Crompton Instruments Integra Ci3: Digital Metering System
Crompton Instruments Integra Ci3: Digital Metering System
Crompton Instruments Integra Ci3: Digital Metering System
Programmable Functions
Easy clip-in mounting
Integra Ci3 dms is programmable to suit single-phase, three-phase three-wire and three-phase four-wire system configurations. Programmable CT ratios enable to display any current range.
Display Features
DIN 96 enclosure Backlit LCD screen Bezel depth 6.1mm Plug-in output modules Programmable CT ratio True rms measurement User programmable system configuration
The parameters can be viewed on a backlit LCD display. The 15 screens are accessible via four buttons on the front panel allowing to scroll between various screens making the navigation very user-friendly, intuitive and above all simple.
Plug in Modules
Integra Ci3 dms features two output options ports at the rear of the product. This allows to fit either pulsed relay or communication modules, e.g. ModbusTM communication output.
Panel Mounting
Integral retention clips allow fast, safe and secure panel mounting in various material thicknesses without the need for external screws or clips.
Benefits
Cost effective Intuitive navigation Crompton renowned quality UK manufactured Easy clip-in panel mounting Ex-stock delivery
Product Code
Description
Integra Ci3 base unit Options Pulsed output ModbusTM RS485 Accessories IP65 protective cover IP54 panel gasket
Part number
CI3-01
CI-PUL-01 CI-MOD-01
Standards
IEC 61326 IEC 61010-1 IEC 62053-21 RoHS compliant
3 G365 02 3 C345 01
Dimensions
Panel cut-out
Specifications
Input Nominal input voltage Max. continuous input overload voltage Max. short duration input voltage Nominal input voltage burden Nominal input current Max. continuous input overload current Max. short duration input current Frequency Auxiliary Operating range 100-289V AC L-N (173-500V AC L-L) 120% of nominal 2 x range maximum (1 second application repeated 5 times at 5 minute intervals) < 0.2VA per phase 5A AC rms 120% of nominal 10 x nominal (1 second application repeated 5 times at 5 minute intervals) 45-66Hz 110-400V AC nominal +/-10% (99-440V AC absolute limits) or 120-350V DC +/-20% (96-420V DC absolute limits) 0.5% 0.5% 4% 0.1 Hz 1% of unity +/- 1% of range +/- 1% of range +/- 1% of range Class 1 (IEC 62053-21) +/- 1% of range 1% up to 31st harmonic 1sec 1 per module (2 modules fitted per Ci3) 50mA max at 250V AC Solid state relay 1 ModbusTM channel per module (maximum of 1 module fitted per Ci3) 2-wire half duplex 2400, 4800, 9600, 19200, 38400 Other communication modules available in 2010 DIN 96 panel mount 96x96x64.1mm (depth behind panel without module 58mm, with module 82.5mm) 92x92mm 1-5mm IP52 IP30 Polycarbonate to UL94V0 300g Shrouded screw-clamp 0.05-4mm wire -10C to +55C -20C to +70C 0-90% non-condensing 30g in 3 planes 10Hz to 50Hz Withstand test 3.25kV rms 50Hz for 1 minute between comms and measuring inputs, comm and aux, aux and measuring inputs
Accuracy Voltage (V) Current (A) Neutral current calculated (A) Frequency (Hz) Power factor (PF) Active power (W) Reactive power (VAr) Apparent power (VA) Active energy (kWh) Reactive energy (kVArh) THD Response time Output modules (optional) Pulsed output relays Contact rating Type RS485 ModbusTM output module Type Baud rate Enclosure Enclosure style Dimensions Panel cut-out Panel thickness Front protection rating Case protection rating Material Weight Terminals Environment Operating temperature Storage temperature Relative humidity Shock Vibration Dielectric voltage
Parameters
Button V/Hz Screen 1 Parameters Volts L1 - N Volts L2 - N Volts L3 - N Volts L1 -L2 Volts L2 - L3 Volts L3 - L1 Frequency Volts L1 - N THD% Volts L2 - N THD% Volts L3 - N THD% Volts L1 -L2 THD% Volts L2 - L3 THD% Volts L3 - L1 THD% Current L1 Current L2 Current L3 Neutral Current L1 Current Max Demand L2 Current Max Demand L3 Current Max Demand Neutral Current Max Demand Current L1 THD% Current L2 THD% Current L3 THD% kW kVAr kVA kW Max Demand Power Factor kWh kVArh
3 4
2 3
4 5
P/PF
2 3 E 1 2
Wiring Diagrams
1 PHASE 2 WIRE 3 PHASE 3 WIRE 3 PHASE 4 WIRE
Features
CT ratios from 5/5 to 4000/5 Accuracy up to Class 0.5 Integral terminal cover High impact, flame retardant moulded case Busbar, DIN-rail or foot mounting options
Benefits
Wide range of apertures and case sizes Reduction of high currents for ease of metering Long product life
System voltage: Test voltage: System frequency: Short circuit thermal current (Ith): Overload withstand: Dynamic current (Idyn): Saturation coefficient: Service temperature: Insulation class: BS2757 IEC85: Enclosure code: Integral terminal cover: Complies with: Humidity: Secondary terminals screw clamp: Fast On:
1.2 x rated current continuously = 2.55 x Ith <5 for through aperture models <10 for wound primary -20C to 85C Class E IP40 IP20B IEC 60044-1:2003 Up to 95% RH (non condensing) Up to 10mm2 cable 6.3mm type
Approvals
BS EN 61010-1 IEC 61010-1 IEC 60044-1 UL Recognized file no: E257877 (MA5Y, M55E, M53J, M63N, M93L, MB5D, MB5Z only)
While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Crompton is a trademark of Crompton Parkinson and is used by Tyco Electronics under a licence. Other Trademarks mentioned herein are the property of their respective owners.
Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters.
Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5287 Email: [email protected] www.crompton-instruments.com