Humidity Temperature Controller
HTC307
OPERATING INSTRUCTIONS
Doc. name: OP INST HTC307 = OP3172-V01
Selec Controls Pvt. Ltd., India
Tel.: +91-22-4141 8468 / 452
Website : www.selec.com
Email: sales @selec.comCONTENT selec
A) OVERVIEW.
T.FOAtUreS.... eee cece eee cee cee eeeceeceecetaeseecseteaseneeseeseee 1
B) SPECIFICATIONS. ....0.......ceseseseeeeesesetereeeeeeetenenes 2
C) INSTALLATION.
1.Safety Information
2. Terminal connections.
3.Sensor input wiring...
4.Control output wiring
D) PROGRAMMING.
T.FUNCtION MENU... cece eseeseeseeeeeeeseeeeeeeeeeeeeaneaees
2.Keys’ description
3.Level 0- Temperature Module.
4.Level 1- Humidity Module
5.Level 2- Alarm Module
6.Level 4-Lockout Module
7.Level 5-Communication Module.
8.Online Display Option
E) USER GUIDE..............cccscseccsesesseseseeeeeeeeteeeeeeeeneees 24
F) CALIBRATION CERTIFICATE ...Overview selec
96 x 96 ce€
SALIENT FEATURES
xRTD & Humidity Input
Provision of analog input for RTD and Humidity controlling action.
xAdaptive Tuning
For better performance, a feature of adaptive tuning is added along with self &
Auto tuning.
xSelectable lower display
User selectable lower display options enable quick setting of different
parameters such as Set points,Humidity PV,PID values, Tuning etc.
xOutputs
In single output model both control & alarm o/p is provided for humidity as well
as temperature.
xSpecial Modes
User selectable special modes
PID & proportional control for temp.& Humidity respectively along with ON/OFF
control,auto/manual,soft start.
Others
x Dual 4 digit display x 90 to 270VAC/DC
x Digital Filtering x Compliance-C€
x Sensor break indication x IP65 front panel protection
x Sensor error compensation
x Programmable parameter lockoutsSpecifications selec
1. TECHNICAL SPECIFICATIONS
1. DISPLAY
Display
IHTC307 - 96 X 96 — Dual 4 digit 7- segment LED.Upper display:18.5mm high White(Temp.
process value).Lower Display(selectable):10.9mm high Green(Default:Humidity process value).
Led Status =
OUT1,OUT2, AL1, AL2, AT,
Annunciators , , a
2. INPUT
Humidity: HS-A-100.
Input RTD: Ptt00.
Sampling time 200 ms
Resolution 1/0.1° For RTD
1/0.1° For Humidity
RTD: + 0.25% of span or 1° whichever is greater.
Indication accuracy (20min of warmup time)
Cold Junction Calibration accuracy for
RTD input 0.1% of F.S $1°C.
HUMIDITY: $3% for RH 10% to 80%
t4% for below 10% or above 80%
Digital filtering OFF, 1 to 99 sec.
3. OUTPUT
3.1. Control Output
Relay 1 & Relay 3 : 10A@250VAC or 28VDC
Relay contact output Life expectancy : 100000 cycles at maximum load ratingSpecifications
selec
3.2. Alarm Output
Relay contact output
Relay 2 & Relay 4 : 5A@250VAC or 30VDC
Life expectancy : 100000 cycles at maximum load rating
4, FUNCTION
Main control
Control:PID (temperature) & P(Humidity) or ON/OFF.
Output:Time Proportioning or Linear DC
Proportional band: 0 to 400°
Integral time: 0 to 3600 sec
Derivative time: 0 to 200sec
Cycle time:0.1 to 100.0sec
Auto tune, Self tune,Adaptive tune.
Programmable % output
Alarms
Modes : Deviation high,Deviation Low,Band,
Full scale high, full scale low,sensor break.
Operation: Absolute, Deviation & break mode
Hystersis: Programmable
Reset action: Automatic
Probe break action: Programmable
5. SERIAL COMMUNICATION
Interface standard RS485
Communication address 1 .... 99, Maximum of 32 units per line.
Transmission mode Half duplex.
Transmission protocol MODBUS RTU.
Transmission distance
500 m maximum.
Transmission speed
115200,57600,38400,19200,9600,4800,2400 bits/sec.
Parity
None, Odd, Even.
Stop bits
1or2.
Response time
100ms (max and independent of baud rate).Specifications
selec
6. ENVIRONMENTAL CONDITIONS
Operating range 0... 50°C.
Storage range -20 .... 75°C.
Storage humidity
85% max. RH (non condensing) from 0 to 50°C.
7. POWER SUPPLY
Power supply 90... 270VAC/DC.
Frequency 50/60Hz.
Power consumption
6 VA max.
8. ISOLATION BREAKDOWN RATINGS
AC line w.r.t. all inputs and outputs
2500volts
All other inputs and outputs w.r.t. Relay contacts
2500volts
9. SAFETY AND EMC STANDARDS
Compliance CE.
LVD As per BS EN 61010.
EMC As per BS EN 61326.
Panel sealing IP65.
WEIGHT : HTC307 : 280gms
10. HOUSING : Flame retardant engineering plastic.
11. INPUT SENSOR RANGES :
Sensor type Range
PT100 -100 to 850°C
HS-A-100 0 to 100%Installation selec
1. SAFETY INFORMATION
SAFETY SUMMARY
This manual is meant for the personnel involved in wiring installation,operation, and
routine maintenance of the equipment Alll safety related modifications; symbols and
instructions that appear in this operating manual or on the equipment must be strictly
followed to ensure the safety of the operating personnel as well as the instrument
If the equipment is not handled in a manner specified by the manufacture it might
impaire the protection provided by the equipment.
- ~
A\ CAUTION: Read complete instructions prior to installation and operation of the unit.
A CAUTION: Risk of electric shock. J
INSTALLATION INSTRUCTIONS
(A\caution: a
1.This equipment, being built-in-type,normally becomes a part of the main control
panel and in such case the terminals do not remain accessible to the end user
after installation and internal wiring.
2.Conductors must not come in contact with the internal circuitry of the equipment
or else it may lead to a safety hazard that may in turn endanger life or cause
electrical shock to the operator.
3.Circuit breaker or mains switch must be installed between power source and
supply terminals to facilitate power ’ON’ or 'OFF’ function. However this switch or
breaker must be installed in a convenient position normally accessible to an
operator.
A\caution:
1.The equipment shall not be installed in environmental conditions other than those|
specified in this manual.
2.Fuse Protection - The equipment does not contain built-in fuse. Installation of
external fuse for electrical circuitry is highly recommended. Recommended rating
of such fuse shall be 275VAC/1Amp.
3.Since this is a built-in type equipment (finds place in main control panel), its
output terminals get connected to host equipment. Such equipment shall also
comply with basic EMI/EMC and safety requirements like BS EN 61326-1 and
BS EN 61010 respectively.
4.Thermal dissipation of equipment is met through ventilation holes provided on
chassis of equipment. Such ventilation holes shall not be obstructed else it can
lead to a safety hazard.
5.The output terminals shall be strictly loaded to the manufacturer specified
\__values/range.
MAINTENANCE
1.The equipment should be cleaned regularly to avoid blockage of ventilating parts.
2.Use soft cloth for cleaning. Do not use isopropyl alcohol or any other organic
cleaning agent.Installation selec
WIRING INSTRUCTION:
A\ CAUTION:
1.To prevent the risk of electric shock power supply to the equipment must
be kept OFF while doing the wiring arrangement.
2.Terminals and electrically charged parts must not be touched when the
power is ON.
3.Wiring shall be done strictly according to the terminal layout with shortest
connections. Confirm that all connections are correct.
4.Use lugged terminals to meet M3.5 screws.
5.To eliminate electromagnetic interference use of short wire with adequate
ratings and twists of the same in equal size shall be made.
6.Cable used for connection to power source, must have a cross section of 1
or greater. These wires shall have insulation capacity made of at least 1.5KV.
ELECTRICAL PRECAUTIONS DURING USE
Electrical noise generated by switching of inductive loads can create momentary
disruption, erratic display, latch up, data loss or permanent damage to the instrument.
To reduce noise:
A) Use of MOV across supply of temperature controller & snubber circuits
across loads are recommended. Part numbers are as follows:
1. Snubber: APRC-01.
B) Use separate shielded wires for inputs.
C) The unit should preferably be shielded from the contactor.
INSTALLATION GUIDELINES
Mechanical Installation:
For installing the controller
1.Prepare the panel cutout with proper dimensions as shown.
OVERALL DIMENSIONS (All dimensions in mm)
Panel Cutout : 92mm X 92mm
i
2.Remove the clamp from the controller.
3.Push the controller into the panel cutout. Secure the controller in its place by
pushing the clamp from the rear side.Installation selec
Z\ caution:
The equipmentin its installed state must not come in close proximity to any heating
sources, caustic vapors, oils, steam, or other unwanted process by-
products.
EMC Guidelines:
1.Use proper input power cables with shortest connections and twisted type.
2.Layout of connecting cables shall be away from any internal EMI source.
2. TERMINAL CONNECTIONS
HTC307
SUPPLY : 90 to 270V AC / DC, 50 / 60Hz,6VA max
RELAY — : RLY1,3:10A@250V AC / 28v DC
RLY2,4: 5A@250V AC / 30V DC
Le 1 10|RD —,
} 2
3 | 2 14 | BL 5
zy S
83 NO| 3 12|GR
Sar
& com! 4 13 |RTD1 55
3
cy no] 5 14|RTD2 |Z
es[ 3
26lcom| 6 15 |RTD3 —!*
Be NO| 7 16 |RS485+
23[_
83'-com| 8 17 |RS485-
26
“ No] 9 18 |com
‘Alarm 2 Output
Note: "PIN RING TYPE LUG" is|
suggested for pannel wiringInstallation selec
3. SENSOR INPUT WIRING
HTC307
RTD
) RTD1
atp2
) RTDS
HUMIDITY
RED
(RH SV)
(|
(@)}-- Bae
a)
(RH_GND)
GREEN
(RH_SIGNAL)
Humidity - HS-A-100.
RTD- PT100.
NOTE : 1) Refer Humidity type selection in level 1(only for humidity sensor) of
programming menu.
2) For2 Wire RTD, short terminals 13 & 14.
4. CONTROL OUTPUT WIRING
Fig 1. Main/Control Output — Relay drive to load (resistive load less than 1A)
HTC307
(3)
NO
LOAD
com
230VAC
N
SUPPLY
L
@)
NO
com
LOAD
N
230VAC
SUPPLY
LInstallation
selec
Fig 2. Alarm Output — Relay drive to load (resistive load less than 1A)
HTC307
() LOAD N
NO
230VAC
SUPPLY
L
com
@) LOAD
N
NO
CoM
(18) ——_—
230VAC
SUPPLY
L
Fig3. Main/Control Output- Relay to drive contactor (For single phase)
For Relay Drive
HTC307
@Hiow}—
230VAC
NO ‘SUPPLY
I +
COM
Contactor Drive
2s0vac.
| SUPPLY
cam
HOO)
J
LOAD
contactor
temperature controller.
NOTE: Use snubber as shown above to increase life of internal relay ofProgramming selec
1. FUNCTIONS MENU
se
Ko _ysh Rh gash soo ron a
L~ so * ot gtiseslite s see ot i gg oe
EPES|UNEJESPHIESPH EFEC edb Ss) EUne Une a AMeS
>
Fd? iy ra S ss
Fa or as ost 9 ss
§ wr as oe oo Pi ros Not et
= & eREAETZ E3Cu) DCICHURE ge -CE- Pb - Pa
8 >
2 we et
> It=0 oh esos oe 2
3 Enh )H3S. HIS E
c Temperature Module
6
ys
< oe ss vw
ws se * ee Wh
3 ose ity i oes cS sia al
© eee (HSU aSURUSH ae
3
a
& ° ,
a 8 oo ee a wo
a ot ws yo 68 ss oO
ay PSEEHEAPINEES SH(HHICS=ORTEx—|
S
z Fle
3 oF oo :
° Aa a
F PSe eC Soe
Humidity Module
(EULA
oe
a ne a . os
ecm (AL PaleeS URIS)
se
aa i a gs oe
Alarm Module
1Programming selec
(EDLY
® 08 ss
o ot Se FS ss so" sg
ys? ns » emmetE SEE Renta SEES }
(o_Jesre) s ee Lock MobULE
s gt ets eg [TSS
{ EBC TEP: CGALPIGE REM Nee}
Lockout Module
Communication Module
(@ Appearance of all shaded menus dependent on selection of other parameters.
Refer programming for further details.
12Programming
selec
selec
——
HTC307
Boga =
Fe SSH 4g
2. KEYS DESCRIPTION
Functions
Key press
To enter or exit program mode
A +¥ together for 3 seconds
To change levels
v+A/¥ to increase or decrease the
level number.
To view function on the same level and
to display the current option.
‘Aorv key once to view the next /
previous function.
To increase or decrease the value of a
particular function.
v+Ato increase and¥ +V¥ to
decrease the function value.
To view and change parameters online
@key to view the parameter and@+A /
yto scroll through the parameters. Press
v_+A /¥ to change parameter value.
INDICATIONS AND DISPLAY
NOTE: The unit will autoexit program mode after 30 seconds of inactivity.
1 | Temp.Process-value (PV) Displays the processed temperature value.
2 | Humidity Process- value(PV)| Displays the processed humidity value.
3] OUT1 Indicates the status of Temp. control output(relay 1).
4| OUT2 Indicates the status of Humidity Control output(relay 3).
5| AT Indication for Tuning is in progress.
6] Alt Indicates the status of Alarm output 1 (relay 2).
7) AL2 Indicates the status of Alarm output 2(relay 4).
3| => Indicates Communication is in progress.
9] °CrF Temperature Unit
[10] %RH Humidity Unit
13Programming
selec
PROGRAMMING OF LEVELS
3. LEVEL 0: TEMPERATURE MODULE
. inti Display Default
Display Name & Description Range condition value
: 1/0.1 — a1
EP ES] | Temperature Resolution ae .
Uftt | | Temperature unit Oc /oF — oc
ESPH) |Temp.set pointhigh limit [Set point low
ESPH) p-setp a limit to 850. — 6590
an -100 to Set
p.set pi .
Temp.set point Low limit point high limit. _ -100
EFEC]) | Filter Time constant OFF,1 to99 — '
seconds '
—db65} | Temp.Display Bias(DSP -999 to+999 — 0
offset, .
St/At/Adt/ |Pb>0 (PID
EUNE) | Auto Tune OFF Control) | OFF
fonne) P.AU/P.1S to [Tune=AT,ST, !
A Tune Percentage meer Pp.
Lune) 9 P.1GQ | ADT PAU
AAIn Relay 1_ Mode PEIFA — Pe
ra 8% to off
ZED) | Output power lower limit — [power nigh limiPID control] gProgramming selec
- wth Display Default
Display Name & Description Range conditen ‘value
ower lo}
P-H 1} |Output power upper limit PP powsrjow PID control ao
Proportional band- 1 Btoyeas 1g
Integral time 8 to3600sec. | PID control {23
Derivative time Oto2eB0sec. 30
dAC Derivative approach control fan) PID control 10
os USED/
C3Et) | Cycle time usre/a iso | PiD control | ySEer
. 8.1 to!0G0 =
T3GU) | Cycle time-user sec eee time 15.0
0
APY) | Anti-reset windup oon, PID contro) | AUEG
APUP) | Anti-reset windup % Sotoioa% | ARW=MAN | 25.0
p. Hystersi 8.1
HUSE) | Temp. Hystersis 0.170 993 | p45 10
(ON/OFF
HUSH) | Temp. hystersis bias -99To 93 control) a8
0.07099: Pb-1=0 &
Eat) | Timer 8070398 Main=FD 8.0
Manual Reset -99970999 |It=0 & Pb-1>0 b.3
PARAMETER EXPLANATIONS:
° TEMPERATURE UNIT:
The temperature unit is selectable between ‘C and°F.when temperature unit is
changed, the temperature ranges will also change according to the present
selection of unit. If changed, make sure to check all parameter.
* RESOLUTION:
The resolution is selectable between 1 and 0.1 for RTD & for humidity HS-A-100
15Programming selec
* SET POINT LIMIT VALUES:
The controller has programmable high and low set point limit values to restrict the
setting range of the set point.Set the limit values so that the temperature set point
value cannot be set outside the safe operating area of the process.
« FILTER TIME CONSTANT:
The filter is an adaptive digital filter that discriminates between measurement noise
and actual process changes. if the input signal is increasing too greatly due to
measurement noise, increse the filter value.If accurate control is desired,increse the
filter time constant whereas if the fastest controller response is required,decrese the
filter time constant.
* DISPLAY BIAS:(DISPLAY OFFSET)
This function is used to adjust the PV value in cases where it is necessary for PV
value to agree with another recorder or indicator or when the sensor cannot be
Mounted in correct location.
* AUTO TUNING:
Auto tuning is a function whereby the controller learns the process characteristics
By itself and automatically sets the required P,| and D values.the new P,I,D
parameters will Be stored in non-volatile memory automatically. TUNE ON is
indicated by ‘AT’ LED Blinking.(For detailed explanations of PID parameters refer
USER GUIDE).
e« OUTPUT POWER LIMITS:
These parameters are used to limit the minimum and maximum controller output
power. The output power lower limit will ensure that a minimum percentage of output
(as per requirement) is available in case any process disturbances or setpoint
changes occur. The output power high limit ensures that in case any process
disturbance or set point changes occur, the maximum value of outputis limited toa
value as per requirement.
«CYCLE TIME:
There are 3 selectable modes for programming cycle time:
USEr: User can program the cycle time. The mode will be altered to AutO when put to]
autotune.
Usr.F: User can fix the cycle time. This has the highest priority.
AutO: This is recommended. The cycle time value is calculated automatically
during autotune.
e ANTIRESET WINDUP:
The anti-reset windup (ARW) inhibits the integral action until the PV is within the
proportional band thus reducing overshoot on start-up. If the selection is -
1. AutO: The value will be calculated automatically during autotune (Recommended).
2. ManL: The value can be fed manually by the user.
16Programming
selec
4, LEVEL 1 : HUMIDITY MODULE
Display Name & Description Range Display Default
condition value
ATES) | Humidity Resolution ost — a.
Humidity Input Hipo/okHP | = =— H.100
- 0.0 to display
Humidity Display value Value scaling qn
Hest) Scaling point1 point 2 oe
8 Vito Input
7 Humidity Input value v i A
HISU Scaling pointt pang scalng as
Humidity Display value Bisplay value [HRP =OEHP
Humidity Display value int 1
Hd5H) | Scaling point 2 hoinon 188.0
7 Input value
AISA Humidity Input value Sealing point 1 uso
- Scaling point 2 Ito 1B ”
—— Humidity set point Set point low limit| an
HSPH) | High Limit To1B0 108
7 Humidity set point 00 To set point
HSPU | Low Limit high limit ° —_ 8
Humidity Filter time OFF,1 to99 '
HEED) | Constant seconds ‘
(HACE Humidity control action HUa/dHUA — HUA
Pb-C Proportional band 00To 490.0 aa
C5EH) | Cycle time G70 1885 | pp-coo 15.0
HHS) | Humidity Hystersis 8.1 To 993 10
Pb-C=0
HY Sb) Humidity hystersis bias -99To 39 0.8
17Programming. selec
Display Name & Description Range Display Default
Humidity PV bias 4000 To 1808 88
Pb-C=0
Humidity timer 8.8T0333 ao
minute
Reset AG/YES — no
PARAMETER EXPLANTIONS:
SCALING FOR ANALOG INPUT:
To scale the controller,two scaling points are DISPLAY
necessary.Each scaling point has a coordinate pair
of display values and input values.it is recommend-
ed that the two scaling point be at the low and high
ends of the input signal being measured.process
value scaling will be linear between and continue
past the entered points to the limits of the input
range. (Factory setting example will display 0.0
ov a5v
INPUT
at 0.5V input and display 100.0 at 4.5V input. SCL =05 [ISCH= 45
DSC.L =0.0 DSC.H =
100.0
NOTE: This change will not be visible in the programming menu.
* TIMER:
TIMER is main output restart time.In this main output once turned OFF will turn ON
only after set time even if the temperature is increased or more than the set
temperature. This is needed to prevent the compressor from restarting in a short
time (less than the set time)Programming.
5. LEVEL 2 : ALARM MODULE
selec
Display Name & Description Range Display Default
condition value
ALAG Alarm Selection AL-1/AL-2 — Al-!
OFF /dHI.E
/SHIH/SLO
Ri- 4 (SL O.H/bNdE AL _
Alarm 1 mode Tendu/Hace | ALNO=AL-1 | HA-E
/LAPE/SBPE
/SbPH
OFF/dHiE
/SHILH/d LB
= Alarm 2 mode /LOH/bAdE | ALNO=AL-2 -
Abne /bftd.H/ HA-H HA-H
/LR-H/S.bP E
/SbPH
ALPa Feay status for Alarm EN/gEN __ en
These
HYS§) | Hystersis for Alarm 1&2 0.1 To 999 | parameters 1a
are not
prompted if
i Alarm1 & 2
(H4S.b] Hystersis bias for Alarm -93To 93 mode is OFF 0.0
ise /SbrT/sbrH
PARAMETER EXPLANTIONS:
®@ ALARM MODES:
(Refer USER GUIDE for detailed explanation).
19Programming selec
6. LEVEL 4:LOCKOUT MODULE
Display Name & Description Range Display Default
condition value
User ID 8 To 3999 — a
Program access setting # | QAL/LEUL — LEUL
# If LOCK selection is ONL, the following parameters will be prompted.
Display Name & Description Range Display Default
condition value
UALeTP
ESEE] | Lock Set uacesPeRd | uae
HSEE] | Lock Set ite? | = Of uate
AL-1) | Lock set ote? | = — | une
AL- 2] | Lock Set une UPERd — unAle
E UNE] | Lock tune yareyend | = | ute
Loc
Pb- 1) | Lock proportional Un eiPeRd — uUnLe
unLE/P
TME.E) | Lock integral time uacesPeRd | Fun
Hite
dEP.L) | Lock derivative time rata ERd UAL
= uALe/
ANLPY | Lock Manual reset uae eEPeRd — UALR
P.-C) | Lockproportionalband | YRLELPERS — uALe
CHNG) | Change Password id-M/id-¥ —_— id-fi
flEY) | New password — CHAG =1d-Y¥ 8
20Programming. selec
# If LOCK selection is LEVEL, The following parameters will be prompted.
Display Name & Description Range sete Default
Lock Level 0 tatiana — uUnLe
(L- H Lock Level 1 UE eUPeRd — UALR
Lock Level 2 uae eUPend — unLe
(C- 5) Lock Level § ethane — une
Change password id-M/id-¥ ~~
ney New password — CHAG =1d-4 o
NOTE:
UNLK - Full access to the particular level / parameter.
READ - Particular level / parameter can be read but not edited.
LOCK - No access to the particular level / parameter.
IDM Level
‘einking) Display Parameter Description
Ke WHA)
- eur ee onevere ida _ | Independent Downloader Module
$ vey VKoy
3 t UPL Upload from product to IDM
| dale
a
z Baroy axey dfit__| Download from IDM to product
en [ SL ane/Ert dine Operation Successful
roy OTAKor
inna) ere Operation unsuccessful
Note :
1) IDM Level - IDM should be connected before powering on the unit to enter in IDM level.
2) Long press Aor key for 3 sec to exit from IDM mode.
Caution: After Downloading, switch of the unit and then remove the IDM
21Programming
selec
LEVEL 5 - COMMUNICATION PARAMETERS
. seat, Display Default
Display Name & Description Range ae
play P 9 condition value
2400/4800 /9600/
Baud Rate 19208/38400/51600| —_ 9600
"5200
Communication station 1 t099 __ 1
No.
NONE/EVEN
Parity Odd —_ Nene
Stop bit le —_ 1!
CONNECTION DIAGRAM
ASESEC 15
lcoWeRTER
=
vole] | Falem ve] [Lele veL2] | Ielcow
SLAVE 1 SLAVE 2 SLAVE 32
Note: RS485-RS232 Converter
1. Maximum 32 slave controllers can be connected to the master. | Partno.- AC-RS485-RS232-01|
2. The total cable length should not exceed 500 meters.
3. Use shielded twisted -pair cables for RS485 connections.
4. Use terminators having a resistance of 1000hm (% watt).
22Programming
selec
ONLINE DISPLAY OPTION
This function allows user to view online display options.
NOTE:
The parameters shown below are not prompted if they are locked in level 4
DISPLAY DESCRIPTION DISPLAY CONDITION
ESEt Temprature set point —
HSEE Humidity set point —
Alarm 1 set point
Online access for AL1 not
valid if Alarm mode1 = OFF/
sbrT/sbrH
Online access for AL2 not
AL-2 Alarm 2 set point valid if Alarm mode 2 = OFF/
sbrT/sbrH
Auto tune is not prompted if
[E UNE] Auto tune Pb-1=0.
(Pb -1) Proportional band —
Integral time
Integral time is not
prompted if Pb-1=0
Derivative time is not
dt-! Derivative time prompted if Pb-1= 0
Manual reset is prompted
aAhut Manual reset only if Integral-main=0(|t-1=0)
and Pb-1 > 0.
Pb-C Proportional band —
Pere Output percentage This parameter is read only
and cannotbe altered.
Temperature unit
This parameter is read only
jand cannotbe altered.
Blank
23USER GUIDE selec
USER GUIDE
PID - time proportioning
+ AUTO TUNING: with auto reset & rate
Auto tuning is a function whereby the controller
learns the process characteristics by itself and Temp,
automatically sets the required P,| and D values.
The auto-tuning function can be activated at ANY... ein
time during the process after power ON , while \~
temperature is rising or when control has
stabilized. Autotune is indicated by AT LED blinking Time
After the auto tuning procedures are completed,
the AT LED will stop flashing and the unit will
revert to PID control by using its new PID values.
The PID values obtained are stored in the nonvolatile memory.
Proportional band
Reduced overshoot
KK
The auto-tuning is applied in cases of :
@ Initial setup for a new process
@ The set point is changed substantially from the previous auto-tuning value.
@ The control result in unsatisfactory.
The following controller parameters are automatically adjusted by Auto- tune
according to the characteristics of the process:
Proportional Band (Pb-1)
Integral Time (It-1)
Derivative Time (dt-1)
Input Filter (FtC)
If the control performance by using auto-tuning is still unsatisfactory, the following
rules can be applied for further adjustment of PID values:
ADJUST MENT SEQUENCE SYMPTOM SOLUTION
Slow Response Decrease PB
(1) Proportional Band (PB)
High overshoot or Oscillations} Increase PB
Slow Response Decrease IT
(2) Integral Time (IT)
Instability or Oscillations Increase IT
Slow Response or Oscillations) Decrease TD
(3) Derivative Time (TD)
High Overshoot Increase TD
24User Guide selec
« PROPORTIONAL BAND:
Proportional band is the area around the set point where the controller is actually
controlling the process; the output is at some level other than 100% or 0%.
Proportional band is expressed in terms of degree centigrade.
If the proportional band is too narrow an oscillation around the setpoint will result. If
the proportional band is too wide the control will respond in a sluggish manner, could
take a long time to settle at set point and may not respond adequately to upsets.
« MANUAL RESET:
Virtually no process requires precisely 50% output on single output controls or 0%
output on two output controls. The adjustment called manual reset allows the user to
redefine the output requirement at the setpoint. A proportioning control without
manual or automatic reset will settle out somewhere within the proportioning band but
likely not on the setpoint.
« INTEGRAL TIME:
Integral time is defined as the time, in seconds, which corrects for any offset (between
setpoint and process variable) automatically over time by shifting the proportioning
band. Integral action (also known as “automatic reset”) changes the output power to
bring the process to setpoint. Integral times that are too fast (small times) do not allow
the process to respond to the new output value. This causes over-compensation and
leads to an unstable process with excessive overshoot. Integral times that are too
slow (large times) cause a slow response to steady state errors. Integral action may
be disabled by setting the time to zero. If time is set to zero, the previous integral
output power value is maintained. If integral action is disabled, manual reset is
available by modifying the output power offset (“MNL.r” initially set to zero) to
eliminate steady state errors. The controller has the feature to prevent integral action
when operating outside the proportional band. This feature is called “antireset
wind-up”.
« DERIVATIVE TIME
Derivative action is used to shorten the process response time and helps to stabilize
the process by providing an output based on the rate of change of the process. In
effect, derivative action anticipates where the process is headed and changes the
output before it actually “arrives”. The derivative time is calculated in seconds.
Increasing the derivative time helps to stabilize the response, but too much derivative
time coupled with noisy signal processes, may cause the output to fluctuate too
greatly, yielding poor control. None or too little derivative action usually results in
decreased stability with higher overshoots. No derivative action usually requires a
wider proportional and slower integral times to maintain the same degree of stability
as with derivative action. Derivative action is disabled by setting the time to zero.
25User Guide selec
+ DERIVATIVE APPROACH CONTROL:
Derivative approach control (DAC) helps in reducing overshoot at startup. The control output cutoff
pointis derived as DAC x Proportional band. Note that the DAC value is autornatically calculated and
fed after auto tuning (if tuning is initiated at startup).
Self Tune (ST) : It is used where modification of PID parameters is required
repeatedly due to frequent change in process condition eg. Setpoint.
«Tune LED(AT) blinks at slower rate when Self-tuning is in progress.
eAt the completion of self-tuning, Tune LED stop blinking.
Proportional band Reduced overshoot
Temp. {
Set point 7
Self-tuning is initiated under the following conditions :
1)When setpoint is altered.
2)When tune modeis altered. (TUNE=ST)
ST will start only if PV <50% of setpoint.
ST will work only when ACT=RE.
Time —
Adaptive Tune (ADT) : It is used where modification of PID parameter is required
repeatedly due to frequent change in process condition eg. Setpoint , Adaptive.
Tune LED(ADT) blink’s at faster rate when Adaptive tuning is in progress.
At the completion of Adaptive-Tuning, ADT LED stop blinking.
Running Changed
Condition Condition
Adaptive
i Tuning
Time
26User Guide selec
@ ALARM MODES:
1. Absolute alarms (Independent Alarm) :
Absolute alarm is a self-existent alarm independent of the main set point. For
eg.If the main set point is 100°C and absolute alarm is set as 110°C. The alarm will
be activated at 110°C
There are two absolute alarms-
Full scale High Alarm(HA-T/HA-H): sets off alarm signal when PV rises above
set point to a pre-set value above scale minimum. Refer Fig:d.
Full scale Low Alarm(LA-T/LA-H):sets off alarm signal when PV falls below set
point to a pre-set value below scale maximum. Refer Fig:e.
2. Deviation alarms (Error alarm) :
This alarm is activated at an error on the main set point. For eg. If the main set
point is 100°C and deviation alarm is set tot5°C then the alarm will be activated at
100+5=105°C incase of deviation high alarm & for deviation low alarm it will be activated|
at 95°C. Incase of deviation band alarm the alarm will be activated on both sides of set
point i.e.at 95°and 105°.
There are three deviation alarms-
Deviation High Alarm(dHI.t/dHI.h): sets off alarm signal when PV rises above a
pre-set value above the set point.Refer Fig: a.
Deviation Low Alarm(dLo.t/dLo.h): sets off alarm signal when PV falls below a
pre-set value below the set point.Refer Fig:b.
Deviation Band Alarm(bnd.t/bnd.h): sets off alarm signal when PV rises above
or falls below a pre-set value above or below the set point. Refer Fig: c.
27User Guide selec
Configuration Record Sheet
3. BREAK ALARM:
Break Alarm: sets off alarm signal when sensor break/ under range occurs.
Deviation high alarm Deviation low alarm Deviation band alarm Full scale high alarm Full scale low alarm
stam //
A
Z.
TSET/ day Tse
ef ad yee
U
Fig: a. Fig: b. Fig: c. Fig: d. Fig: e.
For deviation & break alarm both the alarm Al1 & Al2 can be used for temperature
(TSET) as well as humidity(HSET). If dhi.t, dlo.t, bnd.t, sbr.t are selected;it will be activated
according to temperature. Whereas dhi-.h, dlo.h, bnd.h, sbr.h are selected it will be activated
according to humidity.
The absolute(HA-T/HA-H/LA-T/LA-H) Alarm 1 will be activated only according to
Temperature & Alarm 2 will be activated according to humidity.
28Calibration Certificate selec
Model No: HTC307
Claimed Accuracy: + 0.1% of full scale +1 digit (After 20min warmup time)
Standard used for calibration of the product is traceable to NABL
The calibration of this unit has been verified at the following values:
CALIBRATION
a DISPLAY DISPLAY
SENSOR | Humidity | yatye(ecy| SENSOR (01 te on) VALUE
35.0 35.0
Voltage 0.0 0.0
HS-A-100 700.0 700.0 (vDc)
1350 1350 10.0 10.0
0.0 0.0
Current 0.0 9.0
PT100 500.0 500.0 (mA)
800.0 800.0 20.0 20.0
The RTD curves are linearised in this microprocessor based product, and hence the
values interpolated between the readings shown above are also equally accurate, at
every pointinthe curve.
Unit is accepted as accuracy is withing the specified limit of claimed accuracy and
certificate is valid upto one year from the date of issue.
29