Calculation Method Load Schdule

Earth
MCB 2 Cable Rating A Cable Rating A
Cable Size mm Cable Size Application Remarks
Rating (A) 2 (Kw) 300C (Kw) 400C
mm
6 1.5 1.5 17.5 (3.4) 15.2 (3.4) Lighting (Light Load)
10 2.5 1.5 24 (4.7) 20.9 (4.1) Lighting (Heavy Load)
16 2.5 1.5 24 (4.7) 20.9 (4.1) Radial Circuit to Socket-Outlets
20 4 2.5 32 (6.3) 27.8 (5.4) Radial Circuit to Fixed Appliance
32 2x4 2.5 45 (9.3) 41.7 (8.1) Ring Circuit to Socket-Outlets
32 6 4 41 (8) 35.7 (7) Radial Circuit to Large Appliance-Cooker
40 10 6 57 (11.1) 49.6 (9.7) Radial Circuit to Large Machinery (Chiller Unit)

XLPE/SWA/PVC 1C, ECC


Min Size of
Cable Size Max Load Main CB
2 CB Capacity (A) Min No. of Earth Electrodes Earth
4c (mm ) (KW) Rating (A)
Conductor
10 40 18 60~100 1 16
16 63 30 200 1 50
25 100 48 300 1 50
35 125 62 400 1 70
50 160 80 500 2 70
70 200 100 600 2 70
95 225 128 800 2 70
120 250 130 1000 2 70
150 300 150 1600 2 70
185 350 175 2000 2 150
240 400 200 2500 2 150
300 500 250
𝑚𝑉 𝑋 𝐼 𝑋 𝐿 𝑚𝑉 𝑋 𝐿 𝑋 1.73 𝑋 𝐾𝑊
2 x 150 600 300 VD= , VD=
2 x 240 800 400
1000 1000
2 x 300 1000 500 34(𝐾𝑊) 𝑋 1000 34000
I= = 554.25 = 61.34
3 x 240 1200 600 3 𝑋 400 𝑋 0.8
4 x 240 1600 800 1.65 𝑥 61.34 𝑋 15
4 x 300 2000 1000 VD= 1000
=1.51
wKfv‡e †fv‡ë Wªc †ei Kiv hvq
Armoured and Unarmoured (‡gvU †jvW*1.732*†Kej †jš_*wgwj ‡fvë / KZUv †Kej*1000)
PVC Sheathed Cables

Voltage Max Cable


Conductor Meter Type &
2 Drop (Per Amp Length from Load in KW Remarks
(mm ) Rating
/Meter) in mV Meter To CT
10 4 100/5A CT Meter 13 Max 55
16 2.5 200/5A CT Meter 28 Max 110
25 1.65 300/5A CT Meter 28 Max 160
35 1.15 600/5A CT Meter 28 Max 350
50 0.87 1000/5A CT Meter 42 Max 550
70 0.6 1600/5A CT Meter 42 Max 800
95 0.45 2000/5A CT Meter 42 Above 800 1500 KVA TR
120 0.37 2500/5A CT Meter 42 Special Case
150 0.3 3000/5A CT Meter 42 Special Case
2
185 0.26 1 Phase Direct Meter Max 25 mm Max 9
240 0.21 3 Phase Direct Meter Max 25 mm2 Max 52
300 0.185
Isolator Load in KW Circuit Diversity Factor
Main CB (A)Room Dimensions (m) 40 18 Air-Conditioning: 0.90
1600-2500 3.5 x 3.5 63 30 Lighting: 0.75
1000- 1200 3x3 100 48 All Small Power: 0.50
600-800 2.5 x 2.5 125 Above 48
400-500 2.5 x 2
200-300 2x2 Note: Transformer: 500KVA-4No of Cable, 1000KVA-7No of Cable, 1500KVA-11No of Cable