06 - Monitoring IO - 20140320
06 - Monitoring IO - 20140320
Slide 2
Overview of Skills
Learn the function of the General, Hardware,
and EGD tabs in a Mark VIe component
Identify hardware configuration and types of
I/O Modules
Relate hardware to drawings
Generate an I/O Report
Force Input and Output signals
Upload from the Controller
Slide 3
General Tab
Requisition Information
o Requisition Engineer
o Turbine Serial Number
o Machine Size (7FA, 9EA, etc)
Network Adapters
Slide 4
Network Adapter Configuration
Host Name - The name of the
Mark VIe component
IP Address – Internet Protocol
for the network port.
Network – Name of the
network to which the network
adaptor is attached
Slide 5
Finding the IP Address in ToolboxST
Slide 6
IP Address for I/O Packs
The base IP addresses for I/O Packs:
R IONet (IoNet1) 192.168.1.# - Red
S IONet (IoNet2) 192.168.2.# - Black
T IONet (IoNet3) 192.168.3.# - Blue
Slide 7
Hardware Tab
Slide 8
I/O Module Configuration
Terminal Board
• TB Ref Double-click
• Type a pack
• HW Form
• Bar Code
• Position
Slide 9
I/O Module Configuration - 2
Module Required – Determines
whether the module must be
present and functioning for the
controller to enter the Control
state upon startup
Slide 10
System Layout Drawing
Column A Column B Column C
Position Code of
I/O Modules
1C2A
1-Cabinet Number
Rows
C-Column
2-Row
A-Position
Slide 11
I/O Variable Report
View → Reports → I/O → Variable
Self Documenting
Feature
Troubleshoot
down to the
Terminal Board
(T/B) and Screw.
Slide 12
I/O Variables Report -2
continued…
Slide 13
I/O Variables Report -3
Slide 14
Module Reports
Right-Click on a I/O Module in the Summary View
and select Create Module Report
> Alarm
> Revision
> Communication
> Hardware
Hardware and Revision reports list the Packs,
Barcodes, Serial Numbers, Types, and more.
Slide 15
Ethernet Global Data Configuration
Slide 16
Forcing I/O Points
Should be
forced at the
Hardware tab
Double click
on green Live
Values.
Select Force
value check
box
Slide 17
Forcing EGD Points
Select the
EGD Tab
Double click
on green Live
Values.
Select Force
value check
box
Slide 18
Viewing Forced Variables
In the Component Editor
View > Forced Variables
Or press and hold {Ctrl+Shift} + F keys
Right-click to
remove the
forces
Slide 19
Uploading from Mark* VIe Device
In the Component Editor select Device > Upload
Follow the wizard’s questions.
• The configuration for G1 will be saved as G1_date as a
new device added to the system.
•The uploaded file will be inserted into the system with
the name G1
•The uploaded configuration G1 will be opened
File > Compare Devices shows differences.
Slide 20