A00 LOCATION PLAN TITLE PAGE Revision P3-Merged
A00 LOCATION PLAN TITLE PAGE Revision P3-Merged
A00 LOCATION PLAN TITLE PAGE Revision P3-Merged
Use figured dimensions and do not scale off drawings. All dimensions and
levels to be checked and verified on site prior to commencement of Works.
Any form of reproduction of this drawing in full or part without the written
permission of collins pennington architects 2024 constitutes an infringement
of copyright.
MOUA
DOWNER
E
UR N E AV
T ST
BLACK
MOUNTAIN
NATURE LYNEHAM
NO RT HB O
RESERVE SPORTSGROUND
ANTILL S T
1 : 10 000 @ A1
DICKSON
LOCATION PLAN
P3 FOR COORDINATION 28/08/24
P2 FOR COORDINATION 20/08/24
P1 FOR COORDINATION 14/08/24
rev: issue: date:
client:
YOWANI COUNTRY CLUB
project:
drawing title:
scale:
date: 28/08/24
project no: 22203
A00 P3
NOT FOR CONSTRUCTION
Use figured dimensions and do not scale off drawings. All dimensions and
levels to be checked and verified on site prior to commencement of Works.
Any form of reproduction of this drawing in full or part without the written
permission of collins pennington architects 2024 constitutes an infringement
of copyright.
143.05 m
LYNEHAM
BLOC K 14 LYNEHAM
SEC TION 64 BLOCK 7
SEC TION 67
LANDSC APED
15000
15000
EARTH BERM
A A
29250
GRID 1 (PARALLEL TO BOUNDARY)
B TERRACE 1
7130
4 5 6 7 8
GRID A (PERPENDICULAR TO BOUNDARY)
C
B
1
A/
N
T IO
RS 5
TE 352
EC
TERRACE 2
4
32231
IN
163
ID
97
GR
15°
C
NO METALLIC FENCE/GATE WITHIN 5m OF
SUBSTATION. REFER LANDSCAPE DOCUMENTATION
15° 9 15°
D
10 TERRACE 3
600
0
NEW
SUBSTATION
NEW 2 STO REY BUILDING
11 600
0
8
12 600
0
24.1 m
282° 2
9' 58" E
13
NEW 1 6100 2 6100 3 6000 4 6000 5 6000 6 6000
VEHICULAR
GRID SETOUT POINT. ENTRY
P4 FOR COORDINATION 28/08/24
7
9750
9 10 600
0 rev: issue: date:
2° 46' 07"
20350
REFER CIVIL
10.6 m
11 600
0
12 600
0
NEW SHARED ZONE 13 E LANDSC APED
EARTH BERM
PICK UP / DROP OFF
Nominated Architects:
7.68 43"
R 19
client:
YOWANI COUNTRY CLUB
NEW SIGNAGE
project:
VISITOR BICYCLE
9 m ' 57"
° 34
PARKING
BLOCK 14 SECTION 64 LYNEHAM &
BLOCK 07 SECTION 67 LYNEHAM
drawing title:
SITE PLAN
R18500
A01 P4
A B C D E F
A30 A30 A30 A31 A31 A31
NOT FOR CONSTRUCTION
WALLS EXTEND Use figured dimensions and do not scale off drawings. All dimensions and
SUBSOIL AREA BEYOND PAGE: levels to be checked and verified on site prior to commencement of Works.
Any form of reproduction of this drawing in full or part without the written
REFER SITE PLAN permission of collins pennington architects 2024 constitutes an infringement
of copyright.
LEGEND
BAL4 BALUSTRADE TYPE 4
6100 6100
CC CONCRETE COLUMN
CH-G CHUTE (GARBAGE)
1 2 3 CH-R CHUTE (RECYCLING)
CONC2 CONCRETE TYPE 2
CPT1 CARPET TYPE 1
CPT2 CARPET TYPE 2
1b
2b 1b CPT3 CARPET TYPE 3
DB DISTRIBUTION BOARD
A A DP1 DOWNPIPE TYPE 1
1b
DP3 DOWNPIPE TYPE 3
@TPD/FIRE: ADDITIONAL REQUIREMENTS HERE?
EM ENTRY MAT
FHR FIRE HOSE REEL
D D
CART WASH
G36 CART STORE 1 G35 FIP FIRE INDICATOR PANEL
B DOWN AREA
8 CARTS
FT1 FLOOR TILE TYPE 1
GCT GLYCOL TANK
FFL 572.500 1d
GRD GRATED DRAIN
1d VN1 VINYL TYPE 1
CONC2 VN3 VINYL TYPE 3
1a
WORKSHOP / 1d
STORE 4a
FHR
1d
4a JG.01 W2 4a 4a 4a
G23
D DP3 D
G33 G32
1d 2f 2f 1b
4 5 6 1
A20
7 8
1d 10a
D 1g
G34
CC CC
1 2
W1
G20 A44 A44
CPT3 PRO SHOP 1g
4a
CPT1 @TPD: DISCUSS CURVED 1a 1a 1c 1a 1c
JG.03 W2 W2
OVER
FFL 572.600 BLOCK METHODOLOGY -- G04
D
4a*
G05 B
W2 IDEALLY A PRODUCT RATHER G23
C W2
G21 10a
G17 THAN FACETED ?
AMBULANT D G
G15 A32
1d
W2
1a 10a
1a
GOLF OFFICE 10a FEMALE 11e G06
10a 10a
OFFICE CPT1 10a LOCKERS CEO
FT1 10a
GATE CPT3 10a 10a CPT1
? 1g
MECH MECH 10e FEMALE 3
1a W2
1d RISER A44
10a D
FFL 572.600 10a AMENITIES 10a G07
G21 FT1 D ? 10a
MECH MECH DP1 D G22
MECH G31 1d D
4a* G14
W2 1e
D 1a P2
G16 1g
G30
MECH CLUB FITTING ACCESSIBLE
11c 2c 11c 11c 11c 2c 11e 2c 04
MECH 10a 1f 1d
D W2
4d* CPT3
WC FT1 @TPD: GRATED G02
12b 11a
G08
H
A32
MECH 10a
1d DRAINS TO EXT. AIRLOCK LOBBY JG.04 RECEPTION
W4 EM W4
OPEN PLANT HWS PAVEMENT? FFL 572.600 G03 CPT1
2e 7 G02
GRD
AMBULANT
HWS G01 VN1
MECH
W2 1e 1a 11a FFL 572.600 1g QUANTITY/SIZE/LOCATION TYP
G15
WALL EXTENDS 2 MSB D CPT3
15°
HWS 10d G16 W2
BEYOND PAGE: A21 D 1a
G09
G27
REFER SITE PLAN FIP
4c*
MECH 10b 1d CPT2 11a
1g C
129 CAVITY
D
MSB ROOM
I
G37 CONC2
@FIRE & ELEC: PLY LINING?
2c
11e CPT1
10a
W2
DP1
15° 9 I
A32 1b 15° A32 2
MECH DP1 FIRE? 10d G10 A20
GATE GCC DP1
INV. INV. INV. 10a
D D
G38
MALE
P2
D
G03
D
G08
NOTE: GATE TO BE MIN. 200
1e
CH-G CH-R 10d AMENITIES 02
VN1 VN1 4
10a STAIR 1 11a 11a D
ABOVE FFL TO ALLOW FOR FFL 572.600 D D
P2
2c G13 1d A44 DP1 1a 1d 1a 1a
FT1 G06 G07 03
CABLES TO GCC D KITCHENETTE @FIRE: PROPOSE
10a G05 W2 W2 W2
WASTE 1a LOCATIONS FOR
D
COLLECTION
2f
D
10a 10a 11e JG.05 10a 10a JG.06
1d G11 1g G12 1g G13 1a
10 EXTINGUISHERS (OR FHR'S) 4f
G39 ? G28 D
CPT2 F. M. JG.08
BAL4
BAL4
CONC2 DB D
1 FFL 572.510 10a ACCESSIBLE 10a 10a
G09
G24
600
0 4g
A51 @CIVIL: CONFIRM WASTE DIMS SUFFICIENT 10a
1a
WC AMB AMB 4g FHR
10a FT1 FT1 10a
CLNR 1
10d
D
@TPD:FT1PLY STORE CLNR 2 CPT1 P2 D
D D
JG.05
2f G29 05 G12
10a VN3 10a D
10d BLOCKING/LININGS TO 11e FT1
G10
G25 G26
HYD ALL WET AREAS? BOARD 2f
D D
STAIR 2 G19 RISER G11 FFL 572.600
1c
10a
?
W3 11e 11e 10a
CPT1 11 600
RFRG.
G01 2d 10a 0
10a LIFT 1 10a ? JG.07 P6 FOR COORDINATION 28/08/24
2a
2f
8 P5 FOR COORDINATION 20/08/24
(UNDER STAIR) ? 10a
10a COMMS
2a P4 FOR COORDINATION 14/08/24
10a 10a COMMUNITY VN3
LIFT 2 KEG BRIDAL SUITE P3 FOR COORDINATION 12/08/24
1a
BY OTHERS MALE 12a 12a 10a ENG. 10a 10a
10a CPT2 VN1
VN1 P2 FOR COORDINATION 02/08/24
LOCKERS 4g
12 SUBSOIL AREA P1 FOR COORDINATION 18/07/24
D FT1
GRD
W2 P1 600
G40B 0 rev: issue: date:
G22 DELIVERY 01 D D
D WC
D FFL 572.590 CPT2 G04 G18 2f
G40A CONC2 GCT GLASS INFILL FROM COLUMN TO MULLION G20 FT1
CLUB STORE
1b ACP CONC2
E D
G17
67 PLACES 2a
2a
W3 1a
2b 2b
G14
FFL 572.490
@WINDOW SUPPLIER: CORNER GLAZE?
6 5
1a 13
SUBSOIL AREA A44 A44 @FACADE: CONFIRM
1 2 3 4 5 6 MANUFACTURER JUNCTION 1b
DETAIL COMPLIES OTHERWISE 4g
6100 6100 6000 6000 6000 6000
WILL NEED TO BE TESTED ON SITE
Level 1 Style Arcade Manuka, Shop 13
2a
1 CART STORE 2 14-16 Franklin St Griffith 2603 t: 02 6295 1433
A21 Nominated Architects:
7 32 CARTS Andrew Collins ACT #2443 NSW #7448
1b
1b FFL 572.490
D David Pennington ACT #2490
client:
YOWANI COUNTRY CLUB
9
project:
10 YOWANI COUNTRY CLUBHOUSE
600
0 2a
G
A32
BLOCK 14 SECTION 64 LYNEHAM &
2a
BLOCK 07 SECTION 67 LYNEHAM
scale: 1 : 100 @ A1
date: 28/08/24
A
A30
B
A30
C
A30
D
A31
E
A31
F
A31
H
A32
12 project no: 22203
600
0
13 E drawing no: issue no:
A10 P6
A B C D E F
A30 A30 A30 A31 A31 A31
NOT FOR CONSTRUCTION
Use figured dimensions and do not scale off drawings. All dimensions and
levels to be checked and verified on site prior to commencement of Works.
Any form of reproduction of this drawing in full or part without the written
permission of collins pennington architects 2024 constitutes an infringement
of copyright.
LEGEND
BAL1 BALUSTRADE TYPE 1
6100 6100
BAL3 BALUSTRADE TYPE 3
BAL4 BALUSTRADE TYPE 4
1 2 3 CH-G CHUTE (GARBAGE)
CH-R CHUTE (RECYCLING)
COMMS
CPT4 CARPET TYPE 4
CPT5 CARPET TYPE 5
DP1 DOWNPIPE TYPE 1
A A DP3 DOWNPIPE TYPE 3
FHR FIRE HOSE REEL
FT1 FLOOR TILE TYPE 1
SH
4h
E
ST
HOB
CT
UR
B SC STEEL COLUMN
EO
VE
3a
SC
TERRACE 1 SPS1 STEEL PLATE SUNSHADE TYPE 1
FFL 576.200 SPS2 STEEL PLATE SUNSHADE TYPE 2
VN1 VINYL TYPE 1
SC VN2 VINYL TYPE 2
D VN3 VINYL TYPE 3
U01
D
3b U02 DP3
W3 SC
U09
4b
SC
UNDER 6000 6000 6000 6000 6000
SC
VN1
SPS1 4 5 6 1
A20
7 8
4b
S PS 2
UNDER
1
SPS1 A53
W3 4h
4b
SC U08 W3 HOB
UNDER
SPORTS U07
BAL1
LOUNGE
4e
B
FFL 576.205 SC SC SC SC G
C CPT4
1
A32
A53
SC JU.02
3d
SC W1
DP1 MEMBERS U06
CPT5
DP1 DINING TERRACE 2 4h
SPS1 FFL 576.205 HOB UPPER FLOOR PLAN NOTE:
CPT5 FFL 576.180
H ALL TILE FINISHES EAST OF GRID 4 ON UPPER LEVEL TO
A32
SC INCLUDE ACOUSTIC UNDERLAY: 5mm REGUPOL 5512.
W1 VN1
U10
IN DRY AREAS, UNDERLAY DIRECTLY BENEATH TILE.
ACP
JU.04 FT4 IN WET AREAS, UNDERLAY BENEATH SCREED.
4b* 11a WATERPROOF PER FLOORING MANUFACTURER'S
D W1
2 UNDER D VN1 FFL 576.200 U03 U05 15° RECOMMENDATION.
SC
A21 U15 SC
JU.03 11d 11c 4a*
BAR SC SC
W1
U11
P1
06 ?
FT1
REFER TO AC&R DRAWINGS
BAL3 CPT5 SC
D
U05 SC SC
4a C
SC 10c
I 4b*
VN2 11a JU.08
10a D
U04 11c
11c
DP1 3e 15° 9 I
A32 3a DP1
CAFE 1
3a DP1 3a 15° A32 2
SC SC 10a 11a 10a
A50 VOID 11d SC SC 3a
A20
ICE
SC
D COOL 2 SC
11c
SC
POSTMIX
BY OTHERS ? 10a SC
CH-G CH-R 10a RISER BAL4
SC STAIR 1 SC
10a 10a 10a 10a DP1 SP
COMMS 11c SC S1
SC
BAL4
10a 3a
SC
11c 10a D
11c 11c
10a 11c
MALE 10c
U16 10
STORE 2 11c FT4 10a
AMBULANT
10a U14 SC
SC 11c
LOBBY 10a D
VOID
VOID
12a
3a
BAL4
11c
M. F. ACC. WC 8 U04 P5 FOR COORDINATION 20/08/24
11a BAR ?
11a
12c BY OTHERS BY OTHERS FT2 AMB. AMB. FT1 P4 FOR COORDINATION 14/08/24
11c REFER TO AC&R
2b BAL4 11c 11c
LIFT 2 2b FT1 FT1 P3 FOR COORDINATION 12/08/24
FEMALE DRAWINGS
SC
STORE 3 11c 12a 12a D
U07
D
U08
D
U09
D
U10 P2 FOR COORDINATION 02/08/24
11c 11c 11c VOID KITCHEN SWB SC SC
12c 11c
VN3
SC
MSSB ELEC
SC 10a 11c 11c
10a 12 P1 FOR COORDINATION 18/07/24
FHR BAL3 600
2b 10a 0 rev: issue: date:
10a
B.O.H. 10b 10a D
U11
SP
S1
VN2 10a D
D D U06 10a
U22 FFL 576.200 D D
U13
U21 U20
VN1 CLNR 4
SC
E SC SC SC SC SC SC
SC
SC
W1 10a ?
3a U01 SPH 3a 3a
DP1
13
3a
SC
D
U12
1 2 3 4 5 6 SC
SC
FUNCTION
3a
6100 6100 6000 6000 6000 6000 SC DP1 FFL 576.200 10a SC
Level 1 Style Arcade Manuka, Shop 13
W1
1 U02
3a SC A/V 14-16 Franklin St Griffith 2603 t: 02 6295 1433
A21 Nominated Architects:
7 Andrew Collins ACT #2443 NSW #7448
SC D
U19
D David Pennington ACT #2490
3a
3c
client:
10a
YOWANI COUNTRY CLUB
9
SC
project:
10 3a
YOWANI COUNTRY CLUBHOUSE
600
0
G
3a
A32
BLOCK 14 SECTION 64 LYNEHAM &
SC BLOCK 07 SECTION 67 LYNEHAM
SC
4b SC drawing title:
11 W1
FLOOR PLAN - UPPER LEVEL
600 U03
0
4a
SC
3a
scale: 1 : 100 @ A1
date: 28/08/24
A
A30
B
A30
C
A30
D
A31
E
A31
F
A31
H
A32
12 project no: 22203
600
0
13 E drawing no: issue no:
A11 P6
A B C D E F
A30 A30 A30 A31 A31 A31
NOT FOR CONSTRUCTION
Use figured dimensions and do not scale off drawings. All dimensions and
levels to be checked and verified on site prior to commencement of Works.
Any form of reproduction of this drawing in full or part without the written
permission of collins pennington architects 2024 constitutes an infringement
of copyright.
LEGEND
BG1 BOX GUTTER TYPE 1
2
DP1 DOWNPIPE TYPE 1
A54
DP3 DOWNPIPE TYPE 3
1 2 3 EG1 EAVES GUTTER TYPE 1
FL1 FLASHING TYPE 1
RS1 ROOF SHEET TYPE 1
SPH STEEL PLATE HOOD
SPS1 STEEL PLATE SUNSHADE TYPE 1
SPS2 STEEL PLATE SUNSHADE TYPE 2
A A
FL1
B TERRACE UNDER
EG1
PERGOLA
RS1
L
FAL
2°
FL1
DP3
FL1
FL1
FL1
4 5 6 1
A20
7 8
ROOF 1
RS1 SPS2
5° FALL
FL1
RS1
DP1 EG1
FL1
FL1
ROOF 1
RS1
H
5° FALL
5° FALL
A32
RS1
EG1
FL1
2 ROOF
RS1
3
A21
2° FALL
C
SPREADER?
I
2° FALL 2° FALL
EG1 EG1
DP1 DP1 9 I
RS1
ROOF 3
RS1
FL1
FL1
SPS1
10
5° FALL
5° FALL
5° FALL
TERRACE UNDER
RS1
L
FAL
E FL1 FL1 FL1
5°
SPH FL1
DP1
FL1
13
ROOF 4 FL1 ROOF 2
1 2 3 4 5 6 RS1
2°
RS1
FL1 FA LL
DP1
Level 1 Style Arcade Manuka, Shop 13
EG1
1 14-16 Franklin St Griffith 2603 t: 02 6295 1433
A21 Nominated Architects:
7 Andrew Collins ACT #2443 NSW #7448
D David Pennington ACT #2490
client:
YOWANI COUNTRY CLUB
9
FL1
FL1 project:
10 YOWANI COUNTRY CLUBHOUSE
G
A32
BLOCK 14 SECTION 64 LYNEHAM &
BLOCK 07 SECTION 67 LYNEHAM
drawing title:
11 ROOF PLAN
scale: 1 : 100 @ A1
date: 28/08/24
A
A30
B
A30
C
A30
D
A31
E
A31
F
A31
H
A32
12 project no: 22203
A12 P5
A B C D E F
A30 A30 A30 A31 A31 A31
NOT FOR CONSTRUCTION
Use figured dimensions and do not scale off drawings. All dimensions and
levels to be checked and verified on site prior to commencement of Works.
Any form of reproduction of this drawing in full or part without the written
permission of collins pennington architects 2024 constitutes an infringement
of copyright.
LEGEND
CC CONCRETE COLUMN
6100 6100
CONC1 CONCRETE TYPE 1
CONC2 CONCRETE TYPE 2
1 2 3 DP3 DOWNPIPE TYPE 3
P PENETRATION
REBATE/FOOTING 572.290 m REBATE/FOOTING 572.290 m P-FW PENETRATION - FLOOR WASTE
SC STEEL COLUMN
A A
NOTE:
200 200
FALL FALL
ALL EXTERNAL BALCONIES MAX FALL 1:80
1 41:
1 :14
1 15:
65:
FALL FALL
P
@CERTIFIER: ACCESSIBLE / NCC THRESHOLD 250
RAMP REQS TBC (SAME AS EXTERNAL
THRESHOLD DETAIL). UPTURN?
50
250
DP3
50
50
4 5 6 1
A20
7 8
300
CC CC
REBATE/FOOTING 572.290 m
B
CONC1
C
50
P
30
P G
0
A32
SSL 572.590 m
300 P P-FW P 50 300
CONC1
CONC1
SSL 572.590 m P-FW CONC1
P SSL 572.540 m
P SSL 572.590 m CC
50
20
20
REBATE/FOOTING 572.290 m
3 00
20 50
300 50 300
P-FW
50
50
300
REBATE/FOOTING 572.290 m
P-FW
SSL 572.570 m 50 300 @TPD & CERTIFIER & CIVIL/HYD &
30
LANDSCAPE: H
A32
P P 20
EXTERNAL THRESHOLD DETAIL TBC: 300
50mm MIN UPTURN vs ACCESSIBILITY CONC1 CONC1
SSL 572.570 m
P REQS vs BLOCK/BRICK WALL SSL 572.590 m
300
60
2 P 15°
REFER SITE PLAN A21
50
FOR EXTENTS
300
P 300 C
FRAME WATERPROOFING HOB FOR
I
220
30 MEMBRANE UPTURN TO ALL WET
AREA SLAB EDGES WITH < 50mm CC
15° 9 I
A32 15° A32 2
EDGE (TYP.) A20
P
D
220 CONC1 REBATE/FOOTING 572.290 m
SC P 300 300
SSL 572.540 m
200
CONC2 50
SSL 572.510 m P P-FW P
50
P 300 10
P P P P
50
600
0
50 50 CONC1 50
P
30 SSL 572.540 m 50
SC P-FW P-FW P-FW P-FW
REBATE/FOOTING 572.290 m 50
CC
P
50
P-FW P P
50
P
CONC1
1200
70
300 150
SSL 572.590 m 11 600
PENETRATION 0
SC
LOCATIONS TBC LIFT 1 P
100 (TYP.) PIT 571.390 m 8 P5 FOR COORDINATION 28/08/24
1200
PIT 571.390 m
P4 FOR COORDINATION 20/08/24
CC
LIFT 2 CONC1 P3 FOR COORDINATION 14/08/24
CONC2
1200
50
PENETRATIONS
CONC2 P WITH AC&R SUBJECT TO PAVEMENT 600
SSL 572.490 m 0 rev: issue: date:
HEIGHT/FALLS/DRAINAGE/ 50 SSL 572.540 m
SSL 572.590 m
150 ETC CC CC CC P-FW 50
300
50
50
E P
13
1 2 3 4 5 6 REBATE/FOOTING 572.290 m
client:
YOWANI COUNTRY CLUB
9
project:
10 YOWANI COUNTRY CLUBHOUSE
600
0
G
A32
BLOCK 14 SECTION 64 LYNEHAM &
BLOCK 07 SECTION 67 LYNEHAM
drawing title:
11 SLAB PLAN - GROUND
600
0
scale:
date: 28/08/24
A
A30
B
A30
C
A30
D
A31
E
A31
F
A31
H
A32
12 project no: 22203
600
0
13 E drawing no: issue no:
A14 P5
RL 573.996
A LANDING B C D E F
A30 A30 A30 A31 A31 A31
NOT FOR CONSTRUCTION
Use figured dimensions and do not scale off drawings. All dimensions and
levels to be checked and verified on site prior to commencement of Works.
Any form of reproduction of this drawing in full or part without the written
LEGEND
CONC1 CONCRETE TYPE 1
6100 6100
CONC2 CONCRETE TYPE 2
RL 575.542
LANDING
P PENETRATION
1 2 3 P-BC PENETRATION - BEER CABLE
CONCRETE STAIR
P-FW PENETRATION - FLOOR WASTE
P-PM PENETRATION - POST-MIX MACHINE
RL 576.160 SC STEEL COLUMN
HOB 576.140 TOP TREAD
A A
20
50
50
NOTE:
1 :59
1 :59
1 :56
1 :67
1 :5
HOB 576.140
1 :53
SC
1 7:
1 00
50
1 :52
1
6:7
1 :67
950
SC
1 00
150° 4 5 6 1
A20
7 8
CONC1
SSL 576.190 m
HOB 576.140
SC
50
SC
SC SC SC G
C
1 7:3
A32
COLUMN BASE PLATES CAST INTO SLAB.
REFER STRUCTURAL DETAIL (TYP.) 1 :97
SC P-FW 1:63
50
1 9:4
CONC2
SC
CONC1 100
9500
CONC1 SSL 576.190 m HOB 576.140
1 9:4
50
SSL 576.190 m
SC H
1 :25
A32
P-FW 1:62
COORDINATE PENETRATIONS SC
50
15°
1 3:6
2
A21 SC WITH AC&R
CONC1 SC SC SC
BAR SC C
50
SSL 576.140 m
50
50
SC
I 50 50 SC
50 HOB 576.140
15° 9 I HOB 576.140
A32 15° A32 2
P SC COOL 2 SC
A20
CONC1
D
50
SC
100 100
SC
50
SC SC
50
SSL 576.040 m HOB 576.140 50
100 STAIR VOID HOB 576.140
1 6:2
150° P-FW
1 :76
1 :86
P-PM SC SC
SC SC KITCHEN
1 0:7
GARBAGE CHUTE SC
50
PENETRATIONS TO COORDINATE PENETRATIONS
P-FW 1
06:
PENETRATION SC SC
MANUFACTURER'S SPEC.
10
1 :6
WITH AC&R
LOCATIONS TBC P-FW 20
50 50
1 00
1 6:4
CONC1 (TYP.) CONC1 600CONC2 50
CONC1 SSL 576.140 m 0 178 APPROX. RISER TYP.
SSL 576.190 m P
1 :05
P P P P
4:8
1
SSL 576.190 m
50
CONCRETE STAIR
RL 576.190 RL 574.409 RL 572.628
50
100
SC P P P
11
9800
50 P P P P P-FW 60
SC P P SC 600
P 50 1 :36
0
LIFT 1 FREEZER COOL 1 HOB 576.140
4:2
1
P
CONC1
P P P P CONC1 CONC1 100
CONC1
P P SSL 576.140 m 8 P-BC
P5 FOR COORDINATION 28/08/24
STAIR VOID SSL 575.980 m SSL 576.040 m P4 FOR COORDINATION 20/08/24
SSL 576.140 m
210
1 00
50
50
SC
P-FW P2 FOR COORDINATION 02/08/24
50
SC SC
150
12
50
50
SC
P1 FOR COORDINATION 18/07/24
SC 600
0 rev: issue: date:
50
CONC1
50
SC SC P
SC SC SC SC SC P
E
50
SC
SC
CONC1
RISERS YET TO BE CONFIRMED AND
COORDINATED: 150°
SSL 576.190 m 13
SC
- @ELEC
SC
1 2 3 - @HYD 4 5 6
- @MECH SC
6100 6100 6000 6000 6000 6000 SC
POTENTIAL LOCATIONS INDICATED SC Level 1 Style Arcade Manuka, Shop 13
WITH MAGENTA HATCH SC 14-16 Franklin St Griffith 2603 t: 02 6295 1433
1
A21 SC Nominated Architects:
7 Andrew Collins ACT #2443 NSW #7448
D David Pennington ACT #2490
client:
YOWANI COUNTRY CLUB
9 SC
project:
10 YOWANI COUNTRY CLUBHOUSE
600
0
G
A32
50
BLOCK 14 SECTION 64 LYNEHAM &
113
SC BLOCK 07 SECTION 67 LYNEHAM
SC
SC
50 drawing title:
11 FALL SLAB PLAN - UPPER LEVEL
600
0 SSL 576.090 m
SC
scale:
date: 28/08/24
A
A30
B
A30
C
A30
D
A31
E
A31
F
A31
H
A32
12 project no: 22203
600
0
13 E drawing no: issue no:
A15 P5
A B C D E F
A30 A30 A30 A31 A31 A31
NOT FOR CONSTRUCTION
Use figured dimensions and do not scale off drawings. All dimensions and
levels to be checked and verified on site prior to commencement of Works.
Any form of reproduction of this drawing in full or part without the written
permission of collins pennington architects 2024 constitutes an infringement
of copyright.
LEGEND
AP ACCESS PANEL
BH BULKHEAD
C-G1 CEILING - GRID TYPE 1
1 2 3 C-PB1 CEILING - PLASTERBOARD TYPE 1
(MOISTURE-RESISTANT PB IN WET AREAS)
C-PB2 CEILING - PLASTERBOARD TYPE 2
C-PBP CEILING - PERFORATED PLASTERBOARD
C-TB1 CEILING - TIMBER BATTENS TYPE 1
CONC2 CONCRETE TYPE 2
A A DL DOWNLIGHT (REFER ELEC.)
DP1 DOWNPIPE TYPE 1
IN-S1 SLAB INSULATION TYPE 1
ME REFER MECHANICAL ENG. DWGS
C-FC
CART STORE 1 2400
PL PENDANT LIGHT (REFER ELEC.)
CONC2 RP RECESSED PELMET
B
WF1 WINDOW FURNISHING - BLOCKOUT BLINDS
WF2 WINDOW FURNISHING - SHEAR BLINDS
WL WALL LIGHT (REFER ELEC.)
WORKSHOP /
STORE
IN-S1
STAFF
C-G1
C-FC 2700 C-FC
3000 RP 2400
IN-S1 4 5 6 7 8
ABOVE
C-G1
WF1 C-FC
IN-S1 ABOVE
2700
WF2 PRO SHOP 2400 FC2 C-TB? 1
WF1 2700 3000 A53
WF1 - WINDOW FURNISHING 1
WF2 BLOCKOUT BLINDS
RP B
WF2 - WINDOW FURNISHING 2
IN-S1 ABOVE
C C-FC AP
C-PB1 - 1850
CEILING GRID SETOUT POINT 1
SHEAR BLINDS
2400
FEMALE FC1 A53
C-PB1 2400
GOLF OFFICE LOCKERS 2700
WF3 - WINDOW FURNISHING 3
WF2 BLOCKOUT CURTAIN
WF1 OFFICE CEILING GRID SETOUT POINT C-G1 AP CEO RP
2700 CEILING GRID
SETOUT POINT
C-G1 FULL HEIGHT INSULATED
BH WF1
AP 2700 INTERNAL WALL TO U/S OF SLAB
WF2
FC1 OVER (GROUND LEVEL), OR
BH 2400
FEMALE C-PB1 150mm ABOVE FCL (UPPER
2700 LEVEL).
AMENITIES
SETOUT
SAME
ACC. NO SOFFIT
ALL EXTERNAL WALLS ARE FULL
CONC2 HEIGHT U.N.O.. REFER WALL
CLUB FITTING WC TYPES AND FLOOR PLANS.
NO CEILING C-FC REFER ACOUSTIC REPORT.
FC2 2400
C-PB1
2700 2700 C-TB? AIRLOCK LOBBY C-TB1 RECEPTION
3000 3000
IN-S1
G
ABOVE
B AR
OPEN OFFICE
C-G1 C-FC H
2700 WF1 A32
C-TB1 2400
FC1 SETOUT POINT WF2
3000
MSB ROOM C-G1 C
2700
IN-S1
I
MALE AP VOID FOR DOWNPIPE 9 I
A32 AMENITIES DP1
TRANSFER FROM ABOVE
C-FC
A32
IN-S1
C-PB1 STAIR 2400
D 2700 VOID
C-G1
SAME
SETOUT
ABOVE C-FC
2400 FC1 REVISIONS
C-FC FC1
2700 3000 NO SOFFIT
VOID VOID C-PB1 2400 3000 9 - INDICATED IN-S1
STAIR 1 RP CONC2
2700 IN-S1 ABOVE
SETOUT
SETOUT
SETOUT
SAME
SAME
SAME
AP
WASTE F. M. WF2
COLLECTION
C-PB1
3000
C-FC - 2400 WF1 10
AMB AMB C-FC
IN-S1 ACCESSIBLE STORE CLNR 2 2400
C-G1 C-G1 RP
WC 2400 2400 C-G1
SAME
SETOUT
2700 C-G1 CONC2
C-G1
C-G1 2700
2400
2700 BOARD
SETOUT
SETOUT
SAME
SAME
STAIR 2 C-G1
2700 11
RISER
C-PB1 LIFT 1
2700 CONC2
SKIMCOAT
8 P5 FOR COORDINATION 28/08/24
BH COMMS
UNDERSIDE OF
COMMUNITY P4 FOR COORDINATION 20/08/24
STAIR
C-FC LIFT 2 KEG MALE BRIDAL SUITE C-G1 P3 FOR COORDINATION 14/08/24
ENG.
C-PB1 - 1850
3000 2400
LOCKERS C-G1 P2 FOR COORDINATION 12/08/24
N
C-PB1 C-PB1
3000
12
T IO
C-PB1 BH 3000 3000 P1 FOR COORDINATION 02/08/24
NC
TO BAR
FU
ABOVE C-PB1 - 3000 2700 rev: issue: date:
WC
TO
CLUB STORE
300
E FCL 3100
FCL 3300
FC1
13
3000
1 2 3 4 5 6
client:
YOWANI COUNTRY CLUB
9
project:
10 YOWANI COUNTRY CLUBHOUSE
G IN-S1
A32 ABOVE BLOCK 14 SECTION 64 LYNEHAM &
BLOCK 07 SECTION 67 LYNEHAM
drawing title:
11 REFLECTED CEILING PLAN -
GROUND
scale:
IN-S1
date: 28/08/24
A
A30
B
A30
C
A30
D
A31
E
A31
F
A31
H
A32
12 ABOVE
project no: 22203
A16 P5
A B C D E F
A30 A30 A30 A31 A31 A31
NOT FOR CONSTRUCTION
Use figured dimensions and do not scale off drawings. All dimensions and
levels to be checked and verified on site prior to commencement of Works.
Any form of reproduction of this drawing in full or part without the written
permission of collins pennington architects 2024 constitutes an infringement
of copyright.
LEGEND
AP ACCESS PANEL
BH BULKHEAD
C-G1 CEILING - GRID TYPE 1
1 2 3 C-PB1 CEILING - PLASTERBOARD TYPE 1
(MOISTURE-RESISTANT PB IN WET AREAS)
C-PB2 CEILING - PLASTERBOARD TYPE 2
C-PBP CEILING - PERFORATED PLASTERBOARD
C-TB1 CEILING - TIMBER BATTENS TYPE 1
CJ CONTROL JOINT
A A DL DOWNLIGHT (REFER ELEC.)
FC1 FIBRE CEMENT CLADDING TYPE 1
ME REFER MECHANICAL ENG. DWGS
PB1 PLASTERBOARD TYPE 1
PL PENDANT LIGHT (REFER ELEC.)
RP RECESSED PELMET
B
SC STEEL COLUMN
SPS1 STEEL PLATE SUNSHADE TYPE 1
WF2 SPS2 STEEL PLATE SUNSHADE TYPE 2
FC1
WF1 WINDOW FURNISHING - BLOCKOUT BLINDS
12b RP WF2 WINDOW FURNISHING - SHEAR BLINDS
BH WF3 WINDOW FURNISHING - BLOCKOUT
CURTAIN
WL WALL LIGHT (REFER ELEC.)
C-TB1
3900
WF2
RP
SPS1
SPORTS 12b 4 5 6 7 8
LOUNGE BH C-PB2 RP
3300 3500
C-TB1 SPS2
AP
C-PB1 @TPD / CLIENT: CONFIRM BLINDS/CURTAINS INCLUSION + RECESSED PELMETS
3900
3900 SPS1
WF2
WF2 RP WF2 RP WF2 WF1 - WINDOW FURNISHING 1
BLOCKOUT BLINDS
FC1 - 3300 B
C-TB2 WF2 - WINDOW FURNISHING 2
C-PBP 12b
C 3900
3900
BH C-TB2 C-TB1 12b C-TB1 C-TB1 12b FCL 5142
SHEAR BLINDS
3900 3900 BH 3900 3900 BH
C-PB1 WF3 - WINDOW FURNISHING 3
3900
C-PB1
BLOCKOUT CURTAIN
3900
C-PB1 C-PB1 C-PB1 C-PB1 FULL HEIGHT INSULATED
AP 3900 3900 3900 3900
INTERNAL WALL TO U/S OF SLAB
12b C-PBP OVER (GROUND LEVEL), OR
BH 3900
MEMBERS 150mm ABOVE FCL (UPPER
DINING LEVEL).
ALL EXTERNAL WALLS ARE FULL
3900
FC1
HEIGHT U.N.O.. REFER WALL
TYPES AND FLOOR PLANS.
C-PBP AP AP REFER ACOUSTIC REPORT.
12b C-PBP C-PBP C-TB1
3900
5° FALL
3900 3900 3900
BH
WF1
RP C-PBP C-PBP G
3900 3900 A32
FC2
CJ 12b 4350
BH 12b H
@MECH: CONFIRM 450x450 FCL 4350 A32
RP BH
DIFFUSERS OVER 600 FOR GRID BAR
CEILING? WF1 C-PB1 C
2400 SC
I 9 @MECH: CONFIRM 450x450
I
A32 CAFE A32
DIFFUSERS OVER 600 FOR GRID
D COOL 2 CEILING?
CHUTE BY OTHERS
EXHAUSTS CEILING GRID SETOUT POINT
C-PB1 AP
SAME MALE 2750
STORE 2
SETOUT C-G1
2700
RP
WF1 10
AP WF2
C-G1
2700 KITCHEN SAME
SETOUT C-G1
C-TB1 C-G1
3000 KITCHEN 2700
2700
HOOD CJ
CLNR 3
SETOUT
SAME
WF1
C-G1
ACC. WC WF2
CJ
2700
SAME
C-PB1
SAME
SETOUT
SAME
SETOUT
CEILING GRID
11
SETOUT 2750 C-PB1 RP
SETOUT POINT 10a
LIFT 1 FREEZER COOL 1 M. F. 3300 3500
DRY STORE ACC. WC C-PB1 BH
AMB. AMB.
8 3800 SPS1 P5 FOR COORDINATION 28/08/24
BY OTHERS BY OTHERS P4 FOR COORDINATION 20/08/24
C-G1 C-G1 C-G1
LIFT 2 2400 2400 2400 C- P P3 FOR COORDINATION 14/08/24
C-G1 B1
STORE 3 C-PB1 2700
-3
800
WF1
P2 FOR COORDINATION 12/08/24
FEMALE 2750 C-PB1 - 2700 AP WF2
C-G1
C-PBP
3800
12 P1 FOR COORDINATION 02/08/24
2700 CJ 10a rev: issue: date:
B.O.H. 12b
C-PB1
C-PB1 CJ BH
SAME
@MECH: CONFIRM EXTENT OF BOH CEILING SERVICES 3900 BH 2700 FUNCTION
SETOUT 10a
AP C-PB1 - 2700 C-PBP
BH
E FCL 2700
AP 3800
CJ
12° C-PB1 RP
FA LL 2700
CEILING GRID SETOUT POINT CJ
(ALIGN TO LIFT WALL)
PB1
13
12°
FA
1 2 3 4 5 6 LL 10a
BH
CJ
FCL 4500 AP C-PB1
Level 1 Style Arcade Manuka, Shop 13
NOTE: ALL LEVEL 1 ACOUSTIC WALLS TO ENSURE LIFT SHAFT WALL MEETS
TERMINATE 150mm ABOVE CEILING LEVEL SOUND INSULATION REQUIREMENT CJ C-PBP PROJ
A/V 2700 14-16 Franklin St Griffith 2603 t: 02 6295 1433
Nominated Architects:
UNLESS NOTED OTHERWISE. PLASTERBOARD
FINISH TO EXTEND TO FULL HEIGHT OF THESE
7 3800 SCREEN Andrew Collins ACT #2443 NSW #7448
WALLS (I.E. ABOVE SET CEILING) D David Pennington ACT #2490
C-PBP
AP 3800
client:
YOWANI COUNTRY CLUB
9 C- P
B1
-3
C-PB1
3800
800
WF3
project:
10 RP YOWANI COUNTRY CLUBHOUSE
4400
G 10°
A32 FA LL
CJ
BLOCK 14 SECTION 64 LYNEHAM &
C-PB1
BLOCK 07 SECTION 67 LYNEHAM
FCL 3800
4400
FCL 4400
drawing title:
FC1
11 4750 REFLECTED CEILING PLAN -
UPPER LEVEL
scale:
date: 28/08/24
A
A30
B
A30
C
A30
D
A31
E
A31
F
A31
H
A32
12 project no: 22203
A17 P5
NOT FOR CONSTRUCTION
Use figured dimensions and do not scale off drawings. All dimensions and
levels to be checked and verified on site prior to commencement of Works.
Any form of reproduction of this drawing in full or part without the written
permission of collins pennington architects 2024 constitutes an infringement
of copyright.
LEGEND
AG ALUMINIUM-FRAMED GLAZING
AGD ALUMINIUM-FRAMED GLAZED DOOR
ASD ALUMINIUM-FRAMED GLAZED SLIDING
DOOR
ATG ALU/TIMBER-FRAMED GLAZING
BAL2 BALUSTRADE TYPE 2
BAL3 BALUSTRADE TYPE 3
BAL4 BALUSTRADE TYPE 4
BW1 BLOCKWORK TYPE 1
FC1 FIBRE CEMENT CLADDING TYPE 1
FC2 FIBRE CEMENT CLADDING TYPE 2
FL1 FLASHING TYPE 1
MC1 METAL CLADDING TYPE 1
MCD
RD ROLLER DOOR
RS1 ROOF SHEET TYPE 1
RW1 RENDERED WALL TYPE 1
SPS1 STEEL PLATE SUNSHADE TYPE 1
8 7 6 5 4 3 2 1
ROOF
RL +582.00 m
MC1
MC1
RS1
1900
UPPER FCL 3
MC1 RL +580.10 m
600
UPPER FCL 2
MC1 SPS1 RL +579.50 m
600
FC2 ATG ATG UPPER FCL 1
RL +578.90 m
FC1
ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG
2700
BAL3 AGD AGD
BAL3 BAL4
UPPER FFL
RL +576.20 m
FC1
FC1 FC1
900
FC1 GROUND FCL
BW1 RL +575.30 m
BW1 FL1
BW1 FC1
2700
FC1
RD AG AGD AG
MCD AG AG ASD AG AG
GROUND FFL
LINE OF STAIR BEHIND WALL RL +572.60 m
NORTH ELEVATION
1 SCALE: 1 : 100
ROOF
RL +582.00 m
FC1 MC1
MC1
1900
FC1 FC1
Level 1 Style Arcade Manuka, Shop 13
MC1 UPPER FCL 3 14-16 Franklin St Griffith 2603 t: 02 6295 1433
MC1 MC1 RL +580.10 m
AG Nominated Architects:
600
UPPER FCL 2
SPS1 AG AG AG AG AG RL +579.50 m Andrew Collins ACT #2443 NSW #7448
David Pennington ACT #2490
600
MC1 FC1 UPPER FCL 1
RL +578.90 m
client:
YOWANI COUNTRY CLUB
AG ATG ATG
AGD AG AG AG AG
2700
BAL4
BAL2 project:
BAL3 BAL3 UPPER FFL
RL +576.20 m
RW1
FC1
YOWANI COUNTRY CLUBHOUSE
GROUND FCL
RL +575.30 m
BW1
BLOCK 14 SECTION 64 LYNEHAM &
BLOCK 07 SECTION 67 LYNEHAM
3600
RD
AGD AG AG AG AG AG AG AGD drawing title:
BW1 LINE OF STAIR BEHIND WALL
GROUND FFL ELEVATIONS - SHEET 1
RL +572.60 m
scale: 1 : 100 @ A1
date: 23/09/24
project no: 22203
LEGEND
AG ALUMINIUM-FRAMED GLAZING
AGD ALUMINIUM-FRAMED GLAZED DOOR
ATG ALU/TIMBER-FRAMED GLAZING
AW AWNING WINDOW
BAL2 BALUSTRADE TYPE 2
BW1 BLOCKWORK TYPE 1
DP1 DOWNPIPE TYPE 1
EG1 EAVES GUTTER TYPE 1
FC1 FIBRE CEMENT CLADDING TYPE 1
FE1 FENCE TYPE 1
FL1 FLASHING TYPE 1
LVR LOUVRE
MC1 METAL CLADDING TYPE 1
MCD
ME REFER MECHANICAL ENG. DWGS
RD ROLLER DOOR
RW1 RENDERED WALL TYPE 1
SPH STEEL PLATE HOOD
1 2 3 4 5 6 7 8
ROOF
RL +582.00 m
1900
MC1
FC1
MC1 UPPER FCL 3
RL +580.10 m
AG AG
600
UPPER FCL 2
RL +579.50 m
600
UPPER FCL 1
RL +578.90 m
AG AG AG AG AG AG AG AG
AG AG
2700
UPPER FFL
RL +576.20 m
MC1
900
RW1
GROUND FCL
RW1 ME ME RL +575.30 m
BW1 RW1
2700
ATG ATG ATG ATG ATG ATG ATG ATG AGD ATG ATG ATG
REFER LANDSCAPE DOCUMENTATION REFER LANDSCAPE DOCUMENTATION REFER LANDSCAPE DOCUMENTATION
SOUTH ELEVATION
1 SCALE: 1 : 100
P6 FOR COORDINATION 23/09/24
P5 FOR COORDINATION 28/08/24
P4 FOR COORDINATION 20/08/24
P3 FOR COORDINATION 14/08/24
P2 FOR COORDINATION 02/08/24
P1 FOR COORDINATION 18/07/24
rev: issue: date:
B C D E
A
MC1 ROOF
RL +582.00 m
EG1
MC1 MC1
MC1
1900
MC1
MC1
600
UPPER FCL 2 Nominated Architects:
FL1 EG1 RL +579.50 m
Andrew Collins ACT #2443 NSW #7448
FC1 FC1
600
UPPER FCL 1 David Pennington ACT #2490
RL +578.90 m
BAL2
client:
SPH
AG AW AG AW YOWANI COUNTRY CLUB
2700
DP1
FC1
UPPER FFL
RL +576.20 m project:
900
DP1 GROUND FCL
BW1 BW1 RL +575.30 m
BW1 BW1 BW1
LVR LVR
FC1
BLOCK 14 SECTION 64 LYNEHAM &
FE1 BLOCK 07 SECTION 67 LYNEHAM
RD LINE OF SCREEN TO MECHANICAL PLANT SPACE
2700
AG AG AG RD MCD MCD
AGD MCD MCD
LINE OF STAIR (AND NOMINALLY LANDSCAPED EARTH BERM) BEHIND WALL BW1 drawing title:
LINE OF LANDSCAPED EARTH
BERM BEHIND WALL GROUND FFL
RL +572.60 m
ELEVATIONS - SHEET 2
scale: 1 : 100 @ A1
date: 23/09/24
project no: 22203
B C D E
A
LEGEND
1
A40 2 AG ALUMINIUM-FRAMED GLAZING
2 A40 ATG ALU/TIMBER-FRAMED GLAZING
A41
SIM
EG1 EAVES GUTTER TYPE 1
ROOF
RL +582.00 m FC1 FIBRE CEMENT CLADDING TYPE 1
EG1
EG1
FC3 FIBRE CEMENT CLADDING TYPE 3
MC1 METAL CLADDING TYPE 1
1900
MC1
MC1 PV2 PAVER TYPE 2
RS1 UPPER FCL 3
RL +580.10 m RS1 ROOF SHEET TYPE 1
600 600
UPPER FCL 2
RL +579.50 m RW1 RENDERED WALL TYPE 1
UPPER FCL 1 SPH STEEL PLATE HOOD
RL +578.90 m
SPS1 STEEL PLATE SUNSHADE TYPE 1
SPORTS UPPER
LOUNGE BAR DELIVERY
2700
LIFT SHAFT
CLNR 3
PV2
UPPER FFL
RL +576.20 m
900
GROUND FCL
RL +575.30 m
RW1
STAIR 3
WORKSHOP / WASTE
2700
CART STORE 1 STORE PRO SHOP CLUB FITTING MSB ROOM COLLECTION KEG DELIVERY
GROUND FFL
RL +572.60 m
SECTION A
A SCALE: 1 : 100
B C D E
A
EG1 RS1
EG1
1900
SPS1 MC1 UPPER FCL 3
RL +580.10 m
600 600
UPPER FCL 2
RL +579.50 m
UPPER FCL 1
RL +578.90 m
UPPER
MEMBERS CAFE MALE ACC. WC FEMALE DELIVERY
2700
PV2
UPPER FFL
RL +576.20 m
900
GROUND FCL
RL +575.30 m
RW1
3600
2700
CART STORE 1 STORE PRO SHOP AMENITIES LOCKERS
GROUND FFL
RL +572.60 m
SECTION B
B SCALE: 1 : 100
1900
MC1
RS1
600 600
UPPER FCL 2
RL +579.50 m
UPPER FCL 1
AG RL +578.90 m
2700
Nominated Architects:
LOBBY Andrew Collins ACT #2443 NSW #7448
David Pennington ACT #2490
UPPER FFL
RL +576.20 m
client:
900
FC1 MC1
GROUND FCL
RL +575.30 m YOWANI COUNTRY CLUB
FC3
2700
project:
drawing title:
SECTIONS - SHEET 1
SECTION C
C SCALE: 1 : 100 scale: 1:100 @ A1
date: 23/09/24
project no: 22203
A30 P6
NOT FOR CONSTRUCTION
Use figured dimensions and do not scale off drawings. All dimensions and
levels to be checked and verified on site prior to commencement of Works.
Any form of reproduction of this drawing in full or part without the written
permission of collins pennington architects 2024 constitutes an infringement
of copyright.
B C D E
2 LEGEND
A41
AG ALUMINIUM-FRAMED GLAZING
ATG ALU/TIMBER-FRAMED GLAZING
RS1 EG1 EAVES GUTTER TYPE 1
ROOF
RL +582.00 m FC1 FIBRE CEMENT CLADDING TYPE 1
EG1
RS1 EG1 MC1 METAL CLADDING TYPE 1
RS1 ROOF SHEET TYPE 1
1900
RS1
MC1 MC1
SPH STEEL PLATE HOOD
SPS1 SPH UPPER FCL 3
RL +580.10 m SPS1 STEEL PLATE SUNSHADE TYPE 1
600 600
UPPER FCL 2
RL +579.50 m
AG UPPER FCL 1
RL +578.90 m
4
ATG
DINING A50
2700
Sim
LOBBY
UPPER FFL
RL +576.20 m
FC1
900
MC1
GROUND FCL
RL +575.30 m
AMENITIES
FEMALE
2700
GOLF OFFICE AIRLOCK LOBBY
GROUND FFL
RL +572.60 m
SECTION D
D SCALE: 1 : 100
B C D E
2
2 A40
A41 SIM
RS1 SIM
ROOF
RL +582.00 m
RS1
EG1 EG1
RS1
1900
MC1
600 600
UPPER FCL 2
RL +579.50 m
UPPER FCL 1
RL +578.90 m
ATG
DINING KITCHEN
2700
LOBBY
UPPER FFL
RL +576.20 m
FC1 LIFT SHAFT
900
GROUND FCL
RL +575.30 m
FEMALE
2700
AMENITIES LOBBY
GROUND FFL
RL +572.60 m
SECTION E
E SCALE: 1 : 100
1900
MC1
RS1
SPS1 UPPER FCL 3
MC1 RL +580.10 m
600 600
UPPER FCL 2
RL +579.50 m
UPPER FCL 1
RL +578.90 m
2700
Nominated Architects:
Andrew Collins ACT #2443 NSW #7448
David Pennington ACT #2490
UPPER FFL
RL +576.20 m
FC1
client:
900
GROUND FCL
RL +575.30 m YOWANI COUNTRY CLUB
COMMUNITY
FEMALE
2700
project:
OPEN OFFICE M. AMBULANT M. AMBULANT
ENG.
LOCKERS YOWANI COUNTRY CLUBHOUSE
GROUND FFL
RL +572.60 m
BLOCK 14 SECTION 64 LYNEHAM &
BLOCK 07 SECTION 67 LYNEHAM
drawing title:
SECTIONS - SHEET 2
SECTION F
F SCALE: 1 : 100 scale: 1:100 @ A1
date: 23/09/24
project no: 22203
A31 P6
NOT FOR CONSTRUCTION
Use figured dimensions and do not scale off drawings. All dimensions and
levels to be checked and verified on site prior to commencement of Works.
Any form of reproduction of this drawing in full or part without the written
permission of collins pennington architects 2024 constitutes an infringement
of copyright.
D E
LEGEND
ATG ALU/TIMBER-FRAMED GLAZING
EG1 EAVES GUTTER TYPE 1
MC1 METAL CLADDING TYPE 1
ROOF
RL +582.00 m RS1 ROOF SHEET TYPE 1
RW1 RENDERED WALL TYPE 1
SPS1 STEEL PLATE SUNSHADE TYPE 1
1900
UPPER FCL 3
RL +580.10 m
600 600
UPPER FCL 2
RL +579.50 m
UPPER FCL 1
RL +578.90 m
FUNCTION LOBBY
2700
UPPER FFL
RL +576.20 m
900
GROUND FCL
RL +575.30 m
2700
BOARD CLUB STORE
GROUND FFL
RL +572.60 m
SECTION G
G SCALE: 1 : 100
D E
ROOF
RL +582.00 m
RS1
EG1
1900
UPPER FCL 3
MC1 RL +580.10 m
SPS1
600 600
UPPER FCL 2
RL +579.50 m
UPPER FCL 1
RL +578.90 m
2 ATG
FUNCTION
A53
2700
UPPER FFL
RL +576.20 m
900
GROUND FCL
RW1 RL +575.30 m
2700
CART STORE 2
GROUND FFL
RL +572.60 m
SECTION H
H SCALE: 1 : 100
client:
YOWANI COUNTRY CLUB
project:
drawing title:
SECTIONS - SHEET 3
scale: 1:100 @ A1
date: 23/09/24
project no: 22203
A32 P6
NOT FOR CONSTRUCTION
Use figured dimensions and do not scale off drawings. All dimensions and
levels to be checked and verified on site prior to commencement of Works.
Any form of reproduction of this drawing in full or part without the written
permission of collins pennington architects 2024 constitutes an infringement
of copyright.
1 2 3 4 5 6 7 8 LEGEND
AG ALUMINIUM-FRAMED GLAZING
ATG ALU/TIMBER-FRAMED GLAZING
BAL4 BALUSTRADE TYPE 4
RS1
BW1 BLOCKWORK TYPE 1
ROOF
RS1 RL +582.00 m EG1 EAVES GUTTER TYPE 1
RS1 FC1 FIBRE CEMENT CLADDING TYPE 1
MC1 FC2 FIBRE CEMENT CLADDING TYPE 2
1900
MC1
FC1 LVR LVR
FC1
MC1 FC3 FIBRE CEMENT CLADDING TYPE 3
RS1 RS1 EG1 UPPER FCL 3
EG1 LVR
RL +580.10 m FL1 FLASHING TYPE 1
600 600
UPPER FCL 2 LVR LOUVRE
RL +579.50 m
FC1 UPPER FCL 1 MC1 METAL CLADDING TYPE 1
RL +578.90 m
PV1 PAVER TYPE 1
RS1 ROOF SHEET TYPE 1
BAR CAFE KITCHEN
AG RW1 RENDERED WALL TYPE 1
2700
SCD SOLID CORE DOOR
PV1 BAL4
FC1 SPH STEEL PLATE HOOD
UPPER FFL
RL +576.20 m SPS2 STEEL PLATE SUNSHADE TYPE 2
FC1
900
MC1
GROUND FCL
RL +575.30 m
FC1
MALE
2700
MSB ROOM AMENITIES LOBBY OPEN OFFICE
GROUND FFL
RL +572.60 m
SECTION I
I SCALE: 1 : 100
8 7 6 5 4 3 2 1
1900
RS1 RS1
600
EG1 UPPER FCL 2
EG1 RL +579.50 m
600
FC2 UPPER FCL 1
RL +578.90 m
B.O.H. &
MC1
KITCHEN KITCHEN LOBBY CAFE BAR COOL 2 STORE 2
2700
FC2 UPPER FFL
RL +576.20 m
900
GROUND FCL
BW1 BW1 BW1 RL +575.30 m
FC1 BW1
FC3
FC1
BW1 ATG BW1
MALE
2700
AG OPEN OFFICE LOBBY AMENITIES MSB ROOM BW1
GROUND FFL
RL +572.60 m
SECTION J
J SCALE: 1 : 100
E D C
A
P1 FOR COORDINATION 23/09/24
rev: issue: date:
FL1
FL1 RS1 MC1 ROOF
RS1 RL +582.00 m
EG1
EG1
1900
MC1 RS1 MC1
UPPER FCL 3
SPH SPS2 RL +580.10 m
600
FL1 FL1 UPPER FCL 2
FL1 RL +579.50 m
600
UPPER FCL 1
RL +578.90 m
2700
Andrew Collins ACT #2443 NSW #7448
David Pennington ACT #2490
UPPER FFL
RL +576.20 m client:
MC1 FC1 RW1 YOWANI COUNTRY CLUB
900
GROUND FCL
BW1 RL +575.30 m
FC3
BW1 FC3
project:
2700
SCD
LINE OF LANDSCAPED EARTH BERM BEHIND WALL
250
drawing title:
SECTIONS - SHEET 4
scale: 1:100 @ A1
SECTION K
K SCALE: 1 : 100 date: 23/09/24
project no: 22203
A33 P1
NOT FOR CONSTRUCTION
Use figured dimensions and do not scale off drawings. All dimensions and
levels to be checked and verified on site prior to commencement of Works.
Any form of reproduction of this drawing in full or part without the written
permission of collins pennington architects 2024 constitutes an infringement
of copyright.
REFER TO SIMILAR DETAIL
UPPER FCL 1
RL +578.90 m
WINDOW FRAME TRANSOM
SUSPENDED CEILING SYSTEM
C-PB1
SQUARE SET PB CORNICE (TYP.)
CLNR 3 B.O.H.
OUTSIDE INSIDE
SPORTS
MC1 RIB DEPTH
LOUNGE PB1
STEEL STUD WITH IN-W1 MC1
SK1 35mm BATTEN
VN1 VB1
UPPER FFL
RL +576.20 m
IN-S3
FRAMING w/ IN-W1
GROUND FCL
RL +575.30 m
IN-S1
FC1 CEILING LINING
VB1
P3 FOR COORDINATION 28/08/24
STEEL STUD WITH IN-W1 KEG DELIVERY P2 FOR COORDINATION 20/08/24
PB1
P1 FOR COORDINATION 14/08/24
BY OTHERS
LIFT DOORS BY OTHERS
LIFT 400 rev: issue: date:
SHAFT MIN
NGL
FC1
IN-S2
VB1
PB1
92mm STUD w/ IN-W1 BW1
PFS 50mm CAVITY
VB1 VB1
client:
STAIR 1
VB1 TO LAP DPC AND TERMINATE NOM. 50mm BELOW TOP OF DPC
YOWANI COUNTRY CLUB
BITUMEN-COATED SOLID ALUMINIUM DAMP-PROOF TILE
COURSE (DPC) PINNED & SEALED TO DINCEL
SCREED TO ACHIEVE FALLS
project:
120
BLOCK 14 SECTION 64 LYNEHAM &
BLOCK 07 SECTION 67 LYNEHAM
BRICK COMMONS COURSES BELOW GROUND
CONCRETE SLAB
FILL CAVITY BELOW FGL WITH CONCRETE CONCRETE SLAB
SLAB MEMBRANE drawing title:
SAND BLINDING SLAB MEMBRANE
SAND BLINDING WALL DETAIL SECTIONS - SHEET
2
scale: As indicated @ A1
CONCRETE PAD FOOTING date: 28/08/24
project no: 22203
2
A30
DETAIL D-1
SCALE: 1 : 20
3
A31
DETAIL F-1
SCALE: 1 : 20
A41 P3
NOT FOR CONSTRUCTION
Use figured dimensions and do not scale off drawings. All dimensions and
levels to be checked and verified on site prior to commencement of Works.
Any form of reproduction of this drawing in full or part without the written
3128 3128 500 1505 2453 2453 2453 1993 1993 2624 2624 permission of collins pennington architects 2024 constitutes an infringement
EQ PARTS EQ PARTS EQ PARTS EQ PARTS EQ PARTS EQ PARTS EQ PARTS of copyright.
CL CL
CL
1002 503 1002 1451 991 1002
325
300
300
ACP ALUMINIUM COVER PLATE
AG ALUMINIUM-FRAMED GLAZING
AGD ALUMINIUM-FRAMED GLAZED DOOR
AUTO ASD ALUMINIUM-FRAMED GLAZED SLIDING
3000
AUTO DOOR
2700
2675
AG AG
FLM AGD AG ASD SIMILAR TO
2400
2400
AGD AG AG AG AG AG AG AG AG AGD AG AG AG
WINDOW G13 AUTO AUTOMATIC SLIDING DOOR
VI VI VI VI VI VI VI VI VI VI VI VI VI VI VI VI VI VI VI VI AW AWNING WINDOW
FLM FULL HEIGHT FILM
1237 MCD
920 920
LEAF LEAF OPENING GROUND FFL VI VISUAL INDICATOR
RL +572.60 m
W4 W4 W2 W2 W2 W2 W2 W2 W2 W2 W2 W2
G02 G03 G05 G04 G10 G09 G08 G07 G06 G13 G12 G11
762
1570 1535 4025 1485
CL CL CL
1002 568 533 1002 3920 1025 3000 610
EQ PARTS EQ PARTS
GROUND FCL
RL +575.30 m
300
650
E.
N OT
EE
-S
1800
)
45 AW
(Rw
GU
CD
1200
TI AG
2700
2700
2700
2700
2700
S
AGD AG AG AGD AGD AG OU AG AG MCD MCD
SIMILAR TO AC
2400
AG AG AG
FLM FLM WINDOW G17
VI VI VI VI VI VI
CL
920 455 920
920 LEAF LEAF
900
920 LEAF
850
AG
LEAF
LEAF
GROUND FFL
RL +572.60 m
W2 W2 W1 W2 W2 W2
G23
GLAZING NOTES & LEGEND:
G15 G16 G20 G21 G22
W2 W2 ALL DIMENSIONS TO BE CHECKED AND VERIFIED ON
G17 G18
SITE PRIOR TO SHOP DRAWINGS AND GLAZING ORDER.
WINDOW TYPES
W1 150mm ALUMINIUM
W2 100mm ALUMINIUM
W3 COMPOSITE TIMBER + ALUMINIUM
W4 AUTOMATIC SLIDING DOOR
RD ROLLER DOOR
500
UPPER FCL 3
RL +580.10 m
AG AG
600
600
P4 FOR COORDINATION 28/08/24
875
AG AG AG AG AG
P3 FOR COORDINATION 20/08/24
CL
CL
CL
CL
P1 FOR COORDINATION 02/08/24
rev: issue: date:
4400
4400
3900
3900
AG AG AG AG AG AG AG AG
3300
3300
AG AG
3025
3025
AGD AGD AG AG AG AG
VI VI VI VI VI VI
920 920
LEAF LEAF
UPPER FFL Level 1 Style Arcade Manuka, Shop 13
RL +576.20 m 14-16 Franklin St Griffith 2603 t: 02 6295 1433
Nominated Architects:
Andrew Collins ACT #2443 NSW #7448
David Pennington ACT #2490
W1 W1 W1 W1 W1
U01 U02 U03 U05 U06
client:
YOWANI COUNTRY CLUB
project:
drawing title:
E .
E. SE
EN
OT WINDOW SCHEDULE -
NO T
EE )-
GU (
R w 45
)-S
w
45 ALUMINIUM GLAZING
1500
D (R
AG STIC AG
DGU
A CO U TIC
AW S AW
OU scale: 1:50 @ A1
AC
date: 28/08/24
W1 W1 project no: 22203
U10 U11
900
A90 P4
NOT FOR CONSTRUCTION
Use figured dimensions and do not scale off drawings. All dimensions and
levels to be checked and verified on site prior to commencement of Works.
17320 Any form of reproduction of this drawing in full or part without the written
10982
permission of collins pennington architects 2024 constitutes an infringement
EQ PARTS EQ PARTS of copyright.
300
300
GROUND FCL
RL +575.30 m
LEGEND
AG ALUMINIUM-FRAMED GLAZING
AGD ALUMINIUM-FRAMED GLAZED DOOR
ATG ALU/TIMBER-FRAMED GLAZING
VI VISUAL INDICATOR
3060
3060
ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG AGD ATG ATG ATG ATG
2700
2700
VI VI VI VI VI VI VI VI VI
1091 (APPROX.)
LEAF GROUND FFL
RL +572.60 m
60
60
W3 W3
G01 G14
18000
CL CL CL CL CL
9000 1100 1900 1900 1100 3000
EQ PARTS EQ PARTS
UPPER FCL 2
RL +579.50 m
520 50
ATG ATG
CL
GLAZING NOTES & LEGEND:
ALL DIMENSIONS TO BE CHECKED AND VERIFIED ON
SITE PRIOR TO SHOP DRAWINGS AND GLAZING ORDER.
3300
ATG ATG ATG ATG ATG ATG ATG AG ATG ATG MAX. U-VALUE (w): 3.35
MAX. SHGC: 0.5
2780
AGD AGD
VI VI VI VI VI VI VI VI VI VI VI VI VI VI
MEASUREMENTS INCLUDE SUB-HEAD AND SUB-SILL,
AND MEASURE THE TOTAL WINDOW OPENING.
CL CL
920 920 920 920 ALL GLAZING SYSTEMS DOUBLE-GLAZED AND
LEAF LEAF LEAF LEAF THERMALLY BROKEN U.N.O.
UPPER FFL
RL +576.20 m
DOOR LEAF DIMENSIONS TAKE PRECEDENCE OVER
0
REFER PLAN.
RADIUS 12650mm (APPROX.) IN A 30 DEGREE ARC
50
50
UPPER FCL 2
RL +579.50 m
3100
ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG ATG
P4 FOR COORDINATION 28/08/24
P3 FOR COORDINATION 20/08/24
FACETED GLAZING FRAME P2 FOR COORDINATION 14/08/24
WITH FLAT GLASS P1 FOR COORDINATION 02/08/24
rev: issue: date:
UPPER FFL
RL +576.20 m
200
200
W3
W3 U08
U07
570
ATG ATG
CL
SHARES MULLION WITH U08
project:
2730
AGD AGD
drawing title:
VI VI VI VI VI
CL CL
WINDOW SCHEDULE -
920 920 920 920 COMPOSITE GLAZING
200
date: 28/08/24
W3 project no: 22203
U09
A91 P4
NOT FOR CONSTRUCTION
Use figured dimensions and do not scale off drawings. All dimensions and
2885 1650 1650 1620 2100 levels to be checked and verified on site prior to commencement of Works.
Any form of reproduction of this drawing in full or part without the written
CL CL CL CL CL permission of collins pennington architects 2024 constitutes an infringement
1500 970 415 625 995 680 970 450 of copyright.
UPPER FCL 1
RL +578.90 m
GROUND FCL
RL +575.30 m
LEGEND
1400 AG ALUMINIUM-FRAMED GLAZING
AGD ALUMINIUM-FRAMED GLAZED DOOR
RD ROLLER DOOR
VI VISUAL INDICATOR
3000
600
AG AG AG
AGD
2700
2700
2700
2700
AGD AG AGD AG AG AGD AG
VI VI VI VI VI VI VI VI VI VI VI VI
900
920
920 920 920 UPPER FFL
920 LEAF RL +576.20 m
LEAF LEAF LEAF LEAF
GROUND FFL
RL +572.60 m
P1
06
P1 P2 P2 P2 P2
01 02 03 04 05
125 425
125 425
RL +575.30 m
125 425
EXTERIOR ROLLER DOORS
WINDOW TYPES
RD RD
W1 150mm ALUMINIUM
OPENING
OPENING
RD
RD
OPENING
2700
2700
W2 100mm ALUMINIUM
OPENING
2500
2400
4400
4300
OPENING
RD
LINE OF COUNTERTOP
1100
client:
YOWANI COUNTRY CLUB
project:
drawing title:
date: 28/08/24
project no: 22203
A92 P4
NOT FOR CONSTRUCTION
Use figured dimensions and do not scale off drawings. All dimensions and
levels to be checked and verified on site prior to commencement of Works.
Any form of reproduction of this drawing in full or part without the written
permission of collins pennington architects 2024 constitutes an infringement
of copyright.
1BLOCKWORK
- BW NOTE: REFER STRUCTURAL DOCUMENTATION
FOR PFS THICKNESS & DETAILS
3STANDING
- MC SEAM METAL CLADDING
10 - INTERIOR
INTERIOR PARTITIONS LEGEND
BW1 BLOCKWORK TYPE 1
EXT EXT BW2 BLOCKWORK TYPE 2
FC1 FIBRE CEMENT CLADDING TYPE 1
BW1 > 50mm CAVITY > VB1 > PFS (REF. STRUCTURAL) >
1a 92mm STUD w/ IN-W2 > PB1 3a MC1 > VB1 > 150mm STUD w/ IN-W1 > PB1 10a PB1 > 92mm STUD > PB1 FC2 FIBRE CEMENT CLADDING TYPE 2
IN-W1 WALL INSULATION TYPE 1
VARIES 198 mm 118 mm
IN-W2 WALL INSULATION TYPE 2
IN-W3 WALL INSULATION TYPE 3
EXT EXT
MC1 METAL CLADDING TYPE 1
BW1 > 50mm CAVITY > PFS (REF. STRUCTURAL) PB1 PLASTERBOARD TYPE 1
1b NOTE: INCLUDE WPS WHERE AGAINST FILL 3b MC1 > VB1 > 150mm STUD w/ IN-W1 > 2 x PB1 10b PB1 > 2 x 92mm STUD > PB1 PB2 PLASTERBOARD TYPE 2
PLY PLYWOOD
VARIES 211 mm 210 mm
RW1 RENDERED WALL TYPE 1
VB1 VAPOUR BARRIER TYPE 1
EXT EXT
WPS WATER-PROOFING SYSTEM
BW1 > 50mm CAVITY > VB1 > 92mm STUD w/ IN-W1 >
1c 108mm CAVITY > 92mm STUD > PB1
3c MC1 > VB1 > 150mm STUD w/ IN-W1 > VB1 > MC1 10c PB1 > 150mm STUD > PB1
CAVITY
445 mm EXT 220 mm 176 mm
EXT
BW1 > 50mm CAVITY > VB1 > 92mm STUD w/IN-W1 >
1d PB1
10d PLY > VB1 > 92mm STUD w/ IN-W2 > PB1
EXT
BETWEEN EXTERIOR SPACE:
WALL TAG:
245 mm 121 mm
@FIRE & ELEC: CONFIRM PLYWOOD TO EXTERNAL SPACES REQUIRED WHERE INDICATED IN PLAN LAYERS OF MATERIALS COMPOSING WALL
MC1 > VB1 > 150mm STUD w/ IN-W1 > 155mm CAVITY >
3d 92mm STUD > 2 x PB1 CODE F/R/L (IF APPLICABLE)
EXT CAVITY NOTES (IF APPLICABLE)
458 mm TOTAL
BW1 > 50mm CAVITY > VB1 > 92mm STUD w/IN-W1 > THICKNESS
1e 10e 2 x PB1 > 92mm STUD > PB1
PLY
245 mm 131 mm
WALL SYSTEMS:
EXT WALL SYSTEMS INCLUDE CLADDING, SUBSTRATES
AND STRUCTURE.
BW1 > 50mm CAVITY > PFS (REF. STRUCTURAL) > 35mm MC1 > VB1 > 150mm STUD > 148mm CAVITY > 92mm
1f FURRING CHANNEL > PB1
3e STUD > VB1 > FC2
CAVITY
MC1 METAL CLADDING ON STEEL BATTENS
VARIES 469 mm FC1 FIBRE CEMENT CLADDING ON STEEL BATTENS
FC2 FIBRE CEMENT CLADDING ON STEEL BATTENS
VB1 CLASS 4 VAPOR PERMEABLE MEMBRANE
EXT EXT
BW2
11 - ACOUSTIC NOTE:
EXT
2PERMANENT
- PFS FORMWORK
NOTE: REFER STRUCTURAL DOCUMENTATION
FOR PFS THICKNESS & DETAILS
4FIBRE-CEMENT
FC CLADDING ENGINEER
11b
PB1 > 2 x 92mm STEEL STUD w/ IN-W3 > PB1
Rw 40
INSULATION OR ACOUSTIC BAFFLES TO CONTINUE
TO U/S OF SLAB.
VARIES
FC1 > VB1 > 92mm STUD w/ IN-W1 > PLY 2 x PB2 > 64mm STUD w/ IN-W4 > DISCONTINUOUS AIR
PB1 > 35mm FURRING CHANNEL > PFS (REF.
20
2c 4c * REPLACE FC1 WITH FC2 (REF. PLAN) 11e GAP (20mm U.N.O.) > 64mm STUD > 2 x PB2
STRUCTURAL) > 35mm FURRING CHANNEL > PB1
Rw 50 DISCONTINUOUS
VARIES 152 mm VARIES
FC > PFS (REF. STRUCTURAL) > VB1 > 92mm STUD w/ P4 FOR COORDINATION 28/08/24
PB1 > 35mm FURRING CHANNEL > PFS (REF. STRUCTURAL
2d > 92mm STUD > PB1
4d IN-W1 > PB P3 FOR COORDINATION 20/08/24
* REPLACE FC1 WITH FC2 (REF. PLAN)
P2 FOR COORDINATION 14/08/24
VARIES VARIES
P1 FOR COORDINATION 02/08/24
EXT rev: issue: date:
2e
PLY > VB1 > 92mm STUD w/ IN-W1 > PFS (REF.
STRUCTURAL) > 35mm FURRING CHANNEL > PB1
COLUMN WITHIN CAVITY. REFER STRUCTURAL. 4e
FC1 > STEEL COLUMN (REF. STRUCTURAL) > VB1 >
150mm STUD w/ IN-W1 > PB1
12 - LININGS
ATTACHED TO WALLS
NOTE: ALL LININGS DESCRIBED BELOW ATTACH TO OTHER WALL
TYPES. E.G. "TB1" BATTENS FIX TO THE PLASTERBOARD BEHIND;
378 mm @STRUCT & TPD:
IT DOES NOT REPLACE THE PLASTERBOARD.
VARIES
HOW TO FIX BATTENS TO COLUMN ZONE? GIRTS?
EXT REFER INTERIOR DRAWINGS.
FC1 > PFS (REF. STRUCTURAL) > WPS > FILL
PFS (REF. STRUCTURAL) > VB1 > 92mm STUD w/ IN-W1 >
2f PB1 4f NOTE: EXTERNAL EXPOSED SURFACES TO BE RENDERED
RW1.
VARIES FILL BEHIND ALL LININGS TO BE CONFIRMED
44 mm Level 1 Style Arcade Manuka, Shop 13
WHEN DEVELOPING INTERIORS 14-16 Franklin St Griffith 2603 t: 02 6295 1433
Nominated Architects:
Andrew Collins ACT #2443 NSW #7448
David Pennington ACT #2490
4g FC1 > VB1 > 92mm STUD w/ IN-W1 > VB1 > FC1 client:
180 mm
YOWANI COUNTRY CLUB
project:
4h FC1 > VB1 > 150mm STUD w/ IN-W1 > VB1 > FC1 YOWANI COUNTRY CLUBHOUSE
238 mm BLOCK 14 SECTION 64 LYNEHAM &
BLOCK 07 SECTION 67 LYNEHAM
drawing title:
scale: 1:25 @ A1
date: 28/08/24
project no: 22203
A93 P4