GXR Fault Finding
GXR Fault Finding
S S
GENERATOR SETUP
INVERTER CONTROL
PCB OVERVIEW
C
S GXR Inverter control
RV5
board overview
Potentiometer & switch locations
RV16
RV3 SW1
RV4 RV1
S
RV6 RV8
RV2
RV9
SW2
SW3
RV13
RV14
BOTTOM
C
S GXR
SW1
Inverter control board overview
Switch descriptions
SW2
Position 1 (left) – Manual power control (generator panel)
Position 2 (middle) – Proportional (line speed)
Position 3 (right) – Remote (PLC)
SW3
A – UTS frequency – Up = high / down = low
B – UTS override – Up = override / Down = sensor
C – Not used
D – Power demand I/P – Up = 0-10V / Down = 4-20mA
C
S GXR
Inverter control board overview
Potentiometer descriptions
BOTTOM
C
S GXR Inverter
LED 1
control board overview
LED Descriptions
LED2 LED3
S
A – 24v (A) A – Shutdown A – UTS signal
B – 15v (B) B – + Mismatch B – Rotation sensor (pulses)
C – -15v (B) C – - Mismatch C – N/A
D – 15V (C) D – Overcurrent trip D – Treat on
E – Interlocks closed E – Skip E – N/A
F – Overtemperature (OK) F – Skip signal F – N/A
G – 24v (B) G – Remote skip / treat G – No error IGBT driver 1
H – Start H – High alarm H – No error IGBT driver 2
I – Relays closed I – Low alarm I – Remote not stop
J – Line up to speed J – UTS signal J – Remote / Local
C
S S
GENERATOR SETUP
MATCHING GENERATOR TO
TREATER STATION
C
S Matching generator to
treater station
• The following steps show how to match a
S
GXR generator to a treater station
• This ensures the generator, HT
transformer and treater station are running
at there most efficient
• Matching should be carried out when a
system is first installed or when a
substantial change has occurred i.e.
changing air gap to suit a different material
C
S CAUTION S
IN ORDER TO CARRY OUT THE FOLLOWING
ADJUSTMENTS THE GENERATOR CABINET
DOOR WILL NEED TO OPEN WHEN THE
GENERATOR IS RUNNING
Caution
2/4 Set HT transformer tap S
Generator
To
Ensure generator is switched off HT3
and isolated from the supply
before commencing any work on
the HT transformer
A 15.00
2
S
5 4.12 3
18.0 B
4
Caution
4/4 Unable to achieve full power S
1
Ensure generator is switched off
and isolated from the supply
before commencing any work
on the HT transformer
AUTOMATIC FREQUENCY
CONTROL
C
S Automatic frequency control S
• The following steps show how to re-set the
automatic frequency control
• This ensures the generator is running at its
most efficient throughout the power range
• The automatic frequency control should be
re-adjusted whenever a new control PCB
or a new HT transformer is installed
C
S CAUTION S
IN ORDER TO CARRY OUT THE FOLLOWING
ADJUSTMENTS THE GENERATOR CABINET
DOOR WILL NEED TO OPEN WHEN THE
GENERATOR IS RUNNING
5.00
4
1
3
1
3
1 – Put SW1 A in the down position (auto frequency control)
2 – Press start button,
3 – Ensure true power meter (A) reads full power & reactive
power meter (B) reads 0.00 +/- 0.05. If not return to step
2/4.
3 – Press stop button
C
S
A – Site supply 380-420v B – 240v AC 50/60Hz C – 330v +/- 10% DC
AC 50/60 Hz
C
S Generator circuit overview
Key Voltages & waveforms
D
S E
J I G
S
H
D E F
B
A – Contactor K1 F – IGBT’s x 4
B – Contactor K2 G – Pulse driver 1
C – Resistor 100Ω R1-R3 H – Pulse driver 2
D – Bridge rectifier BR1 I – Capacitor discharge resistor 1kΩ R4
E – Smoothing capacitors C2 J – Thermal switch TH1
C
S
Trouble shooting
General faults
Generator does not reach full power when started in automatic
S
frequency control or after a web splice. Generator may become
noisy
4
S
7.50
2
TB2 3 4.12
10 5
18.0
1
1
6
TB7
S
1 10 CAUTION
1
Ensure Oscilloscope ground
TP6
2 has been removed.
1 – Adjust the frequency up & down. Frequency of pulses should change (A)
If frequency stays fixed ensure generator is in manual frequency
If no waveform check PWM circuit DWG A4.500001.05/06 paying attention to IC1,16
As can be seen from the waveform the pulses are 180 degrees out of phase
I waveform OK then go to pulse driver test
C
S Fault Finding
1/2 Inverter heatsink assy – Pulse driver test
1 – Connect oscilloscope probe on G1 & ground
clip to E1 on master driver PCB. Check for
square wave (A) G2 R3
S Conn
R4 1
2 – Connect oscilloscope probe on G1 & ground DRIVER
E2 R5
clip to E1 on Slave driver PCB. Check for
SKHI 22A
square wave (A). 1 R3
E1
R4
G1 R5
A Master
G2
R4
E2 R5
2 E1 R6
R7
If no waveform present go to next step 2/2 G1
If waveform present go to IGBT test Slave
C
S Fault Finding
2/2 Inverter heatsink assy – Pulse driver test
1 – Connect oscilloscope probe on right hand side
of R4 & ground clip to E2 on master driver G2 R3
1
S Conn
PCB. Check for square wave. Repeat for R5 R4 1
DRIVER
E2 R5
2 – Connect oscilloscope probe on right hand side 2
of R6 & ground clip to E1 on master driver SKHI 22A
R6
PCB. Check for square wave. Repeat for R7 E1
R7
3 – Repeat above for slave PCB G1 R8
Master
If no square wave present driver device
(SKHI 22A) faulty – Replace driver or
complete driver PCB assembly
If square wave OK, resistors failed – Replace
resistors and return to step 1/2
G2 3
R4
E2 R5
Resistor values
Generator
Resistor E1 R6
GX 100R GX 150R R7
G1
R3, R8 15KΩ 15KΩ
Slave
R4 - R7 56Ω 10Ω
C
S Fault Finding
Inverter heatsink assy – IGBT test
NOTE: If testing IGBT’s in inverter, DC smoothing capacitors must be removed prior to testing
Use a Digital multi meter (diode function) to measure between the following points
S
IGBT types
OC – Open circuit
SC – Short circuit
FD – Forward diode (0.3v dc)
Red Lead + Black Lead - Result Red Lead + Black Lead - Result
1 2 OC 1 5 SC
2 1 FD 1 4 OC
1 3 FD 7 1 FD
3 2 OC 6 1 OC
1 7 OC 5 1 SC
1 6 OC 4 1 OC
C
S S
TROUBLE SHOOTING
&
FAULT FINDING
HT Transformer
HT 8
C
S Fault Finding
HT Transformer – HT8
Secondary Secondary
Open circuit Short circuit
TAP’S mH mH
( WRT 1 )
7 8.86 .22 .068
6 7.18 .21 .058
5 5.68 .20 .049
4 4.35 .20 .040
3 3.20 .20 .032
2 2.22 .20 .024
OUTPUT 0.913H .301 S/C
TO
GROUND