions for Flameproof Type Transmitters
5) Carefully pull the CPU assembly straight
Users are prohibited by law from modifying the
forward to remove it.
construction of a flameproof type transmitter. If
6) Disconnect the flat cable (cable with white
you wish to replace the capsule assembly with
connector at the end) that connects the CPU
one of a different measurement range, contact
assembly and the capsule.
Yokogawa.
The user is permitted, however, to replace a
NOTE capsule assembly with another of the same
Be careful not to apply excessive force to the measurement range. When doing so, be sure to
CPU assembly when removing it. observe the following.
• The replacement capsule assembly must
have the same part number as the one being
■ Mounting the CPU Assembly replaced.
1) Connect the flat cable (with white connector) • The section connecting the transmitter and
between the CPU assembly and the capsule. capsule assembly is a critical element in
2) Connect the output terminal cable (with brown preservation of flameproof performance, and
connector). must be checked to verify that it is free of
dents, scratches, and other defects.
NOTE • After completing maintenance, be sure to
securely tighten the setscrews that fasten
Make certain that the cables do not get pinched the transmitter section and pressure-detector
between the case and the edge of the CPU section together.
assembly.

3) Align and engage the zero-adjustment screw


pin with the groove on the bracket on the CPU
assembly. Then insert the CPU board assembly
straight onto the post in the amplifier case.
4) Tighten the two bosses. If the transmitter is
equipped with an integral indicator, refer to
subsection 8.4.1 to mount the indicator.

IM 01C25B01-01E
<8. Maintenance> 8-5
■ Removing the Capsule Assembly 3) After the pressure-detector section has been
reassembled, a leak test must be performed to
IMPORTANT verify that there are no pressure leaks.
4) Reattach the transmitter section to the
Exercise care as follows when cleaning the pressure-detector section.
capsule assembly. Reattach the stopper with the hexagon-head
• Handle the capsule assembly with care, and screw.
be especially careful not to damage or distort 5) Tighten the two setscrews. (Tighten the screws
the diaphragms that contact the process to a torque of 1.5 N·m)
fluid. 6) Install the CPU assembly according to
• Do not use a chlorinated or acidic solution for subsection 8.4.2.
cleaning. 7) After completing reassembly, adjust the zero
• Rinse thoroughly with clean water after point and recheck the parameters.
cleaning.
Transmitter section
1) Remove the CPU assembly as shown in
subsection 8.4.2.
2) Remove the two setscrews that connect the
transmitter section and pressure-detector
section.
Setscrew
3) Remove the hexagon-head screw and the
stopper.
4) Separate the transmitter section and pressure- Nut

detector section.
5) Remove the nuts from the four flange bolts. Capsule gasket
6) While supporting the capsule assembly with
Flange bolt
one hand, remove the cover flange.
7) Remove the capsule assembly.
8) Clean the capsule assembly or replace with a
new one.
■ Reassembling the Capsule Assembly
1) Insert the capsule assembly between the flange Pressure-detector section
bolts, paying close attention to the relative Cover flange
F0804.ai
positions of the H (high pressure side) and
Figure 8.4 Removing and Mounting the Pressure-
L (low pressure side) marks on the capsule detector Section
assembly.
Replace the two capsule gaskets with new
gaskets. IMPORTANT
2) Install the cover flange on the high pressure
If you remove the vent/drain plugs when
side, and use a torque wrench to tighten the
disassembling EJ130 and EJ440
four nuts uniformly to a torque shown below.
transmitters, install the plugs again before
EJ110, EJ310, EJ430 reassembling the cover flanges with the capsule
Model Wetted parts material code EJ120 assmbly.
S H,M,T,A,D,B
Torque(N·m) 17* 40 40
{kgf·m} {1.7} {4.1} {4.1}
*: 40 for measurement span code F.

EJ130 EJ440
Model Bolts & nuts material code
G, C J G, C J
Torque(N·m) 90 110 70 100
{kgf·m} {9.2} {11.2} {7.1} {10.2}

IM 01C25B01-01E
<8. Maintenance> 8-6
8.4.4 Replacing the Process Connector 8.5.1 Basic Troubleshooting
Gaskets
First determine whether the process variable
This subsection describes process connector is actually abnormal or a problem exists in the
gasket replacement. (See figure 8.5.) measurement system.
(a) Loosen the two bolts, and remove the process If the problem is in the measurement system,
connectors. isolate the problem and decide what corrective
(b) Replace the process connector gaskets. action to take.
(c) Remount the process connectors. Tighten the
This transmitter is equipped with a self-diagnostic
bolts securely and uniformly to a torque shown
function which will be useful in troubleshooting,
below, and verify that there are no pressure
and the transmitter equipped with an integral
leaks.
indicator will show an alarm code as a result of self-
EJ110 EJ440 diagnosis.
EJ120 See subsection 8.5.3 for the list of alarms.
Model EJ130
EJ310 C capsule D capsule See also each communication manual.
EJ430
: Areas where self-diagnostic offers support
Torque(N·m) 39 to 49 49 to 59
{kgf·m} {4 to 5} {5 to 6} Abnormalities appear in measurement.

Bolt

Process connector YES Is process variable


itself abnormal?

Process connector gasket


Inspect the NO
Measurement system problem
process system.

Isolate problem in
measurement system.

F0805.ai
YES Does problem exist in
Figure 8.5 Removing and Mounting the Process receiving instrument?
Connector
NO
Inspect receiver.

8.5 Troubleshooting
If any abnormality appears in the measured values, Environmental conditions Transmitter itself
use the troubleshooting flow chart below to isolate
and remedy the problem. Since some problems Check/correct
Check transmitter.
have complex causes, these flow charts may environmental conditions.
not identify all. If you have difficulty isolating or Operating conditions
correcting a problem, contact Yokogawa service
personnel. Check/correct operating
conditions.
F0806.ai

Figure 8.6 Basic Flow and Self-Diagnostics

IM 01C25B01-01E
<8. Maintenance> 8-7
8.5.2 Troubleshooting Flowcharts
Output travels beyond 0% or 100%.

The following sorts of symptoms indicate that transmitter


may not be operating properly.
Example : • There is no output signal. Connect a communicator and check self-diagnostics.
• Output signal does not change even though
process variable is known to be varying.
• Output value is inconsistent with value
inferred for process variable.
Does the self- YES
diagnostic indicate problem
location?
Connect communicator and check self-diagnostics.
NO Refer to error message summary in
each communication manual to take
actions.

Does the self-diagnostic YES


indicate problem location?
Is power supply NO
polarity correct?
NO Refer to error message summary in
Subsection 8.5.3 or in each
communication manual to take actions. YES Refer to Section 6.3 to check/correct
polarity at each terminal from power
supply to the terminal box.

Is power supply NO
polarity correct?
Are valves opened or NO
closed correctly?
YES Refer to Section 6.3 to check/correct
polarity at each terminal from power
supply to the terminal box. YES Fully close equalizing valve, and fully
open high pressure and low pressure
valves.
Are power
NO
supply voltage and load
resistance correct?
YES
Is there any pressure leak?
YES Refer to Section 6.6 for rated voltage
and load resistance.
NO
Fix pressure leaks, paying particular
attention to connections for impulse
piping, pressure-detector section, etc.

Are valves opened or NO


closed correctly?
Is impulse piping NO
to high pressure and low
pressure side correct?
YES Fully close equalizing valve, and fully
open high pressure and low pressure
valves. YES Refer to individual model user manuals
and connect piping as appropriate for
the measurement purpose.
YES
Is there any pressure leak?
Is zero point NO
adjusted correctly?
NO Fix pressure leaks, paying particular
attention to connections for impulse
piping,pressure-detector section, etc. YES Adjust the zero point.

Is there
continuity through the Contact Yokogawa service personnel.
NO
transmitter loop wiring? F0808.ai
Do the loop numbers
match?

Find/correct broken conductor or


YES
wiring error.

Contact Yokogawa service personnel.


F0807.ai

IM 01C25B01-01E
<8. Maintenance> 8-8

Large output error.

Connect a communicator and check self-diagnostics.

Does the self- YES


diagnostic indicate problem
location?

NO Refer to error message summary in


each communication manual to take
actions.

Are valves opened or NO


closed correctly?

YES Fully close equalizing valve, and fully


open high pressure and low pressure
valves.

Is impulse piping NO
connected correctly?

YES Refer to individual model user manuals


and connect piping as appropriate for
the measurement purpose.

Are power supply NO


voltage and load resistance
correct?

YES Refer to Section 6.6 for rated voltage


and load resistance.

Is transmitter
installed where there is YES
marked variation in
temperature?

Provide lagging and/or cooling, or allow


NO adequate ventilation.

Were appropriate NO
instruments used for
calibration?

YES Refer to Section 8.2 when selecting


instruments for calibration.

NO
Is output adjusted correctly?

YES Adjust the output.

Contact Yokogawa service personnel.


F0809.ai

IM 01C25B01-01E
<8. Maintenance> 8-9
8.5.3 Alarms and Countermeasures
Table 8.3 Alarm Message Summary
Output Operation
Indicator Cause Countermeasure
during Error
None
AL. 01 Sensor problem. Outputs the signal (Hold, High, or Replace capsule when error
CAP. ERR Capsule temperature sensor Low) set with parameter. keeps appearing even after
problem. restart.
Capsule EEPROM problem.
AL. 02 Amplifier temperature sensor Outputs the signal (Hold, High, or Replace amplifier.
AMP. ERR problem. Low) set with parameter.
Amplifier EEPROM problem.
Amplifier problem.
AL. 10 Input is outside measurement Outputs high range limit value or Check input or replace capsule
PRESS range limit of capsule. low range limit value. when necessary.
AL. 11 Static pressure exceeds limit. Continues to operate and output.
ST. PRSS
AL. 12 Capsule temperature is outside Use heat insulation or make
CAP. TMP range (–50 to 130°C). lagging to keep temperature
AL. 13 Amplifier temperature is outside within range.
AMP. TMP range (–50 to 95°C)
AL. 30 Output is outside upper or lower Outputs high range limit value or Check input and range setting,
RANGE range limit value. low range limit value. and change them as needed.
AL. 31 Static pressure exceeds specified Holds output immediately before
SP. RNG range. error occurred.
AL. 35 *1 Input pressure exceeds specified Continues to operate and Check input.
P. HI threshold. output.
AL. 36 *1
P. LO
AL. 37 *1 Input static pressure exceeds
SP. HI specified threshold.
AL. 38 *1
SP. LO
AL. 39 *1 Detected temperature exceeds
TMP. HI specified threshold.
AL. 40 *1
TMP. LO
AL. 50 Specified value is outside of setting Holds output immediately before Check setting and change them
P. LRV range. error occurred. as needed.
AL. 51
P. URV
AL. 52
P. SPN
AL. 53 Continues to operate and output. Check input.
P. ADJ
AL. 54 Continues to operate and output Check setting and change them
SP. RNG holding static pressure in %. as needed.
AL. 55 Continues to operate and output. Check input.
SP. ADJ
AL. 60 Specified values or settings to Check setting and change
SC. CFG define signal characterizer function them as needed.
do not satisfy the condition.
AL. 79 Displayed value exceeds limit.
OV. DISP

*1: These alarms may appear only when process alarm function is activated.

IM 01C25B01-01E
<9. General Specifications> 9-1

9. General Specifications
9.1 Standard Specifications EJX310A
Measurement psi abs mbar abs mmHg abs
kPa abs
Refer to IM 01C25T02-01E for FOUNDATION Span/Range (/D1) (/D3) (/D4)
Fieldbus communication type and IM 01C25T04- Span 0.5 to 10
0.15 to 2.95
5 to 100 3.8 to 75
L inHg
01EN for PROFIBUS PA communication type for
Range 0 to 10 0 to 2.95 inHg 0 to 100 0 to 75
the items marked with “◊”. 0.39 to 38
Span 1.3 to 130 13 to 1300 9.8 to 970
M inHg
Range 0 to 130 0 to 38 inHg 0 to 1300 0 to 970
 Performance Specifications 0.0175 to 3.5 0.175 to 35 0.175 to 35
Span 2.5 to 500
A MPa bar kgf/cm2
See General Specifications sheet of each model.
Range 0 to 3.5 MPa 0 to 500 0 to 35 bar 0 to 35 kgf/cm2
0.08 to 16 0.8 to 160 0.8 to 160
 Functional Specifications B
Span
MPa
12 to 2300
bar kgf/cm2
Range 0 to 16 MPa 0 to 2300 0 to 160 bar 0 to 160 kgf/cm2
Span & Range Limits
EJX430A
EJX110A
Measurement kgf/cm2
Measurement MPa psi (/D1) bar(/D3)
kPa inH2O(/D1) mbar(/D3) mmH2O(/D4) Span/Range (/D4)
Span/Range
2.5 to 500 10 to 2000
Span 0.1 to 5 0.4 to 20 1 to 50 10 to 500 Span 0.025 to 5 0.025 to 5
F* kPa inH2O
Range -5 to 5 -20 to 20 -50 to 50 -500 to 500 H
-100 to 500 -400 to 2000
Span 0.1 to 10 0.4 to 40 1 to 100 10 to 1000 Range -1 to 5 -1 to 5
L* kPa inH2O
Range -10 to 10 -40 to 40 -100 to 100 -1000 to 1000 Span 0.0175 to 3.5 2.5 to 500 0.175 to 35 0.175 to 35
Span 0.5 to 100 2 to 400 5 to 1000 50 to 10000 A
Range -0.1 to 3.5 -15 to 500 -1 to 35 -1 to 35
M -10000 to Span 0.08 to 16 12 to 2300 0.8 to 160 0.8 to 160
Range -100 to 100 -400 to 400 -1000 to 1000 B
10000
Range -0.1 to 16 -14.7 to 2300 -1 to 160 -1 to 160
0.025 to 5
Span 2.5 to 500 10 to 2000 25 to 5000
kgf/cm2
H
-5 to 5 EJX440A
Range -500 to 500 -2000 to 2000 -5000 to 5000
kgf/cm2 Measurement
MPa psi (/D1) bar(/D3) kgf/cm2(/D4)
0.07 to 14 0.7 to140 Span/Range
Span 10 to 2000 psi 0.7 to 140 bar
MPa kgf/cm2 Span 0.25 to 32 36 to 4500 2.5 to 320 2.5 to 320
V C
-0.5 to 14 -71 to 2000 -5 to 140 Range -0.1 to 32 -14.5 to 4500 -1 to 320 -1 to 320
Range -5 to 140 bar
MPa psi kgf/cm2 Span 0.25 to 50 36 to 7200 2.5 to 500 2.5 to 500
D
Range -0.1 to 50 -14.5 to 7200 -1 to 500 -1 to 500
*: F capsule is applicable for wetted parts material code S.
L capsule is applicable for wetted parts material code
other than S.
EJA110E
EJX120A Measurement
kPa inH2O(/D1) mbar(/D3) mmH2O(/D4)
Measurement Span/Range
kPa inH2O(/D1) mbar(/D3) mmH2O(/D4)
Span/Range Span 0.5 to 5 2.0 to 20 5 to 50 50 to 500
F*
Span 0.025 to 1 0.1 to 4 0.25 to 10 2.5 to 100 Range -5 to 5 -20 to 20 -50 to 50 -500 to 500
E
Range -1 to 1 -4 to 4 -10 to 10 -100 to 100 Span 0.5 to 10 2.0 to 40 5 to 100 50 to 1000
L*
Range -10 to 10 -40 to 40 -100 to 100 -1000 to 1000

EJX130A Span 1 to 100 4 to 400 10 to 1000 100 to 10000


M -10000 to
Measurement Range -100 to 100 -400 to 400 -1000 to 1000
kPa inH2O(/D1) mbar(/D3) mmH2O(/D4) 10000
Span/Range
0.05 to 5
Span 1 to 100 4 to 400 10 to 1000 100 to 10000 Span 5 to 500 20 to 2000 50 to 5000
M kgf/cm2
Range -100 to 100 -400 to 400 -1000 to 1000 -10000 to 10000 H
-5 to 5
Span 5 to 500 20 to 2000 50 to 5000 0.05 to 5 kgf/cm2 Range -500 to 500 -2000 to 2000 -5000 to 5000
H kgf/cm2
Range -500 to 500 -2000 to 2000 -5000 to 5000 -5 to 5 kgf/cm2
0.14 to 14 1.4 to140
Span 20 to 2000 psi 1.4 to 140 bar
MPa kgf/cm2
V
-0.5 to 14 -71 to 2000 -5 to 140
Range -5 to 140 bar
MPa psi kgf/cm2

*: F capsule is applicable for wetted parts material code S.


L capsule is applicable for wetted parts material code
other than S.

IM 01C25B01-01E
<9. General Specifications> 9-2
EJA120E Failure Alarm “◊”
Measurement
kPa inH2O(/D1) mbar(/D3) mmH2O(/D4)
Output status at CPU failure and hardware
Span/Range
error;
Span 0.1 to 1 0.4 to 4 1 to 10 10 to 100
E
Range -1 to 1 -4 to 4 -10 to 10 -100 to 100
Up-scale: 110%, 21.6 mA DC or more
(standard)
EJA130E Down-scale: –5%, 3.2 mA DC or less
Measurement
Note: Applicable for Output signal code D and E
kPa inH2O(/D1) mbar(/D3) mmH2O(/D4)
Span/Range
Span 1 to 100 4 to 400 10 to 1000 100 to 10000 Damping Time Constant (1st order)
M
Range -100 to 100 -400 to 400 -1000 to 1000 -10000 to 10000 Amplifier damping time constant is adjustable
H
Span 5 to 500 20 to 2000 50 to 5000 0.05 to 5 kgf/cm2 from 0 to 100.00 seconds and added to
Range -500 to 500 -2000 to 2000 -5000 to 5000 -5 to 5 kgf/cm2
response time.
Note: For BRAIN protocol type, when amplifier damping
EJA310E is set to less than 0.5 seconds, communication
Measurement psi abs mbar abs mmHg abs
may occasionally be unavailable during the
kPa abs operation, especially while output changes
Span/Range (/D1) (/D3) (/D4)
dynamically. The default setting of damping
0.2 to 2.95 ensures stable communication.
Span 0.67 to 10 6.7 to 100 5 to 75
L inHg
Range 0 to 10 0 to 2.95 inHg 0 to 100 0 to 75 Update Period “◊”
0.39 to 38
M
Span 1.3 to 130
inHg
13 to 1300 9.8 to 970 Differential Pressure: 45 ms
Range 0 to 130 0 to 38 inHg 0 to 1300 0 to 970 Static Pressure: 360 ms
0.03 to 3.5 0.3 to 35
A
Span
MPa
4.3 to 500
bar
0.3 to 35 kgf/cm2 Zero Adjustment Limits
Range 0 to 3.5 MPa 0 to 500 0 to 35 bar 0 to 35 kgf/cm2 Zero can be fully elevated or suppressed, within
Span
0.14 to 16
20 to 2300
1.4 to 160 1.4 to 160 the lower and upper range limits of the capsule.
B MPa bar kgf/cm2
Range 0 to 16 MPa 0 to 2300 0 to 160 bar 0 to 160 kgf/cm2 External Zero Adjustment “◊”
External Zero is continuously adjustable with
EJA430E 0.01% incremental resolution of span. Re-range
Measurement
MPa psi (/D1) bar(/D3)
kgf/cm2 can be done locally using the digital indicator
Span/Range (/D4) with range-setting switch.
20 to 2000
Span 5 to 500 kPa 0.05 to 5 0.05 to 5
H
inH2O Integral Indicator (LCD display)
-100 to 500 -400 to 2000 5-digit Numerical Display, 6-digit Unit Display
Range -1 to 5 -1 to 5
kPa inH2O
Span 0.03 to 3.5 4.3 to 500 0.3 to 35 0.3 to 35
and Bar graph.
A The indicator is configurable to display one or
Range -0.1 to 3.5 -14.5 to 500 -1 to 35 -1 to 35
Span 0.14 to 16 20 to 2300 1.4 to 160 1.4 to 160 up to four of the following variables periodically.;
B
Range -0.1 to 16 -14.5 to 2300 -1 to 160 -1 to 160 Differential pressure in %, Scaled Differential
pressure, Differential Pressure in Engineering
EJA440E unit, Static Pressure in Engineering unit.
Measurement
MPa psi (/D1) bar(/D3) kgf/cm2(/D4) See “Setting When Shipped” for factory setting.
Span/Range

C
Span 5 to 32 720 to 4500 50 to 320 50 to 320 Local Parameter Setting (Output signal code D
Range -0.1 to 32 -14.5 to 4500 -1 to 320 -1 to 320
and J)
Span 5 to 50 720 to 7200 50 to 500 50 to 500
D
Range -0.1 to 50 -14.5 to 7200 -1 to 500 -1 to 500
Parameter configuration by the external zero
adjustment screw and push button (Integral
Output “◊” indicator code E) offers easy and quick setup
Two wire 4 to 20 mA DC output with digital for parameters of Tag number, Unit, LRV, URV,
communications, linear or square root Damping, Output mode (linear/square root),
programmable. BRAIN or HART FSK protocol Display out 1, and Re-range by applying actual
are superimposed on the 4 to 20 mA signal. pressure (LRV/URV).
Output range: 3.6 mA to 21.6 mA Burst Pressure Limits
Output limits conform to NAMUR NE43 can be [EJ110, EJ310, EJ430]
pre-set by option C2 or C3. 69 MPa (10000 psi)
[EJ130, EJ440]
132 MPa (19100 psi)

IM 01C25B01-01E
<9. General Specifications> 9-3
 Normal Operating Condition Minimum Pressure Limit
(Selected features may affect limits.) See graph below

Ambient Temperature Limits EJ110, EJ130, EJ430, EJ440


–40 to 85°C (–40 to 185°F)
Atmospheric
–30 to 80°C (–22 to 176°F) with LCD display 100(14.5)
pressure
–25 to 80°C (–40 to 176°F) for EJ120 Working
pressure
Process Temperature Limits kPa abs
–40 to 120°C (–40 to 248°F) (psi abs)
–25 to 80°C (–40 to 176°F) for EJ120 Applicable range
10(1.4)
–40 to 100°C (–40 to 212°F) for EJ310
L capsule
Ambient Humidity Limits 2.7(0.38)
0 to 100% RH
1(0.14)
Working Pressure Limits (Silicone oil) -40 0 40 80 120
(-40) (32) (104) (176) (248)
EJ120 -50 to 50 kPa
Process temperature °C (°F)
Maximum Pressure Limits F0901.ai

EJX110A EJ310
100(750)
Capsule Pressure
F, L 16 MPa (2300 psi)
M,A and B capsule
M, H, V 25 MPa (3600 psi)*
L capsule
* 16 MPa for wetted parts material code H, M, T, A, D, 10(75)
and B.

EJA110E 2.7(20)
Capsule Pressure Working Applicable range
F, L, M, H, V 16 MPa (2300 psi)* pressure 1(7.5)
kPa abs
* 25 MPa (3600 psi) when /HG is specified. (mmHg abs) 0.46
(3.45)
EJ130 0.13(1)
0.1(0.75)
Capsule Pressure
M, H 32 MPa (4500 psi)

EJ310 0.013(0.1)
Capsule Pressure 0.01(0.075)
-40 0 40 80 120 (248)
L 10 kPa abs (2.95 inHg abs) (-40) (32) (104)(176) 85
(185)
M 130 kPa abs (38 inHg abs)
Process temperature °C (°F)
A 3.5 MPa abs (500 psia) F0902.ai

B 16 MPa abs (2300 psia) Figure 9.1 Working Pressure and Process
Temperature
EJ430
Capsule Pressure
H 500 kPa (2000 inH2O)
A 3.5 MPa (500 psi)
B 16 MPa (2300 psi)

EJ440
Capsule Pressure
C 32 MPa (4500 psi)
D 50 MPa (7200 psi)

IM 01C25B01-01E
<9. General Specifications> 9-4
Maximum Over Pressure Supply Voltage
EJ310 10.5 to 42 V DC for general use and flameproof
Capsule Pressure type.
L, M 500 kPa abs (72 psia) 10.5 to 32 V DC for lightning protector (Option
A 16 MPa abs (2300 psia) code /A).
B 25 MPa abs (3600 psia) 10.5 to 30 V DC for intrinsically safe, type n or
EJ430 non-incendive type.
Minimum voltage limited at 16.6 V DC for digital
Capsule Pressure
H, A 16 MPa (2300 psi) communications, BRAIN and HART
B 25 MPa (3600 psi)* Load (Output signal code D, E and J)
* 24 MPa for wetted parts material code H, M, T, A, D, and 0 to 1290 Ω for operation
B. 250 to 600 Ω for digital communication
EJ440
Capsule Pressure Communication Requirements “◊”
C 48 MPa (6750 psi) (Safety approvals may affect electrical
D 75 MPa (10800 psi)* requirements.)
* 60 MPa (8700 psi) for EJA440E. BRAIN
Supply & Load Requirements “◊” (Optional Communication Distance
features or approval codes may affect Up to 2 km (1.25 miles) when using CEV
electrical requirements.) polyethylene-insulated PVC-sheathed cables.
With 24 V DC supply, up to a 550 Ω load can be Communication distance varies depending on
used. See graph below. type of cable used.
Load Capacitance
0.22 μF or less
600
E-10.5 Load Inductance
R=
External 0.0244 Digital 3.3 mH or less
load Communication
resistance range Input Impedance of communicating device
BRAIN and HART
10 kΩ or more at 2.4 kHz.
250
HART
R (Ω)
Communication Distance
Up to 1.5 km (1 mile) when using multiple
10.5 16.6 25.2 42 twisted pair cables. Communication distance
Power supply voltage E (V DC) varies depending on type of cable used.
F0903.ai

Figure 9.2 Relationship Between Power Supply


Voltage and External Load Resistance EMC Conformity Standards ,
EN61326-1 Class A, Table2 (For use in industrial
locations)
EN61326-2-3

IM 01C25B01-01E
<9. General Specifications> 9-5
 Physical Specifications Weight
[Installation code 7, 8, and 9 and wetted parts
Wetted Parts Materials material code S for EJ110, EJ310, and
Diaphragm, Cover Flange, Process EJ430 (Except for measurement span code
Connector, Capsule Gasket, and Vent/Drain F)]
Plug 2.8 kg (6.2 lb) without integral indicator,
Refer to “Model and Suffix Code.” mounting bracket, and process connector.
[Installation code 7, 8, and 9 for EJ120]
Process Connector Gasket/o-ring
3.7 kg (8.2 lb) without integral indicator,
[EJ110, EJ120, EJ430, EJ310]
mounting bracket, and process connector.
PTFE Teflon
[Installation code 7, 8, and 9 for EJ130]
Fluorinated rubber for Option code /N2 and /N3
6.8 kg (14.3 lb) without integral indicator,
[EJ130]
mounting bracket, and process connector.
Fluorinated rubber (O-ring)
[Installation code 7, 8, and 9 for EJ440]
[EJ440]
4.9 kg (10.8 lb) without integral indicator,
Fluorinated rubber (O-ring) for C capsule
mounting bracket, and process connector.
Glass reinforced Teflon (gasket) for D capsule
Add 1.5 kg(3.3lb) for amplifier housing code 2.
Non-wetted Parts Materials
Connections
Bolting
Refer to “Model and Suffix Code.”
ASTM-B7 carbon steel, 316L SST stainless
steel, or ASTM grade 660 stainless steel Process Connection of Cover Flange (models
except for EJ440-D): IEC61518
Housing
Low copper cast aluminum alloy with
polyurethane paint or ASTM CF-8M stainless
steel
Degrees of Protection
IP66/IP67, NEMA TYPE 4X
Cover O-rings
Buna-N, fluoro-rubber (option)
Nameplate and tag
316SST (including /N4 wired tag)
Fill Fluid
Silicone, Fluorinated oil (option)

IM 01C25B01-01E
<9. General Specifications> 9-6
9.2 Model and Suffix Codes
Model EJX110A
Model Suffix Codes Description
EJX110A ...................... Differential pressure transmitter
Output -D . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
signal -E . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART protocol)
-J . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART 5/HART 7 protocol)
-F . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01E)
-G . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, refer to IM 01C25T04-01EN)
Measurement F . . . . . . . . . . . . . . . . . . . 0.1 to 5 kPa (0.4 to 20 inH2O) (For Wetted parts material code S)
span (capsule) L . . . . . . . . . . . . . . . . . . . 0.1 to 10 kPa (0.4 to 40 inH2O)
(For Wetted parts material code M, H, T, A, D and B)
M . . . . . . . . . . . . . . . . . . . 0.5 to 100 kPa (2 to 400 inH2O)
H . . . . . . . . . . . . . . . . . . . 2.5 to 500 kPa (10 to 2000 inH2O)
V . . . . . . . . . . . . . . . . . . . 0.07 to 14 MPa (10 to 2000 psi)
Wetted parts  . . . . . . . . . . . . . . . . . Refer to Table. 1 Wetted Parts Materials on Page 9-18.
material *1
Process 0 . . . . . . . . . . . . . . . without process connector (Rc1/4 female on the cover flanges)
connections 1 . . . . . . . . . . . . . . . with Rc1/4 female process connector
2 . . . . . . . . . . . . . . . with Rc1/2 female process connector
3 . . . . . . . . . . . . . . . with 1/4 NPT female process connector
4 . . . . . . . . . . . . . . . with 1/2 NPT female process connector
► 5 . . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts J . . . . . . . . . . . . . ASTM-B7 carbon steel
material G . . . . . . . . . . . . . 316L SST stainless steel
C . . . . . . . . . . . . . ASTM grade 660 stainless steel
Installation -2 . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection upside
-3 . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection downside
-6 . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection upside
-7 . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection downside
-8 . . . . . . . . . . . . Horizontal piping and right side high pressure
► -9 . . . . . . . . . . . . Horizontal piping and left side high pressure
-B . . . . . . . . . . . . Bottom Process Connection, left side high pressure
-U . . . . . . . . . . . . Universal flange
Amplifier housing 1 . . . . . . . . . . Cast aluminum alloy
2 . . . . . . . . . . ASTM CF-8M stainless steel
3 . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties
Electrical connection 0 . . . . . . . . G1/2 female, one electrical connection without blind plugs
► 2 . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . G1/2 female, two electrical connections and a blind plug
7 . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug
9 . . . . . . . . M20 female, two electrical connections and a blind plug
A . . . . . . . . G1/2 female, two electrical connections and a 316 SST blind plug
C . . . . . . . . 1/2 NPT female, two electrical connections and a 316 SST blind plug
D . . . . . . . . M20 female, two electrical connections and a 316 SST blind plug
Integral indicator D . . . . . . Digital indicator
E . . . . . . Digital indicator with the range setting switch (push button)
► N . . . . . . None
Mounting bracket ► B . . . . . 304 SST 2-inch pipe mounting, flat type (for horizontal piping)
D . . . . . 304 SST 2-inch pipe mounting, L type (for vertical piping)
G . . . . . 304 SST 2-inch pipe mounting (for bottom process connection type)
J . . . . . 316 SST 2-inch pipe mounting, flat type (for horizontal piping)
K . . . . . 316 SST 2-inch pipe mounting, L type (for vertical piping)
M . . . . . 316 SST 2-inch pipe mounting (for bottom process connection type)
N . . . . . None
Optional codes /  Optional specification
The “►” marks indicate the most typical selection for each specification.
*1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate
materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the
corrosive process fluids.

IM 01C25B01-01E
<9. General Specifications> 9-7
Model EJX120A
Model Suffix Codes Description
EJX120A ...................... Differential pressure transmitter
Output -D . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
signal -E . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART protocol)
-J . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART 5/HART 7 protocol)
-F . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01E)
-G . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, refer to IM 01C25T04-01EN)
Measurement E . . . . . . . . . . . . . . . . . . . 0.025 to 1 kPa (0.1 to 4 inH2O)
span (capsule)
Wetted parts S . . . . . . . . . . . . . . . . . Refer to Table. 1 Wetted Parts Materials on Page 9-18
material *1
Process 0 . . . . . . . . . . . . . . . without process connector (Rc1/4 female on the cover flanges)
connections 1 . . . . . . . . . . . . . . . with Rc1/4 female process connector
2 . . . . . . . . . . . . . . . with Rc1/2 female process connector
3 . . . . . . . . . . . . . . . with 1/4 NPT female process connector
4 . . . . . . . . . . . . . . . with 1/2 NPT female process connector
► 5 . . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts J . . . . . . . . . . . . . ASTM-B7 carbon steel
material G . . . . . . . . . . . . . 316L SST stainless steel
C . . . . . . . . . . . . . ASTM grade 660 stainless steel
Installation -2 . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection upside
-3 . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection downside
-6 . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection upside
-7 . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection downside
-8 . . . . . . . . . . . . Horizontal piping and right side high pressure
► -9 . . . . . . . . . . . . Horizontal piping and left side high pressure
-U . . . . . . . . . . . . Universal flange
Amplifier housing 1 . . . . . . . . . . Cast aluminum alloy
2 . . . . . . . . . . ASTM CF-8M stainless steel
3 . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties
Electrical connection 0 . . . . . . . . G1/2 female, one electrical connection without blind plugs
► 2 . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . G1/2 female, two electrical connections and a blind plug
7 . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug
9 . . . . . . . . M20 female, two electrical connections and a blind plug
A . . . . . . . . G1/2 female, two electrical connections and a 316 SST blind plug
C . . . . . . . . 1/2 NPT female, two electrical connections and a 316 SST blind plug
D . . . . . . . . M20 female, two electrical connections and a 316 SST blind plug
Integral indicator D . . . . . . Digital indicator
E . . . . . . Digital indicator with the range setting switch (push button)
► N . . . . . . None
Mounting bracket ► B . . . . . 304 SST 2-inch pipe mounting, flat type (for horizontal piping)
D . . . . . 304 SST 2-inch pipe mounting, L type (for vertical piping)
G . . . . . 304 SST 2-inch pipe mounting (for bottom process connection type)
J . . . . . 316 SST 2-inch pipe mounting, flat type (for horizontal piping)
K . . . . . 316 SST 2-inch pipe mounting, L type (for vertical piping)
N . . . . . None
Optional codes / Optional specification
The “►” marks indicate the most typical selection for each specification.
*1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate
materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the
corrosive process fluids.

IM 01C25B01-01E
<9. General Specifications> 9-8
Model EJX130A
Model Suffix Codes Description
EJX130A ...................... Differential pressure transmitter
Output -D . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
signal -E . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART protocol)
-J . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART 5/HART 7 protocol)
-F . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01E)
-G . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, refer to IM 01C25T04-01EN)
Measurement M . . . . . . . . . . . . . . . . . . . 1 to 100 kPa (4 to 400 inH2O)
span (capsule) H . . . . . . . . . . . . . . . . . . . 5 to 500 kPa (20 to 2000 inH2O)
Wetted parts S . . . . . . . . . . . . . . . . . Refer to Table. 2 Wetted Parts Materials on Page 9-18
material *1
Process 3 . . . . . . . . . . . . . . . with 1/4 NPT female process connector *2
connections 4 . . . . . . . . . . . . . . . with 1/2 NPT female process connector *2
► 5 . . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts J . . . . . . . . . . . . . ASTM-B7 carbon steel
material G . . . . . . . . . . . . . 316L SST stainless steel
C . . . . . . . . . . . . . ASTM grade 660 stainless steel
Installation -2 . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection upside
-3 . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection downside
-6 . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection upside
-7 . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection downside
-8 . . . . . . . . . . . . Horizontal piping and right side high pressure
► -9 . . . . . . . . . . . . Horizontal piping and left side high pressure
-U . . . . . . . . . . . . Universal flange
Amplifier housing 1 . . . . . . . . . . Cast aluminum alloy
2 . . . . . . . . . . ASTM CF-8M stainless steel
3 . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties
Electrical connection 0 . . . . . . . . G1/2 female, one electrical connection without blind plugs
► 2 . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . G1/2 female, two electrical connections and a blind plug
7 . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug
9 . . . . . . . . M20 female, two electrical connections and a blind plug
A . . . . . . . . G1/2 female, two electrical connections and a 316 SST blind plug
C . . . . . . . . 1/2 NPT female, two electrical connections and a 316 SST blind plug
D . . . . . . . . M20 female, two electrical connections and a 316 SST blind plug
Integral indicator D . . . . . . Digital indicator
E . . . . . . Digital indicator with the range setting switch (push button)
► N . . . . . . None
Mounting bracket ► B . . . . 304 SST 2-inch pipe mounting, flat type (for horizontal piping)
D . . . . 304 SST 2-inch pipe mounting, L type (for vertical piping)
J . . . . 316 SST 2-inch pipe mounting, flat type (for horizontal piping)
K . . . . 316 SST 2-inch pipe mounting, L type (for vertical piping)
N . . . . None
Optional codes / Optional specification
The “►” marks indicate the most typical selection for each specification.
*1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate
materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the
corrosive process fluids.
*2: Lower limit of ambient and process temperature is -15˚C.

IM 01C25B01-01E
<9. General Specifications> 9-9
Model EJX310A
Model Suffix Codes Description
EJX310A ...................... Absolute pressure transmitter
Output -D . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
signal -E . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART protocol)
-J . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART 5/HART 7 protocol)
-F . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01E)
-G . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, refer to IM 01C25T04-01EN)
Measurement L . . . . . . . . . . . . . . . . . . . 0.5 to 10 kPa abs (0.15 to 2.95 inHg abs)
span (capsule) M . . . . . . . . . . . . . . . . . . . 1.3 to 130 kPa abs (0.39 to 38 inHg abs)
A . . . . . . . . . . . . . . . . . . . 0.0175 to 3.5 MPa abs (2.5 to 500 psia)
B . . . . . . . . . . . . . . . . . . . 0.08 to 16 MPa abs (12 to 2300 psia)
Wetted parts S . . . . . . . . . . . . . . . . . Refer to Table. 1 Wetted Parts Materials on Page 9-18.
material *1
Process 0 . . . . . . . . . . . . . . . without process connector (Rc1/4 female on the cover flanges)
connections 1 . . . . . . . . . . . . . . . with Rc1/4 female process connector
2 . . . . . . . . . . . . . . . with Rc1/2 female process connector
3 . . . . . . . . . . . . . . . with 1/4 NPT female process connector
4 . . . . . . . . . . . . . . . with 1/2 NPT female process connector
► 5 . . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts J . . . . . . . . . . . . . ASTM-B7 carbon steel
material G . . . . . . . . . . . . . 316L SST stainless steel
C . . . . . . . . . . . . . ASTM grade 660 stainless steel
Installation -2 . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection upside
-3 . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection downside
-6 . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection upside
-7 . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection downside
-8 . . . . . . . . . . . . Horizontal piping and right side high pressure
► -9 . . . . . . . . . . . . Horizontal piping and left side high pressure
-B . . . . . . . . . . . . Bottom process connection, left side high pressure
-U . . . . . . . . . . . . Universal flange
Amplifier housing 1 . . . . . . . . . . Cast aluminum alloy
2 . . . . . . . . . . ASTM CF-8M stainless steel
3 . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties
Electrical connection 0 . . . . . . . . G1/2 female, one electrical connection without blind plugs
► 2 . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . G1/2 female, two electrical connections and a blind plug
7 . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug
9 . . . . . . . . M20 female, two electrical connections and a blind plug
A . . . . . . . . G1/2 female, two electrical connections and a 316 SST blind plug
C . . . . . . . . 1/2 NPT female, two electrical connections and a 316 SST blind plug
D . . . . . . . . M20 female, two electrical connections and a 316 SST blind plug
Integral indicator D . . . . . . Digital indicator
E . . . . . . Digital indicator with the range setting switch (push button)
► N . . . . . . None
Mounting bracket ► B . . . . . 304 SST 2-inch pipe mounting, flat type (for horizontal piping)
D . . . . . 304 SST 2-inch pipe mounting, L type (for vertical piping)
G . . . . . 304 SST 2-inch pipe mounting (for bottom process connection type)
J . . . . . 316 SST 2-inch pipe mounting, flat type (for horizontal piping)
K . . . . . 316 SST 2-inch pipe mounting, L type (for vertical piping)
M . . . . . 316 SST 2-inch pipe mounting (for bottom process connection type)
N . . . . . None
Optional codes / Optional specification
The “►” marks indicate the most typical selection for each specification.
*1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate
materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the
corrosive process fluids.

IM 01C25B01-01E
<9. General Specifications> 9-10
Model EJX430A
Model Suffix Codes Description
EJX430A ...................... Gauge pressure transmitter
Output -D . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
signal -E . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART protocol)
-J . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART 5/HART 7 protocol)
-F . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01E)
-G . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, refer to IM 01C25T04-01EN)
Measurement H . . . . . . . . . . . . . . . . . . . 2.5 to 500 kPa (10 to 2000 inH2O)
span (capsule) A . . . . . . . . . . . . . . . . . . . 0.0175 to 3.5 MPa (2.5 to 500 psi)
B . . . . . . . . . . . . . . . . . . . 0.08 to 16 MPa (12 to 2300 psi)
Wetted parts  . . . . . . . . . . . . . . . . . Refer to Table. 1 Wetted Parts Materials on Page 9-18
material *1
Process 0 . . . . . . . . . . . . . . . without process connector (Rc1/4 female on the cover flanges)
connections 1 . . . . . . . . . . . . . . . with Rc1/4 female process connector
2 . . . . . . . . . . . . . . . with Rc1/2 female process connector
3 . . . . . . . . . . . . . . . with 1/4 NPT female process connector
4 . . . . . . . . . . . . . . . with 1/2 NPT female process connector
► 5 . . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts J . . . . . . . . . . . . . ASTM-B7 carbon steel
material G . . . . . . . . . . . . . 316L SST stainless steel
C . . . . . . . . . . . . . ASTM grade 660 stainless steel
Installation -2 . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection upside
-3 . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection downside
-6 . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection upside
-7 . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection downside
-8 . . . . . . . . . . . . Horizontal piping and right side high pressure
► -9 . . . . . . . . . . . . Horizontal piping and left side high pressure
-B . . . . . . . . . . . . Bottom Process Connection, left side high pressure
-U . . . . . . . . . . . . Universal flange
Amplifier housing 1 . . . . . . . . . . Cast aluminum alloy
2 . . . . . . . . . . ASTM CF-8M stainless steel
3 . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties
Electrical connection 0 . . . . . . . . G1/2 female, one electrical connection without blind plugs
► 2 . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . G1/2 female, two electrical connections and a blind plug
7 . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug
9 . . . . . . . . M20 female, two electrical connections and a blind plug
A . . . . . . . . G1/2 female, two electrical connections and a 316 SST blind plug
C . . . . . . . . 1/2 NPT female, two electrical connections and a 316 SST blind plug
D . . . . . . . . M20 female, two electrical connections and a 316 SST blind plug
Integral indicator D . . . . . . Digital indicator
E . . . . . . Digital indicator with the range setting switch (push button)
► N . . . . . . None
Mounting bracket ► B . . . . . 304 SST 2-inch pipe mounting, flat type (for horizontal piping)
D . . . . . 304 SST 2-inch pipe mounting, L type (for vertical piping)
G . . . . . 304 SST 2-inch pipe mounting (for bottom process connection type)
J . . . . . 316 SST 2-inch pipe mounting, flat type (for horizontal piping)
K . . . . . 316 SST 2-inch pipe mounting, L type (for vertical piping)
M . . . . . 316 SST 2-inch pipe mounting (for bottom process connection type)
N . . . . . None
Optional codes / Optional specification
The “►” marks indicate the most typical selection for each specification.
*1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate
materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the
corrosive process fluids.

IM 01C25B01-01E
<9. General Specifications> 9-11
Model EJX440A
Model Suffix Codes Description
EJX440A ...................... Gauge pressure transmitter
Output -D . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
signal -E . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART protocol)
-J . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART 5/HART 7 protocol)
-F . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01E)
-G . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, refer to IM 01C25T04-01EN)
Measurement C . . . . . . . . . . . . . . . . . . . 0.25 to 32 MPa (36 to 4500 psi)
span (capsule) D . . . . . . . . . . . . . . . . . . . 0.25 to 50 MPa (36 to 7200 psi)
Wetted parts S . . . . . . . . . . . . . . . . . Refer to Table. 3 Wetted Parts Materials on Page 9-18.
material *1
Process 3 . . . . . . . . . . . . . . . with 1/4 NPT female process connector *2*3
connections 4 . . . . . . . . . . . . . . . with 1/2 NPT female process connector *2*3
► 5 . . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts J . . . . . . . . . . . . . ASTM-B7 carbon steel
material G . . . . . . . . . . . . . 316L SST stainless steel
C . . . . . . . . . . . . . ASTM grade 660 stainless steel
Installation -2 . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection upside
-3 . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection downside
-6 . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection upside
-7 . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection downside
-8 . . . . . . . . . . . . Horizontal piping and right side high pressure
► -9 . . . . . . . . . . . . Horizontal piping and left side high pressure
-U . . . . . . . . . . . . Universal flange
Amplifier housing 1 . . . . . . . . . . Cast aluminum alloy
2 . . . . . . . . . . ASTM CF-8M stainless steel
3 . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties
Electrical connection 0 . . . . . . . . G1/2 female, one electrical connection without blind plugs
► 2 . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . G1/2 female, two electrical connections and a blind plug
7 . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug
9 . . . . . . . . M20 female, two electrical connections and a blind plug
A . . . . . . . . G1/2 female, two electrical connections and a 316 SST blind plug
C . . . . . . . . 1/2 NPT female, two electrical connections and a 316 SST blind plug
D . . . . . . . . M20 female, two electrical connections and a 316 SST blind plug
Integral indicator D . . . . . . Digital indicator
E . . . . . . Digital indicator with the range setting switch (push button)
► N . . . . . . None
Mounting bracket ► B . . . . . 304 SST 2-inch pipe mounting, flat type (for horizontal piping)
D . . . . . 304 SST 2-inch pipe mounting, L type (for vertical piping)
J . . . . . 316 SST 2-inch pipe mounting, flat type (for horizontal piping)
K . . . . . 316 SST 2-inch pipe mounting, L type (for vertical piping)
N . . . . . (None)
Optional codes / Optional specification
The “►” marks indicate the most typical selection for each specification.
*1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate
materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the
corrosive process fluids.
*2: Lower limit of ambient and process temperature is -15°C for capsule code C.
*3: Specify the process connections code 3 or 4, when using the process connector for D capsule. Without the process connector, use
the 1/4 NPT male piping to directly connect to the cover flange.

IM 01C25B01-01E
<9. General Specifications> 9-12
Model EJA110E
Model Suffix Codes Description
EJA110E ............................ Differential pressure transmitter
Output -D . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
signal -J . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication
(HART 5/HART 7 protocol)
-F . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01E)
-G . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, refer to
IM 01C25T04-01EN)
Measurement F . . . . . . . . . . . . . . . . . . . . . . . . 0.5 to 5 kPa (2.0 to 20 inH2O) (For Wetted parts material code S)
span (capsule) L . . . . . . . . . . . . . . . . . . . . . . . . 0.5 to 10 kPa (2.0 to 40 inH2O)
(For Wetted parts material code M, H, T, A, D and B)
M . . . . . . . . . . . . . . . . . . . . . . . . 1 to 100 kPa (4 to 400 inH2O)
H . . . . . . . . . . . . . . . . . . . . . . . . 5 to 500 kPa (20 to 2000 inH2O)
V . . . . . . . . . . . . . . . . . . . . . . . . 0.14 to 14 MPa (20 to 2000 psi)
Wetted parts  . . . . . . . . . . . . . . . . . . . . . . Refer to Table.1 Wetted Parts Material on Page 9-18
material *1
Process connections 0 . . . . . . . . . . . . . . . . . . . without process connector (Rc1/4 female on the cover flanges)
1 . . . . . . . . . . . . . . . . . . . with Rc1/4 female process connector
2 . . . . . . . . . . . . . . . . . . . with Rc1/2 female process connector
3 . . . . . . . . . . . . . . . . . . . with 1/4 NPT female process connector
4 . . . . . . . . . . . . . . . . . . . with 1/2 NPT female process connector
► 5 . . . . . . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts materia J . . . . . . . . . . . . . . . . . B7 carbon steel
G . . . . . . . . . . . . . . . . . 316L SST
C . . . . . . . . . . . . . . . . . 660 SST
Installation -2 . . . . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection
upside
-3 . . . . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection
downside
-6 . . . . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection
upside
-7 . . . . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection
downside
-8 . . . . . . . . . . . . . . . Horizontal piping and right side high pressure
► -9 . . . . . . . . . . . . . . . Horizontal piping and left side high pressure
-B . . . . . . . . . . . . . . . Bottom Process Connection, left side high pressure
-U . . . . . . . . . . . . . . . Universal flange
Amplifier housing 1 . . . . . . . . . . . . Cast aluminum alloy
3 . . . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties
2 . . . . . . . . . . . . ASTM CF-8M stainless steel
Electrical connection 0 . . . . . . . . . . G1/2 female, one electrical connection without blind plugs
► 2 . . . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . . . G1/2 female, two electrical connections and a blind plug
7 . . . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug
9 . . . . . . . . . . M20 female, two electrical connections and a blind plug
A . . . . . . . . . . G1/2 female, two electrical connections and a SUS316 blind plug
C . . . . . . . . . . 1/2 NPT female, two electrical connections and a SUS316 blind plug
D . . . . . . . . . . M20 female, two electrical connections and a SUS316 blind plug
Integral indicator D . . . . . . . Digital indicator
E . . . . . . . Digital indicator with the range setting switch (push button)
► N . . . . . . . None
Mounting bracket ► B . . . . . 304 SST 2-inch pipe mounting, flat type (for horizontal piping)
D . . . . . 304 SST 2-inch pipe mounting, L type (for vertical piping)
J . . . . . 316 SST 2-inch pipe mounting, flat type (for horizontal piping)
K . . . . . 316 SST 2-inch pipe mounting, L type (for vertical piping)
M . . . . . 316 SST 2-inch pipe mounting (for bottom process connection type)
N . . . . . None
Optional Codes /  Optional specification
The “►” marks indicate the most typical selection for each specification.
*1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate
materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the
corrosive process fluids.

IM 01C25B01-01E
<9. General Specifications> 9-13
Model EJA120E
Model Suffix Codes Description
EJA120E ............................ Differential pressure transmitter
Output -D . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
signal -J . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication
(HART 5/HART 7 protocol)
-F . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01E)
-G . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, refer to
IM 01C25T04-01EN)
Measurement E . . . . . . . . . . . . . . . . . . . . . . . . 0.1 to 1 kPa (0.4 to 4 inH2O)
span (capsule)
Wetted parts  . . . . . . . . . . . . . . . . . . . . . . Refer to Table.1 Wetted Parts Material on Page 9-18
material *1
Process connections 0 . . . . . . . . . . . . . . . . . . . without process connector (Rc1/4 female on the cover flanges)
1 . . . . . . . . . . . . . . . . . . . with Rc1/4 female process connector
2 . . . . . . . . . . . . . . . . . . . with Rc1/2 female process connector
3 . . . . . . . . . . . . . . . . . . . with 1/4 NPT female process connector
4 . . . . . . . . . . . . . . . . . . . with 1/2 NPT female process connector
► 5 . . . . . . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts materia J . . . . . . . . . . . . . . . . . B7 carbon steel
G . . . . . . . . . . . . . . . . . 316L SST
C . . . . . . . . . . . . . . . . . 660 SST
Installation -2 . . . . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection
upside
-3 . . . . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection
downside
-6 . . . . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection
upside
-7 . . . . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection
downside
-8 . . . . . . . . . . . . . . . Horizontal piping and right side high pressure
► -9 . . . . . . . . . . . . . . . Horizontal piping and left side high pressure
-U . . . . . . . . . . . . . . . Universal flange
Amplifier housing 1 . . . . . . . . . . . . Cast aluminum alloy
3 . . . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties
2 . . . . . . . . . . . . ASTM CF-8M stainless steel
Electrical connection 0 . . . . . . . . . . G1/2 female, one electrical connection without blind plugs
► 2 . . . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . . . G1/2 female, two electrical connections and a blind plug
7 . . . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug
9 . . . . . . . . . . M20 female, two electrical connections and a blind plug
A . . . . . . . . . . G1/2 female, two electrical connections and a SUS316 blind plug
C . . . . . . . . . . 1/2 NPT female, two electrical connections and a SUS316 blind plug
D . . . . . . . . . . M20 female, two electrical connections and a SUS316 blind plug
Integral indicator D . . . . . . . Digital indicator
E . . . . . . . Digital indicator with the range setting switch (push button)
► N . . . . . . . None
Mounting bracket ► B . . . . . 304 SST 2-inch pipe mounting, flat type (for horizontal piping)
D . . . . . 304 SST 2-inch pipe mounting, L type (for vertical piping)
J . . . . . 316 SST 2-inch pipe mounting, flat type (for horizontal piping)
K . . . . . 316 SST 2-inch pipe mounting, L type (for vertical piping)
N . . . . . None
Optional Codes /  Optional specification
The “►” marks indicate the most typical selection for each specification.
*1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate
materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the
corrosive process fluids.

IM 01C25B01-01E
<9. General Specifications> 9-14
Model EJA130E
Model Suffix Codes Description
EJA130E ............................ Differential pressure transmitter
Output -D . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
signal -J . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication
(HART 5/HART 7 protocol)
-F . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01E)
-G . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, refer to
IM 01C25T04-01EN)
Measurement M . . . . . . . . . . . . . . . . . . . . . . . . 1 to 100 kPa (4 to 400 inH2O)
span (capsule) H . . . . . . . . . . . . . . . . . . . . . . . . 5 to 500 kPa (20 to 2000 inH2O)
Wetted parts S . . . . . . . . . . . . . . . . . . . . . . Refer to Table.1 Wetted Parts Material on Page 9-18
material *1
Process connections 3 . . . . . . . . . . . . . . . . . . . with 1/4 NPT female process connector*2
4 . . . . . . . . . . . . . . . . . . . with 1/2 NPT female process connector*2
► 5 . . . . . . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts materia J . . . . . . . . . . . . . . . . . B7 carbon steel
G . . . . . . . . . . . . . . . . . 316L SST
C . . . . . . . . . . . . . . . . . 660 SST
Installation -2 . . . . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection
upside
-3 . . . . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection
downside
-6 . . . . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection
upside
-7 . . . . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection
downside
-8 . . . . . . . . . . . . . . . Horizontal piping and right side high pressure
► -9 . . . . . . . . . . . . . . . Horizontal piping and left side high pressure
-U . . . . . . . . . . . . . . . Universal flange
Amplifier housing 1 . . . . . . . . . . . . Cast aluminum alloy
3 . . . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties
2 . . . . . . . . . . . . ASTM CF-8M stainless steel
Electrical connection 0 . . . . . . . . . . G1/2 female, one electrical connection without blind plugs
► 2 . . . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . . . G1/2 female, two electrical connections and a blind plug
7 . . . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug
9 . . . . . . . . . . M20 female, two electrical connections and a blind plug
A . . . . . . . . . . G1/2 female, two electrical connections and a SUS316 blind plug
C . . . . . . . . . . 1/2 NPT female, two electrical connections and a SUS316 blind plug
D . . . . . . . . . . M20 female, two electrical connections and a SUS316 blind plug
Integral indicator D . . . . . . . Digital indicator
E . . . . . . . Digital indicator with the range setting switch (push button)
► N . . . . . . . None
Mounting bracket ► B . . . . . 304 SST 2-inch pipe mounting, flat type (for horizontal piping)
D . . . . . 304 SST 2-inch pipe mounting, L type (for vertical piping)
J . . . . . 316 SST 2-inch pipe mounting, flat type (for horizontal piping)
K . . . . . 316 SST 2-inch pipe mounting, L type (for vertical piping)
N . . . . . None
Optional Codes /  Optional specification
The “►” marks indicate the most typical selection for each specification.
*1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate
materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the
corrosive process fluids.
*2: Lower limit of ambient and process temperature is -15°C.

IM 01C25B01-01E
<9. General Specifications> 9-15
Model EJA310E
Model Suffix Codes Description
EJA310E ............................ Absolute pressure transmitter
Output -D . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
signal -J . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication
(HART 5/HART 7 protocol)
-F . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01E)
-G . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, refer to
IM 01C25T04-01EN)
Measurement L . . . . . . . . . . . . . . . . . . . . . . . . 0.67 to 10 kPa abs (0.2 to 2.95 inHg abs)
span (capsule) M . . . . . . . . . . . . . . . . . . . . . . . . 1.3 to 130 kPa abs (0.39 to 38 inHg abs)
A . . . . . . . . . . . . . . . . . . . . . . . . 0.03 to 3.5 MPa abs (4.3 to 500 psia)
B . . . . . . . . . . . . . . . . . . . . . . . . 0.14 to 16 MPa abs (20 to 2300 psia)
Wetted parts S . . . . . . . . . . . . . . . . . . . . . . Refer to Table.1 Wetted Parts Material on Page 9-18
material *1
Process connections 0 . . . . . . . . . . . . . . . . . . . without process connector (Rc1/4 female on the cover flanges)
1 . . . . . . . . . . . . . . . . . . . with Rc1/4 female process connector
2 . . . . . . . . . . . . . . . . . . . with Rc1/2 female process connector
3 . . . . . . . . . . . . . . . . . . . with 1/4 NPT female process connector
4 . . . . . . . . . . . . . . . . . . . with 1/2 NPT female process connector
► 5 . . . . . . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts materia J . . . . . . . . . . . . . . . . . B7 carbon steel
G . . . . . . . . . . . . . . . . . 316L SST
C . . . . . . . . . . . . . . . . . 660 SST
Installation -2 . . . . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection
upside
-3 . . . . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection
downside
-6 . . . . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection
upside
-7 . . . . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection
downside
-8 . . . . . . . . . . . . . . . Horizontal piping and right side high pressure
► -9 . . . . . . . . . . . . . . . Horizontal piping and left side high pressure
-B . . . . . . . . . . . . . . . Bottom Process Connection, left side high pressure:
-U . . . . . . . . . . . . . . . Universal flange
Amplifier housing 1 . . . . . . . . . . . . Cast aluminum alloy
3 . . . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties
2 . . . . . . . . . . . . ASTM CF-8M stainless steel
Electrical connection 0 . . . . . . . . . . G1/2 female, one electrical connection without blind plugs
► 2 . . . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . . . G1/2 female, two electrical connections and a blind plug
7 . . . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug
9 . . . . . . . . . . M20 female, two electrical connections and a blind plug
A . . . . . . . . . . G1/2 female, two electrical connections and a 316 SST blind plug
C . . . . . . . . . . 1/2 NPT female, two electrical connections and a 316 SST blind plug
D . . . . . . . . . . M20 female, two electrical connections and a 316 SST blind plug
Integral indicator D . . . . . . . Digital indicator
E . . . . . . . Digital indicator with the range setting switch (push button)
► N . . . . . . . (None)
Mounting bracket ► B . . . . . 304 SST 2-inch pipe mounting, flat type (for horizontal piping)
D . . . . . 304 SST 2-inch pipe mounting, L type (for vertical piping)
J . . . . . 316 SST 2-inch pipe mounting, flat type (for horizontal piping)
K . . . . . 316 SST 2-inch pipe mounting, L type (for vertical piping)
M . . . . . 316 SST 2-inch pipe mounting (for bottom process connection type)
N . . . . . (None)
Optional Codes /  Optional specification
The “►” marks indicate the most typical selection for each specification.
*1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate
materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the
corrosive process fluids.

IM 01C25B01-01E
<9. General Specifications> 9-16
Model EJA430E
Model Suffix Codes Description
EJA430E ............................ Gauge pressure transmitter
Output -D . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
signal -J . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication
(HART 5/HART 7 protocol)
-F . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01E)
-G . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, refer to
IM 01C25T04-01EN)
Measurement H . . . . . . . . . . . . . . . . . . . . . . . . 5 to 500 kPa (20 to 2000 inH2O)
span (capsule) A . . . . . . . . . . . . . . . . . . . . . . . . 0.03 to 3.5 MPa (4.3 to 500 psi)
B . . . . . . . . . . . . . . . . . . . . . . . . 0.14 to 16 MPa (20 to 2300 psi)
Wetted parts  . . . . . . . . . . . . . . . . . . . . . . Refer to Table.1 Wetted Parts Material on Page 9-18
material *1
Process connections 0 . . . . . . . . . . . . . . . . . . . without process connector (Rc1/4 female on the cover flanges)
1 . . . . . . . . . . . . . . . . . . . with Rc1/4 female process connector
2 . . . . . . . . . . . . . . . . . . . with Rc1/2 female process connector
3 . . . . . . . . . . . . . . . . . . . with 1/4 NPT female process connector
4 . . . . . . . . . . . . . . . . . . . with 1/2 NPT female process connector
► 5 . . . . . . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts materia J . . . . . . . . . . . . . . . . . B7 carbon steel
G . . . . . . . . . . . . . . . . . 316L SST
C . . . . . . . . . . . . . . . . . 660 SST
Installation -2 . . . . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection
upside
-3 . . . . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection
downside
-6 . . . . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection
upside
-7 . . . . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection
downside
-8 . . . . . . . . . . . . . . . Horizontal piping and right side high pressure
► -9 . . . . . . . . . . . . . . . Horizontal piping and left side high pressure
-B . . . . . . . . . . . . . . . Bottom Process Connection, left side high pressure
-U . . . . . . . . . . . . . . . Universal flange
Amplifier housing 1 . . . . . . . . . . . . Cast aluminum alloy
3 . . . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties
2 . . . . . . . . . . . . ASTM CF-8M stainless steel
Electrical connection 0 . . . . . . . . . . G1/2 female, one electrical connection without blind plugs
► 2 . . . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . . . G1/2 female, two electrical connections and a blind plug
7 . . . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug
9 . . . . . . . . . . M20 female, two electrical connections and a blind plug
A . . . . . . . . . . G1/2 female, two electrical connections and a 316 SST blind plug
C . . . . . . . . . . 1/2 NPT female, two electrical connections and a 316 SST blind plug
D . . . . . . . . . . M20 female, two electrical connections and a 316 SST blind plug
Integral indicator D . . . . . . . Digital indicator
E . . . . . . . Digital indicator with the range setting switch (push button)
► N . . . . . . . (None)
Mounting bracket ► B . . . . . 304 SST 2-inch pipe mounting, flat type (for horizontal piping)
D . . . . . 304 SST 2-inch pipe mounting, L type (for vertical piping)
J . . . . . 316 SST 2-inch pipe mounting, flat type (for horizontal piping)
K . . . . . 316 SST 2-inch pipe mounting, L type (for vertical piping)
M . . . . . 316 SST 2-inch pipe mounting (for bottom process connection type)
N . . . . . (None)
Optional Codes /  Optional specification
The “►” marks indicate the most typical selection for each specification.
*1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate
materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the
corrosive process fluids.

IM 01C25B01-01E
<9. General Specifications> 9-17
Model EJA440E
Model Suffix Codes Description
EJA440E ............................ Gauge pressure transmitter
Output -D . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
signal -J . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication
(HART 5/HART 7 protocol)*1
-F . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01E)
-G . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, refer to
IM 01C25T04-01EN)
Measurement C . . . . . . . . . . . . . . . . . . . . . . . . 5 to 32 MPa (720 to 4500 psi)
span (capsule) D . . . . . . . . . . . . . . . . . . . . . . . . 5 to 50 MPa (720 to 7200 psi)
Wetted parts S . . . . . . . . . . . . . . . . . . . . . . Refer to Table.1 Wetted Parts Material on Page 9-18
material *1
Process connections 3 . . . . . . . . . . . . . . . . . . . with 1/4 NPT female process connector*2*3
4 . . . . . . . . . . . . . . . . . . . with 1/2 NPT female process connector*2*3
► 5 . . . . . . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts materia J . . . . . . . . . . . . . . . . . B7 carbon steel
G . . . . . . . . . . . . . . . . . 316L SST
C . . . . . . . . . . . . . . . . . 660 SST
Installation -2 . . . . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection
upside
-3 . . . . . . . . . . . . . . . Vertical piping, right side high pressure, and process connection
downside
-6 . . . . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection
upside
-7 . . . . . . . . . . . . . . . Vertical piping, left side high pressure, and process connection
downside
-8 . . . . . . . . . . . . . . . Horizontal piping and right side high pressure
► -9 . . . . . . . . . . . . . . . Horizontal piping and left side high pressure
-U . . . . . . . . . . . . . . . Universal flange
Amplifier housing ► 1 . . . . . . . . . . . . Cast aluminum alloy
3 . . . . . . . . . . . . Cast aluminum alloy with corrosion resistance properties
2 . . . . . . . . . . . . ASTM CF-8M stainless steel
Electrical connection 0 . . . . . . . . . . G1/2 female, one electrical connection without blind plugs
► 2 . . . . . . . . . . 1/2 NPT female, two electrical connections without blind plugs
4 . . . . . . . . . . M20 female, two electrical connections without blind plugs
5 . . . . . . . . . . G1/2 female, two electrical connections and a blind plug
7 . . . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug
9 . . . . . . . . . . M20 female, two electrical connections and a blind plug
A . . . . . . . . . . G1/2 female, two electrical connections and a 316 SST blind plug
C . . . . . . . . . . 1/2 NPT female, two electrical connections and a 316 SST blind plug
D . . . . . . . . . . M20 female, two electrical connections and a 316 SST blind plug
Integral indicator D . . . . . . . Digital indicator
E . . . . . . . Digital indicator with the range setting switch (push button)
► N . . . . . . . (None)
Mounting bracket ► B . . . . . 304 SST 2-inch pipe mounting, flat type (for horizontal piping)
D . . . . . 304 SST 2-inch pipe mounting, L type (for vertical piping)
J . . . . . 316 SST 2-inch pipe mounting, flat type (for horizontal piping)
K . . . . . 316 SST 2-inch pipe mounting, L type (for vertical piping)
N . . . . . (None)
Optional Codes /  Optional specification
The “►” marks indicate the most typical selection for each specification.
*1: Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying inappropriate
materials has the potential to cause serious damage to human body and plant facilities resulted from an unexpected leak of the
corrosive process fluids.
*2: Specify the process connections code 3 or 4, when using the process connector for D capsule. Without the process connector, use
the 1/4 NPT male piping to directly connect to the cover flange.
*3: Lower limit of ambient and process temperature is -15°C for capsule code C.

IM 01C25B01-01E
<9. General Specifications> 9-18
Table. 1 Wetted Parts Materials for EJ110, EJ120, EJ310, and EJ430
Wetted parts Cover flange and
Capsule Capsule gasket Vent/Drain plug
material code process connector
Hastelloy C-276 (Diaphragm)
Teflon-coated 316L SST
S# ASTM CF-8M F316L SST, 316L SST 316 SST
PTFE for EJX120A
(Others)
H ASTM CF-8M Hastelloy C-276 PTFE (Teflon) 316 SST
M ASTM CF-8M Monel PTFE (Teflon) 316 SST
T ASTM CF-8M Tantalum PTFE (Teflon) 316 SST
A Hastelloy C-276 equivalent Hastelloy C-276 PTFE (Teflon) Hastelloy C-276
D Hastelloy C-276 equivalent Tantalum PTFE (Teflon) Hastelloy C-276
B Monel equivalent Monel PTFE (Teflon) Monel
The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use of 316 SST
material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for details.

Table. 2 Wetted Parts Materials for EJ130


Wetted parts Cover
process connector Capsule Capsule gasket Vent/Drain plug
material code flange
Hastelloy C-276*2
Teflon-coated
S# F316 SST ASTM CF-8M *1 (Diaphragm) 316 SST
316L SST
F316L SST, 316L SST (Others)
*1: Cast version of 316 SST. Equivalent to SCS14A.
*2: Hastelloy C-276 or ASTM N10276.
The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use of
316 SST material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for details.

Table. 3 Wetted Parts Materials for EJ440


Wetted parts Cover Vent/
process connector Capsule Capsule gasket
material code flange Drain plug
ASTM CF-8M *1 (C-capsule) Hastelloy C-276 *2 (Diaphragm) Teflon-coated
S# F316 SST 316 SST
F316L SST (D-capsule) F316L SST, 316L SST (Others) 316L SST
*1: Cast version of 316 SST. Equivalent to SCS14A.
*2: Hastelloy C-276 or ASTM N10276.
The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use of
316 SST material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for details.

IM 01C25B01-01E
<9. General Specifications> 9-19
9.3 Optional Specifications
Item Description Code
Factory Mutual (FM) FM Explosionproof *1
Explosionproof for Class I, Division 1, Groups B, C and D
FF1
Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G
Hazardous (classified) locations, indoors and outdoors (NEMA 4X)
FM Intrinsically safe *1*3
Intrinsically Safe for Class I, Division 1, Groups A, B, C and D, Class II,
Division 1,Groups E, F and G and Class III, Division 1 Hazardous Locations. FS1
Nonincendive for Class I, Division 2, Groups A, B, C and D, Class II,
Division 2, Groups F and G, Hazardous Locations.
Combined FF1 and FS1 *1*3 FU1
ATEX ATEX Flameproof *1
II 2G, 2D Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db KF22
Special fastener: ClassA2-50(A4-50) or more
ATEX Intrinsically safe Ex ia *1*3
KS21
II 1G, 2D Ex ia IIC T4 Ga, Ex ia IIIC T85°C T100°C T120°C Db
Combined KF22, KS21 and ATEX Intrinsically safe Ex ic *1*3
KU22
Ex ic: II 3G Ex ic IIC T4 Gc
Canadian Standards CSA Explosionproof *1
Association (CSA) Explosionproof for Class I, Groups B, C and D
Dustignitionproof for Class II/III, Groups E, F and G
Enclosure TYPE 4X, Temp.Code:T6...T4
Ex d IIC T6...T4 Enclosure IP66/IP67 CF1
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required
Primary seal failure annuniciation: at the zero adjustment screw
CSA Intrinsically safe *1 *3
[For CSA C22.2]
Intrinsically safe for Class I, Division 1, Groups A, B, C and D, Class II,
Division 1, Groups E, F and G, Class III, Division 1
Nonincendive for Class I, Division 2, Groups A, B, C and D, Class II,
Division 2, Groups F and G, Class III, Division 1
CS1
[For CSA E60079]
Ex ia IIC T4, Ex nL IIC T4
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required
Primary seal failure annuniciation: at the zero adjustment screw
Combined CF1 and CS1 *1*3 CU1
IECEx IECEx flameproof *1
SF2
Flameproof for Zone1, Ex d IIC T6...T4
IECEx Intrinsically safe, type n and flameproof *1*3
Intrinsically safe and type n
Ex ia IIC T4, Ex nL IIC T4 SU2
Flameproof
Flameproof for Zone1, Ex d IIC T6...T4
Combination of Approval Combination of KU22, FU1 and CU1 V1U1
Painting Color change Terminal cover only P
Both sides of amplifier covers, Munsell 7.5 R4/14 PR
Coating change Anti-corrosion coating X2
316 SST exterior parts 316 SST name plate, tag plate and zero adjustment screw HC
Fluoro-rubber O-ring All O-rings of amplifier housing. Lower limit of ambient temperature: –15°C(5°F) HE
Lightning protector Transmitter power supply voltage:
10.5 to 32 V DC (10.5 to 30 V DC for intrinsically safe type.)
A
Allowable current: Max. 6000 A (1×40 μs), Repeating 1000 A (1×40 μs) 100 times
Applicable Standards: IEC 61000-4-4, IEC 61000-4-5
Status output *11 Transistor output (sink type)
AL
Contact rating: 10.5 to 30 VDC, 120 mA DC(max) Low level: 0 to 2 VDC
Oil-prohibited use *4 Degrease cleansing treatment. K1
Degrease cleansing treatment and with fluorinated oilfilled capsule.
K2
Operating temperature –20 to 80°C( –4 to 176°F)

IM 01C25B01-01E
<9. General Specifications> 9-20
Item Description Code
Oil-prohibited use with Degrease cleansing treatment and dehydrating treatment. K5
dehydrating treatment *4 Degrease cleansing treatment and dehydrating treatment with fluorinated oilfilled
K6
capsule. Operating temperature –20 to 80°C( –4 to 176°F)
Capsule fill fluid Fluorinated oil filled in capsule
K3
Operating temperature –20 to 80°C( –4 to 176°F)
Calibration units *5 P calibration (psi unit) D1
(See Table for Span and
bar calibration (bar unit) D3
Range Limits.)
M calibration (kgf/cm2 unit) D4
Long vent *6 Total length: 119 mm (standard: 34 mm); Total length when combining with
U1
Optional code K1, K2, K5, and K6: 130 mm. Material: 316SST.
Gold-plated capsule gasket Gold-plated 316L SST capsule gasket. No PTFE is used for wetted parts.
GS
*13
Gold-plated diaphragm *14 Surface of isolating diaphragm is gold plated, effective for hydrogen permeation. A1
130 Pa abs calibration *12 Minimum input puressure at calibration testing: 130 Pa abs (1 mmHg abs) S1
Output limits and failure Failure alarm down-scale: Output status at CPU failure and hardware error is
C1
operation *7 –5%, 3.2 mA DC or less.
NAMUR NE43 Compliant Failure alarm down-scale: Output status at CPU
C2
Output signal limits: failure and hardware error is –5%, 3.2 mA DC or less.
3.8 mA to 20.5 mA Failure alarm up-scale: Output status at CPU
C3
failure and hardware error is 110%, 21.6 mA or more.
Body option *8 Without drain and vent plugs N1
N1 and Process connection, based on IEC61518 with female thread on both sides
N2
of cover flange, with blind kidney flanges on back.
N2 and Material certificate for cover flange, diaphragm, capsule body, and blind
N3
kidney flange
Stainless steel tag plate 304SST tag plate wired onto transmitter N4
Data configuration at Data configuration for HART Software damping, Descriptor, Message
CA
factory *9 communication type
Data configuration for BRAIN Software damping
CB
communication type
European Pressure PED 97/23/EC
Directive *10 Category: III, Module: H, Type of Equipment; Pressure Accessory-Vessel, Type of
PE3
Fluid; Liquid and gas, Group of Fluid: 1 and 2
Lower limit of Process and Ambient temperature for EJX110A : –29°C
Advanced diagnostics *27 Multi-sensing process monitoring
• Impulse line blockage detection *28 DG6
• Heat trace monitoring
Material certificate *15 Cover flange *16 M01
Cover flange, Process connector *17 M11
Pressure test/ Test Pressure: 16 MPa (2300 psi) *18 T12
Leak test certificate Test Pressure: 25 MPa (3600 psi) *19 T13
Test Pressure: 3.5 MPa (500 psi)* 20 Nitrogen(N2) Gas *25 T01
Retention time: one minute
Test Pressure: 500 kPa (2000 inH2O) *21 T11
Test Pressure: 50 kPa (200 inH2O) *22 T04
Test Pressure: 32 MPa (4500 psi) *23 Nitrogen(N2) Gas or water *26 T09
Test Pressure: 50 MPa (7200 psi) *24 Retention time: one minute T08
High accuracy type High accuracy HAC
High pressure-proof Maximum working pressure for differential pressure measurement: 25MPa*29
HG
structure
Contact Yokogawa representative for the codes indicated as ‘-’.
*1: Applicable for Electrical connection code 2, 4, 7, and 9.
*2: Applicable for Electrical connection code 2 and 7.
*3: Not applicable for option code /AL.
*4: Applicable for Wetted parts material code S, H, M, and T.
*5: The unit of MWP (Max. working pressure) on the name plate of the housing is the same unit as specified by Option code D1, D3,
and D4.
*6: Applicable for vertical impulse piping type (Installation code 7) and Wetted parts material code S, H, M, and T.
*7: Applicable for output signal code D, E and J. The hardware error indicates faulty amplifier or capsule.
*8: Applicable for Wetted parts material code S, H, M, and T; Process connection code 3, 4, and 5; Installation code 9; and Mounting
bracket code N. Process connection faces on the other side of zero adjustment screw.

IM 01C25B01-01E
<9. General Specifications> 9-21
*9: Also see ‘Ordering Instructions’.
*10: Applicable for M, H and V capsules of EJX110A with wetted parts material code S, and all the ranges of EJ130 and EJ440.
Applicable also for EJA110E with option code /HG.
*11: Not applicable for output signal code F.
*12: Applicable only for EJ310 M and A capsules whose upper range value is set as smaller than 53.3 kPa abs.
*13: Applicable for wetted parts material code S; process connection code 0 and 5; and installation code 8 and 9. Not applicable for
option code U1, N2, N3 and M11. Not applicable for EJ120.
*14: Applicable for wetted parts material code S.
*15: Material traceability certification, per EN 10204 3.1B.
*16: Applicable for Process connections code 0 and 5.
*17: Applicable for Process connections code 1, 2, 3, and 4.
*18: Applicable for EJA110E, Capsule code F and L of EJX110A, Capsule code B of EJ430 and EJX310A, and all the capsules of
EJX110A with wetted parts maerial code H, M, T, A, D, and B.
*19: Applicable for Capsule code M, H and V of EJX110A with wetted parts material code S.
*20: Applicable for Capsule code A of EJ430 and EJ310.
*21: Applicable for Capsule code H of EJ430.
*22: Applicable for EJ120 and Capsule code L and M of EJ310.
*23: Applicable for EJ130 and Capsule code C of EJ440.
*24: Applicable for Capsule code D of EJ440.
*25: Pure nitrogen gas is used for oil-prohibited use (Option code K1, K2, K5, and K6).
*26: Pure nitrogen gas or pure water is used for oil-prohibited use (Option code K1, K2, K5, and K6).
*27: Applicable only for output signal code E and J.
*28: The change of pressure fluctuation is monitored and then detects the impulse line blockage. See TI 01C25A31-01E for detailed
technical information required for using this function. The detection is for one side only.
*29: Applicable for EJA110E, Measurement span code M, H, and, V; and wetted parts material code S. The URL of static pressure range
is also extended to 25 MPa.

IM 01C25B01-01E
<9. General Specifications> 9-22
9.4 Dimensions
Model EJ110
Unit: mm (approx. inch)
● Vertical Impulse Piping Type
Process connector downside Electrical connection
(Installation code 7) for code 5, 9, A, and D.
242(9.53) 110(4.33)

54 (0.24)
6
175(6.89)
12 39
97 129(5.08) 2-inch pipe
(0.47)

(2.13)
(3.82) (1.54) (O.D. 60.5 mm)
Mounting bracket Vent/Drain Process connector upside
(L-type,optional) plugs
(2.05)

(Installation code 6)
52

Process
Integral indicator External indicator connection
(optional) Conduit connection
97(3.82)

(optional)
223(8.78)

67(2.64)

(1.61)
ø78(3.07)

138(5.43)*2
95(3.74)

ø70(2.76)

41
(1.61)
67(2.64)

223(8.78)
41

97(3.82)
Process
Conduit connector
connection (optional)
Process connection 54
Zero adjustment High Low

(2.05)
pressure (2.13) pressure

52
Ground terminal side*1 side*1

● Horizontal Impulse Piping Type (Installation code 9) Conduit


External indicator 89(3.50) 67 connection Zero 110(4.33)
Conduit connection (2.64) adjustment 12 39
Integral indicator
(optional) 95(3.74) (0.47) (1.54)
(optional)
54
ø78(3.07)

(2.76)
(2.13)

ø70
6
175(6.89)
145(5.71)

129(5.08)
(0.24)
Vent plug, Ground
Drain plug*4 terminal Vent plug*4

Electrical connection Vent plug*4


for code 5, 9, A, and D.
Drain plug*4 Drain plug*4
124(4.88)

41
54(2.13)
(1.61) Process High Low
115(4.53) connection pressure pressure
side*1 side*1
Process connector
(1.85)
47

Mounting bracket (optional) 2-inch pipe


(Flat-type,optional) (O.D. 60.5 mm)
130(5.12)*3
*1: When Installation code 2, 3, or 8 is selected, high and low pressure side on the above figure
are reversed. (i.e. High pressure side is on the right side.)
*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.
*3: When Option code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value in the figure.
*4: Not available when option code GS is specified.

F0904.ai

IM 01C25B01-01E
<9. General Specifications> 9-23
Unit: mm (approx. inch)
● Vertical Impulse Piping Type
Process connector downside Electrical connection
(Installation code 7) for code 5, 9, A, and D.
256(10.10)
110(4.33)

(0.24)
194(7.64)

6
97 143(5.63) 9*4 39
2-inch pipe
(3.82) (0.35) (1.54)
(O.D. 60.5 mm)

(2.13)
54
Mounting bracket Vent/Drain plugs Process connector upside
(Installation code 6)
(2.05)

(L-type,optional)
52

Process connection
External indicator
Integral indicator Conduit connection
102(4.02)

(optional) (optional)
234(9.21)

72(2.83)

(1.81)
ø78(3.07)

148(5.83)*2

46
(3.74)

(2.76)
ø70
95
(1.81)

234(9.21)
72(2.83)
46

102(4.02)
Process
Conduit connector
connection (optional) 54
Process connection
Zero adjustment High (2.13) Low

(2.05)
pressure pressure

52
Ground terminal side*1 side*1

● Horizontal Impulse Piping Type (Installation code 9)


External indicator Conduit connection
Conduit connection 94(3.70) 72(2.83) 110(4.33)
Zero
(optional) adjustment 39
95(3.75) Integral indicator 9*4
54 (optional) (0.35) (1.54)

ø78(3.07)
(2.13)
6

(2.76)
ø70
(0.24)
159(6.26)

143(5.63)
194(7.64)

Ground terminal
Electrical connection
for code 5, 9, A, and D.
Vent plug
Vent plug
Drain plug
124(4.88)

46 Process connection Drain plug


(1.81) 54
High Low
125(4.92) Process connector pressure (2.13) pressure
(optional) side*1 side*1
2-inch pipe
(1.85)

(O.D. 60.5 mm)


47

Mounting bracket
(Flat-type,optional)

133*3
*1: When Installation code 2, 3, or 8 is selected, high and low pressure side on the above figure (5.24)
are reversed. (i.e. High pressure side is on the right side.)
*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.
*3: When Option code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value in the figure.
*4: 15 mm(0.59 inch) for right side high pressure.
F0905.ai

IM 01C25B01-01E
<9. General Specifications> 9-24
Unit: mm (approx. inch)
● Bottom Process Connection (Installation code -B)
54
(2.13) 95(3.74) 188(7.40)
6
Integral indicator
(0.24) 73 Zero 110(4.33)
(optional)
(2.87) adjustment
12 39
Conduit connection (0.47) (1.54)
Electrical connection

ø78(3.07)
for code 5, 9, A, and D.

(2.76)
ø70

109(4.29)
159(6.26)
Extenal indicator
Conduit connection
(optional)
Ground terminal

(2.36)
Mounting bracket*2

60
(optional) Vent plug
2-inch pipe Process connector 54
(O.D. 60.5 mm) (optional) High (2.13) Low
pressure pressure
Process connection side 130(5.12) side
129(5.08)

F0906.ai

● Universal Flange (Installation code -U), Measurement Span code M, H and V


58 67 110(4.33)
(2.28) (2.64) Zero
External indicator adjustment
Conduit connection Conduit connection 12 39
95(3.74)
(optional) Integral indicator (0.47) (1.54)
54 (optional)
ø78(3.07)

(2.13)

(2.76)
6

ø70
145(5.71)

(0.24)

129(5.08)
175(6.89)

Ground terminal

Electrical connection
for code 5, 9, A, and D.
Vent plug
Drain plug
41 54 Drain plug
High Low
Vent plug (1.61) pressure (2.13) pressure
115(4.53) side 130*1 side
Process connection
Drain plug (5.12)
Process connector
(optional)

● Universal Flange (Installation code -U), Measurement Span code F


External indicator 63 72 Zero 110(4.33)
Conduit connection adjustment
Conduit connection (2.48) (2.83)
9 39
(optional) 95(3.74) Integral indicator
(0.35) (1.54)
54 (optional)
ø78(3.07)

(2.13)
6
(2.76)
ø70

(0.24)
159(6.26)

143(5.63)
194(7.64)

Ground terminal

Electrical connection
for code 5, 9, A, and D.
Vent plug
Drain plug
46 Drain plug
54
Vent plug (1.81) High Low
pressure (2.13) pressure
Process connection side side
125(4.92) 133(5.24)*1
Drain plug Process connector (optional)

*1: When Option code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value.
*2: A transmitter with SST housing is not applicable for mounting to horizontal 2-inch pipe. F0907.ai

IM 01C25B01-01E
<9. General Specifications> 9-25
Model EJ120
Unit: mm (approx. inch)
● Vertical Impulse Piping Type
Process connector downside Electrical connection
(Installation code 7) for code 5, 9, A, and D.
256(10.10) 110(4.33)

54 (0.24)
6
194(7.64)
97 143(5.63) 12 39
2-inch pipe

(2.13)
(3.82) (0.47) (1.54)
(O.D. 60.5 mm)

Mounting bracket Vent/Drain plugs Process connector upside


(Installation code 6)
(2.05)

(L-type,optional)
52

Extenal indicator Process connection


Integral indicator Conduit connection
(optional) (optional)
102(4.02)
234(9.21)

72(2.83)

(1.81)
ø78(3.07)

148(5.83)*2

46
(3.74)

(2.76)
ø70
95
(1.81)

234(9.21)
72(2.83)
46

102(4.02)
Process
Conduit connector
connection (optional)
Process connection 54
Zero adjustment High Low
pressure (2.13) pressure

(2.05)
Ground terminal

52
side*1 side*1

● Horizontal Impulse Piping Type (Installation code 9)


Extenal indicator Conduit connection
Conduit connection 94(3.70) 72(2.83) 110(4.33)
Zero
(optional) adjustment
95(3.75) Integral indicator 12 39
(optional) (0.47) (1.54)
54
(2.13)

ø78(3.07)
6

(2.76)
ø70
(0.24)
159(6.26)

143(5.63)
194(7.64)

Ground terminal
Electrical connection
for code 5, 9, A, and D.
Vent plug
Vent plug
Drain plug
124(4.88)

46 Process connection Drain plug


(1.81) 54
High (2.13) Low
125(4.92) Process connector pressure pressure
(optional) side*1 side*1
2-inch pipe
(1.85)

(O.D. 60.5 mm)


47

Mounting bracket
(Flat-type,optional)

133*3
*1: When Installation code 2, 3, or 8 is selected, high and low pressure side on the above figure (5.24)
are reversed. (i.e. High pressure side is on the right side.)
*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.
*3: When Option code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value in the figure.
F0908.ai

IM 01C25B01-01E
<9. General Specifications> 9-26
Unit: mm (approx. inch)
● Universal Flange (Installation code -U)
External indicator 63 72 Zero 110(4.33)
Conduit connection adjustment
Conduit connection (2.48) (2.83)
(optional) 12 39
95(3.74) Integral indicator
(0.47) (1.54)
54 (optional)

ø78(3.07)
(2.13)

(2.76)
6

ø70
(0.24)

159(6.26)

143(5.63)
194(7.64)
Ground terminal

Electrical connection
for code 5, 9, A, and D.
Vent plug
Drain plug
46 54 Drain plug
Vent plug (1.81) High (2.13) Low
pressure pressure
125(4.92) Process connection side 133(5.24)*1 side
Drain plug Process connector
(optional)
*1: When Option code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value.
F0909.ai

IM 01C25B01-01E
<9. General Specifications> 9-27
Model EJ130
Unit: mm (approx. inch)
● Vertical Impulse Piping Type
Process connector downside Electrical connection
(Installation code 7) for code 5, 9, A, and D.
256(10.1) 132(5.2)

(0.24)
197(7.76) 110(4.33)
143(5.63) 9 39 2-inch pipe

6
97
(3.82) (0.35) (1.54) (O.D. 60.5 mm)

(2.13)
54
Vent/Drain plugs
Mounting bracket Process connector upside
(2.05)

(L-type,optional) (Installation code 6)


52

External indicator Process connection


Integral indicator Conduit connection
(optional)
(optional)
(4.88)
124

(3.66)
277(10.9)

93
192(7.56)*2
ø70(2.76)
ø78(3.07)
(3.74)
95

277(10.9)
(3.66)
93

Process

(4.88)
124
Conduit connector
connection (optional)
Process connection Zero adjustment High 54 Low
pressure (2.13) pressure
Ground terminal

(2.05)
side*1 side*1

52
● Horizontal Impulse Piping Type (Installation code 9)
Conduit connection
External indicator 116(4.57) 93(3.66) Zero 110(4.33)
Conduit connection adjustment
95(3.74) Integral indicator 9*4 39
(optional) (optional) (0.35) (1.54)

ø78(3.07)
54

(2.76)
ø70
(2.13)
6
197(7.76)
159(6.26)

143(5.63)
(0.24)
Vent plug,
Drain plug*5 Ground terminal Vent plug*5

Electrical connection Vent plug*5


for code 5, 9, A, and D. Process
connection
Drain plug*5
Drain plug*5
124(4.88)

68
54(2.13) Low
(2.68) High
pressure pressure
Process connector side*1
169(6.65) side*1
(optional)
(1.85)
47

Mounting bracket
(Flat-type,optional) 2-inch pipe
(O.D. 60.5 mm)

154(6.06)*3
*1: When Installation code 2, 3, or 8 is selected, high and low pressure side on the above figure
are reversed. (i.e. High pressure side is on the right side.)
*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.
*3: When Option code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value in the figure.
*4: 15 mm(0.59 inch) for right side high pressure.
*5: Not available when Option code GS is specified.

IM 01C25B01-01E
<9. General Specifications> 9-28
Unit: mm (approx. inch)
● Universal Flange (Installation code -U)
External indicator 85(3.35) 93(3.66) Zero 110(4.33)
Conduit connection Conduit connection adjustment
(optional) 9 39
95(3.74) Integral indicator (0.35) (1.54)
(optional)
54

ø78(3.07)
(2.13)

(2.76)
ø70
6

159(6.26)
(0.24)

143(5.63)
197(7.76)
Ground terminal

Electrical connection
for code 5, 9, A, and D.
Vent plug
Drain plug
68 Drain plug
54
Vent plug (2.68) (2.13)
High Low
169(6.65) 154(6.06)*1
Drain plug Process connection pressure pressure
side side
Process connector
(optional)

*1: When Option code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value.
F0911.ai

IM 01C25B01-01E
<9. General Specifications> 9-29
Model EJ310
Unit: mm (approx. inch)
● Vertical Impulse Piping Type
Process connector downside Electrical connection
(Installation code 7) for code 5, 9, A, and D.
242(9.53) 110(4.33)

54 (0.24)
175(6.89)

6
12 39
97 129(5.08) 2-inch pipe
(3.82) (0.47) (1.54) (O.D. 60.5 mm)

(2.13)
Mounting bracket Vent/Drain Process connector upside
(L-type,optional) plugs (Installation code 6)
(2.05)
52

Integral indicator Extenal indicator Process connection


(optional) Conduit connection
97(3.82)

(optional)
223(8.78)

67(2.64)

(1.61)
ø78(3.07)

138(5.43)*2
95(3.74)

ø70(2.76)

41
(1.61)
67(2.64)

223(8.78)
41

97(3.82)
Process
Conduit connector
connection (optional)
Process connection 27
Zero adjustment High Low

(2.05)
pressure (1.06) pressure

52
Ground terminal side*1 side*1

● Horizontal Impulse Piping Type (Installation code 9)


89(3.50) 67 Conduit connection 110(4.33)
Extenal indicator Zero
Conduit connection (2.64) Integral indicator adjustment 12 39
(optional) 95(3.74) (optional) (0.47) (1.54)
54

ø78(3.07)

(2.76)
(2.13)

ø70
6
175(6.89)
145(5.71)

129(5.08)
(0.24)
Vent plug,
Ground
Drain plug*3 terminal

Electrical connection Vent plug*3


for code 5, 9, A, and D. Drain plug*3
Process
124(4.88)

41 connection 27(1.06)
(1.61) Low
High
Process connector pressure
pressure
115(4.53) side*1
(optional) side*1
(1.85)
47

Mounting bracket 2-inch pipe


(Flat-type,optional) (O.D. 60.5 mm)

65*2
*1: When Installation code 2, 3, or 8 is selected, high and low pressure side on the above figure (2.56)
are reversed. (i.e. High pressure side is on the right side.)
*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.
*3: Not available when Option code GS is specified.

F0912.ai

IM 01C25B01-01E
<9. General Specifications> 9-30
Unit: mm (approx. inch)
● Bottom Process Connection (Installation code -B)
54
(2.13) 95(3.74) 188(7.40)
6
Integral indicator
(0.24) 73 Zero 110(4.33)
(optional)
(2.87) adjustment
12 39
Conduit connection (0.47) (1.54)
Electrical connection

ø78(3.07)
for code 5, 9, A, and D.

(2.76)
ø70

109(4.29)
159(6.26)
Extenal indicator
Conduit connection
(optional)
Ground terminal

Vent plug
High Low

(2.36)
Mounting bracket*2

60
pressure pressure
(optional) side side

2-inch pipe Process connector 27


(O.D. 60.5 mm) (optional) (1.06)
Process connection 65 129
(2.56) (5.08)
F0913.ai

● Universal Flange (Installation code -U)

58 67 110(4.33)
Zero
External indicator (2.28) (2.64) adjustment
Conduit connection Conduit connection 12 39
95(3.74)
(optional) Integral indicator (0.47) (1.54)
54 (optional)
ø78(3.07)

(2.13)

(2.76)
6

ø70
145(5.71)

(0.24)

129(5.08)
175(6.89)

Ground terminal

Electrical connection
for code 5, 9, A, and D.
Drain plug
41 65* 1
High Low
Vent plug (1.61) pressure (2.56) pressure
115(4.53) side side
Process connection
Drain plug
Process connector
(optional)
*1: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value.
*2: A transmitter with SST housing is not applicable for mounting to horizontal 2-inch pipe. F0914.ai

IM 01C25B01-01E
<9. General Specifications> 9-31
Model EJ430
Unit: mm (approx. inch)
● Vertical Impulse Piping Type
Process connector downside Electrical connection
(Installation code 7) for code 5, 9, A, and D.
242(9.53)

6(0.24)
110(4.33)
175(6.89)
12 39
97 129(5.08) 2-inch pipe
(3.82) (0.47) (1.54) (O.D. 60.5 mm)

(2.13)
54
Mounting bracket Vent/Drain Process connector upside
(L-type,optional) plugs (Installation code 6)
(2.05)
52

Integral indicator External indicator Process connection


(optional) Conduit connection
97(3.82)

(optional)
223(8.78)

67(2.64)

(1.61)
ø78(3.07)

138(5.43)*2
95(3.74)

ø70(2.76)

41
(1.61)
67(2.64)

223(8.78)
41

97(3.82)
Process
Conduit connector
Process connection connection (optional) 27
Zero adjustment High Low

(2.05)
pressure (1.06) pressure

52
Ground terminal side*1 side*1
Open to atmosphere
ø10(0.39)
● Horizontal Impulse Piping Type (Installation code 9)
External indicator 89(3.50) 67 Conduit connection Zero 110(4.33)
Conduit connection (2.64) adjustment 12 39
Integral indicator
(optional) 95(3.74) (0.47)
(optional) (1.54)
54

ø78(3.07)

(2.76)
(2.13)

ø70
6
175(6.89)
145(5.71)

129(5.08)
(0.24)
Vent plug, Ground
Dran plug*3 terminal

Vent plug*3
Electrical connection
for code 5, 9, A, and D. Drain plug*3 Open to atmosphere
124(4.88)

41 ø5(0.20)
Process connection 27(1.06)
(1.61) Low
High
Process connector pressure pressure
115(4.53) side*1
(optional) side*1
(1.85)
47

Mounting bracket 2-inch pipe


(Flat-type,optional) (O.D. 60.5 mm)

65*2
*1: When Installation code 2, 3, or 8 is selected, high and low pressure side on the above figure (2.56)
are reversed. (i.e. High pressure side is on the right side.)
*2: When option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.
*3: Not available when option code GS is specified.
F0915.ai

IM 01C25B01-01E
<9. General Specifications> 9-32
Unit: mm (approx. inch)
● Vertical Impulse Piping Type
Process connector downside Electrical connection
(Installation code 7) for code 5, 9, A, and D.
256(10.10) 110(4.33)

6(0.24)
194(7.64)
12 39
97 143(5.63)
(0.47) (1.54) 2-inch pipe
(3.82)

(2.13)
(O.D. 60.5 mm)

54
Mounting bracket Vent/Drain plugs
Process connector upside
(2.05)

(L-type,optional)
52

Process connection (Installation code 6)


Integral indicator External indicator
Conduit connection
(optional)
102(4.02)

(optional)
234(9.21)

72(2.83)

(1.81)
148(5.83)*2
ø78(3.07)

46
(3.74)

(2.76)
ø70
95
(1.81)

234(9.21)
72(2.83)
46

102(4.02)
Conduit
connection High 27 Low
Process connection pressure pressure
Zero adjustment side*1 (1.06)

(2.05)
side*1

52
Ground
terminal Process connector
(optional) Open to atmosphere
ø10(0.39)
● Horizontal Impulse Piping Type (Installation code 9)
External indicator
Conduit connection 94(3.70) 72(2.83) Conduit connection 110(4.33)
Zero
(optional) 95(3.75) adjustment 12 39
Integral indicator
(optional) (0.47) (1.54)
54

ø78(3.07)
(2.13)
6

(2.76)
ø70
(0.24)
159(6.26)

143(5.63)
194(7.64)

Ground terminal
Electrical connection
for code 5, 9, A, and D.
Vent plug
Open to atmosphere
Drain plug ø5(0.20)
124(4.88)

46 Process connection
(1.81) 54
Process connector High (2.13) Low
125(4.92) pressure pressure
(optional)
side*1 side*1
2-inch pipe
(1.85)

(O.D. 60.5 mm)


47

Mounting bracket
(Flat-type,optional)
67*2
*1: When Installation code 2, 3, or 8 is selected, high and low pressure side on the above figure (2.64)
are reversed. (i.e. High pressure side is on the right side.)
*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.
F0916.ai

IM 01C25B01-01E
<9. General Specifications> 9-33
Unit: mm (approx. inch)
● Bottom Process Connection (Installation code -B)
54
(2.13) 95(3.74) 188(7.40)
6
73 Integral indicator
(0.24) Zero 110(4.33)
(2.87) (optional)
adjustment
12 39
Conduit connection
(0.47) (1.54)
Electrical connection

ø78(3.07)
for code 5, 9, A, and D.

(2.76)
ø70

109(4.29)
159(6.26)
Extenal indicator
Conduit connection
(optional)
Ground terminal

Vent plug
High Low

(2.36)
Mounting bracket*2 pressure pressure

60
(optional) side side

2-inch pipe Process connector


27
(O.D. 60.5 mm) (optional)
(1.06) Open to
Process connection atmosphere
65 129 ø10(0.39)
(2.56) (5.08)
F0917.ai

● Universal Flange (Installation code -U)

58 67 110(4.33)
Zero
External indicator (2.28) (2.64) adjustment
Conduit connection Conduit connection 12 39
95(3.74)
(optional) Integral indicator (0.47) (1.54)
54 (optional)
ø78(3.07)

(2.13)

(2.76)
6

ø70
145(5.71)

(0.24)

129(5.08)
175(6.89)

Ground terminal

Electrical connection
for code 5, 9, A, and D.
Drain plug Open to atmosphere
41 Shrouding bolt*2 65*1 (ø5)
Vent plug (1.61) High Low
pressure (2.56) pressure
115(4.53) side side
Process connection
Drain plug
Process connector
(optional)
*1: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value.
*2: A transmitter with SST housing is not applicable for mounting to horizontal 2-inch pipe. F0918.ai

IM 01C25B01-01E
<9. General Specifications> 9-34
Model EJ440
Unit: mm (approx. inch)
● Vertical Impulse Piping Type
Process connector downside Electrical connection
for code 5, 9, A, and D.
(Installation code 7)
120(4.72)

6(0.24)
242(9.53)
175(6.89) 110(4.33)
97 129(5.08) 12 39 2-inch pipe
(0.47) (1.54)

(2.13)
(3.82) (O.D. 60.5 mm)

54
Mounting bracket Vent/Drain plugs Process connector upside
(L-type,optional)
(2.05)

(Installation code 6)
52

Process connection
Integral indicator Extenal indicator
267(10.5) [C capsule]
265(10.4) [D capsule]

(optional) Conduit connection


119(4.69)

(optional)

88(3.46)*4
182(7.17)*2 [C capsule]
177(6.97)*2 [D capsule]

(2.48)
63
267(10.5) [C capsule]
265(10.4) [D capsule]
ø78(3.07)
(3.74)

(2.76)
ø70
95
88(3.46)*4

(2.48)
63

119(4.69)
Conduit High
connection pressure
Zero adjustment side*1
Process connection Process 27 Open to
Ground terminal connector atmospher
(1.06)

(2.05)
(optional) ø5(0.20)

52
● Horizontal Impulse Piping Type (Installation code 9)
Extenal indicator 111(4.37) 88(3.46)*4 Conduit connection 110(4.33)
Conduit connection Zero 12 39
95(3.74) Integral indicator adjustment
(optional) (0.47) (1.54)
(optional)
54
ø78(3.07)

(2.76)
(2.13)

ø70
6 Vent
145(5.71)

129(5.08)
(0.24) plug*3
175(6.89)

Vent plug*3 Ground


Drain plug*3 terminal
Electrical connection
for code 5, 9, A, and D. Open to
Process connection atmosphere ø5(0.20)
124(4.88)

63 27(1.06)
(2.48) Process connector High Low
159(6.26)*5 (optional) pressure pressure
side*1 side*1
Drain plug*3
(1.85)
47

Mounting bracket 2-inch pipe


(Flat-type,optional) (O.D. 60.5 mm)

70*2
(2.76)
*1: When Installation code 2, 3, or 8 is selected, high and low pressure side on the above figure
are reversed. (i.e. High pressure side is on the right side.)
*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.
*3: Not available when Option code GS is specified.
*4: 87 mm(3.43 inch) for capsule code D.
*5: 157 mm(6.18 inch) for capsule code D.
F0919.ai

IM 01C25B01-01E
<9. General Specifications> 9-35
Unit: mm (approx. inch)
● Universal Flange (Installation code -U)
External indicator 80 88*2 Zero 110(4.33)
Conduit connection adjustment
(3.15) (3.46) Conduit connection
(optional) 12 39
95(3.74) Integral indicator (0.47) (1.54)
54 (optional)
(2.13)

ø78(3.07)
6

(2.76)
ø70
(0.24)
145(5.71)

129(5.08)
175(6.89)
Ground terminal
Electrical connection
for code 5, 9, A, and D.
Drain plug
63 Process connection Open to atmosphere
Vent plug 27
(2.48) ø5(0.2)
Drain plug Process connector (1.06)
159(6.26)*3 (optional) 70*1
High Low
pressure (2.76) pressure
side side
*1: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value.
*2: 87(3.43) for D capsule.
*3: 157(6.18) for D capsule. F0920.ai

● Terminal Configuration ● Terminal Wiring


+ 1
Power supply and output terminals
SUPPLY – 2

CHECK + 3 External indicator (ammeter) terminals*1*2


– 2
or or
+ 3 Status contact output terminals*2
ALARM – 2 (when /AL is specified)
Ground terminal
*1: When using an external indicator or check meter, the internal
resistance must be 10 Ω or less. A check meter or indicator
cannot be connected when /AL option is specified.
Terminal 1 Terminal 3 *2: Not available for FOUNDATION Fieldbus and PROFIBUS PA
Terminal 2 communication types. F0921.ai

IM 01C25B01-01E
i

Revision Information
 Title : Differential Pressure and Pressure Transmitters
EJ110, EJ120, EJ130, EJ310, EJ430, and EJ440
 Manual No. : IM 01C25B01-01E

Edition Date Page Revised Item


1st Mar. 2004 — New publication
2nd Apr. 2004 — Revise words and phrases.
2-6 2.9.3 • Correct Ambient temperature –60 → –50
4-4 4.5 • Change the description of rotation angle.
8-3 8.4 • Add Allen wrench nominal 3mm to Table 8.4.1.
3rd Feb. 2005 — Re-number figure and table title.
i Add subsection 6.3.5.
ii Add note for Safety Transmitter.
1-1 1. • Add note for Fieldbus communication type.
1-3 1.1 • Add (f) Modification.
2-3 2.9 • Add NOTE for fieldbus communication type.
2-5 2.9.2 • Modify descriptions and instructions for CSA certification
2-7 2.9.3 • Correct number in Note 4. 10 MINUTES → 5 MINUTES
2-8 • Delete WARNING on non-incendive power supply.
• Correct number for Electrical data Ci. 6 nF → 10 nF
3-1 3. • Correct label of the switch in the figure. N → E, Y → D
• Add descriptions in Note 2.
4-3 4.4.1 • Add description about process connector in 3).
4-4 4.6 • Add section 4.6.
6-1 6.3.1, 6.3.2 • Add limitation/note when /AL is specified.
6-2 6.3.4 • Add limitation when /AL is specified.
6-2 6.3.5 • Add subsection 6.3.5.
7-3 7.2.1 • Add descriptions about zero adjustment.
9-1, 9-2 9.1 • Add notes for FOUNDATION fieldbus communication type.
• Add capsule code H.
9-4, 9-5 9.2 • Add output signal code -F and capsule code H.
9-6 9.3 • Add CSA approvals and note *2 and *3
9-8 9.4 • Add note *3.
9-10 9.4 • Add notes for /AL and FOUNDATION Fieldbus.
4th Sep. 2005 1-1 1. • Add model names to the manual coverage.
2-3 to 2-8 2. • Add applicable standard and certificate number for each
approval.
2-11 2.10 • Change australian reference standard.
2-11 2.11 • Add descriptions for PED.
2-12 2.11 • Add section 2.12.
4-1 4.1 • Add model name.
4-2 4.3 • Add table 4.1.
8-5 8.4.3 • Add table for torque.
Add notes for reassembling EJX130A and EJX440A.
8.4.4 • Add table for torque.
9-1 to 9-18 9. • Add specifications, codes, and dimensions for EJX130A,
EJX310A and EJX440A.
5th July 2006 2-8- 2.9.3 • Change applicable standards for ATEX type n.—
6th Nov. 2007 1-1 1. • Add model code table.
2-3 2.9 • Add note for EJX130A.
9-10 9.3 • Add note for EJX130A.
9-15 9.4 • Modify dimensions of EJX130A.
A-1 APPENDIX 1. Add "EJX130A ADDITIONAL INFORMATION."

IM 01C25B01-01E
ii
Edition Date Page Revised Item
7th Feb. 2008 — Change of the style code, add EJX120A.
General • Change the figure of amplifier housing.
1-1 1 • Add style code table.
2-1 2.1 • Update the Figure 2.2.
2-5 2.9.1 • Add code /V1U.
2-6 2.9.2 • Revise information for CSA Explosionproof type.
2-7 2.9.2 • Add code /V1U.
2-8 2.9.3 • Revise information for KEMA flameproof type. Add code /V1U.
2-9 2.9.3 • Revise Figure in (2) Electrical connection and (6) Nameplate.
2-10 2.9.4 • Revise information for IECEx flameproof type.
9-1 to 9-3 9.1 • Add information for EJX120A.
9-5 to 9-10 9.2 • Add new suffix codes for 316 SST blind plugs and brackets.
Add EJX120A.
9-11 9.3 • Remove /KF2 and /KU2. Add /KF21, /KU21, /SF2 and /V1U.
9-12 • Add /HC.
9-14 to 9-20 9.4 • Revise external dimensions.Add EJX120A.
— • Remove Appendix 1 'Additional Information for EJX130A.'
8th June 2008 2-6 2.9.2 • Correct certification number.
2-8 2.9.3 • Revise applicabble standards for ATEX Type n.
2-11 2.11 • Add EJX110A V capsule, wetted parts matterial code S and
EJX310A L capsule.
4-1 4.2 • Add information of Universal flange.
8-5 8.4.3 • Add wetted parts material code in the torque table.
9-1 to 9-27 9. • Add EJX110A V capsule, EJX110A/EJX430A wetted parts
material code H, M, T, A, D, and B, EJX310A L capsule and
option code /S1, and universal flange.
9-10 9.3 • Add statement of sealing certification for CSA approval.
9th Aug. 2009 2-1 2.1 • Replace a name plate.
2-11 2.10 • Revise standards.
2.11 • Revise information of PED.
9-4 to 9-9 9.2 • Modify descriptions of materials.
9-11 to 9-12 9.3 • Add /GS, /A1,and /DG6.
9-13 to 9-26 9.4 • Correct errors. Add note for /GS.
10th Apr. 2010 2-4 to 2-11 2.9 • Add limitation of ambient temperature for /HE.
8-1 8.3 • Add description for warm up time.
9-4 9.1 • Add O-ring material.
9-12 9.3 • Add /HE.
11th Mar. 2012 2-3 2.9 • Add note for blind plugs.
9-4 9.1 • Change description for a plate material.
9-5 to 9-10 9.2 • Add amplifier housing code 3.
12th June 2012 — • Add EJA-E series. Add measurement span code F for
EJX110A.
1-1 1. • Add Note. Add model name of EJA-E series.
2.3 to 2.12 2.9 • Delete /V1U.
2-7 to 2-10 2.9.3 • Delete /KS2, /KF21, and /KU21. Add /KS21, /KF22, and /KU22.
8-5 • Add note for measurement span code F.
9.1 to end • Add information for EJA-E series. Add output signal code –J
and measurement span code F.
13th June 2013 — Add note for PROFIBUS PA communication type.
2-3 Add note for multiple approval type.
2-6, 2-7 2.9.2 • Correct CSA applicable standards.
2-8 to 2-11 2.9.3 • Replace ATEX type n by ATEX Intrinsically safe Ex ic.
• Add note for CE marking notified body number.
2-13 2.11 • Add EJA110E with /HG.
9-3 9.1 • Add MWP for EJA110E with /HG.
9-6 to 9-17 9.2 • Add PROFIBUS PA communication type.
• Add process connection code 2, 3 and 6.
9-19 to 9-20 9.3 • Replace ATEX type n by ATEX Intrinsically safe Ex ic.
• Add /V1U1. Add /HG.
9-22 to 9-35 9.4 • Add process connection codes 2, 3 and 6. Correct drawing of
EJ430 universal flange type. Add note for shrouding bolt.

IM 01C25B01-01E
iii
Edition Date Page Revised Item
14th June 2014 1-2 1. • Add note for symbols.
2-6 2.9.2 • Revise category for CSA Nonincendive.
2-13 2.12 • Update safety requirement standard.
6-1 to 6-4 6. • Revise drawings and symbols for terminal.
6-1 6.3.1 • Add note for power supply.
6-2, 7-2 Add note for BRAIN communication.
7-5 to 7-10 7.6 • Add local parameter setting function.
9-18 9.2 • Revise wetted parts material for capsule.
9-22 to 9-35 9.4 • Revise a part of dimension for horizontal piping use.
9-35 • Change terminal drawing.

IM 01C25B01-01E

You might also like