Journal Electronics 2
Journal Electronics 2
Journal Electronics 2
[email protected]
3 BEARS, University Town, NUS Campus, Singapore 138602, Singapore
4 Department of Electrical Engineering, College of Engineering, King Saud University, Riyadh 11421,
Saudi Arabia
* Correspondence: [email protected] (H.M.); [email protected] (M.A.A.)
Abstract: This paper presents the stability improvement of the three-phase four-wire (3P-4W) grid-
tied PV-hybrid energy storage system (HESS) using chaotic grew wolf optimization (CGWO) for
DC bus voltage (𝑉 ) and AC bus voltage (𝑉 ) control. The CGWO tuned fractional order pro-
portional–integral (FOPI) controllers reduce the 𝑉 and 𝑉 variations during diverse, dynamic
conditions, i.e., sudden irradiation variations, deep voltage sag/swell, etc. The DC bus is responsible
for the current injection/extraction control, maximum PV power extraction, bi-directional power
flow, dc second-harmonics component elimination, and active power balance. At the point of com-
mon coupling (PCC), the AC bus is accountable for bi-directional power flow and active and reac-
tive power control. The two-level voltage source converter (VSC) is controlled by a novel variable
Citation: Chankaya, M.; Hussain, I.; step-size incremental least mean square (VSS-ILMS) in zero voltage regulation (ZVR) mode. Due to
Ahmad, A.; Malik, H.; Alotaibi, M.A. its varying step size, VSC control is less prone to noise signals offers better stability, improved con-
Stability Analysis of Chaotic vergence rate, dc offset rejection, and tracking speed during dynamics, i.e., large oscillations. A bat-
Grey-Wolf Optimized Grid-Tied tery and ultracapacitor are coupled to the DC link by buck-boost converters in the HESS. To regulate
PV-Hybrid Storage System during
power transit between the DC bus and the grid, the HESS current control technique is designed to
Dynamic Conditions. Electronics
shift frequently from charging to discharging stage and vice versa. The novelty of the PV-HESS
2022, 11, 567. https://doi.org/10.3390/
system lies in CGWO tuned VSS-ILMS control of VSC, which effectively and efficiently filter out
electronics11040567
the active fundamental constituents of load current and eliminate dc offset from VSC output. The
Academic Editor: Zbigniew HESS control maintains the DC bus voltage profile by absorbing and delivering energy (during
Leonowicz dynamic conditions) rather than curtailing it. The presented system is simulated in a MATLAB/SIM-
Received: 30 January 2022 ULINK environment. The simulation results in graphical and numerical forms verify the stable and
Accepted: 11 February 2022 satisfactory operation of the proposed system as per IEEE519 standard.
Published: 13 February 2022
Keywords: PV power generation; DC bus stability; power electronics; power quality; adaptive con-
Publisher’s Note: MDPI stays neu-
trol; hybrid energy storage system; chaotic grey wolf optimization; optimization techniques
tral with regard to jurisdictional
claims in published maps and institu-
tional affiliations.
1. Introduction
Nowadays, photovoltaic (PV) power generation is widely acclaimed due to its scal-
Copyright: © 2022 by the authors. Li- able nature and less initial investment than wind energy systems [1]. The grid-tied PV
censee MDPI, Basel, Switzerland. systems offer generation diversification, peak shaving capability, improved reliability, re-
This article is an open access article
duced ancillary reserves, improved voltage profile, and reduced transmission losses, etc.
distributed under the terms and con-
Moreover, grid-tied PV systems as distributed generators (DG) lessen the impact of cyber-
ditions of the Creative Commons At-
attack improve power utility security while delivering the critical load [2,3]. In India, the
tribution (CC BY) license (https://cre-
total installed capacity of renewable energy sources (RES) is 103 GW by 2021 (excluding
ativecommons.org/licenses/by/4.0/).
hydropower), in which PV installation is 40%. The total RES installed capacity is expected
to grow up to 450 GW by 2030 with a 60% share of PV power (280 GW) [4]. Due to the
cost-effectiveness, fewer space constraints, compact size, and ready availability make the
grid-tied PV systems suitable for both utility-scale and rooftop plants.
The penetration of RES is increasing day by day in the modern grid to match the
energy requirements, which raises many technical issues to be managed before delivering
PV power to the grid [5,6]. Considering the cost of PV arrays in PV power generation
systems, it is highly desirable to operate them at the highest efficiency. Maximum power
point tracking (MPPT) algorithms are utilized for the same. In [7,8] many conventional
and artificial intelligence (AI) based MPPT algorithms are given. The transformer-less PV-
HESS grid integration is more economical and efficient. However, dual-stage configura-
tion with DC–DC boost converter is best suited for enhanced DC bus stability rather than
using single-stage configuration [9,10]. Several technical challenges related to grid inte-
gration of PV systems involves designing and control of voltage source converters (VSC),
voltage and current harmonics, active and reactive power control, voltage and frequency
deviations, stability, power balancing at DC and AC bus, weak grid conditions, PV power
fluctuations, bi-directional power flow, lower efficiency, reliability issues, etc. [11,12]. For
the satisfactory and healthy operation of grid integration of PV system and to deliver PV
power to the grid, technical complications, i.e., stability and power quality issues, must
be dealt with.
The stability of the grid-tied PV system significantly relies on DC bus and AC bus
stability. The DC bus plays an essential role in managing bi-directional power flow, active
power balance, maximum PV power extraction, reducing PV power fluctuations, gener-
ating active loss component of current, etc. [13,14]. At the point of common coupling
(PCC), the AC bus manages bi-directional active and reactive power flow, islanding de-
tection, low voltage ride through, reactive power compensation, etc. In the case of grid-
following converters, the PCC voltage is very much dependent on the grid, which reduces
the burden of the AC bus and leaves it with mainly reactive power control [15].
The PI controllers generally control the dc and ac buses due to their simple design
procedure, good performance, less computational complexity, and ease of tuning [16,17].
Much artificial intelligence (AI), i.e., fuzzy logic and neural network-based controls, have
also been utilized for proportional–integral (PI) controller gain tuning, which increases
the system’s complexity [18,19]. Many metaheuristic optimization techniques (MOTs)
have been implemented in an offline mode to deliver optimal gains of the PI controller
[14,20–23]. The fractional-order PI controller offers enhanced performance than the PI con-
troller due to its non-integer integral gain. The gains of fractional-order PI (FOPI) can be
obtained by using MOTs, i.e., salp swarm optimization (SSO), chaotic grey wolf optimi-
zation (CGWO), and many more [20,23]. The increased tuning parameter as non-integer
integral gain increases the system’s robustness to deliver optimal control, better system
response, and power quality [24–26]. The FOPI controlled DC bus and AC bus reduces
the initial transients and dynamic variations of the DC bus (𝑉 ) and AC bus voltage
magnitude (𝑉 ) to a greater extent and performs significantly better than the PI control-
ler. Table 1 presents the optimization technique for parameter optimization in a grid-tied
system
The HESS consists of static storage devices (i.e., battery, ultracapacitor (UC), fuel
cells), which have a shorter response time to any system dynamics than the compressed
air storage system (flywheel storage, etc.) [14,20]. Energy storage systems with faster re-
sponse times are suitable for handling sudden, sustained, and prolonged disturbances,
i.e., fault, load variations, and voltage sag/swell.
Electronics 2022, 11, 567 3 of 23
Operational Operating
Ref Optimization Technique Objective DG Used
Mode Conditions
𝑉
regulation, filter pa-
[13] Jaya optimization Solar PV Grid-Tied Load unbalancing
rameter estimation
[14] GNDO 𝑉 regulation Solar PV-HESS Grid-Tied Weak grid weak
[15] Fuzzy logic 𝑉 , 𝑉 regulation Solar PV Grid-Tied grid
[18] Fuzzy parameter optimization 𝑉 regulation Solar PV Grid-Tied PF correction
[20] SSO 𝑉 regulation Solar PV-HESS Grid-Tied Weak grid
[21] MRFO, GWO, WO, GHO, ASO 𝑉 , 𝑉 , MPPT regulation Solar PV Grid-Tied Insolation change
[22] Taylor approximation 𝑉 regulation Solar PV Grid-Tied Unstable control
The power quality issues, i.e., voltage and current harmonics suppression, should be
seriously considered while designing the VSC controls. Various advance control algo-
rithms have been used to reduce the total harmonics distortion (THD) level well below
5% as per IEEE 519 standard and perform multi-functional operations. Time-domain con-
trols, i.e., synchronous reference frame (SRF), power balance theory (PBT), etc. [27,28],
have been widely used due to their ease of implementation, fairly adequate performance,
and less computational burden. The time-domain control does not perform well under
transients, delivers a low convergence rate during dynamic conditions, and achieves
multi-functional operations. The frequency-domain controls, i.e., wavelet and Stockwell
transform algorithms, offer better filtering capability but at the cost of higher computa-
tional burden and slow convergence rate [29,30]. The adaptive controls, i.e., least mean
square (LMS), least mean fourth (LMF), etc., come up with ease of implementation and
with slightly higher complexity in comparison to time-domain controls [16,17]. The LMS
algorithm uses a fixed step size for adaptation to find the balance between the conver-
gence equation and maladjustment error results at low-convergence speed and more sig-
nificant steady-state oscillations. The LMF algorithm acts as a higher-order adaptive filter
for better MSE reduction with a fixed step size. Due to the fixed adaptation size, efficiency
reduces during abrupt dynamic changes. The above-mentioned adaptive algorithm has
inspired many derivatives of these controls, i.e., variable step-size LMS (VSS-LMS), de-
layed LMS (DLMS), median LMS (MLMS), hyperbolic cosine LMS (HCLMS), combined
LMS-LMF, etc. VSS-LMS [31] offers reduced steady-state error, but its performance re-
duces during significant dynamic changes. DLMS [32] is similar to LMS, introducing a
delay factor in the unit template for better weight generation. MLMS [33], with an addi-
tional scaling factor other than step-size, improves the noise cancellation. HC-LMS [34]
offers a better convergence rate during dynamic conditions than LMS. Combined LMS-
LMF [35] shifts control from LMS to LMF (higher-order filter) depending on the magni-
tude of the error. Variable step-size incremental LMS (VSS-ILMS) [36] is a new addition
to the derivatives of the LMS algorithm, which offers better filtering capability against
noise signals in the sparse environment due to its incremental nature of adaptation step.
The main objective is to present a stable grid-tied PV-HESS with low voltage ride-
through capability during fragile grid conditions. The DC and AC bus voltages are stable
even during deep voltage sag/swell conditions. The power quality of the system remains
intact with CGWO tuned FOPI controllers. The novelty of the presented work lies in VSS-
ILMS based VSC control that performs multi-functional operations, including power and
load balancing, active and reactive power control, power quality enhancement, dc offset
removal, etc. The CGWO tuned FOPI controlled DC, and the AC bus also stabilizes the
system during deep voltage sag/swell conditions.
This paper is organized in the following manner: Section 2 presents the general de-
scription of the system and topology implemented; Section 3: illustrates the implemented
research methodology; Section 4: gives the detailed explanation of implemented control
algorithms, including, 𝑉 and HESS control and VSS-ILMS based VSC control. Section
Electronics 2022, 11, 567 4 of 23
5: Simulation results are presented and discussed in detail to show the efficacy of the pro-
posed work; Section 6: Conclusion of the presented work is given.
2. System Description
Figure 1 shows the topology of the proposed system. The presented system is a three-
phase four-wire (3P-4W) grid-tied PV-HESS. The PV array of 32 kW is connected to the
DC bus via a DC-DC boost converter to stabilize PV voltage (𝑉 ) during irradiation var-
iation. The MPPT is achieved by using the incremental conductance (InC) method. The
HESS involving battery and UC is also attached to the DC bus via a bidirectional DC-DC
buck-boost converter to control the charging and discharging operation.
RS & LS
IBat
Rs Lb Sb1
Multi-Objective Chaotic Grey
Vdc Wolf Optimization VPCC iSa iSb iSc
Cp Rp Sb2 Optimized Optimized Vterr
Verr
B - gains gains - iSn
FOPI FOPI
Buck-Boost Converter and Battery + Control Control +
Three-Phase Four-Wire AC
SUC1 Grid 415V at 50Hz
RUC LUC IUC
to VSC Control
SUC2 PCC Voltage Control
CUC
Sb1 & Sb2 +
Buck-Boost Converter and UC Control PI IBat
PWM -
Control &
SUC1 & SUC2
Control
IUC
Bidirectional Buck-Boost Converter Control
The two-level VSC is attached to the PCC via interfacing inductors and R–C filters to re-
duce the current and voltage ripples produced due to VSC switching. The grid at 415 V,
50 Hz is also attached to the PCC.
The primary characteristics of the presented work are as follows.
a. Smart grid-tied PV operation: The grid-tied PV system performs satisfactorily in three
modes: (1) PV to grid mode, (2) PV-DSTATCOM mode, (3) PV-DSTATCOM to
DSTATCOM, and vice versa mode.
b. Dynamic state operations: The presented system is observed under weak grid condi-
tions like load unbalancing and deep voltage sag/sell condition, i.e., 20%, 40%, and
60%, respectively.
c. Multi-functional operation: The proposed system performs multiple operations, i.e.,
load balancing, harmonics elimination, active and reactive power control, etc.
d. DC and AC bus stability performance: The DC and AC bus control is provided by
CGWO tuned FOPI controller to stabilize the system during dynamic conditions.
e. HESS: The HESS ensures continuous supply to critical load and enhances the system’s
power quality by suppressing the second-harmonics content at the DC bus.
Obj– 1 = (𝑉 ∗ – 𝑉 ) = (𝑉 ) (1)
Obj– 2 = 𝑉∗ – 𝑉 = (𝑉 ) (2)
NO
Termination criteria
D ecision Phase
satisfied
YES
Stop
𝑃 0≤𝑝 ≤𝑎
⎧ ⎫
⎪ 𝑎 ≤ 𝑝 ≤ 0.5 ⎪
.
𝑃 = (3)
⎨ 0.5 ≤ 𝑝 ≤ 1 − 𝑎⎬
.
⎪ ⎪
⎩ 1−𝑎 ≤𝑝 ≤1 ⎭
𝐷 ⃗ = 𝐶⃗ × 𝑝 ⃗ − 𝑝⃗ , 𝐷 ⃗ = 𝐶⃗ × 𝑝 ⃗ − 𝑝⃗ , 𝐷 ⃗ = 𝐶⃗ × 𝑝 ⃗ − 𝑝⃗ (4)
𝑝 ⃗ = 𝑝 ⃗ − 𝐴 ⃗ × 𝐷 ⃗, 𝑝 ⃗ = 𝑝 ⃗ − 𝐴 ⃗ × 𝐷 ⃗, 𝑝 ⃗ = 𝑝 ⃗ − 𝐴 ⃗ × 𝐷 ⃗ (5)
4. Controlling Strategies
The proposed system is controlled by mainly three controls, which are (1). Incremen-
tal conductance (InC) based MPPT control. (2). DC bus and HESS current control and (3)
VSS-ILMS based VSC control.
𝜇 = = , where x = a, b, c
(9)
The 𝑊 , where x = a, b, c are calculated for each phase as a function of the error
signal and incremental step-size (𝜇 (𝑖 + 1)) as per (10) and (11).
𝑊 (𝑛 + 1) = 𝑊 (𝑛) + 𝜇 (𝑖 + 1) × 𝜇 ×𝑒 ; where x = a, b, c (10)
𝜇 (𝑖 + 1) = 𝛼 × 𝜇 (𝑖) + 𝛾 × 𝑒 (𝑖) (11)
The overall direct weight signal (𝑊 ) is calculated as a function of average weight
components (𝑊 ) and feed-forward term (𝑊 ) as per (12)–(15).
𝑊 = = (12)
𝑊 = 𝑊 +𝑊 +𝑊 (13)
𝑊 =𝑊 −𝑊 (14)
𝑖∗ =𝑊 ×𝜇 where x = a, b, c (15)
For the quadrature weight component generation (𝑊 , where x = a, b, c), error signals
(𝑒 , where x = a, b, c) are calculated as per (16). The quadrature-phase components
(𝜇 , where, x = a, b, c) is calculated as a function of in-phase components as per (17).
𝑒 = 𝑖 (𝑛) − 𝜇 × 𝑊 (𝑛), where x = a, b, c (16)
Electronics 2022, 11, 567 9 of 23
√ ∗ √ ∗
𝜇 = ; 𝜇 = + ;𝜇 =− + (17)
√ √ √
The 𝑊 , where x = a, b, c are calculated for each phase as a function of the error signal
and incremental step-size (𝜇 (𝑖 + 1)) as per (18) and (19).
𝑊 (𝑛 + 1) = 𝑊 (𝑛) + 𝜇 (𝑖 + 1) × 𝜇 ×𝑒 ; where x = a, b, c (18)
𝜇 (𝑖 + 1) = 𝛼 × 𝜇 (𝑖) + 𝛾 × 𝑒 (𝑖) (19)
The overall direct weight signal (𝑊 ) is calculated as a function of average weight
components (𝑊 ) and 𝑖 as per (20)–(22).
1
𝑊 = 𝑊 +𝑊 +𝑊 (20)
3
𝑊 =𝑊 −𝑖 (21)
𝑖∗ =𝑊 ×𝜇 where x = a, b, c (22)
∗
The overall reference current (𝑖 , where x = a, b, c) is generated by doing the sum of
∗
𝑖 and 𝑖 ∗ as per (23).
𝑖∗ = 𝑖∗ + 𝑖∗ where x = a, b, c (23)
∗
The 𝑖 , where x = a, b, c are delivered to the hysteresis current controller (HCC) for
VSC switching signal generation.
300 40
Signal
10
iL a (A )
iS a (A )
v S a (V )
0 0 0
-40 -10
-300
0.12 0.13 0.14 0.15 0.16 0.17 0.18 0.19 0.2 0.21 0.1 0.12 0.14 0.16 0.18 0.1 0.12 0.14 0.16 0.18
FFT analysis
Time (s)
FFT analysis
Time (s) FFT analysis
Time (s)
100 100 100
Grid Voltage (V) = 339V, Load Current(A) = 18.16A,
Source Current (A) = 43.36A,
THD= 1.13% at 50Hz THD= 39.62% at 50Hz
v S a(V )
iL a(A )
iS a (A )
0 0 0
0 200 400 600 800 1000 0 200 400 600 800 1000 0 200 400 600 800 1000
Frequency (Hz) Frequency (Hz) Frequency (Hz)
(a) (b) (c)
Figure 6. (a–c). THD analysis of 𝑣 , 𝑖 , and 𝑖 .
Table 2. THD comparison of 𝑣 , 𝑖 , 𝑖 with the PI and FOPI controllers tuned by GA and
CGWO during steady-state.
Without
Quantity FOPI-CGWO FOPI-GA PI-CGWO PI-GA
Optimization
𝑣 1.13% 1.42% 1.33% 1.6% 1.62%
𝑖 2.94% 2.96% 3.12% 3.38% 3.56%
𝑖 39.62% 39.62% 39.62% 39.62% 39.62%
The VSC control of the above-described system was also compared with the other
adaptive controls to prove the better filtering capability of the implemented VSS-ILMS
control. Table 3 shows the THD performance of the grid with LMS, LMF, and VSS-ILMS
control. For this analysis, AC and DC buses were regulated by CGWO tuned FOPI con-
troller.
Table 3. THD comparison of 𝑣 , 𝑖 , 𝑖 with VSS-ILMS, LMF, and LMS-based VSC controls.
300
0
-300
50
(A) i C n (A) i (A) i La (A) i C a (A) i Sabc (A)
0
-50
50
0
-50
20
0
-20
2
0
Sn
-2
20
0
-20
20
0
Ln
-20
V pcc (V) i
360
340
320
0.2 0.3 0.4 0.5 0.6 0.7
Mode1: PV to Grid Mode2: PV and Grid both Time(s) Mode3: PV-DSTATCOM to DSTATCOM
and vice versa
Figure 7. Smart PV mode analysis of 𝑣 ,𝑖 , 𝑖 , 𝑖 , 𝑖 , 𝑖 , 𝑖 , and 𝑉 .
Electronics 2022, 11, 567 12 of 23
Mode-2 operation was executed from 0.4 s to 0.5 s, where the irradiation level was
reduced from 1000 W/m2 to 600 W/m2 to confirm the combined operation of the grid and
PV system. With reduced irradiation level, the power delivered to the grid reduces, hence,
𝑖 also. Though 𝑣 and 𝑖 remained in phase opposition as PV power at the re-
duced insolation level was sufficient for load requirements. The 𝑖 and 𝑖 were in
phase opposition, canceling out each other at three times the fundamental frequency. The
𝑖 was maintained near zero, hence confirming the neutral current compensation.
Mode-3 is executed from 0.6 s to 0.7 s, during which the irradiation level is reduced
to zero. In the absence of PV power system shifts from PV-DSTATCOM to DSTATCOM
operation. At 0.6 s, the phase reversal of 𝑖 was observed, earlier 𝑣 and 𝑖 were
in phase opposition, but after 0.6 s, both came in phase with each other, confirming the
power supply from the grid to load. After 0.7 s, the irradiation level was again increased
to 1000 W/m2, due to which the system shifted from DSTATCOM to PV-DSTATCOM op-
eration. The 𝑉 magnitude was maintained at the desired level with the help of AC bus
voltage control.
Figure 8 shows the behavior of DC quantities during smart PV operations. The PV
voltage, current, and power (𝑉 , 𝐼 and 𝑃 ), battery and UC voltages and currents
(𝑉 , 𝐼 , 𝑉 , 𝐼 ) and DC bus voltage 𝑉 are shown as DC quantities of the system.
During Mode-1: The irradiation level is maintained at 1000 W/m2, where whole
power was delivered to the grid. The battery and UC start charging during mode-1, 𝐼
and 𝐼 became slightly negative and, 𝑉 and 𝑉 started increasing. The 𝑉 was
maintained at the desired of 700 V during PV to grid operation.
During mode-2: the irradiation level was reduced from 1000 W/m2 to 600 W/m2. The
𝑉 was kept at the fixed voltage level of 600 V, whereas 𝐼 and 𝑃 changed with the
reduced irradiation level. During this mode, both PV and the grid manage the load de-
mand. The 𝑉 was maintained at the desired level.
(kW) I (A) V PV (V)
600
0
80
40
PV
0
40
20
PV
0
(A)V Bat(V) I UC (A) V UC (V)P
400
390
380
10
0
-15
400
399
398
50
0
Bat
-50
V dc (V) I
720
700
680
0.2 0.3 0.4 0.5 0.6 0.7
Mode 1: PV to Grid Mode 2: PV and Grid both Time(s) Mode 3: PV-DSTATCOM to DSTATCOM
and vice versa
Figure 8. Smart PV mode analysis of 𝑉 , 𝐼 , 𝑃 , 𝑉 , 𝐼 , 𝑉 ,𝐼 , and 𝑉 .
Electronics 2022, 11, 567 13 of 23
During mode-3, the solar irradiation level reduced from 1000 W/m2 to 0 W/m2 result-
ing in the proposed system shifting from PV-DSTATCOM to DSTATCOM operation. The
𝑉 , 𝐼 , and 𝑃 became zero to simulate the absence of sunshine. The grid itself and
HESS charges managed the load slowly from the grid power. After 0.7 s system shifts from
DSTATCOM to PV-DSTATCOM operation without any significant transient on load and
grid side of the system. The 𝑉 was maintained at the desired level of 700 V, as shown
in Figure 8.
Figure 9 shows the active and reactive power flow of the grid side (𝑃 , 𝑄 ), load
side (𝑃 ,𝑄 ) and compensator side (𝑃 , 𝑄 ) during three modes of smart PV op-
erations. The reactive power delivered by the grid (𝑄 ) remained almost zero through-
out the smart PV operation as VSC gives the necessary reactive power to load, keeping
the reactive power exchange with grid minimum. The grid active power exchange (𝑃 )
changed with the mode of operation. During PV to grid mode, 𝑃 became negative as
the grid absorbed the active power. The load demand of active and reactive power became
zero as the load was disconnected during this mode. The compensator was converting DC
power to AC power and delivering to the grid, so the 𝑃 , 𝑄 was the same as
𝑃 ,𝑄 during mode-1.
(kW)
20
PGrid
Grid
0 Q Grid
/Q
-20
Grid
-40
P
(kW)
8
6
Load
4
/Q
2 PLoad
Load
0 Q Grid
P
(kW)
40
VSC
20
/Q
0
VSC
PVSC Q VSC
-20
P
at PCC and compensate reactive power. The load PF remained around 0.8 p.u. during
smart PV operation and load unbalancing, which changed slightly with the connection
and disconnection of load during PV to grid mode. Both VSC and grid PFs have the same
behavior. During PV-DSTATCOM mode, the grid PF reached –1 due to the reversal of
flow of power, and the earlier grid was absorbing, and then the grid was supplying.
0.5
Power Factor
-1
0 0.2 0.4 0.6 0.8 1.0
Time(s)
Figure 10. Power factor variations analysis during smart PV mode.
300
0
-300
50
0
-50
50
0
-50
20
0
-20
10
0
-10
20
0
-20
20
0
-20
360
340
320
0.75 0.8 0.85 0.9 0.95
Time(s)
Electronics 2022, 11, 567 15 of 23
On the DC side, 𝑉 , 𝐼 and 𝑃 showed no change and kept following their refer-
ences as irradiation level was kept fixed at 1000 W/m2. The 𝐼 and 𝐼 charging rate
increased slightly. The DC bus stability was preserved, and 𝑉 was maintained at 700 V
while following the 𝑉 ∗ . As shown in Figure 12. The PF and grid, load, and VSC power
are demonstrated in Figures 9 and 10.
V P V (V )
600
300
0
60
P V (k W ) I P V (A )
50
40
35
25
V U C (V ) P
400
395
390
10
U C (A )
0
V d c (V ) I B a t (A )V B a t (V ) I
400
399
398
50
0
-50
720
700
680
0.75 0.8 0.85 0.9 0.95
Time(s)
Figure 12. Load unbalancing analysis of 𝑉 , 𝐼 , 𝑃 , 𝑉 , 𝐼 , 𝑉 ,𝐼 , and 𝑉 .
whereas UC does not require high current protection, so the variation in 𝐼 was higher
than 𝐼 . The DC bus is crucial for the system’s stability; during deep voltage sag/swell
the 𝑉 variations were not very significant. The FOPI-based 𝑉 control along with VSC
control stabilized the DC bus quickly and did not allow a huge deviation from the refer-
ence point during extremely weak grid conditions.
Figure 15 shows the grid, load, and VSC active and reactive power performance dur-
ing abnormal grid voltage conditions (extreme weak grid conditions). With grid voltage
abnormalities, load active and reactive power requirements increased sharply. During
deep voltage, sag/swells reactive power demand increases rapidly, collectively managed
by the grid and VSC to maintain the healthy operation.
Figure 16 shows the PF variations of load, grid, and VSC side. The load weak grid PF
remained the same throughout the operation. With voltage sag and swell conditions, the
PF adjusted itself to new values depending on the phase variation with source currents.
The VSC PF complements the grid PF, but during deep voltage, sag/swell conditions PF
decreased to a shallow level confirming the growing demand for reactive power during
extreme weak grid conditions.
(A ) i C n (A ) i S n (A ) i L a (A ) i C a (A ) S abc v S abc (V )
300
0
-300
200
(A )
0
-200
i
200
0
-200
20
0
-20
10
0
-10
20
0
-20
20
0
Ln
-20
V p cc (V ) i
600
400
200
1 1.1 1.2 1.3 1.4 1.5 1.6 1.7
20% Voltage Sag/Swell Time(s) 40% Voltage Sag/Swell 60% Voltage Sag/Swell
700
(A) V PV (V)
600
500
60
PV
50
(kW) I
35
PV
25
(A)V Bat(V) I UC (A) V UC (V) P
450
400
360
150
0
-150
400
399
398
50
0
Bat
-50
V dc (V) I
750
700
650
1 1.1 1.2 1.3 1.4 1.5 1.6 1.7
20% Voltage Sag/Swell 40% Voltage Sag/Swell Time(s) 60% Voltage Sag/Swell
20
PGrid
10 Q Grid
-10
15
10
PLoad
5
Q Grid
Load
0
P VSC / Q VSC (kW) P
10
0
PVSC
-10
Q VSC
-20
1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9
40% Voltage Time(s) 60% Voltage Sag/Swell
20% Voltage Sag/Swell
Sag/Swell
Figure 15. Abnormal grid voltage analysis of 𝑃 ,𝑄 ,𝑃 ,𝑄 ,𝑃 , and 𝑄 .
Electronics 2022, 11, 567 18 of 23
0.5
Power Factor
-1
1.0 1.2 1.4 1.6 1.8 1.9
Time(s)
Figure 16. Power factor variations analysis during abnormal grid voltage conditions.
V without
800 V PI-GA
dc
dc V PI-CGWO
dc
V FOPI-GA
dc
V FOPI-CGWO
dc V*
dc
optimization
780 710
705
710
700 700
760 700 690
695
0.6 0.7 0.8 0.9 1.0 1.1
740 Load
20% voltage
Mode3: PV-STATCOM Unbalancing sag/swell
V dc(V)
720 to STATCOM
700
680 Mode1: PV to Grid Mode2: PV and
Grid both
660 705
705
0
(A)
PV mode 3 Unbalanced
10 Loading
-100
i
5
4 IdLoss during
0 2
40% Voltage sag/swell
-150 -5 0
0.2 0.3 -2
0.2 0.3
IdLoss during
-200 60% Voltage sag/swell
Without
Parameters CGWO-FOPI GA-FOPI CGWO-PI GA-PI
Optimization
Steady-state error 0.57% 1.26% 1% 1.14% 1.71%
Convergence speed 5 ms 7 ms 7.8 ms 11 ms 16 ms
Dynamic state transients (PV to grid mode) 1.12% 1.87% 2.12% 2.18% 2.42%
Dynamic state transients (Irradiation change) 0.10% 0.17% 0.14% 1.12% 1.12%
Dynamic state transients (PV-DSTATCOM-STATCOM) 0.13% 1.14% 1.29% 1.71% 2%
Dynamic state transients (Unbalanced load) 0.29% 0.43% 0.57% 0.85% 0.13%
Dynamic state transients (Voltage sag/swell 20%) 1.71% 2% 2.57% 3.14% 3.57%
Dynamic state transients (Voltage sag/swell 40%) 4.98% 5.42% 8.29% 8.56% 10.20%
Dynamic state transients (Voltage sag/swell 60%) 6.68% 6.56% 7.62% 9.52% 11.45%
Without
Quantity FOPI-CGWO FOPI-GA PI-CGWO PI-GA
Optimization
Mode1: PV to Grid mode
𝑣 1.35% 1.44% 1.49% 1.66% 1.66%
𝑖 1.94% 2.20% 2.12% 2.38% 2.53%
𝑖 39.62% 39.62% 39.62% 39.62% 39.62%
Mode2: PV and Grid mode during Irradiation Change from 1000 W/m2 to 600 W/m2
𝑣 0.97% 1.22% 1.35% 1.62% 1.65%
𝑖 6.23% 6.51% 6.70% 6.99% 7.22%
𝑖 39.62% 39.62% 39.62% 39.62% 39.62%
Mode3: PV-DSTATCOM to DSTATCOM and vice versa mode
𝑣 0.97% 1.22% 1.35% 1.62% 1.62%
𝑖 6.23% 6.22% 6.25% 6.37% 7.29%
𝑖 39.62% 39.62% 39.62% 39.62% 39.62%
Load Unbalancing
𝑣 1.2% 1.49% 1.35% 1.62% 1.62%
𝑖 4.01% 5.32% 4.80% 4.91% 5.10%
𝑖 39.62% 39.62% 39.62% 39.62% 39.62%
Voltage Sag of 0.8 p.u.
𝑣 1.61% 1.62% 1.61% 1.62% 1.62%
𝑖 0.83% 0.92% 1.12% 1.72% 2.12%
𝑖 39.62% 39.62% 39.62% 39.62% 39.62%
Voltage Swell 1.2 p.u.
𝑣 1.61% 1.61% 1.61% 1.62% 1.62%
𝑖 1.28% 2.16% 2.76% 3.15% 4.29%
𝑖 39.62% 39.62% 39.62% 39.62% 39.62%
Voltage Sag of 0.6 p.u.
𝑣 1.61% 1.62% 1.61% 1.62% 1.62%
𝑖 0.56% 0.77% 1.78% 3.36% 4.17%
𝑖 39.62% 39.62% 39.62% 39.62% 39.62%
Electronics 2022, 11, 567 21 of 23
6. Conclusions
This paper describes a FOPI VSS-ILMS based VSC control of a three-phase four-wire
grid-tied PV-HESS system. The DC and AC buses are regulated by the chaotic grey wolf
optimized FOPI controller to reduce 𝑉 and 𝑉 voltage variation during induced dy-
namic conditions. The DC bus controls the active power flow from PV and HESS to the
grid and load, along with the flow of power, which makes the DC bus control crucial for
maintaining the overall system’s stability during steady and dynamic states. The opti-
mized DC bus eliminates the second-harmonics component on the DC coupling capacitor,
resulting in enhanced power quality. On the other hand, in the case of grid-following in-
verters, the AC bus voltage is partially controlled by the grid itself. Implementing differ-
ent controls for the AC bus regulation will have a minute impact on overall system per-
formance. The AC bus control helps to achieve desired reactive power flow while operat-
ing under zero voltage regulation mode. Both optimized AC and DC buses produce direct
and quadrature loss components of currents, which further enhance the VSC control per-
formance by generating accurate weight signals and reference current signals. The VSC
control suppresses the dc offset at PCC, which improves the system’s performance. The
VSS-ILMS algorithm controls the VSC, which increases the step size in each iteration to
accommodate a wide variety of noise signals to be passed through the filtering window.
The network approximation with proposed gradient-based adaptive control is easy, per-
forming better with the sparse network. The proposed control provides VSC with the ca-
pability to perform a multi-functional operation while ensuring the system’s stability. The
proposed system performs active and reactive power control, neutral current compensa-
tion, load balancing, harmonics elimination, etc., during the diverse, dynamic, and ex-
tremely weak grid conditions. Due to the offset rejection capability of the VSC and opti-
mized DC and AC buses, the system remains stable up to 60% voltage sag/swell condi-
tions. The THD of the attached distribution grid voltage is merely 1.13% and the current
is 2.94% during steady-state. Even during dynamic conditions, the THD level is well main-
tained with 5%, even during dynamic conditions, i.e., PV to grid mode, load unbalancing
and deep voltage sag/swell conditions. The CGWO tuned DC bus minimize the deviation
of 𝑉 from its reference. The steady-state deviation of 𝑉 is hardly 0.57% (≅3 V), how-
ever, during 60% voltage sag/swell condition, it varies maximum up to 6.68% (≅45 V),
which surely reduces the stress on DC coupling capacitor and VSC switches. The overall
performance of the proposed system is found satisfactory as per the IEEE519 standard.
Author Contributions: Conceptualization, M.C., I.H., A.A., H.M. and M.A.A.; methodology, M.C.,
I.H., A.A., H.M. and M.A.A.; software, M.C., I.H., A.A., H.M., and M.A.A.; validation, M.C.,
I.H., A.A., H.M., and M.A.A.; formal analysis, M.C., I.H., A.A., H.M. and M.A.A.; investiga-
tion, M.C., I.H., A.A., H.M. and M.A.A.; resources, M.C., I.H., A.A., H.M., and M.A.A.; data
curation, M.C., I.H., A.A., H.M., and M.A.A.; writing—original draft preparation, M.C., I.H.,
A.A., H.M. and M.A.A.; writing—review and editing, M.C., I.H., A.A., H.M., and M.A.A.;
Electronics 2022, 11, 567 22 of 23
visualization, M.C., I.H., A.A., H.M., and M.A.A.; supervision, M.A.A.; project administration,
H.M. and M.A.A.; funding acquisition, H.M. and M.A.A. All authors have read and agreed to the
published version of the manuscript.
Funding: The authors extend their appreciation to the Researchers Supporting Project at King Saud
University, Riyadh, Saudi Arabia, for funding this research work through the project number RSP-
2021/278.
Institutional Review Board Statement: Not applicable.
Informed Consent Statement: Not applicable.
Data Availability Statement: Not applicable.
Acknowledgments: The authors would like to acknowledge the support from King Saud Univer-
sity, Saudi Arabia. The authors would like to acknowledge the support from Intelligent Prognostic
Private Limited Delhi, India Researcher’s Supporting Project (XX-02/2021).
Conflicts of Interest: The authors declare no conflict of interest.
References
1. Das, B.K.; Alotaibi, M.A.; Das, P.; Islam, M.S.; Das, S.K.; Hossain, M.A. Feasibility and Techno-Economic Analysis of Stand-
Alone and Grid-Connected PV/Wind/Diesel/Batt Hybrid Energy System: A Case Study. Energy Strategy Rev. 2021, 37, 100673.
https://doi.org/10.1016/j.esr.2021.100673.
2. Shah, F.A.; Khan, I.A.; Khan, H.A. Performance Evaluation of Two Similar 100 MW Solar PV Plants Located in Environmentally
Homogeneous Conditions. IEEE Access 2019, 7, 161697–161707. https://doi.org/10.1109/ACCESS.2019.2951688.
3. Rehman, S.; Ahmed, M.A.; Mohamed, M.H.; Al-Sulaiman, F.A. Feasibility Study of the Grid Connected 10MW Installed
Capacity PV Power Plants in Saudi Arabia. Renew. Sustain. Energy Rev. 2017, 80, 319–329.
https://doi.org/10.1016/j.rser.2017.05.218.
4. IRENA. Renewable Power Generation Costs in 2020; International Renewable Energy Agency: Abu Dhabi, United Arab Emirates,
2021. ISBN 978-92-9260-348-9 (accessed on 10 January 2022).
5. Gandhi, O.; Kumar, D.S.; Rodríguez-Gallegos, C.D.; Srinivasan, D. Review of Power System Impacts at High PV Penetration
Part I: Factors Limiting PV Penetration. Sol. Energy 2020, 210, 1–21. https://doi.org/10.1016/j.solener.2020.06.097.
6. Kumar, D.S.; Gandhi, O.; Rodríguez-Gallegos, C.D.; Srinivasan, D. Review of Power System Impacts at High PV Penetration
Part II: Potential Solutions and the Way Forward. Sol. Energy 2020, 210, 202–221. https://doi.org/10.1016/j.solener.2020.08.047.
7. Karami, N.; Moubayed, N.; Outbib, R. General Review and Classification of Different MPPT Techniques. Renew. Sustain. Energy
Rev. 2017, 68, 1–18. https://doi.org/10.1016/j.rser.2016.09.132.
8. Villegas-Mier, C.G.; Rodriguez-Resendiz, J.; Álvarez-Alvarado, J.M.; Rodriguez-Resendiz, H.; Herrera-Navarro, A.M.;
Rodríguez-Abreo, O. Artificial Neural Networks in Mppt Algorithms for Optimization of Photovoltaic Power Systems: A
Review. Micromachines 2021, 12, 1–19. https://doi.org/10.3390/mi12101260.
9. Estévez-Bén, A.A.; Alvarez-Diazcomas, A.; Rodríguez-Reséndiz, J. Transformerless Multilevel Voltage-Source Inverter
Topology Comparative Study for PV Systems. Energies 2020, 13, 1–26. https://doi.org/10.3390/en13123261.
10. López, H.; Rodríguez-Reséndiz, J.; Guo, X.; Vázquez, N.; Carrillo-Serrano, R.V. Transformerless Common-Mode Current-Source
Inverter Grid-Connected for PV Applications. IEEE Access 2018, 6, 62944–62953. https://doi.org/10.1109/ACCESS.2018.2873504.
11. Singh, B.; Chandra, A.; Al-haddad, K. Power Quality Problems and Mitigation Techniques, 1st ed; John Wiley Online Library.; West
Sussex,UK, 2015; ISBN 9781118922057.
12. Sevilla-Camacho, P.Y.; Zuniga-Reyes, M.A.; Robles-Ocampo, J.B.; Castillo-Palomera, R.; Muniz, J.; Rodriguez-Resendiz, J. A
Novel Fault Detection and Location Method for PV Arrays Based on Frequency Analysis. IEEE Access 2019, 7, 72050–72061.
https://doi.org/10.1109/ACCESS.2019.2920053.
13. Mishra, S.; Ray, P.K. Power Quality Improvement Using Photovoltaic Fed DSTATCOM Based on JAYA Optimization. IEEE
Trans. Sustain. Energy 2016, 7, 1672–1680. https://doi.org/10.1109/TSTE.2016.2570256.
14. Chankaya, M.; Hussain, I.; Ahmad, A.; Malik, H.; García Márquez, F.P.; Márquez, F.P.G. Generalized Normal Distribution
Algorithm-Based Control of 3-Phase 4-Wire Grid-Tied PV-Hybrid Energy Storage System. Energies 2021, 14, 4355.
https://doi.org/10.3390/en14144355.
15. Mosalam, H.A.; Amer, R.A.; Morsy, G.A. Fuzzy Logic Control for a Grid-Connected PV Array through Z-Source-Inverter Using
Maximum Constant Boost Control Method. Ain Shams Eng. J. 2018, 9, 2931–2941. https://doi.org/10.1016/j.asej.2018.10.001.
16. Agarwal, R.K.; Hussain, I.; Singh, B. Application of LMS-Based NN Structure for Power Quality Enhancement in a Distribution
Network under Abnormal Conditions. IEEE Trans. Neural Netw. Learn. Syst. 2018, 29, 1598–1607.
https://doi.org/10.1109/TNNLS.2017.2677961.
17. Agarwal, R.K.; Hussain, I.; Singh, B. LMF-Based Control Algorithm for Single Stage Three-Phase Grid Integrated Solar PV
System. IEEE Trans. Sustain. Energy 2016, 7, 1379–1387. https://doi.org/10.1109/TSTE.2016.2553181.
Electronics 2022, 11, 567 23 of 23
18. Zheng, Z.; Zhang, T.; Xue, J. Application of Fuzzy Control in a Photovoltaic Grid-Connected Inverter. J. Electr. Comput. Eng.
2018, 2018. https://doi.org/10.1155/2018/3806372.
19. Bhattacharyya, S.; Singh, B.; Chandra, A.; Al-Haddad, K. Artificial Neural Network Based Advanced Current Control for Grid-
Tied Photovoltaic System. In Proceedings of the 2019 National Power Electronics Conference, NPEC, Tiruchirappalli, India, 13–
15 December 2019. https://doi.org/10.1109/NPEC47332.2019.9034761.
20. Chankaya, M.; Hussain, I.; Ahmad, A.; Khan, I.; Muyeen, S.M. Nyström Minimum Kernel Risk-Sensitive Loss Based Seamless
Control of Grid-Tied PV-Hybrid Energy Storage System. Energies 2021, 14, 1365. https://doi.org/10.3390/en14051365.
21. Alturki, F.A.; Omotoso, H.O.; Al-Shamma’a, A.A.; Farh, H.M.H.; Alsharabi, K. Novel Manta Rays Foraging Optimization
Algorithm Based Optimal Control for Grid-Connected PV Energy System. IEEE Access 2020, 8, 187276–187290.
https://doi.org/10.1109/access.2020.3030874.
22. Tayebi, S.M.; Hu, H.; Batarseh, I. Advanced DC-Link Voltage Regulation and Capacitor Optimization for Three-Phase
Microinverters. IEEE Trans. Ind. Electron. 2019, 66, 307–317. https://doi.org/10.1109/TIE.2018.2823700.
23. Kohli, M.; Arora, S. Chaotic Grey Wolf Optimization Algorithm for Constrained Optimization Problems. J. Comput. Des. Eng.
2018, 5, 458–472. https://doi.org/10.1016/j.jcde.2017.02.005.
24. Thangam, T.; Muthuvel, K. Hybrid Algorithm Based PFoPID Control Design of a Grid-Connected PV Inverter for MPPT. In
Proceedings of the 2nd International Conference on Inventive Research in Computing Applications, ICIRCA, Coimbatore, India,
15–17 July 2020; pp. 992–998. https://doi.org/10.1109/ICIRCA48905.2020.9182806.
25. Lakshmi, M.; Hemamalini, S. Decoupled Control of Grid Connected Photovoltaic System Using Fractional Order Controller.
Ain Shams Eng. J. 2018, 9, 927–937. https://doi.org/10.1016/j.asej.2016.06.002.
26. Nasir, A.; Rasool, I.; Sibtain, D.; Kamran, R. Adaptive Fractional Order PID Controller Based MPPT for PV Connected Grid
System Under Changing Weather Conditions. J. Electr. Eng. Technol. 2021, 16, 2599–2610. https://doi.org/10.1007/s42835-021-
00782-w.
27. Rezkallah, M.; Chandra, A.; Singh, B.; Singh, S. Microgrid: Configurations, Control and Applications. IEEE Trans. Smart Grid
2019, 10, 1290–1302. https://doi.org/10.1109/TSG.2017.2762349.
28. Singh, B.; Solanki, J. A Comparison of Control Algorithms for DSTATCOM. IEEE Trans. Ind. Electron. 2009, 56, 2738–2745.
https://doi.org/10.1109/TIE.2009.2021596.
29. Mus-Ab, A.; Mishra, M.K. Wavelet Transform Based Algorithms for Load Compensation Using DSTATCOM. In Proceedings of
the 2017 IEEE PES Asia-Pacific Power and Energy Engineering Conference (APPEEC), Bangalore, India, 8–10 November 2017.
30. Kumar, R.; Singh, B.; Kumar, R.; Marwaha, S. Recognition of Underlying Causes of Power Quality Disturbances Using Stockwell
Transform. IEEE Trans. Instrum. Meas. 2020, 69, 2798–2807. https://doi.org/10.1109/TIM.2019.2926876.
31. Pradhan, S.; Hussain, I.; Singh, B.; Panigrahi, B.K. Modified VSS-LMS-Based Adaptive Control for Improving the Performance
of a Single-Stage PV-Integrated Grid System. IET Sci. Meas. Technol. 2017, 11, 388–399. https://doi.org/10.1049/iet-smt.2016.0351.
32. Hussain, I.; Agarwal, R.K.; Singh, B. Delayed LMS Based Adaptive Control of PV-DSTATCOM System. In Proceedings of the
2020 3rd International Conference on Energy, Power and Environment: Towards Clean Energy Technologies, Shillong, India,
5–7 March 2021; pp. 1–6.
33. Seema, S.S.; Singh, B.; Panigrahi, B.K. Median LMS Control Approach for SPV Grid Integrated Distribution System. In
Proceedings of the 2021 International Conference on Sustainable Energy and Future Electric Transportation (SEFET),
Hyderabad, India, 21–23 January 2021; pp. 1–5.
34. Kumar, A.; Seema; Singh, B.; Jain, R. Double Stage Grid-Tied Solar PV System Using HC-LMS Control. In Proceedings of the
PIICON 2020-9th IEEE Power India International Conference, Sonepat, India, 28 February–1 March 2020; pp. 3–8.
https://doi.org/10.1109/PIICON49524.2020.9112906.
35. Srinivas, M.; Hussain, I.; Singh, B. Combined LMS-LMF-Based Control Algorithm of DSTATCOM for Power Quality
Enhancement in Distribution System. IEEE Trans. Ind. Electron. 2016, 63, 4160–4169. https://doi.org/10.1109/TIE.2016.2532278.
36. Saeed, M.O.B.; Pasha, S.A.; Zerguine, A. A Variable Step-Size Incremental LMS Solution for Low SNR Applications. Signal
Processing 2021, 178, 107730. https://doi.org/10.1016/j.sigpro.2020.107730.
37. Malik, H.; Iqbal, A.; Yadav, A.K. Soft computing in condition monitoring and diagnostics of electrical and mechanical systems.
In Novel Methods for Condition Monitoring and Diagnostics; Springer: Berlin/Heidelberg, Germany, 2020; Volume 1096, p. 499.
https://doi.org/10.1007/978-981-15-1532-3.
38. Malik, H.; Iqbal, A.; Joshi, P.; Agrawal, S.; Bakhsh, F.I. (Eds.) Metaheuristic and Evolutionary Computation: Algorithms and
Applications; Springer Nature: Singapore, 2021; Volume 916, p. 820. https://doi.org/10.1007/978-981-15-7571-6.
39. Malik, H.; Fatema, N.; Alzubi, J.A. AI and Machine Learning Paradigms for Health Monitoring System: Intelligent Data Analytics;
Springer Nature: Singapore, 2021; Volume 86, p. 513. https://doi.org/10.1007/978-981-33-4412-9.
40. Iqbal, A.; Malik, H.; Riyaz, A.; Abdellah, K.; Bayhan, S. Renewable Power for Sustainable Growth; Springer Nature: Singapore, 2021;
Volume 723, p. 805. https://doi.org/10.1007/978-981-33-4080-0.
41. Tomar, A.; Malik, H.; Kumar, P.; Iqbal, A. Machine Learning, Advances in Computing, Renewable Energy and Communication;
Springer Nature: Singapore, 2022; Volume 768, p. 659. https://doi.org/10.1007/978-981-16-2354-7.