Power System
Power System
ENGINEERING.
FACILITATOR : MR .BROWN
SEMISTER :I
𝑌𝑍
𝐵 = 𝑍 × (1 + )
4
1
= (12 + 𝑗62.4) [1 + (𝑗4 × 10−4 ) × (12 + 𝑗62.4) ]
4
= (12 + 𝑗62.4)(0.99376 + 𝑗0.0012)
= (𝟏𝟏. 𝟖𝟓𝟎𝟐𝟒 + 𝒋𝟏𝟏. 𝟗𝟏𝟎𝟕𝟐)ohms
𝐶 = 𝑌 = 𝑗4 × 10−4
= 𝟎. 𝟎𝟎𝟎𝟒 𝑺
∴ 𝑨 = 𝑫 = (𝟎. 𝟗𝟖𝟕𝟓𝟐 + 𝒋𝟎. 𝟎𝟎𝟐𝟒)
𝑩 = (𝟏𝟏. 𝟖𝟓𝟎𝟐𝟒 + 𝒋𝟏𝟏. 𝟗𝟏𝟎𝟕𝟐)ohms
𝑪 = 𝟎. 𝟎𝟎𝟎𝟒 𝑺
Question Two
The 𝐴, 𝐵, 𝐶, 𝐷 constants of a three- phase transmission line are 𝐴 = 𝐷 = 0.936 + 𝑗0.016,
𝐵 = 33.5 + 138 Ohms and 𝐶 = (−0.9280 + 901.223) × 10−6 . The load at the
receiving end is 40 MW at 200𝑘𝑉 with pf of 0.86 lagging. Find the magnitude of the
sending-end voltage, current, power and voltage regulation. Assume that he magnitude of
sending end voltage remains constant.
SOLUTION
Data given,
𝐴 = 𝐷 = 0.936 + 𝑗0.016
𝐵 = 33.5 + 138 Ohms
𝐶 = (−0.9280 + 901.223) × 10−6
𝑃𝑅 = 40𝑀𝑊 and 𝑉𝑅 = 200𝑘𝑉
Receiving-end phase voltage,
200 × 1000
𝑉𝑅 = = 1𝟏𝟓, 𝟒𝟕𝟎𝑽
√3
Receiving-end current,
40 𝑥 106
𝐼𝑅 = = 𝟏𝟑𝟒. 𝟐𝟕𝑨
√3 𝑥 200𝑥103 𝑥 0.86
Power factor,cos 𝜑 = 0.86
Phase angle, 𝜑 = cos−1 0.86 = −30.68°
sin 𝜑 = 0.51
𝐴 = 𝐷 = 0.936 + 𝑗0.016 = 0.93614∠0.98°
𝐵 = 33.5 + 𝑗138 = 142∠76.355° Ω
𝐶 = (−0.9280 + 𝑗901.223)𝑥10−6
= 901.2235∠90.06° 𝑥10−6 Ω
Taking receiving-end phase voltage as reference phasor, we have
𝑉𝑅 = 115,470(1 + 𝑗0) = 115,470∠0° 𝑉
𝐼𝑅 = 134.27∠−30.68° 𝐴
𝑉𝑆𝐿 = √3 𝑥 𝑉𝑆 = √3𝑥122,386
= 211,979𝑉 𝑜𝑟 211.98𝑘𝑉
Sending-end current,
𝐼𝑆 = 𝐶𝑉𝑅 + 𝐷𝐼𝑅
= (901.2235 𝑥 10−6 ∠90.06° 𝑥 115,470∠0° ) + (0.93614∠0.98° 𝑥 134.27∠−30.68° )
= 104.064∠90.06° + 125.696∠−29.7°
= (−0.109 + 𝑗104.064) + (109.18 − 𝑗62.28)
= (𝟏𝟎𝟗. 𝟎𝟕𝟏 + 𝒋𝟒𝟏. 𝟕𝟖𝟒) = 𝟏𝟏𝟔. 𝟖∠𝟐𝟎. 𝟗𝟔° 𝑨
Sending-end phase angle,
𝝋𝑺 = 𝟐𝟎. 𝟗𝟔° − 𝟕. 𝟐𝟕° = 𝟏𝟑. 𝟔𝟗° = 𝟎. 𝟗𝟕𝟏𝟔(𝒍𝒆𝒂𝒅𝒊𝒏𝒈)
Sending -end power
Data given.
Load = 50MVA
Received Voltage (𝑉𝑅 )=110𝑘𝑉
cos 𝜃𝑅 =0.8 𝜃𝑅 =cos −1 0.8 =36.87°
Solution
P=√3 𝑉𝑅 𝐼𝑅 cos 𝜃𝑅
50×10 6
𝑃⁄ = ×110 ×103 ×0.8
√3 𝑉𝑅 𝐼𝑅 cos 𝜃𝑅 √3
𝐼𝑅 =328.044A
𝐼𝑅 =328.044(𝑗 sin 𝜃𝑅 )
𝐼𝑅 = 328.84 × 𝑗0.6 = 𝑗196.82 𝐴
The receiving current = 196.82<90° A
110000
The receiving end voltage = 110kv = = 63509 V
√3
From.
i. Sending end voltage.
𝑃𝑅𝑒𝑐𝑒𝑖𝑣𝑒𝑑
iv. Efficiency = × 100%
𝑃𝑆𝑒𝑛𝑑
Question 04
A 3-phase, 50Hz 300𝐾𝑚 long transmission line has the following parameters 𝑟 =
0.15 Ω/𝑘𝑚; 𝑥 = 0.5 Ω/𝑘𝑚; 𝑦 = 3 × 10−6 Ω/𝐾𝑚. if the line represented by nominal-π,
determine
i. The ABCD constants for the line (derive the formula you might have used)
ii. The power at unity power factor that can be received if the voltage at each end is
maintained at 220𝑘𝑉
iii. The sending end voltage required if a load of 200𝑀𝑊 at 0.85lagging power factor is
to be delivered with the receiving end voltage remaining at 220𝑘𝑉
Solution
Total line parameters are;
Resistance, 𝑅 = 𝑟 𝑥 𝑙 = 0.15 𝑥 300 = 45Ω
Reactance, 𝑋 = 𝑥 × 𝑙 = 0.5 𝑥 300Ω
Susceptance, 𝑌 = 𝑦 × 𝑙 = 3 × 10 − 6 × 300 = 9 × 10 − 4𝑠
For nominal-π equivalent
Let
𝑌 = 𝑗𝑋𝐶 = Admittance
𝐴, 𝐵, 𝐶 and 𝐷 = Constant
Generalized Constant of the transmission line is given by sending end voltage and sending
end current equation
𝐼1 = 𝐼𝑅 + 𝐼𝐶1
𝐼1 = 𝐼𝑅 + (Y/2) 𝑉𝑅 ……………………………………………………………(3)
𝐼𝑆 = 𝐼1 + 𝐼𝐶2
= 𝑉𝑅 + Z 𝐼𝑅 + (ZY/2) 𝑉𝑅
= 𝑉𝑅 + (ZY/2) 𝑉𝑅 + Z 𝐼𝑅
= (1 + ZY/2) 𝑉𝑅 + Z 𝐼𝑅
𝑉𝑆 = A𝑉𝑅 + B𝐼𝑅
𝑉𝑆 = (1 + ZY/2) 𝑉𝑅 + Z 𝐼𝑅
𝐼𝑆 = 𝐼𝑅 + (Y/2) 𝑉𝑅 + (Y/2) 𝑉𝑆
𝐼𝑆 = C𝑉𝑅 + D𝐼𝑅
B=Z
𝒀𝒁
C = Y (1 + )
𝟒
𝒀𝒁
D=1+ 𝟐
i. 𝐴 = 𝐷 = 1 + 1⁄2 𝑌𝑍
= 𝑗9 × (0.96625 + 𝑗0.010125)
= 8.67 × 10−4 ∠90.6⁰
ii. Taking receiving end phase voltage as the reference phasor
We have,
220
VR = × 1.000 (1 + j0) = 127.000∠0⁰ V
√3
VS = AVR + BIR
= 𝟏𝟒𝟏. 𝟏𝟕𝟓 𝑨
Power received,
𝑖𝑖𝑖. 𝑉𝑅 = 127,000 𝑉
200 × 106
𝐼𝑅 = = 617.5 𝐴
√3 × 220000 × 0.85
𝑉𝑆 = 𝐴𝑉𝑅 + 𝐵𝐼𝑅
Question 05
Two 3-phase transmission lines have the generalized constants:
𝐴1 =𝐷1 =0.98∠2° ,𝐵1=28∠69° Ω,𝐶1 =0.0002∠88° S,
𝐴2 =𝐷2 =0.95∠3° , 𝐵2=40∠85° Ω, 𝐶2 =0.0004∠90° S
They are connected in series and delivers a load current of 200A at 0.95pf lagging at 110KV.
Determine the sending end voltage and sending end current.
solution
Data given:
𝐴1 =𝐷1 =0.98∠2° ,𝐵1=28∠69° Ω,𝐶1 =0.0002∠88° S,
𝐴2 =𝐷2 =0.95∠3° , 𝐵2=40∠85° Ω, 𝐶2 =0.0004∠90° 𝑠
𝑉𝑅 =110kV,
𝐼𝑅 =200A,
Cos𝜃𝑅 = 𝑝𝑓 = 0.95𝑙𝑎𝑔𝑔𝑖𝑛𝑔,
i. Sending end voltage:
from,
A=𝐴1 𝐴2+ 𝐵1 𝐶2
A=0.931∠5° +0.0112∠159°
A= 0.917+ j0.O85
A=0.921∠5.3°
Also;
B=𝐴1 𝐵2+ 𝐵1 𝐷2
B=39.2∠87° +26.6∠72°
B=10.2715+j64.444
B=65.26∠80.94° Ω
Then;
C=𝐶1 𝐴2+ 𝐷1 𝐶2
C=0.00019∠91° +0.000392∠92°
C=-0.00001668+j0.000582
C=0.000582∠91.67°S
Then;
D=𝐶1 𝐵2+ 𝐷1 𝐷2
D=0.008∠+0.931< 3°
D=0.91952+j0.0821
D=0.923∠5.1°
Cos𝜃𝑅 = 0.95
𝜃𝑅 =18.1949° lagging
𝐼𝑅 =200∠ − 18.195° A
From,
𝑉𝑆 =𝐴 𝑉𝑅 + 𝐵𝐼𝑅
𝑉𝑆 =58420∠5.3° +13052∠62.745°
𝑉𝑆 =64.147+j16998
𝑉𝑆 =66361∠14.84° V
from
𝐼𝑆 = C𝑉𝑅 + 𝐷𝐼𝑅 ,
= 36.957∠91.67° + 184.6∠−13.095°
Question Six
The two identical three phase transmission lines are connected in parallel to supply a load of
100 MW at 132 kV and 0.8 pf lagging at the receiving-end. The ABCD constants of each
transmission line are as follows
A = D = 0.98< 1° ; B = 100< 𝟕𝟓°Ω 𝒑𝒆𝒓 𝒑𝒉𝒂𝒔𝒆; C = 0.0005< 90° ; S per phase. Determine
i. The ABCD constants of the combined network.
ii. The sending-end power factor.
Solution
Generalized constant of two lines combined in parallel are;
𝑨𝟏 𝑩𝟏 + 𝑨𝟐 𝑩𝟐
A= 𝑩𝟏 + 𝑩𝟐
0.98<1°×100<75°+0.98<1°×100<75°
= 100<75°+100<75°
= 0.98∠𝟏°
B1 • B2 100∠75° ×100∠75°
B= =
B1 +B2 100∠75°+100∠75°
= 50∠75°
( A1 − A2 ) ( D1 − D2 )
C = C1 + C2 − B1 + B2
C1 + C2 ⸫ A1 = A2 and D1 = D2
Hence (A1 − A2 ) = 0
And (D1 − D2 ) = 0
= 0.0005 ∠90° + 0.000 ∠90°
= 0.001 ∠90° S
𝐁𝟏 𝐃𝟐 + 𝐁𝟐 𝐃𝟏
D= = A =0.98∠1°
𝐁𝟏 + 𝐁𝟐