Manual Tecnico Unidad Tecumseh FHT2511ZBR
Manual Tecnico Unidad Tecumseh FHT2511ZBR
Manual Tecnico Unidad Tecumseh FHT2511ZBR
Current (Amp)
Load Rated Amp 11.5
Max Cont Current 24.4
Lock Rotor Amp 71
Fan
Speed (rpm) 1335
Power (W) 90.0
Diameter (mm) 350
Protection Overload
IP Level IP44
Condenser M350/9100
Liquid Receiver
Capacity (L) 1.5
Maximum Pressure (Bars) 32.0
Suction Line
Suction Type Vanne Orientable
For Tubing Out Diam 15.9 (5/8")
Suction Connection Type Brased
Liquid Line
Liquid Line Type Vanne Orientable
* EN13215 : T°Ambient 32.0°C / T°Evap. -35.0°C / T°Return gas temp.. 20.0°C
For Tubing Out Diam 9.5 (3/8")
T°Subcooling. 3.0K
Liquid Connecton Type Brased
Connection Type VR
Fan Guard maille < à 8mm
Note : Tecumseh reserves the right to change information contained in this document without notification.
50 Hz R404A
N°User-157
5 | T ambiance 6 | T évaporation (°C) -40 -35 -30 -25 -20 -15 -10
25 1 | P frigorifique (Watt) 1657 2332 3094 3932 4836 5801 6832
2 | P absorbée (W) 1397 1695 2009 2347 2719 3131 3586
3 | I absorbée (A) 8.10 8.48 8.96 9.56 10.3 11.2 12.2
4 | Tc (°C) 30.9 32.4 34.6 37.4 40.7 44.2 47.7
32 1 | P frigorifique (Watt) 1341 1971 2672 3438 4261 5140 6086
2 | P absorbée (W) 1349 1672 2012 2377 2777 3217 3701
3 | I absorbée (A) 8.01 8.47 9.01 9.67 10.4 11.4 12.4
4 | Tc (°C) 37.0 38.4 40.5 43.2 46.2 49.5 52.8
43 1 | P frigorifique (Watt) 856 1409 2012 2663 3359 4105 4927
2 | P absorbée (W) 1220 1585 1967 2376 2821 3309 3841
3 | I absorbée (A) 7.73 8.31 8.96 9.70 10.6 11.5 12.6
4 | Tc (°C) 46.5 47.8 49.8 52.2 55.0 57.9 60.8
1 = cooling capacity 2 = power input 3 = current 4 = condensing temperature 5 = ambiant temperature 6 = evaporating temperature
Nota : Tecumseh se réserve le droit de modifier les informations contenues dans ce document sans préavis.
Note : Tecumseh reserves the right to change information contained in this document without notification.
Page 2/3
FHT2511ZBR-XC Tension XC : 220 - 240V 1~ 50 Hz
50 Hz R449A (*)
N°User-159
5 | T ambiance 6 | T évaporation (°C) -30 -25 -20 -15 -10
25 1 | P frigorifique (Watt) 2437 3283 4249 5325 6496
2 | P absorbée (W) 1738 2056 2400 2778 3203
3 | I absorbée (A) 7.77 8.38 9.10 9.94 10.9
4 | Tc (°C) 31.9 34.0 36.5 39.5 42.9
32 1 | P frigorifique (Watt) 2078 2864 3762 4765 5862
2 | P absorbée (W) 1717 2064 2439 2849 3305
3 | I absorbée (A) 7.71 8.40 9.19 10.1 11.1
4 | Tc (°C) 38.0 40.0 42.4 45.2 48.5
43 1 | P frigorifique (Watt) 1518 2207 2998 3889 4873
2 | P absorbée (W) 1630 2024 2449 2912 3420
3 | I absorbée (A) 7.46 8.28 9.18 10.2 11.3
4 | Tc (°C) 47.6 49.5 51.7 54.2 57.2
1 = cooling capacity 2 = power input 3 = current 4 = condensing temperature 5 = ambiant temperature 6 = evaporating temperature
(*) Veuillez vous référer strictement aux Recommandations d’Utilisation et Bulletins Marketing Tecumseh du fait de la température de refoulement élevée pour les applications LBP.
(*) Due to very high discharge temperature especially on LBP conditions, please strictly refer to Tecumseh Guidelines & Marketing Bulletin when using this refrigerant.
Nota : Tecumseh se réserve le droit de modifier les informations contenues dans ce document sans préavis.
Note : Tecumseh reserves the right to change information contained in this document without notification.
Page 3/3