MV Cable
MV Cable
CONSIDERATIONS:
Transformer Parameters:
A sample calculation has been done below for minimum cable size required for a motor feeder for the specified
short circuit rating. As per IEC 60364-5-54, Clause No.543.1.1,
S = (Isc x √t) / K
Where, S: Cross sectional area, in Square milimeters
Isc: Value (a.c. rms) of fault current for a fault of negligible impedance, which can flow through the protective device in amperes.
t: operating time of the disconnecting device, in seconds.
K: factor depend on the material of the protective conductor.
Transformer Running Voltage Drop (%) = L *Sqrt(3) * IFL( R cosφr+X sin φr)
(VL-L/100)* 1000 *No.of runs
= 0.12 %
Hence, the Selected Cable Size is 3.6/6 (7.2)kV, 1RX3Cx185 sq.mm, (2XFY) XLPE, Flat Armoured,Copper cable
SYSTEM PARAMETERS
Nominal System Voltage kV 11
System Configuration - Ring Main
Connected Load MVA 9.35
Demand Load
Power Factor (pf)
MW
p.u 0.85
5
MV CABLE SIZING
Demand Ring Load Current (I) Amp 309
Ring Length (L) km 1.575
Maximum Permissible %Voltage Drop % 3.5
DERATING FACTORS
Method of Cable Installation The cable shall be buried directly underground at an average depth of 1000 ~ 1100mm in trefoil configuration.
Ground Temperature Correction Factor 0.83 Assuming a ground temperature of 500 C
Depth of Laying Correction Factor 0.96 Assuming a burial depth of 1100 m
Soil Thermal Resistivity Correction Factor 0.77 Assuming dry soil with thermal resistivity of 2.0 K.m/W
Cable Grouping Correction Factor 1.0 Only applicable to multiple circuits
Harmonic Current Correction Factor 1.0 Assuming a third harmonic content of less than 15%
Total Cable Current Derating Factor 0.61
CABLE SIZING
Cable Voltage Grade 8.7/15 kV
Cable Construction 1 x 3 Core Cu/XLPE/SWA/XLPE 3 x 1 Core Cu/XLPE/AWA/PVC 3 x 1 Core Al/XLPE/AWA/PVC
2
Cable Size (S) mm 185 240 300 185 240 300 300 400 500
Cable Resistance (R ) ohm/km 0.128 0.098 0.079 0.127 0.098 0.078 0.13 0.102 0.08
Cable Reactance (X) ohm/km 0.1 0.09 0.09 0.12 0.11 0.11 0.11 0.11 0.1
Rated Current Carrying Capacity Amp 383 436 481 405 463 516 405 454 507
Derated Current Carrying Capacity Amp 235 268 295 248 284 317 248 279 311
Voltage Drop Volt 136 110 96 144 119 105 142 122 102
%Voltage Drop % 1.24 1.00 0.88 1.31 1.08 0.95 1.29 1.11 0.92
Short Circuit Current Rating for 1 sec kAmp 45 47
Short Circuit Current Rating for 3 sec kAmp 25 28
SELECTED CABLES
300 mm2 3 x 1 Core Cu/XLPE/AWA/PVC
500mm2 3 x 1 Core Al/XLPE/AWA/PVC
The two selected cables (highlighed in green) satisfy the requsite current carrying and volatge drops demands of the envisaged system and also provide short circuit current
capability equal to or beyond the 25 kA rating of 11kV feeder switchgear.
MEDUIM VOLTAGE CABLE SIZING
1- Assumptions:
1.1 Minimum cable size for Meduim Voltage feeders is 50 sq.mm
1.2 Circuit breaker tripping time on short circuit is 200ms.
1.3 Constant reflecting conductor material constant and temperature rise during
short circuit condition is 143 for XLPE.
1.4 As per client requirement, cable sizes above 185 sq.mm shall be single
core installed in trefoil.
1.5 Starting current for medium voltage motors are equals to 5 times the full load current.
2- References:
2.1 Electrical design basis specification no.. 24613-200-3DR-E12F-00001.
2.2 PIRELLI Cables catalogue for 300V-33000V cables
3- Calculations
3.1 Medium Voltage Cable size based on short circuit current check:
Table below reflects the designed cable sizes for diffirent effective short
circuit current values.
3.2 Medium Voltage cable size based on current carrying capacity check:
Table below reflects the designed cable sizes based on the maximum
premissible current through the MV cable after consideration of de-rating factor.
b) Table below reflects the designed cable sizes based on the maximum
premissible voltage drop for the medium voltage motor feeders.
ETEC
'
.-ah.--, ..
S
Men by awayéaaéa
How to Select an Electric Cable
AuLhor’s name; R. Hardie
Page 2 of 26
to
I Voltage
I Distance to load
I Fault current:
I Mechanical Conditions:
- Sheath requirements.
, - - 1<W><1@@@ -
X/3x Voltage x Cos ®
Q1‘ I 3 P P
KVA
;_;.___..
x W1000
.__a.<—~— ~
(/3 X Voltage
Horsepower X 0.746 X 1000
or I --~ ~
0 J3 XVo1tage Xcose
EXAMPLE:
= 19 Volts (Excellent)
T ‘m 1-\;-3 ‘_E'7j) Vi-(}‘§-c'_¢{_
-r.‘-', ‘-"?‘.l7""'-.'-'¥’-F
5
I'irEP§;l;'*§.';‘Yf-' -3.21..-
OQLES
f-‘owe rrach E}
How to Select an Electric Cable
Author‘s name: R. Hardie
Page 6 of 26
CURRENT RATING AND VOLTAGE DROP OF 3 AND 4 CORE PVC INSULATED CABLES WITH
STRANDED COPPER CONDUCTORS
_ — ——~ ~ __. —* -
, 4 ) 5,52 l 38 31 32 1 9,561
6 6,69 I 46 l 39 A 40 3 6,691
10 ‘ 2,19 64 I 52 54 ; 6,796
_7 _ J __ _____ ._
16 1,38 1‘ 62 A 67 ;\ 72 , 2,690
._ _2-=‘— —
l l
._ if _
70 *2; i
1
.,r
0,6625
*7’. A AA» L
‘ .2
215 175 , 207 l 0,576
l
A 95 0,2460 257 210 256 0,427
(
1
_
120
_, _.. .
0,2012 292 239 296 0,646
l
150 ~i 0,1698 328 269 gi 666 l 0,294
185 l 0,1445 669 , 303 664 l 0,250
ea‘, _ =__ Re J . as
240
__
\ 0,1220
_.__ _____
_ . 7
l
,i_ . _ __.
422__
_ _
7 7, _ l
2__
348 , 447 , 0,211
300 0,1 090 472 397 509 l 0,189
. _ ’__ .__. "1 __,_l W. ___, . . , , _l
6
72>",-:52 2*?”-6.1165
OQLES
'1?-’owert.ech L1
How to Select an Electric Cable
Author's name: R. Hardie
Page 7 of 26
CURRENT RATING AND VOLTAGE DROP OF 3 AND 4 CORE PVC INSULATED CABLES WITH SOUD
ALUMINIUM CONDUCTORS
, , oaouno pucr ‘ lT
AIR 1
TTT T T T TTT’ K’ T W 1 T’ T" T H T ‘ ' W T T ' T P T TTT’ T T T" T,’ Tl
l
1 25 1,4446 98 79 88 6 2,502
35 1 1,0465 119 95 108 1,813
1 _, _ 6: —— :_ ~ _._ "7 __
l
, l
95 . 0,6964 1 204 165 201,__. 0,681
, _t\_ T T TTTT” T 7* l TOT” _ __ ,l_ _ ___ W H , _ W.
l‘ ‘
,_‘
.24
120 0,6146 235 189 264 l 0,545
l
_ — [ — ———— ___ — —— —‘ 7 ——
T_ T621100"
,__._..._
7 0,1706 0 l
,_ _. __,______,/I ,_ H _
340 278 A T T 662T T l T0,296‘T T.‘
1-
(
lf the distance was 200 metres, then volt drop would have
been:
" 8
016155
P01-VBr'i'8Ch 1:?
How to Select an Electric Cable
Author s name R. Hardie
Page 9 of 26
lLl
CALCULATION VOLTDROP
.r"""{' 1
22.2
22>-I-E—— ';"'f>~i3t.':»
You must use this method with caution if you are close to the
grew
W 10
0151.55
6; Powe-rte h L
How to Select an Electric Cable
Author’s name: R. Hardie
Page 11 of 26
5% x 400V x 1 000mV/V
------------------------------ = 4,17mV/A/m
480A x 10m
But this cable cannot carry 160A required full load current!
1 -
r;.Ztt2et..".a2i@=~4
046155
1. Powerteclt L3
How to Select an Electric Cable
Author's name: R. Hardie
Page l3 of 26
CAIBLES
Powertech E3
How to Select an Electric Cable
Author’s name: R. Hardie
Page l4 of 26
Grouping of PlLC cables in Horizontal Formation at standard depths of laying and in standard
soil conditions (multicore cables).
1 In l “
group
24 .
2
A
0,80
22-.-. 2,2,, l
0,85 0,89 0,90 0,92 0,88 0,91 ; 0,96
_ ,_,,_ 12,.
0,94
,A 3 ) 0,69 0,75
..l
0,80 0,84 1 0,66 0,80 0,84 0,67 0,89
4 0,63 0,70 0,77 0,80 0,64 0,75 0,81 0,64 0,87
5 0,57 0,66 i 0,76 0,76 0,61 0,71 0,77 0,62 0,65
6 .
0,55 0,63 0,71 0,76 0,80 ; 0,69 0,75 , 0,60 0,64
Ground Temperature derating factors
‘ 25 A 30 35 40 45
1 1,00 0,95 0,90 0,65 0,60
Air Temperature derating factors
25 60 40 45 "
L
1,10 1,00 0,94 0,67 T 0,79
.
0581.55
Powe rtech U
How to Select an Electric Cable
Author's name: R. Hardie
Page 15 of 26
_§i_2PE_I.NS,Ul_:_ATED,__QABLE§_
A C3 1,08 1,12
2,0
2224.
0,80 I 0,85
1lT T T an-1‘
I 2,5 0,72
l
0,80
3,
ll
ll
it
, 3,0 l 0,66 0,74
J.
15
5.2»
r.-.~ Powertech E3
How to Select an Electric Cable
Autl1or’s name: R. Hardie
Page 16 of 26
Grouping of XLPE cables in horizontal formation at standard depths of laying and in standard
soil conditions (multicore cables).
if —— — _ —_ ;_ 7 — 2
f Touching A
————— — — 7 — — — — —— — .2
250
22 222222222
A 700
. "<72 *2 22 fie 2.22
I Touching —— .22 —— — 2 —— _ ‘ 47
250 W7
l 700
F
TIT l
l
‘‘ 2 0,79 0,85 A 0,67 0,67 0,91 A 0,93
A
l l
3
_2
I 0,69
_:2.2 .
Al 0,75
2 2.2222. 2. ..
I
.22
0,79
22
iAf
L2 2
0,60 .2. l2
0,86 0,91
4 0,66 l 0,66 0,75 0,75 0,80 0,87
» 5 0,56 0,64 A 0,72 * 0,72 E 0,78 I 0,86
6 0,55 0,60 0,69 I 0,69 0,74 0,66
25 A 60 65 40 45 l
l
1 .
T’)
1,0 0,96 0,92 0,66 0,84
16
OBLES
tr; Powerteclt E;
How to Select an Electric Cable
Author’s name: R. Hardic
Page 17 of 26
_ 17
til" '3'"- at~1.:
3.. Id“ -gt’!
git-,\
r--»-=
w ?ov-rertech ll}
How to Select an Electric Cable
Auth0r’s name: R. Hardie
Page 18 of 26
Derating factors for grouping of cables in horizontal formation, at standard depths of laying
and in standard soil conditions. Multicore cables (up to
300mm?)
_, ffl i ,_ ffi, rrfeiee ___,_,,,,*, W W ,_ ,1 _ _____, 1 99*, __ i
5 0,59 0,70
_
0,78 l
0,88 ‘ 0,87
— ,1 ____;, 7 — 4
0,75 § 0,82 0,87 I 0,90
‘F l l 77
25 30 35 40 I
18
.rf§“"§ "*8 ~'.'t‘e.E.-8
OIBLES
‘;. \ . .-»\. '1:. ,- Powertech [.3
How to Select an Electric Cable
Author’s name: R. Hardie
Page 19 of 26
No of cables 1 I 2 I 3 I 6 j 9
gar . . !;;;z.'-.-A
CFBLES
FAULT CURRENT
This topic is normally very important with higher voltages than
LV.
115X70 = 8,05 kA
lsc = ---------
~11
If the protection is fast, (say 0.2 seconds) then the conductor
will have a 0.2 second short circuit rating of:
115x70 = 18 kA
1/0.2
EARTH FAULT CURRENT
If the phase conductor comes into contact with the earth conductor
(lead sheath, copper tape or armour) then we must ensure that this
earth conductor can survive the resulting fault current.
Again the formula is lei = KxA
1/1
Where K Depends on the earth path material. (Steel wire
armour (K=42), lead sheath (K=24), copper tape
(K=143) or Aluminium wire armour (K=76)
A = Cross-sectional area of earth path.
t = Fault duration in seconds.
_:,i-1i!’:!7'T€];‘I’l-a-l‘_'?-2:’-‘_";;1
/=’;I:rf,:'a;’.t‘se.-£85-lat;
0181.55
-,= -»= Powertech L‘;
How to Select an Electric Cable
Author’s name: R. Hardie
Page 22 of 26
250 MVA 3’
Isc \f3x11000
13.137kA
This cable will not survive the prospective short circuit current of
13 137 A.
v’8><11000
= 5254 A
\_
F ‘ _ fg _ Al _, . PL/i,Q_L/,_J,.. 8/~»Cr-—1~<~2»,I“
10 21-PIA. M v’ A/‘~’l'*(’~*" 1 “ft
24
OBLES
~r -1 Fowertecl1L';
How to Select an Electric Cable
Author s name: R. Hardie
Page 25 of 26
Area x K lead
Cable earth fault current withstand is = ------------------
~/0.5
200 x 24
10.5
m 6 800 A (for 0.5 second)
This cable will survive the prospective earth fault current of 5 254 A.
25
OBLES
.- 1:; Powertech £3
How to Select an Electric Cable
Author’s name: R. Hardie
Page 26 of 26
BENDING RADIUS 1
7 -»~r cur"
-u
o
z"7*§§'i;§h‘¥a'r;.-z‘3it:'§.t‘§
CHBLES
2." .1‘ -. *. '=. Powerrech Ill‘
Medium Voltage Cables Grid Substation Construction Projects
1. INTRODUCTION
This document provides the 33 kV medium voltage cable sizing calculation for the Sri Jayawardenapura Grid
Substation. The cable calculations are done as per the IEC standards.
SYSTEM PARAMETERS
(a) Nominal Voltage 33 kV
(b) Maximum Continuous Voltage 36 kV
(c) System Frequency 50 Hz
(d) Method of Earthing Effectively
(e) System fault current 25 kA
(f) Fault duration 1s
SERVICE CONDITIONS
(a) Annual Average Ambient Temperature 30 oC
(b) Maximum Ambient Temperature 40 oC
(c) Maximum relative humidity 90 %
(d) Maximum Short time temperature of the 250 0C
conductor
(e) Cable laying method Direct Burried
(f) Environmental conditions Humid tropical climate with polluted atmosphere
(g) Operational altitude From M.S.L. to 1900 m
(h) Average ground temperature 30 oC
(i) Depth of laying 1.1m