Calculation Method of vd-2
Calculation Method of vd-2
Calculation Method of vd-2
Earth
MCB 2 Cable Rating A Cable Rating A
Cable Size mm Cable Size Application Remarks
Rating (A) 2 (Kw) 300C (Kw) 400C
mm
6 1.5 1.5 17.5 (3.4) 15.2 (3.4) Lighting (Light Load)
10 2.5 1.5 24 (4.7) 20.9 (4.1) Lighting (Heavy Load)
16 2.5 1.5 24 (4.7) 20.9 (4.1) Radial Circuit to Socket-Outlets
20 4 2.5 32 (6.3) 27.8 (5.4) Radial Circuit to Fixed Appliance
32 2x4 2.5 45 (9.3) 41.7 (8.1) Ring Circuit to Socket-Outlets
32 6 4 41 (8) 35.7 (7) Radial Circuit to Large Appliance-Cooker
40 10 6 57 (11.1) 49.6 (9.7) Radial Circuit to Large Machinery (Chiller Unit)